GE Enterprise Solutions GE Multilin 1 SR745 Feeder Management Relay Firmware Revision 5.10 Revised Release Notes GE Publication Number: GER-4108A Copyright © 2009 GE Multilin Overview Summary When upgrading the 745 relay from firmware version 5.00 to 5.10, or replacing an existing 745 relay with the new firmware version 5.10 relay, please ensure that the Ground CT connections are made as per Table 3-2 in the SR 745 Product Instruction Manual, under section 3.2.5.

Upload: deepthik27

Post on 16-Dec-2015

221 views

Category:

Documents


0 download

DESCRIPTION

GER-4108A

TRANSCRIPT

  • GE Enterprise Solutions

    GE Multilin 1

    SR745 Feeder Management Relay

    Firmware Revision 5.10 Revised Release Notes

    GE Publication Number: GER-4108A

    Copyright 2009 GE Multilin

    Overview

    Summary

    When upgrading the 745 relay from firmware version 5.00 to 5.10, or replacing an existing 745 relay with the new firmware version 5.10 relay, please ensure that the Ground CT connections are made as per Table 3-2 in the SR 745 Product Instruction Manual, under section 3.2.5.

  • Overview SR 745 Firmware 5.10 Release notes

    2 GE Multilin

    Release details

    E Product Manual updated to include Ground CT input connections If a 3-winding transformer is used,

    Please configure the new setting in Winding 1(3) setup. Assign proper ground input to the winding. Please refer to table 3-2, Typical Ground Input Connections, under section 3.2.5 of the SR 745 instruction Manual for correct assignment of Ground CT input connections.

    The table is listed below.

    Typical Ground Input Connections

    TRANSFORMER WINDING CONNECTIONS WINDING ASSOCIATED WITH GROUND INPUT

    WINDING 1 WINDING 2 WINDING 3 G1/2 (G10, H10) G2/3 (E12, F12)

    Wye Wye Winding 1 Winding 2

    Delta Delta Winding 1 Winding 2

    Delta Wye Winding 1 Winding 2

    Wye Delta Winding 1 Winding 2

    Wye Zig-Zag Winding 1 Winding 2

    Delta Zig-Zag Winding 1 Winding 2

    Wye Wye Wye Winding 1 Winding 2 Wye Wye Wye Winding 2 Winding 3 Wye Wye Wye Winding 3 Winding 1 Wye Wye Wye Winding 2 Winding 1 Wye Wye Wye Winding 3 Winding 2 Wye Wye Wye Winding 1 Winding 3 Wye Wye Delta Winding 1 Winding 2 Wye Wye Delta Winding 2 Winding 3 Wye Wye Delta Winding 3 Winding 1 Wye Wye Delta Winding 2 Winding 1 Wye Wye Delta Winding 3 Winding 2 Wye Wye Delta Winding 1 Winding 3 Wye Delta Wye Winding 1 Winding 2 Wye Delta Wye Winding 2 Winding 3 Wye Delta Wye Winding 3 Winding 1 Wye Delta Wye Winding 2 Winding 1 Wye Delta Wye Winding 3 Winding 2 Wye Delta Wye Winding 1 Winding 3 Wye Delta Delta Winding 1 Winding 2 Wye Delta Delta Winding 2 Winding 3 Wye Delta Delta Winding 3 Winding 1 Wye Delta Delta Winding 2 Winding 1 Wye Delta Delta Winding 3 Winding 2 Wye Delta Delta Winding 1 Winding 3 Delta Wye Wye Winding 1 Winding 2

  • SR 745 Revision 5.10 release notes Overview

    GE Multilin 3

    TRANSFORMER WINDING CONNECTIONS WINDING ASSOCIATED WITH GROUND INPUT

    WINDING 1 WINDING 2 WINDING 3 G1/2 (G10, H10) G2/3 (E12, F12)

    Delta Wye Wye Winding 3 Winding 1 Delta Wye Wye Winding 2 Winding 1 Delta Wye Wye Winding 3 Winding 2 Delta Wye Wye Winding 1 Winding 3 Delta Wye Delta Winding 1 Winding 2 Delta Wye Delta Winding 2 Winding 3 Delta Wye Delta Winding 3 Winding 1 Delta Wye Delta Winding 2 Winding 1 Delta Wye Delta Winding 3 Winding 2 Delta Wye Delta Winding 1 Winding 3 Delta Delta Delta Winding 1 Winding 2 Delta Delta Delta Winding 2 Winding 3 Delta Delta Delta Winding 3 Winding 1 Delta Delta Delta Winding 2 Winding 1 Delta Delta Delta Winding 3 Winding 2 Delta Delta Delta Winding 1 Winding 3 Delta Delta Wye Winding 1 Winding 2 Delta Delta Wye Winding 2 Winding 3 Delta Delta Wye Winding 3 Winding 1 Delta Delta Wye Winding 2 Winding 1 Delta Delta Wye Winding 3 Winding 2 Delta Delta Wye Winding 1 Winding 3

  • Overview SR 745 Firmware 5.10 Release notes

    4 GE Multilin

    Previous SR745 Firmware Version 5.10 Release Note

    Summary

    GE Multilin issues the SR745, 5.10 release that introduces new protection feature, ease of use and set-up program enhancements. Highlights of this release include:

    50G protection function for Delta winding

    Simplified Output Relay Programming

    This document contains the release notes for the 5.10 release of the SR745 relays.

    Affected products: SR745

    Date of release: Jul 31st, 2007

    Firmware revision: 5.10

    UPGRADE NOTICE:

    This version of the firmware should only be sent to SR745 relays that are of hardware version H or greater

    If users have SR745 relays with the version 5.00 firmware installed, they can download and install this new

    firmware to benefit from these enhancements. If these features are not being used, no upgrading of the relays is required.

    In the following change descriptions, a revision category letter is placed to the left of the description. Refer to the Appendix at the end of this document for additional details.

    Release Details

    Existing features modified N Enable 50G for Delta Winding

    The Ground Input (50G) is enabled for Delta winding. This will allow ground fault detection on Delta windings of the transformers. For a 2-winding transformer, the available ground inputs G1/2 is pre-assigned to winding 1 and G2/3 is pre-assigned to winding2. For a 3-winding transformer, flexibility is provided to the user to assign ground inputs G1/2 or G2/3 to a winding. One new setting per winding is provided to the user to select the ground input. By default, these are None.

    N Simplified Output Relay Programming

    The output relays can now be assigned from the Protection element settings. With this new feature the output relays can be energized either from Flexlogic or from the Protection element setting. By default, these settings have no relays selected. The relays are energized on OPERATE condition of the element. NOTE*** Users can still use the Flexlogic equations to assign the output contacts without using the new feature.

  • SR 745 Revision 5.10 release notes Overview

    GE Multilin 5

    N EnerVista SR745 Setup Software: Protection Summary

    The EnerVista SR745 Setup software is enhanced to provide a new Protection summary page. This page lists all the protection elements on a single page and allows the user to assign output relays to protection elements.

  • Overview SR 745 Firmware 5.10 Release notes

    6 GE Multilin

    Upgrade paths

    It is our recommendation that all customers upgrade to the latest version of SR745 firmware to take advantage of the latest developments and feature enhancements. Firmware upgrades can be easily preformed using the EnerVista 745R Setup software. This software can also convert settings files from an older version to the latest version and provides a difference report once the conversion has been completed. This Difference Report identifies new settings and additional information to assist the user during the upgrade.

  • SR 745 Revision 5.10 release notes Overview

    GE Multilin 7

    Appendix

    Change categories

    This document uses the following categories to classify the changes.

    Table 1: Revision categories

    Code Category Comments

    N New feature A separate feature added to the relay. Changes to existing features even if they significantly expand the functionality are not in this category

    G Change A neutral change that does not bring any new value and is not correcting any known problem

    E Enhancement Modification of an existing feature bringing extra value to the application

    D Changed, incomplete or false faceplate indications

    Changes to, or problems with text messages, LEDs and user pushbuttons

    R Changed, incomplete or false relay records

    Changes to, or problems with relay records (Oscillography, demand, fault reports, etc.)

    C Protocols and communications

    Changes to, or problems with protocols or communication features

    M Metering Metering out of specification or other metering problems

    P Protection out of specification Protection operates correctly but does not meet published specifications (example: delayed trip)

    U Unavailability of protection Protection not available in a self-demonstrating way so that corrective actions could be taken immediately

    H Hidden failure to trip Protection may not operate when it should

    F False trip Protection may operate when it should not

    B Unexpected restart Relay restarts unexpectedly

    The revision category letter is placed to the left of the change description.