hardware description dcs centum vp - inspiring the world · hardware description dcs centum vp pt....
TRANSCRIPT
Hardware Description Hardware Description
DCS Centum VPDCS Centum VP
PT. Yokogawa IndonesiaWisma Aldiron Dirgantara 2nd floor, suite 202-209Jl. Jend. Gatot Subroto Kav.72 Jakarta 12780Phone : 021-799 0102, Fax : 021-799 0070
Training Services Center - SVDPrepared by:Nico Nyoto Raharjo
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Input-Output Module/Node. (19” Rack mounting type)
Input-Output Module/Node. (Cabinet mounting type)
LFCS (dengan RIO)
Field Control Unit (FCU)
FCSKapasitas I/O Modul :Sampai 8 node per FCS dan 5 I/O unit per node.
Vnet Card/Coupler
Power Supply Module
Control Processor
Card
Interface Card
RIO Bus Coupler
Hardware Description - FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
FCS
FCU
FIO
KFCS (With FIO) Kapasitas I/O Modul:Sampai 10 node per FCS (bisa di ekspan sampai 15 node) dan 8 I/O unit per node.
Power Supply Module
Control Processor
Card
Interface Card
Vnet Coupler Unit
I/O Modules
ESB Bus Module
Power Supply Module
ESB Bus Coupler Unit
Battery
Hardware Description - FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
FFCS (dengan FIO)
I/O Modules
Ekstensi Node Modul (ESB Bus)
Control Processor Cards
Power Supply
FIO Node
Vnet Coupler Units
Feature :Feature :
Kompak & bisa di ekspan
ukurannya 60% lebih kecil dari model standar.
Sangat cocok untuk sistem kontrol yang berskala kecil.
I/O node bisa diekspan sampai 3 node (local) & 14 node (remote – optional)
Konfigurasi standar Redundant.
Hardware Description - FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
FFCS (dengan FIO untuk Vnet I/P)Kapasitas I/O Modul:Bisa dikoneksikan sampai dengan 14 node.
Power Supply Modules
Control Processor Cards
Node Expansion Modules (ESB)
I/O Modules
Hardware Description - FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Power supply unitCP451 CPU module
SLOT 1 ~ SLOT 8SLOT 1 ~ SLOT 8
EC401 ESB bus coupler (Note)
Note: Dua slot I/O digunakan untuk ekstensi node.
Vnet/IPTampilan luar dari FFCS-L (AFV10)
Hardware Description - FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Battery Life Temperature
3 years 30 ºC atau kurang
1½ year 40 ºC atau kurang
9 months 50 ºC atau kurang
Maksimum waktu back-up 72 jam !
Mempertahankan memori database dalam prosesor selama listrik mati.
Hardware Description – Baterai FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Teknologi Pair & Spare YokogawaKehandalan sistem redundant yang sangat tinggi diterapkan pada field control unit (FCU) dengan dua modul prosesor, dengan masing-masing card mempunyai sepasang (“Pair”) microprocessor units (MPUs) yang membandingkan hasil proses dari masing-masing kalkulasi. Sedangkan processor cards kedua berfungsi sebagai cadangan ("Spare").
Konfigurasi “Pair & Spare” terdiri dari dua prosesor card yang independen beroperasi terus menerus di waktu yang sama. Satu prosesor mengontrol sistem setiap saat sedangkan yang lainnya bersiap siap menggantikan prosesor pertama tadi. Kedua prosesor harus berjalan dalam program sistem yang sama dan akan melakukan sinkronisasi dengan sempurna apabila suatu waktu terjadi perpindahan kontrol dari prosesor satu ke prosesor yang lainnya.
CPU melakukan proses secara independen dan setiap waktu akan melakukan proses sinkronisasi time
Proses pindah tanpa ganguan !!
Arsitektur CPU FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
I/O RacksI/O Racks
Bisa satu ataupun dua konfigurasi Power Supply
Dual redundant I/O bus
8 I/O slots per node/rack
10 nodes/racks per FCS (bisa diekspan sampai 15)
Standar panel 19“
Bus (Kabel) 1
Bus (Kabel) 2Vnet
Koneksi Redundant ke
kabel Vnet
ESB BusESB BusDual redundant
Kec. Transmisi: 128 Mbps
Jarak Transmisi :10 meter
FCU / CPUFCU / CPU
Bisa satu ataupun dua konfigurasi CPU FCS
Tipe Prosesor VR5432 (133 Mhz)
Kapasitas Memori: 32 MB
KFCS (Dengan FIO)
HKU (House HKU (House Keeping Unit)Keeping Unit)
Kecepatan Kipas
Temperatur udara dan
lingkungan
Arsitektur FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Remote area 2
Remote area 1
ER Bus CouplingER Bus Coupling
ModuleModule
Dual redundant
Max. 4 pairs per FCS
ER BUSER BUS Dual Dual redundantredundant 10 10 MbpsMbps 4 4 segmensegmen perper FCSFCS 185 m 185 m maksmaks (10 base 2)(10 base 2) 2 km 2 km dengandengan fiberfiber optikoptik
RemoteRemote I/O racksI/O racks I/O modules single or dual I/O modules single or dual redundantredundant Dual Dual redundantredundant couplingcoupling to ER bus to ER bus 8 I/O slots 8 I/O slots perper nodenode/rack/rack 8 racks 8 racks perper FCSFCS Option G3 Option G3 andand 7070°°CC 19 "x 5 U (22cm)19 "x 5 U (22cm)
Arsitektur FCS
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
KemampuanKemampuan Field Input/Output Field Input/Output
Terisolasi dari channel ke channel dan dari sistem ke lapangan
Penggantian komponen secara online
Sistem pengkabelan yang mudah
Full dual redundancy jika dibutuhkan
Mendukung tipe protokol field bus
FIO (Field Input/Output)
Arsitektur FCS - FIO
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
AFV10D Duplexed Field Control Unit (untuk Vnet/IP, FIO dan 19-inch rack mountable)
“Dip Switches” untuk mengkonfigurasi nomor station dan domain berada di bagian belakang modul
Domain Number
Station Number
Field Control Station – FFCS-L
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Kabel menggunakan kategori CAT5e (enhanced category 5) atau kabel UTP (Unshielded Twisted Pair) yang lebih tinggi spesifikasinya 1000BASE-T. Kebutuhan kabel juga disesuaikan dengan jarak koneksi antar sistem seperti dalam tabel di bawah ini :
Cable
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Untuk set nomor domain dari from 1 sampai 16Total bit yang di posisi “1” pada bit 4 sampai bit 8 ganjil maka ―> Bit 1 = “0”Total bit yang di posisi “1” pada bit 4 sampai bit 8 genap maka ―> Bit 1 = “1”
1
2
3
4
5
6
7
8
0 110000110
1 0 0 0 0 1 1 0
2² 2¹
4 + 2 = 6Total bit yang di posisi “1” pada bit 4 sampai bit 8 genap maka ―> Bit 1 = “1”
Setting Nomor Domain
OVERVIEW
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
OVERVIEW
Total bit yang di posisi “1” pada bit 2 sampai bit 8 ganjil maka ―> Bit 1 = “0”Total bit yang di posisi “1” pada bit 2 sampai bit 8 genap maka ―> Bit 1 = “1”
1
2
3
4
5
6
7
8
0 110010001
1 0 0 1 0 0 0 1
24 20
16 + 1 = 17Total bit yang di posisi “1” pada bit 2 sampai bit 8 genap maka ―> Bit 1 = “1”
Setting Nomor Station
Untuk set nomor station dari from 1 sampai 64