Operating Instructions · 05/2010

Motor reactors

SINAMICS G130

SINAMICS

s

Page 2: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 2/26

Page 3: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 3/26

 Motor reactors

 ___________________ 

 ___________________ 

 ___________________ 

 ___________________ 

 ___________________ 

 

SINAMICS

SINAMICS G130Motor reactors

Operating Instructions

Control version V4.3 SP2

05/2010A5E00409660A

Safety information 1 

General 2 

Mechanical installation 3 

Electrical installation 4 

Technical specifications 5

Page 4: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 4/26

 Legal informationLegal information

Warning notice system

This manual contains notices you have to observe in order to ensure your personal safety, as well as to preventdamage to property. The notices referring to your personal safety are highlighted in the manual by a safety alertsymbol, notices referring only to property damage have no safety alert symbol. These notices shown below aregraded according to the degree of danger.

DANGER

indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING

indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION

with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

CAUTION

without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

NOTICEindicates that an unintended result or situation can occur if the corresponding information is not taken intoaccount.

If more than one degree of danger is present, the warning notice representing the highest degree of danger willbe used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating toproperty damage.

Qualified Personnel

The product/system described in this documentation may be operated only by personnel qualified for the specifictask in accordance with the relevant documentation for the specific task, in particular its warning notices andsafety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.

Proper use of Siemens products

Note the following:

WARNING

Siemens products may only be used for the applications described in the catalog and in the relevant technicaldocumentation. If products and components from other manufacturers are used, these must be recommendedor approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation andmaintenance are required to ensure that the products operate safely and without any problems. The permissibleambient conditions must be adhered to. The information in the relevant documentation must be observed.

Trademarks

All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in thispublication may be trademarks whose use by third parties for their own purposes could violate the rights of theowner.

Disclaimer of LiabilityWe have reviewed the contents of this publication to ensure consistency with the hardware and softwaredescribed. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, theinformation in this publication is reviewed regularly and any necessary corrections are included in subsequenteditions.

Siemens AGIndustry Sector Postfach 48 4890026 NÜRNBERGGERMANY

A5E00409660AⓅ 08/2010

Copyright © Siemens AG 2010.Technical data subject to change

Page 5: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 5/26

 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 5 

Table of contents

1 Safety information...................................................................................................................................... 7 

1.1 Warnings........................................................................................................................................7 

1.2 Safety and operating instructions...................................................................................................8 

2 General...................................................................................................................................................... 9 

3 Mechanical installation............................................................................................................................. 13 

4 Electrical installation ................................................................................................................................ 17 

5 Technical specifications........................................................................................................................... 19 

Page 6: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 6/26

Table of contents 

Motor reactors

6 Operating Instructions, 05/2010, A5E00409660A

Page 7: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 7/26

 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 7 

Safety information 1

1.1  Warnings

WARNING

Hazardous voltages are present when electrical equipment is in operation.Severe personal injury or substantial material damage may result if these warnings are notobserved.Only qualified personnel are permitted to work on or around the equipment.

This personnel must be thoroughly familiar with all the warnings and maintenanceprocedures described in these operating instructions.The successful and safe operation of this device is dependent on correct transport, proper storage and installation, as well as careful operation and maintenance.National safety guidelines must be observed.

DANGER

Five safety rules

When carrying out any kind of work on electrical devices, the "five safety rules" defined inEN 50110 must always be observed:

1.  Disconnect the system.

2.  Protect against reconnection.3.  Make sure that the equipment is de-energized.

4.  Ground and short-circuit.

5.  Cover or enclose adjacent components that are still live.

NOTICE

For a UL-approved system use 60/75°C copper conductors only.

Page 8: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 8/26

Safety information 

1.2 Safety and operating instructions 

Motor reactors

8 Operating Instructions, 05/2010, A5E00409660A

1.2  Safety and operating instructions

DANGER

This equipment is used in industrial high-voltage installations. During operation, thisequipment contains rotating and live, bare parts. For this reason, they could cause severeinjury or significant material damage if the required covers are removed, if they are used or operated incorrectly, or have not been properly maintained.When the machines are used in non-industrial areas, the installation location must beprotected against unauthorized access (protective fencing, appropriate signs).

Prerequisites

Those responsible for protecting the plant must ensure the following:

●  The basic planning work for the plant and the transport, assembly, installation,commissioning, maintenance, and repair work is carried out by qualified personnel and/or checked by experts responsible.

●  The operating manual and machine documentation are always available.

●  The technical specifications regarding the applicable installation, connection,environmental, and operating conditions are always observed.

●  The plant-specific assembly and safety guidelines are observed and personal protectionequipment is used.

●  Unqualified personnel are forbidden from using these machines and working near them.

This operating manual is intended for qualified personnel and only contain information andnotes relating to the intended purpose of the machines.

The operating manual and machine documentation are written in different languages asspecified in the delivery contracts.

Note

We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work.

Page 9: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 9/26

 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 9 

General 2 

Description

Motor reactors reduce the voltage load on the motor windings by reducing the voltagegradients at the motor terminals that occur during converter operation. At the same time, thecapacitive charge/discharge currents that occur at the converter output when long motor cables are used are reduced.

The maximum output frequency when a motor reactor is used is 150 Hz.

Note

The connecting cables to the Power Module must be kept as short as possible.

CAUTION

The surface temperature of the motor reactors may exceed 80°C.

CAUTION

The 100 mm cooling clearances above and to the side of the components must beobserved.

CAUTION

Provisions for component cooling must be made at the installation site. Power loss data aregiven in the technical specifications.

Page 10: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 10/26

General 

Motor reactors

10 Operating Instructions, 05/2010, A5E00409660A

Assignment of motor reactor and Power Module

Table 2- 1 Assignment of motor reactor and Power ModulePower Module Unit rating of the Power Module Suitable motor reactor

Line voltage 380 – 480 V 3 AC 

6SL3310-1GE32-1AAx 110 kW 6SL3000-2BE32-1AA0 

6SL3310-1GE32-6AAx 132 kW 6SL3000-2BE32-6AA0 

6SL3310-1GE33-1AAx 160 kW 6SL3000-2BE33-2AA0 

6SL3310-1GE33-8AAx 200 kW 6SL3000-2BE33-8AA0 

6SL3310-1GE35-0AAx 250 kW 6SL3000-2BE35-0AA0 

6SL3310-1GE36-1AAx 315 kW 6SL3000-2AE36-1AA0 

6SL3310-1GE37-5AAx 400 kW 6SL3000-2AE38-4AA0 

6SL3310-1GE38-4AAx 450 kW 6SL3000-2AE38-4AA0 6SL3310-1GE41-0AAx 560 kW 6SL3000-2AE41-0AA0 

Line voltage 500 – 600 V 3 AC 

6SL3310-1GF31-8AAx 110 kW 6SL3000-2AH31-8AA0 

6SL3310-1GF32-2AAx 132 kW 6SL3000-2AH32-4AA0 

6SL3310-1GF32-6AAx 160 kW 6SL3000-2AH32-6AA0 

6SL3310-1GF33-3AAx 200 kW 6SL3000-2AH33-6AA0 

6SL3310-1GF34-1AAx 250 kW 6SL3000-2AH34-5AA0 

6SL3310-1GF34-7AAx 315 kW 6SL3000-2AH34-7AA0 

6SL3310-1GF35-8AAx 400 kW 6SL3000-2AH35-8AA0 

6SL3310-1GF37-4AAx 500 kW 6SL3000-2AH38-1AA0 

6SL3310-1GF38-1AAx 560 kW 6SL3000-2AH38-1AA0 

Line voltage 660 – 690 V 3 AC 

6SL3310-1GH28-5AAx 75 kW 6SL3000-2AH31-0AA0 

6SL3310-1GH31-0AAx 90 kW 6SL3000-2AH31-0AA0 

6SL3310-1GH31-2AAx 110 kW 6SL3000-2AH31-5AA0 

6SL3310-1GH31-5AAx 132 kW 6SL3000-2AH31-5AA0 

6SL3310-1GH31-8AAx 160 kW 6SL3000-2AH31-8AA0 

6SL3310-1GH32-2AAx 200 kW 6SL3000-2AH32-4AA0 

6SL3310-1GH32-6AAx 250 kW 6SL3000-2AH32-6AA0 

6SL3310-1GH33-3AAx 315 kW 6SL3000-2AH33-6AA0 

6SL3310-1GH34-1AAx 400 kW 6SL3000-2AH34-5AA0 

6SL3310-1GH34-7AAx 450 kW 6SL3000-2AH34-7AA0 

6SL3310-1GH35-8AAx 560 kW 6SL3000-2AH35-8AA0 

6SL3310-1GH37-4AAx 710 kW 6SL3000-2AH38-1AA0 

6SL3310-1GH38-1AAx 800 kW 6SL3000-2AH38-1AA0 

Page 11: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 11/26

General 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 11 

Using a motor reactor and dv/dt filter to limit the voltage gradient and transients

IGBT converter switching frequencies result in high voltage gradients (dv/dt) at the converter 

output. If long motor cables are used, this leads to an additional current load on theconverter due to capacitive charge/discharge currents. The high voltage gradients, and theresulting transients at the motor terminals, cause the motors' electrical winding load toincrease as compared with direct on-line operation. In conjunction with the connected cablecapacitances, the motor reactors with their adapted inductances reduce the capacitivecharge/discharge currents in the motor cables and, as a function of these motor cables, limitthe voltage gradient (dv/dt) and the transients ÛLL at the motor terminals.

Û /U LL N Û /U LL N Û /U LL N

2

1

0

5

6

4

3

0 100 200 300m

8// 1 8// 1

2

1

0

5

6

4

3

0 100 200 300m

GYGW

&DEOHOHQJWK

GYGW

&DEOHOHQJWK

:LWKRXWRXWSXWVLGHRSWLRQV

:LWKPRWRUUHDFWRU 

:LWKGYGWILOWHUZLWK9ROWDJH3HDN/LPLWHU 

GYGWLQN9wV

GYGWLQN9wV

GYGWLQN9wV

 Figure 2-1 Using a motor reactor and dv/dt filter to limit the voltage gradient and transients

Page 12: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 12/26

General 

Motor reactors

12 Operating Instructions, 05/2010, A5E00409660A

Page 13: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 13/26

 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 13 

Mechanical installation 3 

Dimension drawing

        K        

      D        

        K        

Q

D

Q

Q

        K

        

OO

O

D

D

D

Q

      Q        

Q

G

Q

        K        

        K        

        K        

D

D

0RXQWLQJKROH

7\SH 7\SH

 Figure 3-1 Dimension drawing, motor reactor 

Page 14: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 14/26

Mechanical installation 

Motor reactors

14 Operating Instructions, 05/2010, A5E00409660A

Table 3- 1 Dimensions of motor reactor, 380 V – 480 V 3 AC, part 1 (all specifications in mm)

6SL3000- 2BE32-1AA0 2BE32-6AA0 2BE33-2AA0 2BE33-8AA0

Connectiontype

Type 1 Type 1 Type 1 Type 1

a2 25 25 25 25

a3 5 5 5 5

a4 12.5 12.5 12.5 12.5

a5 11 11 11 11

I4 300 300 300 300

I5 100 100 100 100

h1 - - - -

h2 194 227 194 194

h3 60 60 60 60

h4 285 315 285 285

n1 1) 163 183 163 183

n2 1) 224 224 224 224

n3 257 277 257 277

n4 79 79 79 79

n5 - - - -

d3 M8 M8 M8 M81) Lengths n1 and n2 correspond to the drill hole spacing

Table 3- 2 Dimensions of motor reactor, 380 V – 480 V 3 AC, part 2 (all specifications in mm)6SL3000- 2BE35-0AA0 2AE36-1AA0 2AE38-4AA0 2AE41-0AA0

Connectiontype

Type 2 Type 1 Type 1 Type 1

a2 30 40 40 40

a3 6 8 8 8

a4 15 20 20 20

a5 14 14 14 14

I4 300 410 410 410

I5 100 140 140 140

h1 - 392 392 392

h2 245 252 252 252

h3 60 120 120 120

h4 365 385 385 385

n1 1) 183 191 191 206

n2 1) 224 316 316 316

n3 277 292 292 302

n4 79 84.5 84.5 79.5

n5 - 30 30 -

d3 M10 M10 M10 M101) Lengths n1 and n2 correspond to the drill hole spacing

Page 15: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 15/26

Mechanical installation 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 15 

Table 3- 3 Dimensions of motor reactor, 500 V – 600 V 3 AC, part 1 (all specifications in mm)

6SL3000- 2AH31-8AA0 2AH32-4AA0 2AH32-6AA0 2AH33-6AA0

Connectiontype

Type 1 Type 1 Type 1 Type 1

a2 25 25 25 25

a3 5 5 5 5

a4 12.5 12.5 12.5 12.5

a5 11 11 11 11

I4 300 300 300 300

I5 100 100 100 100

h1 - - - -

h2 194 194 194 194

h3 60 60 60 60

h4 285 285 285 285

n1 1) 118 118 118 118

n2 1) 224 224 224 224

n3 212 212 212 212

n4 79 79 79 79

n5 - - - -

d3 M8 M8 M8 M81) Lengths n1 and n2 correspond to the drill hole spacing

Table 3- 4 Dimensions of motor reactor, 500 V – 600 V 3 AC, part 2 (all specifications in mm)6SL3000- 2AH34-5AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0

Connectiontype

Type 1 Type 1 Type 1 Type 1

a2 30 40 40 40

a3 6 8 8 8

a4 15 20 20 20

a5 14 14 14 14

I4 350 410 410 410

I5 120 140 140 140

h1 - 392 392 392

h2 235 252 252 252

h3 60 120 120 120

h4 330 385 385 385

n1 1) 138 141 141 183

n2 1) 264 316 316 316

n3 215 292 292 279

n4 63 134.5 134.5 79.5

n5 - 30 30 -

d3 M8 M10 M10 M101) Lengths n1 and n2 correspond to the drill hole spacing

Page 16: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 16/26

Mechanical installation 

Motor reactors

16 Operating Instructions, 05/2010, A5E00409660A

Table 3- 5 Dimensions of motor reactor, 660 V – 690 V 3 AC, part 1 (all specifications in mm)

6SL3000- 2AH31-0AA0 2AH31-5AA0 2AH31-8AA0 2AH32-4AA0 2AH32-6AA0

Connection type Type 1 Type 1 Type 1 Type 1 Type 1a2 25 25 25 25 25

a3 5 5 5 5 5

a4 12.5 12.5 12.5 12.5 12.5

a5 11 11 11 11 11

I4 270 270 300 300 300

I5 88 88 100 100 100

h1 - - - - -

h2 150 150 194 194 194

h3 60 60 60 60 60

h4 248 248 285 285 285n1 1) 103 103 118 118 118

n2 1) 200 200 224 224 224

n3 200 200 212 212 212

n4 82 82 79 79 79

n5 - - - - -

d3 M8 M8 M8 M8 M101) Lengths n1 and n2 correspond to the drill hole spacing

Table 3- 6 Dimensions of motor reactor, 660 V – 690 V 3 AC, part 2 (all specifications in mm)

6SL3000- 2AH33-6AA0 2AH34-5AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0

Connection type Type 1 Type 1 Type 1 Type 1 Type 1

a2 25 30 40 40 40

a3 5 6 8 8 8

a4 12.5 15 20 20 20

a5 11 14 14 14 14

I4 300 350 410 410 410

I5 100 120 140 140 140

h1 - - 392 392 392

h2 194 235 252 252 252

h3 60 60 120 120 120h4 285 330 385 385 385

n1 1) 118 138 141 141 183

n2 1) 224 264 316 316 316

n3 212 215 292 292 279

n4 79 63 134.5 134.5 79.5

n5 - - 30 30 -

d3 M8 M8 M10 M10 M101) Lengths n1 and n2 correspond to the drill hole spacing

Page 17: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 17/26

 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 17 

Electrical installation 4 

Important safety precautions

WARNING

The devices are operated with high voltages.All connection procedures must be carried out when the cabinet is de-energized.All work on the device must be carried out by trained personnel only.Death, serious injury, or substantial material damage can result if these warnings are nottaken into account.

Work on an open device must be carried out with extreme caution because external supplyvoltages may be present. The power and control terminals may be live even when themotor is not running.Dangerously high voltage levels are still present in the cabinet up to five minutes after it hasbeen disconnected due to the DC link capacitors on the Power Module. For this reason, thecabinet should not be opened until a reasonable period of time has elapsed.

The operator is responsible for ensuring that the motor reactor and other components areinstalled and connected in accordance with the recognized technical rules in the country of installation and applicable regional guidelines. Special attention should be paid to cabledimensioning, fuses, grounding, shutdown, disconnection, and overcurrent protection.

If an item of protective gear trips in a branch circuit, a leakage current may have beendisconnected. To reduce the risk of fire or an electric shock, the current-conducting partsand other components in the built-in unit should be inspected and damaged parts replaced.When an item of protective gear trips, the cause of the trip must be identified and rectified.

Page 18: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 18/26

Electrical installation 

Motor reactors

18 Operating Instructions, 05/2010, A5E00409660A

Connection

When connecting the motor reactor, you must take into account the following conditions to

ensure that it functions correctly:●  With analog control cables, connecting the shield at both ends can result in coupled-in

noise. To prevent this, the shield must only be connected at one end on the Power Module.

●  Control cables must be routed separately from power cables. Power cables are motor cables or connecting cables from the DC link of the Power Module (terminalsDCPA/DCNA) to other components (e.g., Braking Module). In particular, you must ensurethat control cables and power cables are not routed in parallel in a joint cable raceway,even if all the cables are shielded.

●  You must use shielded motor cables. The shield for the motor cable must be attached tothe shield plate and motor housing.

● 

The ground wire for the motor must be fed directly back to the Power Module.

Connection overview

1U1

1V1

1W1

1U2

1V2

1W2

U2

V2

W2

PE2

U1

V1

W1

PE1

M

~PE

U

V

W

0RWRUUHDFWRU 3RZHU0RGXOH

0DLQVV\VWHP

0RXQWLQJSODWH

0RWRU 

 Figure 4-1 Connecting the motor reactor and Power Module

Page 19: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 19/26

 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 19 

Technical specifications 5 

General technical specifications

Table 5- 1 General technical specifications

Output frequency 0 ... 150 Hz

Product standard EN 61800-5-1

Ambient conditions Storage Transport Operation

Ambient temperature -25 ... +70 °C -25 ... +70 °C 0 ... +50 °CRelative humidity (non-condensing), corresponds toclass:

5 ... 95 %

1K4 to EN 60721-3-1

5 ... 95% at 40 °C

2K3 to EN 60721-3-2

5 ... 95 %

3K3 to EN 60721-3-3

Mechanical stability Storage Transport Operation

Vibrational load:- Displacement- Acceleration

1.5 mm at 5 ... 9 Hz5 m/s² at >9 ... 200 Hz

3.5 mm at 5 ... 9 Hz10 m/s² at >9 ... 200 Hz

0.075 mm at 10 ... 58 Hz10 m/s² at >58 ... 200 Hz

Shock load:- Acceleration 40 m/s² at 22 ms 100 m/s² at 11 ms 100 m/s² at 11 ms

Detailed technical specifications

Table 5- 2 Technical specifications of motor reactors 380 V – 480 V 3 AC, part 1

Order number 6SL3000- 2BE32-1AA0 2BE32-6AA0 2BE33-2AA0 2BE33-8AA0

Suitable for Power Module 6SL3310- 1GE32-1AAx 1GE32-6AAx 1GE33-1AAx 1GE33-8AAx

Rated current A 210 260 310 380

Power loss- at 50 Hz- at 150 Hz

kWkW

0.4360.486

0.4540.5

0.4220.47

0.4480.5

Connections- to the Power Module

- load- PE

M10

M10M8

M10

M10M8

M10

M10M8

M10

M10M8

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00 IP00 IP00 IP00

DimensionsWidthHeightDepth

mmmmmm

300285257

300315277

300285257

300285277

Weight kg 66 66 66 73

Page 20: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 20/26

Technical specifications 

Motor reactors

20 Operating Instructions, 05/2010, A5E00409660A

Table 5- 3 Technical specifications of motor reactors 380 V – 480 V 3 AC, part 2

Order number 6SL3000- 2BE35-0AA0 2AE36-1AA0 2AE38-4AA0 2AE38-4AA0

Suitable for Power Module 6SL3310- 1GE35-0AAx 1GE36-1AAx 1GE37-5AAx 1GE38-4AAxRated current A 490 605 840 840

Power loss- at 50 Hz- at 150 Hz

kWkW

0.4480.5

0.7980.9

0.750.84

0.8340.943

Connections- to the Power Module- load- PE

M12M12M8

M12M12M10

M12M12M10

M12M12M10

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00 IP00 IP00 IP00DimensionsWidthHeightDepth

mmmmmm

300365277

410392292

410392292

410392292

Weight kg 100 130 140 140

Table 5- 4 Technical specifications of motor reactors 380 V – 480 V 3 AC, part 3

Order number 6SL3000- 2AE41-0AA0

Suitable for Power Module 6SL3310- 1GE41-0AAx

Rated current A 985Power loss- at 50 Hz- at 150 Hz

kWkW

0.9391.062

Connections- to the Power Module- load- PE

M12M12M10

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00

DimensionsWidthHeightDepth

mmmmmm

410392302

Weight kg 146

Page 21: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 21/26

Technical specifications 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 21 

Table 5- 5 Technical specifications of motor reactors 500 V – 600 V 3 AC, part 1

Order number 6SL3000- 2AH31-8AA0 2AH32-4AA0 2AH32-6AA0 2AH33-6AA0

Suitable for Power Module 6SL3310- 1GF31-8AAx 1GF32-2AAx 1GF32-6AAx 1GF33-3AAxRated current A 175 215 260 330

Power loss- at 50 Hz- at 150 Hz

kWkW

0.3570.403

0.3760.425

0.3890.441

0.40.454

Connections- to the Power Module- load- PE

M10M10M6

M10M10M6

M10M10M6

M10M10M6

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00 IP00 IP00 IP00DimensionsWidthHeightDepth

mmmmmm

300285212

300285212

300285212

300285212

Weight kg 34 34 40 46

Table 5- 6 Technical specifications of motor reactors 500 V – 600 V 3 AC, part 2

Order number 6SL3000- 2AH34-5AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0

Suitable for Power Module 6SL3310- 1GF34-1AA0x 1GF34-7AAx 1GF35-8AAx 1GF37-4AAx

Rated current A 410 465 575 810Power loss- at 50 Hz- at 150 Hz

kWkW

0.4810.545

0.6310.723

0.7050.801

0.790.91

Connections- to the Power Module- load- PE

M12M12M8

M12M12M8

M12M12M8

M12M12M8

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00 IP00 IP00 IP00

DimensionsWidthHeightDepth

mmmmmm

350330215

410392292

410392292

410392279

Weight kg 68 80 80 146

Page 22: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 22/26

Technical specifications 

Motor reactors

22 Operating Instructions, 05/2010, A5E00409660A

Table 5- 7 Technical specifications of motor reactors 500 V – 600 V 3 AC, part 3

Order number 6SL3000- 2AH38-1AA0

Suitable for Power Module 6SL3310- 1GF38-1AAxRated current A 810

Power loss- at 50 Hz- at 150 Hz

kWkW

0.8771.003

Connections- to the Power Module- load- PE

M12M12M8

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00DimensionsWidthHeightDepth

mmmmmm

410392279

Weight kg 146

Table 5- 8 Technical specifications of motor reactors 660 V – 690 V 3 AC, part 1

Order number 6SL3000- 2AH31-0AA0 2AH31-0AA0 2AH31-5AA0 2AH31-5AA0

Suitable for Power Module 6SL3310- 1GH28-5AAx 1GH31-0AAx 1GH31-2AAx 1GH31-5AAx

Rated current A 100 100 150 150Power loss- at 50 Hz- at 150 Hz

kWkW 0.26 0.3 0.26 0.332

Connections- to the Power Module- load- PE

M10M10M6

M10M10M6

M10M10M6

M10M10M6

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00 IP00 IP00 IP00

DimensionsWidthHeightDepth

mmmmmm

270248200

270248200

270248200

270248200

Weight kg 25 25 25.8 25.8

Page 23: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 23/26

Technical specifications 

Motor reactors

Operating Instructions, 05/2010, A5E00409660A 23 

Table 5- 9 Technical specifications of motor reactors 660 V – 690 V 3 AC, part 2

Order number 6SL3000- 2AH31-8AA0 2AH32-4AA0 2AH32-6AA0 2AH33-6AA0

Suitable for Power Module 6SL3310- 1GH31-8AAx 1GH32-2AAx 1GH32-6AAx 1GH33-3AAxRated current A 175 215 260 330

Power loss- at 50 Hz- at 150 Hz

kWkW 0.403 0.425 0.441 0.454

Connections- to the Power Module- load- PE

M10M10M6

M10M10M6

M10M10M6

M10M10M6

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00 IP00 IP00 IP00DimensionsWidthHeightDepth

mmmmmm

300285212

300285212

300285212

300285212

Weight kg 34 34 40 46

Table 5- 10 Technical specifications of motor reactors 660 V – 690 V 3 AC, part 3

Order number 6SL3000- 2AH34-5AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0

Suitable for Power Module 6SL3310- 1GH34-1AAx 1GH34-7AAx 1GH35-8AAx 1GH37-4AAx

Rated current A 410 465 575 810Power loss- at 50 Hz- at 150 Hz

kWkW 0.545

0.6310.723

0.7050.801

0.780.91

Connections- to the Power Module- load- PE

M12M12M8

M12M12M8

M12M12M8

M12M12M8

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00 IP00 IP00 IP00

DimensionsWidthHeightDepth

mmmmmm

350330215

410392292

410392292

410392279

Weight kg 68 80 80 146

Page 24: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 24/26

Technical specifications 

Motor reactors

24 Operating Instructions, 05/2010, A5E00409660A

Table 5- 11 Technical specifications of motor reactors 660 V – 690 V 3 AC, part 4

Order number 6SL3000- 2AH38-1AA0

Suitable for Power Module 6SL3310- 1GH38-1AAxRated current A 810

Power loss- at 50 Hz- at 150 Hz

kWkW

0.8771.003

Connections- to the Power Module- load- PE

M12M12M8

Max. permissible cablelength between motor reactor and motor 

m 300 (shielded)450 (unshielded)

Degree of protection IP00DimensionsWidthHeightDepth

mmmmmm

410392279

Weight kg 146

Page 25: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 25/26

Page 26: g130 Motor Reactors En

7/28/2019 g130 Motor Reactors En

http://slidepdf.com/reader/full/g130-motor-reactors-en 26/26

 

Subject to change

© Siemens AG 2010