Hazardous Area Lighting
In the areas where flam m able m aterials are m anufactured, produced, processed or stored, m ixing of flam m able gases with air is likely to happen in the atm osphere. If due to the electrical equipm ent installed in such areas, ignition takes place due to a spark or fire, it can lead to a hazardous situation. Although the prim e requirem ent is to avoid the occurrence of such conditions where this is not practical, special m ethods of safeguarding electrical apparatus m ust be em ployed.
Care should be taken to avoid flam m able or explosive atm ospheres, inorder to have an ignition, both a flam m able atm osphere and m eans of ignition m ust exist sim ultaneously.
Types of Hazardous situations :
Depending on the presence of flam m able m aterial the hazardous areas are classified in to Hazardous Zones.
Typical illustration of Zone 0, Zone 1, Zone 2 areas with source of ignition
ZONE 2
ZONE 1
ZONE 0(SOURCE)
ZONE 0
ZONE 1
ZONE 2
THE EXPLOSIVE ATM OSPHERE IS CONTINUOUSLY PRESENT
THE EXPLOSIVE ATM OSPHERE IS OFTEN PRESENT
THE EXPLOSIVE ATM OSPHERE IS ACCIDENTALLY PRESENT
A Zone in which an explosive m ixture is continuously present (in the gaseous phase) inside a receptacle or a closed cham ber constitute Zone 'O’
A Zone in which an explosive m ixture of Gas, Vapour or Dust is likely to occur in norm al operations. In these areas flam eproof lum inaires and accessories are used.
Flam eproof Enclosure - is one which will withstand when all the covers and accessories are properly secured, an internal explosion of the flam m able gas or vapour through the joint gaps and flam e paths provided in the enclosure.
Note: The term 'Flam eproof' is synonym ous with the term 'Explosion-proof' as used in USA or 'Explosion-Proof' type 'd' protection used in Germ any and other Continental countries.
A Zone in which an explosive m ixture is not likely to occur in norm al operations and if it occurs will only exist for a short tim e (Leaks or negligent use). In these areas, Increased Safety Lum inaires are used and are generally provided with gaskets and special lam p holders in case of fittings. These equipm ents are m anufactured as per IS 8224/1976 and IS 6381/1972.
HAZARDOUS AR
It should be noted that fittings com plying with the requirem ents as specified in IS 8224/1976 are not suitable for gases or ovapour having ignition tem perature below 200 C. The following is the list of gases or vapours known to have self/auto ignition
otem perature below 200 C.
1. Ethyl nitrate 2. Isopropyl nitrate3. Carbon disulphide 4. Acetaldehyde5. Diethyl ether 6. Diproplyl ether7. Dibutyl ether 8. Diam yl ether9. Dihexyl ether 10. Benxaldyhyde
11. Ethyl M ethyl ether 12. Diethyl peroxide
Tem perature Classes
Ignition tem perature is the lowest tem perature at which a flam m able gas m ixture ignites. Flam m able vapours and gases can be
classified into tem perature classes according to their ignition tem perature. Surface tem perature of the lum inaire is likely to be
higher than am bient tem perature due to heat generated during fire or explosion inside the enclosure. The m axim um surface
tem perature of the lum inaire m ust always be lower than the ignition tem perature of the gas m ixture present in the air.
Lum inaire of appropriate specified tem perature class should be selected based on the ignition tem perature of the gas.
Dust proof / Dust-tight
Lum inaires are m anufactured as per IS 4012 / IS 4013-1967 and are recom m ended to be installed in industries where in
addition to the recognized explosives, m any other dusts including practically all organic and inorganic dust, (dust of m etals are
flam m able to som e extent depending on the particle size), specific gravity of dust etc. are present.
Dusts have been broadly classified into the following groups.
Class 1 Dust which ignite and propagate flam e readily, the source of heat required for ignition being sm all.
Class 2 Dust which ignite readily with flam e but require a larger source of ignition.
Class 3 Dust which do not ignite.
Dust-tight lum inaires are recom m ended for locations laden with Class 1 Dust. For other class of dust, dustproof lighting fittings
m ay be used.
Temperature Class Maximum Surface Temperature
of Luminaires ( C)
T1 450
T2 300
T3 200
T4 135
T5 100
T6 85
z
S AREA LIGHTING
Group of Enclosures
I
II A
Gas or Vapour
M ethane (fire dam p)
Am m onia, Industrial m athane*, Blast furnace gas, Carbon m onoxide, Propane, Butane, Pentane, Hexane, Heptane, Iso-Octane, Decane, Benzene, Xylene, Cyclohexane, Acetone, Ethyl m ethyl Ketone, M ethyl acetate, Ethyl acetate, N-propyl acetate, N-butyl acetate, Am yl acetate, Chlorothylene, M ethanol, Ethanol, ISO-butanol, N-Butanol, Am yl alcohol, Ethyl nitrate.
Hydrogen
II B
II C
1, 3-Butadine, Ethylene, Diethyl ether, Ethylene oxide, Town gas, Coke-oven gas.
Drip proof IP 22
Rain proof IP 23
Splash proof IP 34
Dustproof / Splashproof IP 54
Dustproof / Jetproof IP 55
Dust-tight / Jetproof IP 65
Ingress Protection System for Enclosures (IP)
This system outlined in IS 2147 is designed to indicate the standard degree of protection: (a) from ingress of solids and (b) from
ingress of liquids which enclosures m ay exhibit and m ust not be confused with explosion protection techniques.
For lum inaires the following IP num bers com m only apply :
Higher the num erical of the first and second characteristic, the greater degree of protection the enclosure offers. E.g. Jetproof
IP 55 m eets all the less onerous degrees such as IP 22, IP 23, IP 34 and IP 54.
Testing Authorities
All our Flam eproof and Increased safety lum inaires are tested and Certified by Central Institure of M ining and Fuel Research
(CIM FR), Dhanbad.
Standards
(a)Flam eproof Construction : IS:2148-2004 (IEC 60079-1/2001)
(b)General design, rating, perform ance & T-class : IS:13346-2004 (IEC 60079-0/2000)
(c ) W eatherproof construction IP-65 : IS:12063-1987 (IEC 60529/1989)
Table 3 of IS 2148/1981
G roup of Enclosures Suitable for Particular Flam m able G as or Vapour (Clauses 1.4 and 3.1.2)
*Industrial M ethane includes m ethane m ixed with not m ore than 10% by volum e of hydrogen.Town gas m ay contain not m ore
than 57% by volum e of hydrogen and not m ore than 16% by volum e of carbon m onoxide, the rem ainder being a m ixture of
paraffin hydrocarbons and inert gas.
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Note :
Due to our continuous efforts in developing products, im provem ent - Bajaj Electricals Lim ited reserves the right to m ake changes in the
design and data without any prior notice.
BJFB 150/200 BC/ES (LM 6)
Lum inaire Body
Lam p
Tem perature Range
CIM FR Certificate
Epoxy finish Cast Alum inium LM 6 housing.
Toughened Type A flat glass.
Two cable entries of 3/4” BS conduit are provided.
Lam p holder suitable for lam p type will be provided (2 pin BC / 3 pin BC / E 27)
Suitable for 100W /150W /200W GLS, 80W /125W H PM V,70W SV/M H/150W M H (E27) 160W M LL, 26W CFL - Retrofit.
80W M V/70W SV/ 70W M H/100W GLS - T4
125M V/150W M H/150W GLS/200W GLS /160W M LL T3
26W CFL - Retrofit - T6
Suitable for Zone 1 & 2 areas where explosive gasses specified under gas groups IIA & IIB are present. This is a non integral lum inaire suitable for indoor application. Separate control gear to be used in case of HID lam ps.
CIM FR/TC/SR/H909 DATED 08.02.2008
Flam eproofBulkhead Lum inaire
Lum inaire Body
Lam p
Tem perature Range
Ingress Protection
CIM FR Certificate No
Note
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant borosilicate tubular glass held in two alum inium cups. Two cable entries of 3/4” BS conduit are provided.
Single or Twin 36W /40 W Fluorescent Tubular lam p/28W T5 lam p. Special variant for 18W /20 W FTL also available.
T6
IP 65
Suitable for Zone 1 & 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
CIM FR/TC/SR/H798 DTD 11.01.2008
External Stove Enam eled Reflector can be provided as an additional feature
Flam eproof Lum inaire For Fluorescent Tubular Lam p
BJFFTL 136/236, 140/240, 128/228
228 135
380
BJFFTL-140 BJFFTL-240
235
170
267
170
125
235
BJFFTL-140/240
1590
235
Lum inaire Body
Lam p
Tem perature Range
Ingress Protection
CIM FR Certificate No
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant and toughened glass enclosure type A with BC/E27 lam p holder Painted M S wire guard. Two cable entries of 3/4” BS conduit are provided. Separate flam eproof control gear box of suitable rating to be used for HID lam ps.
Suitable for 80/125W M V, 70W SV/M H, 150W M H (E27), 200W GLS, 160W M LL, 23W /26W Retrofit CFL lam p.
150W M H (E27), 200W GLS, 160W M LL - T3125W M V - T480W M V/ 70W SV/ 70W M H - T523W /26W Retrofit CFL - T6
Ideal for use in Zone 1 & 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
IP 65
CIM FR/ TC/ SR/ H 1136 DATED 19.03.2008
Flam eproof Non-integral W ellglass Lum inaire
BJFW 80/125 M V NI BC/ES LM 6
247
402
Lum inaire Body
Lam p
Tem perature Range
Ingress Protection
CM RI Certificate No
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant and toughened glass enclosure type A. Painted M S wire guard. Two cable entries of 3/4” BS conduit are provided. Available in cast iron version for special application areas also. This is a non-integral lum inaire. Separate flam eproof control gear box to be used as per the lam p rating.
250 W HPM V, 400W HPM V, 250W HPSV, 400W HPSV, 400W M H lam p.
250W /400W HPM V - T3, 250W HPSV - T5, 400W HPSV/M H - T4
Suitable for use in Zone 1 & 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
IP 65
CM RI/TC/P/H/382 DTD 18.08.2006
BJFW 400 M V CA (NI)BJFW 400 SV/M H CA (NI) / BJFW 250 SV (NI)
Flam eproof Non-integral W ellglass Lum inaire
530
Ø 335
100100
A = 3 Nos.,Ø12.5 HOLE
AAA
BJFW 250 M V I CABJFW 150 SV/M H I
Lum inaire Body
Lam p
Tem perature Range
Ingress Protection
CIM FR Certificate No
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant and toughened glass enclosure type A. Painted M S wire guard. Two cable entries of 3/4” BS conduit are provided. This is an integral lum inaire HID Ballast & accessories fitted inside the housing.
Suitable for 150W HPSV/M H lam p, 250 HPM V lam p.
T 4
Ideal for use in Zone 1& 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
IP 65
CM RI/TC/P/H 378 DATED 18.08.2006
Flam eproofIntegralW ellglassLum inaireForHPM V/HPSV And M etalHalide Lam p
Lum inaire Body
Lam p
Tem perature Range
Ingress Protection
CIM FR Certificate No
Note
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant and toughened glass enclosure-type A. Painted M S wire guard. Two cable entries of 3/4” BS conduit are provided. This is an integral lum inaire. HID ballast and accessories fitted inside the housing.
Suitable for 80W /125 W HPM V, 70W HPSV/M H lam p.
T 4
Ideal for use in Zone 1& 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
IP 65
CIM FR/TC/SR/H840 DATED 24.01.2008
This lum inaire can also be used as non integral for 250W M V/150SV/150 M H BJFW 250 W M V (NI), BJFW 150 W SV (NI), BJFW 150 W M H (NI)
Flam eproof Integral W ellglass Lum inaire For HPM V/HPSV and M etal Halide Lam p
BJFW 80/125 M V I CA BC/ES BJFW 70 SV/M H I
245
480
BJFW 250 M V I
530
Ø 247
Lum inaire Body
Lam p
Tem perature Range
Ingress Protection
CM RI CERTIFICATE NO
Cast Alum inium LM 6 Epoxy finish lam p housing. Heat resistant and toughened flat glass Type A. One Cable entry through 3/4” BS conduit. This is a non integral lum inaire and suitable flam eproof control gearbox should be separately used.
Ideal for use in zone 1 & 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
Suitable for 250 HPM V/250W HPSV/400W HPSV/400W M H.
250W M V - T5 , 400W SV/M H - T4, 250W SV T6.
IP 65
CM RI/TC/P/H 387 DTD. 21.08.2006
Flam eproof Non-integral Flood Light
BJFFL 250/400 NI
Lum inaire Body
Lam p
Tem perature Class
Ingress Protection
CM RI CERT.NO
Cast alum inum LM 6 yellow epoxy powder coated housing. Heat resistant and toughened type A glass enclosure. Two cable entries of 3/4” BS conduit are provided. Ideal for use in zone 1 & 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
Suitable for Neon spiral lam p 75VA
T6
IP 65
CM RI /TC/P/H354 dt. 10th Aug 2006.
Flam eproof Aviation Obstruction Light
BJFAOL 01
700
Ø375
100 100
500
BJFFL 250/400 M V NI
495
Ø 38
Ø245
BJFAOL-01
BJFC 80W /125W /250W M V CABJFC 70W /150W SV/M HBJFC 400 M V/SV/M H
Housing
Lam p
Tem perature Range
Ingress Protection
CIM FR Certificate No
Die-cast alum inium LM 6 housing. Com pletely wired with control gear accessories. Three cable entries of 3/4” BS conduit are provided. Ideal for use in ZONE 1 & 2 areas where explosive gasses specified under gas groups IIA & IIB are present.
Versions available for 80W /125W /250W HPM V lam p, 70W /150W HPSV/M etal Halide lam p and 3 X 26W CFL. Also available for 400W HPM V/400W HPSV/M H lam p.
T6
IP65
CIM FR/TC/SR/H800 DTD. 15/01/2008 for 80W /125W /250 HPM V,70/150SV/M HCIM FR/TC/SR/H837 DTD. 23/01/2008 for 400W HPM V/HPSV/M H lam ps.
Flam eproofControlGearBox
Lum inaire Body
Lam p
Ingress Protection
Tem perature Class
CM RI Certification
Applicable standards and certification
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant well glass cover. Painted M S wire guard. Two cable entries of 3/4” BS conduit are provided. This is a dustproof, dust tight, totally enclosed, increased safety non-integral lum inaire. Separate increased safety control gear box to be used as per Zone 2 the lam p rating.
Suitable for 150/200W GLS, 160W M LL , 80W /125W HPM V, 70W HPSV - Elliptical, 23 W Retrofit CFL.
IP 65
CM RI/TC/P/H1335 DTD 10.11.1998
lS : 2147-1962 Specification for Degree of protectionlS : 8224-1976 Specification for Electric Lighting Fittings for Divn. 2 areaslS: 6381/1972 Specification of Electrical Apparatus with type of
protection 'e'lS: 6381/1972 Specification of construction of Electrical Apparatus with
type of protection 'e'lS : 13947 (part 1) 1993 for lP 65
Increased Safety Non-Integral W ellglass Lum inaire
BJDP/DT/TE/ISW -200 LM 6 NI
Volts 250 Max. GLS HPMV MLL SV CFL
150W 200W 80W 125W 160W 70W 23W
Temperature Classification T5 T5 T6 T5 T5 T6 T6
320
210
335 205
235
238
111
Lum inaire Body
Lam p
CM RI Certification
Applicable standards and certification
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant and toughened glass cover-type A. Painted M S wire guard. Two cable entries of 3/4” BS conduit are provided.
Ideal for use in areas where explosive or ignitable gases are present (Division 2 areas).
Ingress protection: IP 65
Suitable for 80/125W M V lam p, 70W HPSV lam p. HID ballasts and accessories wired inside the housing. It can also be used for 250W HPM V as non integral lum inaire. Separate control gear box to be used for 250W HPM V version - BJISW 250 M V NI.
This lum inaire has been tested and certified by CM RI, Dhanbad vide their letter Ref. No.CM RI/TC/P/H1260 DATED 14-10-1999CM RI/TC/ADDEN/H193 DATED 16-02-2000CCE No. R1(1) 136/ALPINE/418 dated 15-02-2000
IS :2147-1962 Specification for Degree of protectionlS :8224/1976 Specification for Electric Lighting Fittings for Divn.2 areaslS:6381/1972 Specification of construction of Electrical Apparatus with type of protection 'e'lS :13947 (part 1) 1993 for IP 65.
Lum inaire Body
Lam p
Ingress Protection
CM RI Certification
Applicable standards and certification
Cast Alum inium LM 6 housing with Epoxy finish. Heat resistant well glass cover, Ideal for use in Zone 2. Painted M S wire guard. Two cable entries of 3/4” BS conduit are provided. This is a dustproof, dust tight, totally enclosed, increased safety non-integral lum inaire. Separate increased safetycontrolgearboxtobeusedasperthelam prating.
Suitable for 150/200W GLS, 160W M LL , 80W /125W HPM V, 70W HPSV - Elliptical, 23 W Retrofit lam p.
IP 65
CM RI/TC/P/H1455 Dated 26.11.98 for BJISW
lS :2147-1962 Specification for Degree of protectionlS :8224-1976 Specification for Electric Lighting Fittings for Zone 2 areaslS:6381/1972 Specification of Electrical Apparatus with type of protection 'e'lS:6381/1972 Specification of construction of Electrical Apparatus with type of protection 'e'lS : 13947 (part 1) 1993 for lP 65
Increased Safety Non-Integral W ellglass Lum inaire
BJISW 80/125 M V NI/70 SV NI BJISW 80/125 M V (I)BJISW 70SV (I)
210
320
Volts 250 Max. GLS HPMV BLL SV CFL
150W 200W 80W 125W 160W 70W 23W
Temperature Classification T5 T5 T6 T5 T5 T6 T6225
390
Increased Safety Integral W ellglass Lum inaire
BJISCG 80/125/250 M VBJISCG 70/150 SV
HOUSING
Lam p
Ingress Protection
CM RI Certificate No
Die-cast alum inium LM 6 housing. Com pletely wired with control gear accessories. Three cable entries of 3/4” BS conduit are provided.
Ideal for use in Zone 1 & 2 areas where explosive or ignitable gas m ixtures are present for a short period.
Suitable for 80/125W HPM V, 70W HPSV, 150W HPSV, 250M V lam p. Prewired with open construction ballast and accessories suitable for lam p rating.
IP 65
CM RI /TC/P/SL/H1454 DTD 26/11/1998 for 80W /125W HPM V, 70W HPSVCM RI/TC/P/H1361 DTD 12.01.1999 for 250W HPM V, 150W HPSV
210
103
215
200 C/C
102 C/C210
Control Gear Boxfor Increased Safety Lum inaire
FLAM EPROOF LUM INAIRES PRODUCT RANGE DETAILS
SR. NO. CIM FR REVALIDATION CIM FR SUPPLIM ENTARY ITEM CAT NOS. LAM P RATING TEM P. IP ZONE GASCERTIFICATE CERTIFICATE TO RANGE GROUPNO. & DATE REVALIDATION
CERTIFICATE NO. & DATE
1 CIM FR/TC/SR/H840 CIM FR/TC/S/693 BJFW - 250 BJFW - 250 M V (NI) 250 W HPM V T 3 IP 65 1 & 2 IIA & IIB
DTD. 24.01.2008 DTD.19.11.2008 FLAM EPROOF/W P BJFW - 80 M V (I) 80 W HPM V IP 65 1 & 2 IIA & IIB
W ELLGLASS BJFW - 125 M V (I) 125 W HPM V T 4 IP 65 1 & 2 IIA & IIB
LUM INAIRES BJFW - 70 SV (I) 70 W HPSV IP 65 1 & 2 IIA & IIB
BJFW - 70 M H (I) 70 W M H IP 65 1 & 2 IIA & IIB
BJFW - 150 SV (NI) 150 W HPSV T 4 IP 65 1 & 2 IIA & IIB
BJFW - 150 M H (NI) 150 W M H T 4 IP 65 1 & 2 IIA & IIB
BJFW - 150 M H (E27) (I) 150 W M H (E27) T 3 IP 65 1 & 2 IIA & IIB
BJFW - 3X26 CFL (I) 3X26 W CFL T 6 IP 65 1 & 2 IIA & IIB
BJFW - 300 GLS 300 W GLS IP 65 1 & 2 IIA & IIB
2 CIM FR/TC/SR/H1136 CIM FR/TC/S/694 BJFW - 80/125 BJFW - 80 M V (NI) 80 W HPM V T 5 IP 65 1 & 2 IIA & IIB
DTD. 19.03.2008 DTD.19.11.2008 FLAM EPROOF/W P BJFW - 125 M V (NI) 125 W HPM V T 4 IP 65 1 & 2 IIA & IIB
NON-INTEGRAL BJFW - 70 SV (NI) 70 W HPSV T 5 IP 65 1 & 2 IIA & IIB
W ELLGLASS BJFW - 70 M H (NI) 70 W M H T 5 IP 65 1 & 2 IIA & IIB
LUM INAIRES BJFW - 150 SV (E27)(NI) 150 W M H (E27) T 3 IP 65 1 & 2 IIA & IIB
BJFW - 1X23 CFL (NI) 23 W CFL T 6 IP 65 1 & 2 IIA & IIB
BJFW - 3X26 CFL (NI) 3X26 W CFL T 6 IP 65 1 & 2 IIA & IIB
BJFW - 200 GLS (NI) 200 W GLS T 3 IP 65 1 & 2 IIA & IIB
BJFW - 160 M LL (NI) 160 W M LL T 3 IP 65 1 & 2 IIA & IIB
3 CIM FR/TC/SR/H800 CIM FR/TC/S/696 BJFC - 80/125/250 BJFC - 80 M V 80 W HPM V IP 65 1 & 2 IIA & IIB
DTD.15.01.2008 DTD.19.11.2008 FLAM EPROOF/W P BJFC - 125 M V 125 W HPM V IP 65 1 & 2 IIA & IIB
CONTROL BJFC - 250 M V 250 W HPM V T 6 IP 65 1 & 2 IIA & IIB
GEAR BOX BJFC - 70 SV 70 W HPSV T 6 IP 65 1 & 2 IIA & IIB
BJFC - 70 M H 70 W M H T 6 IP 65 1 & 2 IIA & IIB
BJFC - 150 SV 150 W HPSV T 6 IP 65 1 & 2 IIA & IIB
BJFC - 150 M H 150 W M H T 6 IP 65 1 & 2 IIA & IIB
BJFC - 3X26 CFL 3X26 W CFL T 6 IP 65 1 & 2 IIA & IIB
4 CIM FR/TC/SR/H837 CIM FR/TC/S/697 BJFC - 400 M V BJFC - 400 M V 400 W HPM V T 6 IP 65 1 & 2 IIA & IIB
DTD.23.01.2008 DTD.19.11.2008 FLAM EPRROF/W P BJFC - 400 SV 400 W HPSV T 6 IP 65 1 & 2 IIA & IIB
CONTROL BJFC - 400 M H 400 W M H T 6 IP 65 1 & 2 IIA & IIB
GEAR BOX
5 CIM FR/TC/SR/H909 CIM FR/TC/S/695 BJFB - 150/200 BJFB - 80 M V 80 W HPM V T 4 - 1 & 2 IIA & IIB
DTD.08.02.2008 DTD.19.11.2008 FLAM EPROOF BJFB - 125 M V 125 W HPM V T 3 - 1 & 2 IIA & IIB
BULK HEAD BJFB - 70 SV 70 W HPSV T 4 - 1 & 2 IIA & IIB
LUM INAIRE BJFB - 70 M H 70 W M H T 4 - 1 & 2 IIA & IIB
BJFB - 150 SV 150 W HPSV T 3 - 1 & 2 IIA & IIB
BJFB - 150 M H 150 W M H T 3 - 1 & 2 IIA & IIB
BJFB - 160 M LL 160 W M LL T 3 - 1 & 2 IIA & IIBBJFB - 1X26 CFL 26 W CFL T 6 - 1 & 2 IIA & IIBBJFB - 100 GLS 100 W GLS T 4 - 1 & 2 IIA & IIBBJFB - 150 GLS 150 W GLS T 3 - 1 & 2 IIA & IIBBJFB - 200 GLS 200 W GLS T 3 - 1 & 2 IIA & IIB
6 CIM FR/TC/SR/H798 CIM FR/TC/S/H438 BJFFTL - 140 BJFFTL - 140 1X40 W FTL T 6 IP 65 1 & 2 IIA & IIBDTD.11.01.2008 DTD.03.09.2008 FLAM EPROOF/W P BJFFTL - 240 2X40 W FTL IP 65 1 & 2 IIA & IIB
FLUORESCENT BJFFTL - 136 1X36 W FTL T 6 IP 65 1 & 2 IIA & IIBCIM FR/Amend/FLP/Oct./588 TUBE LIGHT BJFFTL - 236 2X36 W FTL IP 65 1 & 2 IIA & IIBDTD.17.10.2008 LUM INAIRE BJFFTL - 120 1X20 W FTL T 6 IP 65 1 & 2 IIA & IIB
BJFFTL - 220 2X20 W FTL IP 65 1 & 2 IIA & IIBBJFFTL - 118 1X18 W FTL T 6 IP 65 1 & 2 IIA & IIBBJFFTL - 218 2X18 W FTL IP 65 1 & 2 IIA & IIBBJFFTL - 128 1X28 W (T5) IP 65 1 & 2 IIA & IIBBJFFTL - 228 2X28 W (T5) IP 65 1 & 2 IIA & IIBBJFFTL - 114 1X14 W (T5) IP 65 1 & 2 IIA & IIBBJFFTL - 214 2X14 W (T5) IP 65 1 & 2 IIA & IIBBJFFTL - 1X20 CFL 1X20 W CFL T 6 IP 65 1 & 2 IIA & IIB
7 CIM FR/TC/SR/H808 BJFJB - 100 BJFJB - 100 - - IP 65 1 & 2 IIA & IIBDTD.16.01.2008 FLAM EPROOF/W P
JUNCTION BOX
FLAM EPROOF LUM INAIRES PRODUCT RANGE DETAILS
SR. NO. CIM FR REVALIDATION CIM FR SUPPLIM ENTARY ITEM CAT NOS. LAM P RATING TEM P. IP ZONE GASCERTIFICATE CERTIFICATE TO RANGE GROUPNO. & DATE REVALIDATION
CERTIFICATE NO. & DATE
8 CM RI/TC/P/H382 BJFW - 400 M V (NI) BJFW - 400 M V (NI) 400 W HPM V T 3 IP 65 1 & 2 IIA & IIBDTD.18.08.2006 FLP/W P BJFW - 400 SV (NI) 400 W HPSV T 4 IP 65 1 & 2 IIA & IIB
W ELLGLASS BJFW - 400 M H (NI) 400 W M H T 4 IP 65 1 & 2 IIA & IIBREVALIDATION NOT LUM INAIRE BJFW - 250 SV (NI) 250 W HPSV T 5 IP 65 1 & 2 IIA & IIBREQUIRED AS TESTEDBYCM RI AS PER REVISED BIS STANDARDS
9 CM RI/TC/P/H387 BJFFL-250/400 M V BJFFL - 250 M V (NI) 250 W HPM V T 5 IP 65 1 & 2 IIA & IIBDTD.21.08.2006 NON-INTEGRAL BJFFL - 250 SV (NI) 250 W HPSV T 6 IP 65 1 & 2 IIA & IIB
FLAM EPROOF/W P BJFFL - 400 SV (NI) 400 W HPSV T 4 IP 65 1 & 2 IIA & IIBREVALIDATION NOT FLOOD LIGHT BJFFL - 400 M H (NI) 400 W M H T 4 IP 65 1 & 2 IIA & IIBREQUIRED AS TESTED LUM INIAREBYCM RI AS PER REVISED BIS STANDARDS
10 CM RI/TC/P/H378 BJFW - 250 M V (I) BJFW - 250 M V (I) 250 W HPM V T 4 IP 65 1 & 2 IIA & IIBDTD.18.08.2006 FLAM EPROOF/W P BJFW - 150 SV (I) 150 W HPSV T 4 IP 65 1 & 2 IIA & IIB
W ELLGLASS BJFW - 150 M H (I) 150 W M H T 4 IP 65 1 & 2 IIA & IIBREVALIDATION NOT LUM INIAREREQUIRED AS TESTEDBYCM RI AS PER REVISED BIS STANDARDS
11 CM RI/TC/P/H354 BJFAOL - 01 BJFAOL - 01 NEON SPIRAL T 6 IP 65 1 & 2 IIA & IIBDTD.10.08.2006 FLP/W P LAM P 75 VA
AVIATIONREVALIDATION NOT OBSTRUCTIONREQUIRED AS TESTED LIGHTBYCM RI AS PER REVISED BIS STANDARDS
INCREASED SAFETY LUM INAIRES
SR. ITEM CAT CM RI CERTIFICATE CM RI ADDENDUM S & SUPPLIM ENTARY
NO. NO. & DATE NOS. DATE CERTIFICATES
NOS. DATE ADDITIONS
1 BJDP/DT/TE/ISW -200 INCREASED SAFETY BJDP/DT/TE/ISW -200 CM RI/TC/P/H1335 CM RI/TC/P/H1259 23 W CFL LAM P 70 W HPSV LAM P W ITH
W ELLGLASS FITTING SUITABLE FOR INCREASED SAFETY DTD.10.11.1998 DTD.14.10.1999 BUILT IN IGNITOR LAM P HOLDER 2 PIN / 3 PIN / E 27
150 / 200 W GLS LAM P 80 / 125 W HPM V LAM P NON INTEGRAL BAKELITE / GFP / PORCELAIN CONNECTOR
160 W M LL LAM P IP 65 W ELLGLASS FITTING
2 BJISW - 80/125 INCREASED SAFETY BJISW - 80/125 CM RI/TC/P/H1455 CM RI/TC/S/H1365 23 W CFL LAM P 70 W HPSV LAM P
W ELLGLASS FITTING SUITABLE FOR INCREASED SAFETY DTD.26.11.1998 DTD.15.11.1999 W ITH OR W ITHOUT BUILT IN ADOPTOR
150 / 200 W GLS LAM P 80 / 125 W HPM V LAM P NON INTEGRAL LAM P HOLDER 2 PIN/ 3 PIN / E 27
160 W M LL LAM P IP 65 W ELLGLASS FITTING
3 BJISW - 80/125 (I) & BJISW - 250 M V (NI) BJISW - 80/125 (I) CM RI/TC/P/H1260 CM RI/TC/ADDEN/H193 BJISW - 80/125 (I) INTEGRAL & BJISW - 250 M V (NI)
INCREASED SAFETY W ELLGLASS FITTING INCREASED SAFETY DTD.14.10.1999 DTD.16.02.2000 NON INTEGRAL INCREASED SAFETY
SUITABLE FOR 80/125 W /250 W HPM V LAM P INTEGRAL W ELLGLASS FITTING
70 W HPSV LAM P W ITH BUILT IN IGNITOR W ELLGLASS FITTING
70 W /150 W HPSV LAM P W ITHOUT IGNITOR IP 65
4 BJISCG - 80/125 M V INCREASED SAFETY/ W P BJISCG - 80/125 CM RI/TC/P/SL/H1454 CM RI/TC/S/H1310 (A) 70 W (B) CONNECTOR AS PORCELAIN / GFP / ELM EX
CONTROL GEAR BOX IP 65 INCREASED SAFETY DTD.26.11.1998 DTD.29.10.1999
CONTROL GEAR BOX
5 BJISCG - 250 HPM V INCREASED SAFETY BJISCG - 250 CM RI/TC/P/H1361
CONTROL GEAR BOX SUITABLE FOR INCREASED SAFETY DTD.12.11.1999
250 W HPM V / 150 W HPSV LAM P IP 65 CONTROL GEAR BOX
BRANCH PHONE FAX E-mail
AHMEDABAD106, Sakar III, Off Ashram RoadNavrangpura, Ahmedabad 380 014. 079-27543964, 27543967, 27540397 079-27543950 lum_am_ahm@ bajajelectricals.com
BANGALOREBajaj Bhavan, No. 16, Residency Road,Bangalore 560 025. 080-22235486, 22238984, 22275505 080-22214878, 22275505 lum_am_ban@ bajajelectricals.com
BHUBANESW ARKharavela Nagar, Janpath, Bhubaneswar 751 001. 0674-2390697, 2396980, 2394052 0674-2390294 lum_am_bhu@ bajajelectricals.com
CHANDIGARHSCO 52, Sector-26, Madhya Marg,Chandigarh 160 026. 0172-4303211 0172-2792932 lum_am_chd@ bajajelectricals.com
CHENNAINavin's Presidium, 8th Floor,A- Block, Old No.103-A, Nelson Manickam Road,Aminjikarai, Chennai 600 029 044-42162200 044-42163300 lum_am_che@ bajajelectricals.com
COCHINCRL House, 42/1107, Tata Oil Mills Road,Cochin 682 018. 0484-2391119, 2396128, 2392039 0484-2391744 lum_am_ccn@ bajajelectricals.com
DELHI1/10, Asaf Ali Road, New Delhi 110 002 011-23236055, 23233056, 23235057 011-23230214 lum_am_del@ bajajelectricals.com
GUW AHATIAgarwal House, Christian Basti,G. S. Road, Guwahati 787 005. 0361-2346497, 2346498, 2346499 0361-2346496 lum_am_guw@ bajajelectricals.com
HARYANA1/10, Asaf Ali Road, New Delhi 110 002 011-43725500 011-23230214 lum_am_hyr@ bajajelectricals.com
HYDERABADH. No. 6-3-1090/2, 3rd Floor, Vithal Das Chambers,Rajbhavan Road, Somaji Guda, Hyderabad 500 082. 040-23442932, 23442933, 2344293 040-23302745 lum_am_hyd@ bajajelectricals.com
INDORECommerce House, 3 rd Floor, 7 Race Course Road,Indore 452 003, MP. 0731-2548909/10/18 0731-2548911 lum_am_ind@ bajajelectricals.com
JAIPURRaghukamal Niwas, M. I. Road, Jaipur 302 001. 0141-2377364, 2369541, 2369542 0141-2374261 lum_am_jai@ bajajelectricals.com
KOLKATA10, Ganesh Chandra Avenue, Kolkata 700 013. 033-22379270, 22377657, 22216638 033-22259111 lum_am_cal@ bajajelectricals.com
LUCKNOWBajaj Bhavan, 21/32 A, Tilak Marg,Lucknow 226 001. 0522-2620595, 2613549 0522-2626513 lum_am_luc@ bajajelectricals.com
MUMBAIHarchandrai House, 3rd Floor, 81, Queens Road,Marine Lines, Mumbai 400 002. 022-22089091 022-22089193 lum_am_mum@ bajajelectricals.com
NAGPUR2nd Floor, Saraf Court, Opp. Yashwant Stadium,Dhantoli, Nagpur. 0712-2440318, 2440319 0712-2420102 lum_am_war@ bajajelectricals.com
NOIDAFlat No. 505-507, 5th Floor, Vikrant Tower,4, Rajendra Place, Pusa Road, New Delhi 110 008. 011-25711961, 25861963, 25861964 011-25861962 lum_am_del2@ bajajelectricals.com
PATNAKashi Place, Dak Bunglow Road, Patna 800 001. 0612-2231427, 2220155, 2225911 0612-2231978, 2231427 lum_am_pat@ bajajelectricals.com
PUNEManeck Hall, 2, General Thimmayya Road,Pune 411 001. 020-26360801, 26361321, 26360703 020-26360698 lum_am_pun@ bajajelectricals.com
RAIPURBajaj Bhavan, G. E. Road,Near Mahaveer Garden, Raipur 492 001. 0771-2263986, 2263976, 2660166 0771-2263310 lum_am_rai@ bajajelectricals.com
LUMINAIRES HEAD OFFICE and R&D OFFICE15/17, Sant Savta marg, Reay Road,Mumbai 400 010. 022-2376 5000 Fax: 022-2373 0504
HEAD OFFICE51, Mahatma Gandhi Road, Mumbai 400 001. 022-22043780, 22851462, 22875135 Fax: 022-22828250
REGISTERED OFFICE