hazardous area basics
DESCRIPTION
Basics for Electrical Equipment in Hazardous Areas by HexagonTRANSCRIPT
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 1/10
HexagonTechnologySiteNavigation NavigationonThisPage
ExHomePage HazardousAreasTraining GasGroups
TechnicalBooks Zones HazardousHazardousAreaBasics TemperatureClasses Area
ATEXDirectives TypesofProtection(Table) BasicsUsefulLinks EquipmentProtectionLevels(EPL)
Contact StandardsGeneral
EquipmentStandards
InstallationStandards DustStandards
EquipmentMarking(NewPage) TypesofProtectionExplanation
(NewPage)
ElectricalApparatusandHazardousAreas(Published2007)
Thisbookgivesfullinformationofbothelectricalandnonelectricalhazardousareatechnology
andcoversterminology,equipmentmarking,ATEX,DSEAR,AreaClassification,TypesofProtectionetc.
Clickherefordetails
Hazardousareasaredefinedbythreemaincriteria:ThetypeofhazardThelikelihoodofthehazardbeingpresentinflammableconcentrationsThe(auto)ignitiontemperatureofthehazardousmaterial
Thetypeofhazard(Groups)
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 2/10
Thehazardwillbeintheformofagas,vapour,dustorfibre.GasesandVapours
Gasesandvapoursarecategorizedintermsoftheirignitionenergyorthemaximumexperimentalsafegap(inrespectofflameproofprotection).ThiscategorizationleadstotheGasGroups:
Mining SurfaceIndustryGroupI GroupII
MethaneIIA IIB IIC
Propane Ethylene Hydrogen
(Thegasesnotedinthetablearetypicalgasesforeachgroup.)
GroupIICisthemostseveregroup.Hazardsinthisgroupcanbeignitedveryeasilyindeed.
EquipmentmarkedassuitableforGroupIICisalsosuitableforIIBandIIA.
EquipmentmarkedassuitableforIIBisalsosuitableforIIAbutNOTforIIC.
Ifequipmentismarked,forexample,ExeIIT4thenitissuitableforallsubgroupsIIA,IIBandIIC.
DustsandFibres(GroupIII)
GroupIIIissubdividedintothreesubgroups:
IIIACombustibleflyings
IIIBNonconductivedust
IIICElectricallyconductivedusts
Dustsandfibresarealsodefinedintermsoftheirignitionpropertiesincludingdustcloudignitionproperties.
BACKTOTOP
Thelikelihoodofthehazardbeingpresentinflammableconcentrations(Zones)
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 3/10
Thelikelihoodofthehazardbeingpresentinflammableconcentrationswillvaryfromplacetoplace.Alocationveryclosetoanopensourceofhazardwillhaveahighlikelihoodofaflammableatmosphere.Ontheotherhand,outsideaflangedpipecontainingaflammableliquid,thelikelihoodofaflammableatmospherebeingpresentismuchlowersinceitwillonlyoccuriftheflangeleaks.Ratherthanworkwithaninfiniterangeofpossibilities,threezonesaredefined.
GasesandVapours
Therearethreezonesforgasesandvapours:
Zone0 Flammableatmospherehighlylikelytobepresentmaybepresentforlongperiodsorevencontinuously
Zone1 Flammableatmospherepossiblebutunlikelytobepresentforlongperiods
Zone2Flammableatmosphereunlikelytobepresentexceptfor
shortperiodsoftimetypicallyasaresultofaprocessfaultcondition.
Zonezeroisthemostseverezone(thehighestprobabilityofflammableatmospherepresence).Equipmentforthiszoneneedstobeverywellprotectedagainstprovidingasourceofignition.
Dusts
Therearethreezonesfordusts:
Zone20 Dustcloudlikelytobepresentcontinuouslyorforlongperiods
Zone21 Dustcloudlikelytobepresentoccasionallyinnormaloperation
Zone22 Dustcloudunlikelytooccurinnormaloperation,butifitdoes,willonlyexistforashortperiod
(Thepresenceofdustlayersdoesnotautomaticallyleadtothedustzone.Thelikelihoodofthedustlayerbeingdisturbedtocreateacloudneedstobeconsidered.Dustlayersalsoneedcarefulconsiderationintermsofignitiontemperature.Becausethedustlayercanmaketheequipmentunderithotterthennormal,afactorofsafetyisappliedtothelayerignitiontemperature.)
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 4/10
BACKTOTOP
The(auto)ignitiontemperatureofthehazardousmaterial(TemperatureClasses)Aswellasconsideringtheprotectionagainstelectricalarcsandsparksignitingaflammableatmosphere,considerationneedstobegiventothesurfacetemperatureofequipment.(Mostelectricalapparatusdissipatessomeheat!)Flammablematerialsarecategorizedaccordingtotheirignitiontemperature.Again,ratherthanworkwithaninfiniterange,sixtemperatureclassesaredefinedasfollows:
TClass Hazardswhichwillnotigniteattemperaturesbelow:T1 450CT2 300CT3 200CT4 135CT5 100CT6 85C
ThebiggertheTnumbertheloweristhetemperature.
TheTemperatureclassificationwillbemarkedonitemsofequipment.IfthehazardousareainwhichyouareinstallingequipmenthasgasesorvapourswithalowautoignitiontemperaturethenyouwillneedequipmentwithabiggerTNumbersoastoensurethatanyhotsurfacesontheequipmentwillnotignitethehazard.
Forexample,ifahazardhasanautoignitiontemperatureof180C,thenitwouldbesafetouseequipmentwhichismarkedT6orT5orT4.ItwouldnotbesafetouseequipmentmarkedT3orT2orT1asthisequipmentcouldexhibitsurfacetemperatureswhicharehotenoughtoignitethehazardousatmosphere.
Don'tforgetthat,unlessthecertificationdocumentsstateotherwise(inwhichcasetherewillbeanadditiontotheTClassificationcodeontheequipmentlabelsuchasT4(60CAmb))theequipmentisonlycertifiedinambienttemperaturesupto40C.Ifexposedtohighertemperaturestherearetwopossibledangers.FirstthestatedTClasstemperaturemaybeexceededandsecondlysafetycomponentswithintheequipmentcouldfailtoanunsafecondition.Ifyouexpectequipmenttobesubjectedtotemperaturesabove40C(suchasindirectsunshineorinaroofspace)youshouldinstallequipmentwhichiscertifiedforahigherambienttemperature.
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 5/10
BACKTOTOP
ProtectingElectricalApparatustomakeitsuitableforuseinhazardousareas
Electricalapparatusforuseinhazardousareasneedstobedesignedandconstructedinsuchawaythatitwillnotprovideasourceofignition.Therearetenrecognizedtypesofprotectionforhazardousareaelectricalapparatus.Eachtypeofprotectionachievesitssafetyfromignitionindifferentwaysandnotallareequallysafe.InadditiontotheequipmentbeingsuitablefortheGasGroupandtheTemperatureClassrequired,thetypeofprotectionmustbesuitableforthezoneinwhichitistobeinstalled.Thedifferenttypesofprotectionandthezonesforwhichtheyaresuitableareasfollows:
Forinformationonequipmentmarking,clickhere(opensnewpage)
TypesofProtectionforGas/VapourHazards
SeealsoinformationonTypesofProtection,Clickhere(opensnewpage)
EquipmentCode Description
Suitableforzones...
EquipmentCategory...
Exia Intrinsicsafety'ia' 0,1,2 1GExib Intrinsicsafety'ib' 1,2 2GExic IntrinsicSafety'ic' 2 3GExd Flameproofprotection 1,2 2GExp Purge/pressurizedprotection 1,2 2G
Expx Purge/pressurizedprotection'px' 1,2 2G
Expy Purge/pressurizedprotection'py' 1,2 2G
Expz Purge/pressurizedprotection'pz' 2 3G
Exe Increasedsafety 1,2 2GExm Encapsulation 1,2 2GExma Encapsulation 0,1,2 1G
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 6/10
Exmb Encapsulation 1.2 2GExmc Encapsulation 2 3GExo Oilimmersion 1,2 2GExq Sand/powder(quartz)filling 1,2 2GExn Typenprotection 2 3GExs Specialprotection Normally1and2
EquipmentcomplyingwithEuropean(CENELEC)standardswillfrequentlybearthecodeEEx(asopposedtoEx)ButnotethattheuseofEExisbeingphasedout,andequipmentdesignedandcertifiedtothelatesteditionsoftheEuropeanStandardswillbecodedEx...(asopposedtoEEx...).
Ingeneral,theEuropeanstandardsforhazardousareaelectricalequipmentaretechnicallyidenticaltotheIEC(InternationalElectrotechnicalCommission)standards.EquipmentmanufacturersoftenhhavetheirequipmentdesignscertifiedtoboththeEuropeanandIECrequirementssothattheycanmarkettheirequipmentworldwide.Thisdoes,unfortunatelymaketheequipmentlabellingplatemorecomplex.
TypesofProtectionforEquipmentforDustHazardLocations
EquipmentCode Description
SuitableforZones...
EquipmentCategory..
tDA20 Protectionbyenclosure 20,21,22 1DtDB20 Protectionbyenclosure 20,21,22 1DiaD IntrinsicSafety 20,21,22 1DmaD Encapsulation 20,21,22 1DtDA21 Protectionbyenclosure 21,22 2DtDB21 Protectionbyenclosure 21,22 2DibD IntrinsicSafety 21,22 2DmbD Encapsulation 21,22 2DpD Pressurization 21,22 2D
tDA22 Protectionbyenclosure 22 3DtDB22 Protectionbyenclosure 22 3D
icD IntrinsicSafety 22 3D
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 7/10
BACKTOTOP
EquipmentProtectionLevelsEPLFrom2007onwards,theIECTechnicalStandardsintheseriesIEC60079,andinparticularIEC60079Part14,haverecognisedthattheremaybeoccasionswhereitisnecessarytoincrease,abovethenormallevels,theprotectionagainstignitionsources.Thisconceptallowsforconsiderationofrisk(ieconsequencesofanexplosion)asopposedtojusttheprobabilityofaflammableatmosphereexistingtheconventionalselectioncriteriabetweenthetypesofprotectionandthezoneofuse.
ThreeEquipmentProtectionLevelsarespecifiedasshowninthetablebelow.
InnormalcircumstancestheeffectoftheseEPLswillbetoretainthenormalzone/equipmentprotectionrelationship.If,however,theriskisconsideredespeciallysevere,thentherequiredEPLforthezonemaybeincreased.Similarly,iftheriskisdeemedtobeespeciallysmallornegligible,theEPLmaybereducedfromthenorm.
ThefollowingtwotablesshowthenormalrelationshipbetweenEPLandzone,andtheEPLawardedtoeachtypeofprotection.
EquipmentProtectionLevel(EPL) NormalApplicableZone(s)
Ga 0(and1and2)Gb 1(and2)Gc 2
EquipmentCode Description EPLExia Intrinsicsafety'ia' GaExib Intrinsicsafety'ib' GbExic IntrinsicSafety'ic' GcExd Flameproofprotection GbExp Purge/pressurizedprotection GbExpx Purge/pressurizedprotection'px' GbExpy Purge/pressurizedprotection'py' GbExpz Purge/pressurizedprotection'pz' Gc
Exe Increasedsafety Gb
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 8/10
Exm Encapsulation GbExma Encapsulation GaExmb Encapsulation GbExo Oilimmersion GbExq Sand/powder(quartz)filling GbExn Typenprotection Gc
Exs SpecialprotectionRefertoequipment
markinganddocumentation
Fordusthazards,theEPLsareasfollows:
EquipmentProtectionLevel(EPL) NormalApplicableZone(s)
Da 20(and21and22)Db 21(and22)Dc 22
BACKTOTOP
StandardsTherearevariousstandardswhichgivedetailsofhazardousarearequirements.Inthemain,theIECstandardsarenowparallelvotedbyCENELEC(Europe).Newstandardsarebeingintroducedatabewilderingrateanditisalwaysworthcheckingagainst,forexample,theBSIwebsite.(SeeUsefulLinksPage)
ItisimportantforequipmentdesignerstodesigntothelatesteditionofATEXharmonisedstandardstheuptodatelistcanbefoundontheECATEXwebsite.(SeeUsefulLinksPage)
Gradually,thetechnicalstandardsforthetechnologyforgas/vapourhazardsandthosefordusthazardsarebeingincorporatedintothesameseries.ForexampleIEC6007910coversareaclassificationIEC60079101dealswithgas/vapourhazardsandIEC60079102dealswithdusthazards.Similarnumberingwillapplyforotheraspectssuchasinstallation.
Toplevelstandard
EN11271Explosiveatmospheres:Explosionpreventionandprotection.Part1:Basicconceptsandmethodology
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 9/10
StandardsforEquipment
IEC60079ELECTRICALAPPARATUSFOREXPLOSIVEGASATMOSPHERESPart0GeneralrequirementsPart1ConstructionandtestofflameproofenclosuresofelectricalapparatusPart2ElectricalapparatustypeofprotectionpPart3SparktestapparatusforintrinsicallysafecircuitsPart4MethodoftestforignitiontemperaturePart5PowderfillingqPart6OilimmersionoPart7Increasedsafetye'Part11ConstructionandtestofintrinsicallysafeandassociatedapparatusPart15Electricalapparatusforexplosivegasatmospheres,typeofprotectionnPart18EncapsulationmPart25IntrinsicallysafesystemsPart26Specialrequirementsforconstructiontestandmarkingofzone0electrical
apparatusPart27Fieldbusintrinsicallysafeconcept(FISCO)
StandardsforInstallationetc.(gasesandvapours)
IEC60079ELECTRICALAPPARATUSFOREXPLOSIVEGASATMOSPHERESPart10ClassificationofhazardousareasPart14Installation(andselection)ofequipmentinhazardousareasPart17InspectionandmaintenanceofequipmentNotethatthe60079seriesofstandardswillgraduallyaddressdusthazardsaswellasgas/vapourhazards.Thestandardnumberwillhaveanadditionalsuffix1or2.Thus,forexample,6124114(seebelow)willbereplacedby60079142[installationforequipmentindusthazards],with60079141dealingwithinstallationsingas/vapourhazards.
StandardsforDustHazardEquipmentandInstallation
IEC61241ELECTRICALAPPARATUSFORUSEINTHEPRESENCEOFCOMBUSTIBLEDUST
Part0GeneralRequirements
-
5/24/2015 HazardousAreaBasics
http://www.hexagontech.co.uk/hazard_basics.htm 10/10
Part1ProtectionbyenclosuretDPart21MethodsfordeterminingtheminimumignitiontemperatureofdustsPart22MethodfordeterminingtheresistivityofdustinlayersPart23MethodfordeterminingminimumignitionenergyofdustairmixturesPart4TypeofprotectionpDPart10ClassificationofareaswherecombustibledustsareormaybepresentPart11ProtectionbyintrinsicsafetyiDPart14SelectionandinstallationPart17InspectionandmaintenancePart18ProtectionbyencapsulationmD
BACKTOTOP
ATEXDirectives
FordetailedinformationonATEX,pleasenavigatetotheATEXpagesonthiswebsite
BACKTOTOPHexagon_Technology