Hexagon Technology Site Navigation Navigation on This Page Ex Home Page Hazardous Areas Training Gas Groups Technical Books Zones Hazardous Hazardous Area Basics Temperature Classes Area ATEX Directives Types of Protection (Table) Basics Useful Links Equipment Protection Levels (EPL) Contact Standards General Equipment Standards Installation Standards Dust Standards Equipment Marking (New Page) Types of Protection Explanation (New Page) Electrical Apparatus and Hazardous Areas (Published 2007) This book gives full information of both electrical and nonelectrical hazardous area technology and covers terminology, equipment marking, ATEX, DSEAR, Area Classification, Types of Protection etc. Click here for details Hazardous areas are defined by three main criteria: The type of hazard The likelihood of the hazard being present in flammable concentrations The (auto) ignition temperature of the hazardous material The type of hazard (Groups)

Upload: waelai

Post on 10-Sep-2015

215 views

Category:

Documents


0 download

DESCRIPTION

Basics for Electrical Equipment in Hazardous Areas by Hexagon

TRANSCRIPT

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 1/10

    HexagonTechnologySiteNavigation NavigationonThisPage

    ExHomePage HazardousAreasTraining GasGroups

    TechnicalBooks Zones HazardousHazardousAreaBasics TemperatureClasses Area

    ATEXDirectives TypesofProtection(Table) BasicsUsefulLinks EquipmentProtectionLevels(EPL)

    Contact StandardsGeneral

    EquipmentStandards

    InstallationStandards DustStandards

    EquipmentMarking(NewPage) TypesofProtectionExplanation

    (NewPage)

    ElectricalApparatusandHazardousAreas(Published2007)

    Thisbookgivesfullinformationofbothelectricalandnonelectricalhazardousareatechnology

    andcoversterminology,equipmentmarking,ATEX,DSEAR,AreaClassification,TypesofProtectionetc.

    Clickherefordetails

    Hazardousareasaredefinedbythreemaincriteria:ThetypeofhazardThelikelihoodofthehazardbeingpresentinflammableconcentrationsThe(auto)ignitiontemperatureofthehazardousmaterial

    Thetypeofhazard(Groups)

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 2/10

    Thehazardwillbeintheformofagas,vapour,dustorfibre.GasesandVapours

    Gasesandvapoursarecategorizedintermsoftheirignitionenergyorthemaximumexperimentalsafegap(inrespectofflameproofprotection).ThiscategorizationleadstotheGasGroups:

    Mining SurfaceIndustryGroupI GroupII

    MethaneIIA IIB IIC

    Propane Ethylene Hydrogen

    (Thegasesnotedinthetablearetypicalgasesforeachgroup.)

    GroupIICisthemostseveregroup.Hazardsinthisgroupcanbeignitedveryeasilyindeed.

    EquipmentmarkedassuitableforGroupIICisalsosuitableforIIBandIIA.

    EquipmentmarkedassuitableforIIBisalsosuitableforIIAbutNOTforIIC.

    Ifequipmentismarked,forexample,ExeIIT4thenitissuitableforallsubgroupsIIA,IIBandIIC.

    DustsandFibres(GroupIII)

    GroupIIIissubdividedintothreesubgroups:

    IIIACombustibleflyings

    IIIBNonconductivedust

    IIICElectricallyconductivedusts

    Dustsandfibresarealsodefinedintermsoftheirignitionpropertiesincludingdustcloudignitionproperties.

    BACKTOTOP

    Thelikelihoodofthehazardbeingpresentinflammableconcentrations(Zones)

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 3/10

    Thelikelihoodofthehazardbeingpresentinflammableconcentrationswillvaryfromplacetoplace.Alocationveryclosetoanopensourceofhazardwillhaveahighlikelihoodofaflammableatmosphere.Ontheotherhand,outsideaflangedpipecontainingaflammableliquid,thelikelihoodofaflammableatmospherebeingpresentismuchlowersinceitwillonlyoccuriftheflangeleaks.Ratherthanworkwithaninfiniterangeofpossibilities,threezonesaredefined.

    GasesandVapours

    Therearethreezonesforgasesandvapours:

    Zone0 Flammableatmospherehighlylikelytobepresentmaybepresentforlongperiodsorevencontinuously

    Zone1 Flammableatmospherepossiblebutunlikelytobepresentforlongperiods

    Zone2Flammableatmosphereunlikelytobepresentexceptfor

    shortperiodsoftimetypicallyasaresultofaprocessfaultcondition.

    Zonezeroisthemostseverezone(thehighestprobabilityofflammableatmospherepresence).Equipmentforthiszoneneedstobeverywellprotectedagainstprovidingasourceofignition.

    Dusts

    Therearethreezonesfordusts:

    Zone20 Dustcloudlikelytobepresentcontinuouslyorforlongperiods

    Zone21 Dustcloudlikelytobepresentoccasionallyinnormaloperation

    Zone22 Dustcloudunlikelytooccurinnormaloperation,butifitdoes,willonlyexistforashortperiod

    (Thepresenceofdustlayersdoesnotautomaticallyleadtothedustzone.Thelikelihoodofthedustlayerbeingdisturbedtocreateacloudneedstobeconsidered.Dustlayersalsoneedcarefulconsiderationintermsofignitiontemperature.Becausethedustlayercanmaketheequipmentunderithotterthennormal,afactorofsafetyisappliedtothelayerignitiontemperature.)

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 4/10

    BACKTOTOP

    The(auto)ignitiontemperatureofthehazardousmaterial(TemperatureClasses)Aswellasconsideringtheprotectionagainstelectricalarcsandsparksignitingaflammableatmosphere,considerationneedstobegiventothesurfacetemperatureofequipment.(Mostelectricalapparatusdissipatessomeheat!)Flammablematerialsarecategorizedaccordingtotheirignitiontemperature.Again,ratherthanworkwithaninfiniterange,sixtemperatureclassesaredefinedasfollows:

    TClass Hazardswhichwillnotigniteattemperaturesbelow:T1 450CT2 300CT3 200CT4 135CT5 100CT6 85C

    ThebiggertheTnumbertheloweristhetemperature.

    TheTemperatureclassificationwillbemarkedonitemsofequipment.IfthehazardousareainwhichyouareinstallingequipmenthasgasesorvapourswithalowautoignitiontemperaturethenyouwillneedequipmentwithabiggerTNumbersoastoensurethatanyhotsurfacesontheequipmentwillnotignitethehazard.

    Forexample,ifahazardhasanautoignitiontemperatureof180C,thenitwouldbesafetouseequipmentwhichismarkedT6orT5orT4.ItwouldnotbesafetouseequipmentmarkedT3orT2orT1asthisequipmentcouldexhibitsurfacetemperatureswhicharehotenoughtoignitethehazardousatmosphere.

    Don'tforgetthat,unlessthecertificationdocumentsstateotherwise(inwhichcasetherewillbeanadditiontotheTClassificationcodeontheequipmentlabelsuchasT4(60CAmb))theequipmentisonlycertifiedinambienttemperaturesupto40C.Ifexposedtohighertemperaturestherearetwopossibledangers.FirstthestatedTClasstemperaturemaybeexceededandsecondlysafetycomponentswithintheequipmentcouldfailtoanunsafecondition.Ifyouexpectequipmenttobesubjectedtotemperaturesabove40C(suchasindirectsunshineorinaroofspace)youshouldinstallequipmentwhichiscertifiedforahigherambienttemperature.

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 5/10

    BACKTOTOP

    ProtectingElectricalApparatustomakeitsuitableforuseinhazardousareas

    Electricalapparatusforuseinhazardousareasneedstobedesignedandconstructedinsuchawaythatitwillnotprovideasourceofignition.Therearetenrecognizedtypesofprotectionforhazardousareaelectricalapparatus.Eachtypeofprotectionachievesitssafetyfromignitionindifferentwaysandnotallareequallysafe.InadditiontotheequipmentbeingsuitablefortheGasGroupandtheTemperatureClassrequired,thetypeofprotectionmustbesuitableforthezoneinwhichitistobeinstalled.Thedifferenttypesofprotectionandthezonesforwhichtheyaresuitableareasfollows:

    Forinformationonequipmentmarking,clickhere(opensnewpage)

    TypesofProtectionforGas/VapourHazards

    SeealsoinformationonTypesofProtection,Clickhere(opensnewpage)

    EquipmentCode Description

    Suitableforzones...

    EquipmentCategory...

    Exia Intrinsicsafety'ia' 0,1,2 1GExib Intrinsicsafety'ib' 1,2 2GExic IntrinsicSafety'ic' 2 3GExd Flameproofprotection 1,2 2GExp Purge/pressurizedprotection 1,2 2G

    Expx Purge/pressurizedprotection'px' 1,2 2G

    Expy Purge/pressurizedprotection'py' 1,2 2G

    Expz Purge/pressurizedprotection'pz' 2 3G

    Exe Increasedsafety 1,2 2GExm Encapsulation 1,2 2GExma Encapsulation 0,1,2 1G

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 6/10

    Exmb Encapsulation 1.2 2GExmc Encapsulation 2 3GExo Oilimmersion 1,2 2GExq Sand/powder(quartz)filling 1,2 2GExn Typenprotection 2 3GExs Specialprotection Normally1and2

    EquipmentcomplyingwithEuropean(CENELEC)standardswillfrequentlybearthecodeEEx(asopposedtoEx)ButnotethattheuseofEExisbeingphasedout,andequipmentdesignedandcertifiedtothelatesteditionsoftheEuropeanStandardswillbecodedEx...(asopposedtoEEx...).

    Ingeneral,theEuropeanstandardsforhazardousareaelectricalequipmentaretechnicallyidenticaltotheIEC(InternationalElectrotechnicalCommission)standards.EquipmentmanufacturersoftenhhavetheirequipmentdesignscertifiedtoboththeEuropeanandIECrequirementssothattheycanmarkettheirequipmentworldwide.Thisdoes,unfortunatelymaketheequipmentlabellingplatemorecomplex.

    TypesofProtectionforEquipmentforDustHazardLocations

    EquipmentCode Description

    SuitableforZones...

    EquipmentCategory..

    tDA20 Protectionbyenclosure 20,21,22 1DtDB20 Protectionbyenclosure 20,21,22 1DiaD IntrinsicSafety 20,21,22 1DmaD Encapsulation 20,21,22 1DtDA21 Protectionbyenclosure 21,22 2DtDB21 Protectionbyenclosure 21,22 2DibD IntrinsicSafety 21,22 2DmbD Encapsulation 21,22 2DpD Pressurization 21,22 2D

    tDA22 Protectionbyenclosure 22 3DtDB22 Protectionbyenclosure 22 3D

    icD IntrinsicSafety 22 3D

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 7/10

    BACKTOTOP

    EquipmentProtectionLevelsEPLFrom2007onwards,theIECTechnicalStandardsintheseriesIEC60079,andinparticularIEC60079Part14,haverecognisedthattheremaybeoccasionswhereitisnecessarytoincrease,abovethenormallevels,theprotectionagainstignitionsources.Thisconceptallowsforconsiderationofrisk(ieconsequencesofanexplosion)asopposedtojusttheprobabilityofaflammableatmosphereexistingtheconventionalselectioncriteriabetweenthetypesofprotectionandthezoneofuse.

    ThreeEquipmentProtectionLevelsarespecifiedasshowninthetablebelow.

    InnormalcircumstancestheeffectoftheseEPLswillbetoretainthenormalzone/equipmentprotectionrelationship.If,however,theriskisconsideredespeciallysevere,thentherequiredEPLforthezonemaybeincreased.Similarly,iftheriskisdeemedtobeespeciallysmallornegligible,theEPLmaybereducedfromthenorm.

    ThefollowingtwotablesshowthenormalrelationshipbetweenEPLandzone,andtheEPLawardedtoeachtypeofprotection.

    EquipmentProtectionLevel(EPL) NormalApplicableZone(s)

    Ga 0(and1and2)Gb 1(and2)Gc 2

    EquipmentCode Description EPLExia Intrinsicsafety'ia' GaExib Intrinsicsafety'ib' GbExic IntrinsicSafety'ic' GcExd Flameproofprotection GbExp Purge/pressurizedprotection GbExpx Purge/pressurizedprotection'px' GbExpy Purge/pressurizedprotection'py' GbExpz Purge/pressurizedprotection'pz' Gc

    Exe Increasedsafety Gb

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 8/10

    Exm Encapsulation GbExma Encapsulation GaExmb Encapsulation GbExo Oilimmersion GbExq Sand/powder(quartz)filling GbExn Typenprotection Gc

    Exs SpecialprotectionRefertoequipment

    markinganddocumentation

    Fordusthazards,theEPLsareasfollows:

    EquipmentProtectionLevel(EPL) NormalApplicableZone(s)

    Da 20(and21and22)Db 21(and22)Dc 22

    BACKTOTOP

    StandardsTherearevariousstandardswhichgivedetailsofhazardousarearequirements.Inthemain,theIECstandardsarenowparallelvotedbyCENELEC(Europe).Newstandardsarebeingintroducedatabewilderingrateanditisalwaysworthcheckingagainst,forexample,theBSIwebsite.(SeeUsefulLinksPage)

    ItisimportantforequipmentdesignerstodesigntothelatesteditionofATEXharmonisedstandardstheuptodatelistcanbefoundontheECATEXwebsite.(SeeUsefulLinksPage)

    Gradually,thetechnicalstandardsforthetechnologyforgas/vapourhazardsandthosefordusthazardsarebeingincorporatedintothesameseries.ForexampleIEC6007910coversareaclassificationIEC60079101dealswithgas/vapourhazardsandIEC60079102dealswithdusthazards.Similarnumberingwillapplyforotheraspectssuchasinstallation.

    Toplevelstandard

    EN11271Explosiveatmospheres:Explosionpreventionandprotection.Part1:Basicconceptsandmethodology

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 9/10

    StandardsforEquipment

    IEC60079ELECTRICALAPPARATUSFOREXPLOSIVEGASATMOSPHERESPart0GeneralrequirementsPart1ConstructionandtestofflameproofenclosuresofelectricalapparatusPart2ElectricalapparatustypeofprotectionpPart3SparktestapparatusforintrinsicallysafecircuitsPart4MethodoftestforignitiontemperaturePart5PowderfillingqPart6OilimmersionoPart7Increasedsafetye'Part11ConstructionandtestofintrinsicallysafeandassociatedapparatusPart15Electricalapparatusforexplosivegasatmospheres,typeofprotectionnPart18EncapsulationmPart25IntrinsicallysafesystemsPart26Specialrequirementsforconstructiontestandmarkingofzone0electrical

    apparatusPart27Fieldbusintrinsicallysafeconcept(FISCO)

    StandardsforInstallationetc.(gasesandvapours)

    IEC60079ELECTRICALAPPARATUSFOREXPLOSIVEGASATMOSPHERESPart10ClassificationofhazardousareasPart14Installation(andselection)ofequipmentinhazardousareasPart17InspectionandmaintenanceofequipmentNotethatthe60079seriesofstandardswillgraduallyaddressdusthazardsaswellasgas/vapourhazards.Thestandardnumberwillhaveanadditionalsuffix1or2.Thus,forexample,6124114(seebelow)willbereplacedby60079142[installationforequipmentindusthazards],with60079141dealingwithinstallationsingas/vapourhazards.

    StandardsforDustHazardEquipmentandInstallation

    IEC61241ELECTRICALAPPARATUSFORUSEINTHEPRESENCEOFCOMBUSTIBLEDUST

    Part0GeneralRequirements

  • 5/24/2015 HazardousAreaBasics

    http://www.hexagontech.co.uk/hazard_basics.htm 10/10

    Part1ProtectionbyenclosuretDPart21MethodsfordeterminingtheminimumignitiontemperatureofdustsPart22MethodfordeterminingtheresistivityofdustinlayersPart23MethodfordeterminingminimumignitionenergyofdustairmixturesPart4TypeofprotectionpDPart10ClassificationofareaswherecombustibledustsareormaybepresentPart11ProtectionbyintrinsicsafetyiDPart14SelectionandinstallationPart17InspectionandmaintenancePart18ProtectionbyencapsulationmD

    BACKTOTOP

    ATEXDirectives

    FordetailedinformationonATEX,pleasenavigatetotheATEXpagesonthiswebsite

    BACKTOTOPHexagon_Technology