fundamentals of distillation column control control basic – inventory control – composition...

30
Standards Certification Education & Training Publishing Conferences & Exhibits Fundamentals of Distillation Column Control by Terry Tolliver ISA Automation Week 2011

Upload: phungkhuong

Post on 24-Apr-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

Standards

Certification

Education & Training

Publishing

Conferences & Exhibits

Fundamentals of Distillation Column Control

by Terry Tolliver

ISA Automation Week 2011

Page 2: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

2

PRESENTER – Terry Tolliver

• Terry is a retired Senior Fellow from Solutia/Monsanto and presently provides contract engineering at ConocoPhillips Wood River refinery. He has 40+ years of experience in process control, simulation, operations, troubleshooting and optimization.

• Terry graduated from the Missouri University of Science and Technology with BS, MS & PhD ChE and was recently inducted into their Academy of Chemical Engineers in 2009. He was inducted into the CONTROL Automation Hall of Fame in 2002.

• He has received several ISA awards including the Distinguished Society Service Award in 1997, the E. G. Baily Award in 1993 and the Excellence in Documentation award in 1987.

• Terry has been an adjunct professor for Washington University from 2004-2008, a Lehigh University Biannual Lecturer from 1974-1986, an ISA Fellow in 1990, an AIChE Fellow in 2000 and a PE since 1974.

Page 3: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

DISTILLATION CONTROL TOPICS

• Levels of control • Classification and pairing of variables • Control objectives and constraints • Dynamic responses • Material and energy balances • Separation • Pressure control • Material balance control • Temperature control • References

3

Presenter
Presentation Notes
Page 4: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

DISTILLATION CONTROL

BASIC –Inventory Control –Composition Control

OPTIMIZING –Floating Pressure –Maximum Profit

SUBOPTIMIZING –Feedforward Control –Two Point Composition Control

4

Presenter
Presentation Notes
Distillation control can be discussed on at least three levels: Basic, Suboptimizing, and Optimizing. Good Basic column control is most important because the more advanced schemes build upon it. Basic column control must provide stable operation while maintaining column vapor and liquid inventories and one composition, usually inferred at some location in the column. Feedforward control is a widely applicable Suboptimizing control technique which improves the performance of the Basic column control by reducing composition variability resulting from measured disturbances.
Page 5: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

CLASSIFICATION and PAIRING of VARIABLES

CONTROLLED VARIABLES distillate composition bottom composition accumulator level sump level column pressure

Y Y

X

X

La

La

Ls

Ls

P

P

5

Presenter
Presentation Notes
Basic distillation control is primarily concerned with the proper pairing of controlled and manipulated variables in order to best reject the effect of disturbance variables. Feed flow is often controlled to a desired flow rate, and then its setpoint is manipulated to establish a production rate, which thus makes the feed flow a disturbance variable to the operation of the distillation column. In fact, feed flow changes are often the most abrupt and severe disturbances that must be handled. Fortunately, feed flow rate is usually a measured disturbance and thus suitable for Feedforward control to be applied.
Page 6: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MANIPULATED VARIABLES distillate flow bottom flow reflux flow reboiler duty condenser duty

D D B

B

R

R

Qr

Qr

Qc

Qc

CLASSIFICATION and PAIRING of VARIABLES

6

Presenter
Presentation Notes
Basic distillation control is primarily concerned with the proper pairing of controlled and manipulated variables in order to best reject the effect of disturbance variables. Feed flow is often controlled to a desired flow rate, and then its setpoint is manipulated to establish a production rate, which thus makes the feed flow a disturbance variable to the operation of the distillation column. In fact, feed flow changes are often the most abrupt and severe disturbances that must be handled. Fortunately, feed flow rate is usually a measured disturbance and thus suitable for Feedforward control to be applied.
Page 7: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

CLASSIFICATION and PAIRING of VARIABLES

DISTURBANCE VARIABLES feed flow feed composition feed temperature reboiler heat supply condenser cooling supply and weather

F F Z Z q q S

S

W

W

7

Presenter
Presentation Notes
Basic distillation control is primarily concerned with the proper pairing of controlled and manipulated variables in order to best reject the effect of disturbance variables. Feed flow is often controlled to a desired flow rate, and then its setpoint is manipulated to establish a production rate, which thus makes the feed flow a disturbance variable to the operation of the distillation column. In fact, feed flow changes are often the most abrupt and severe disturbances that must be handled. Fortunately, feed flow rate is usually a measured disturbance and thus suitable for Feedforward control to be applied.
Page 8: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

CLASSIFICATION and PAIRING of VARIABLES

CONTROLLED MANIPULATED DISTURBANCE VARIABLES VARIABLES VARIABLES distillate composition distillate flow feed flow bottom composition bottom flow feed composition accumulator level reflux flow feed temperature sump level reboiler duty reboiler heat supply column pressure condenser duty condenser cooling supply and weather

8

Presenter
Presentation Notes
Basic distillation control is primarily concerned with the proper pairing of controlled and manipulated variables in order to best reject the effect of disturbance variables. Feed flow is often controlled to a desired flow rate, and then its setpoint is manipulated to establish a production rate, which thus makes the feed flow a disturbance variable to the operation of the distillation column. In fact, feed flow changes are often the most abrupt and severe disturbances that must be handled. Fortunately, feed flow rate is usually a measured disturbance and thus suitable for Feedforward control to be applied.
Page 9: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

CONTROL OBJECTIVES

$/F

RECOVERY

Cost of Product Lost

Cost of Energy

Total Operating Cost

9

Presenter
Presentation Notes
Primary and secondary objectives must be identified as one of the first steps toward selection of a basic control scheme. Typically, the primary objective is to produce one product within its quality specifications, while the secondary objective is to maximize profit by minimizing the total operating costs. When a process is running soldout, the secondary objective to maximize profit usually equates to maximizing throughput.
Page 10: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

COLUMN CONSTRAINTS

Column Pressure

Boilu

p ra

te

Vessel Limit

Weep

Flood

Reboiler

Condenser

10

Presenter
Presentation Notes
Operating constraints must be considered. Proper design of the column should place the normal operating point in the center of the operating window. Flooding is indicated by high pressure drop across the column, rapid accumulator level increase, sump level decrease or an abnormal temperature profile. Weeping gradually decreases separation efficiency. Condenser duty is limited by the temperature difference between the coolant and process temperature. Reboiler duty is limited by the temperature difference between the heat supply and process temperature.
Page 11: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

COLUMN INTERNALS

TRAYS – SIEVE TRAYS – VALVE TRAYS – BUBBLE CAP TRAYS – DUAL FLOW TRAYS

PACKING – RANDOM PACKING – STRUCTURED PACKING – LIQUID & VAPOR DISTRIBUTORS

11

Presenter
Presentation Notes
TRAYS Sieve trays are the most common tray with 70% turndown capability. Valve trays are proprietary and provide 50% turndown. Bubble cap trays have even greater turndown, although used widely in the past, they are now used almost exclusively for columns requiring reaction residence time. Dual flow trays have greater capacity, but they provide less efficiency and the least turndown capability. PACKING Random packing like pall rings or saddles may provide an HETP equivalent to normally spaced trays but with greater capacity. Structured packing provides better HETP, capacity and lower pressure drop also. Vapor and liquid distributors are required at every stream entry or withdrawal point and every 20-25 feet to redistribute the flows. Column turndown is usually limited by the liquid distributor design and levelness of installation. V-notch weir, square-notch weir and orifice hole designs provide increasing turndown capability .
Page 12: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

COLUMN DYNAMICS

RELATIVE RESPONSE TIMES

time

VAPOR - FAST LIQUID - MEDIUM COMPOSITION - SLOW

Response

12

Presenter
Presentation Notes
There are three distinct dynamic responses in both trayed and packed distillation columns. The vapor response is relatively fast and occurs within several seconds from bottom to top. The liquid response is medium, occurring in a few minutes from top to bottom, with the response being predominately deadtime. The composition response is slow, measured in hours throughout the column, with the response being predominately a slow first order lag plus a short deadtime roughly equal to the corresponding liquid response. Packed columns have similar, but often slightly faster dynamics than equivalent trayed columns.
Page 13: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MATERIAL & ENERGY BALANCES

MATERIAL BALANCE F = D + B zF = yD + xB

ENERGY BALANCE hF + Qreb = hD + hB + Qcond

D/F = (z-x)/(y-x)

13

Presenter
Presentation Notes
A Material Balance equation can be developed by combining the overall material balance equation with any component material balance equation. The notation used above applies to the more volatile component in a binary system. The resulting D/F equation shows that for a given feed composition there is a relationship between the two product compositions and the material balance “split”. A second relationship is required to uniquely determine the two product compositions. The Energy Balance equation is usually dominated by the reboiler and condenser duties since the difference in sensible heat for the feed and product streams is often small compared to the latent heat of vaporization of the feed. The reboiler and condenser duties represent the creation and removal of vapor, which directly affects the column pressure. For this reason, column pressure control usually is paired to manipulate one of these duties.
Page 14: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

TOTAL REFLUX αn = [y(1-x)]/[x(1-y)]

SEPARATION

NORMAL OPERATION

S = (α, N, NF, V/F, z, E) f

14

Presenter
Presentation Notes
Separation is the second relationship which is required to uniquely determine the two product compositions. Separation is defined by the “Fenske-Underwood” equation for a column operating at total reflux. In this relationship, the average relative volatility raised to the number of stages of separation is equated to the ratio of product purity to product impurity. Under normal operation this relationship is much more complex, but the concept of a Separation factor can still be defined as the ratio of product purity to product impurity which is primarily a function of V/F, vapor per unit feed. Thus, for given Separation (V/F) and Material Balance (D/F) relationships, the product compositions are uniquely defined.
Page 15: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MATERIAL BALANCE and SEPARATION EFFECTS

D/F

Light

Key

Mol

e Fr

actio

n

0 1.0 0

1.0

y

X

Z

Increasing S

Increasing S

15

Presenter
Presentation Notes
The effect of varying the Material Balance (D/F) and Separation (S) can be visualized for a given column feed composition. Changes in D/F have a much stronger effect on product compositions than changes in Separation, except perhaps at very high product purities.
Page 16: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MATERIAL BALANCE CONTROL

FC

FC

FC

FC

FC

LC

LC

TC

16

Presenter
Presentation Notes
Material Balance control schemes manipulate the D/F ratio either directly or indirectly. In this example the ratio is directly manipulated by the temperature controller adjusting the setpoint on the distillate flow controller. Separation is fixed by a manual setpoint on the steam flow controller at the reboiler.
Page 17: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

SEPARATION CONTROL

FC

FC

FC

FC

FC

LC

LC

TC NOT RECOMMENDED

17

Presenter
Presentation Notes
Separation control is not recommended because it fixes the material balance and requires much larger adjustments to the V/F, energy per unit feed. As a result, its range of control is also severely limited. In this example, the separation is manipulated by the temperature controller adjusting the setpoint on the reboiler steam flow controller. The material balance is fixed by a manual setpoint on the distillate flow controller.
Page 18: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

PRESSURE CONTROL

FC FC LC

VENT

PI

18

Presenter
Presentation Notes
Column pressure is a measure of the moles of material in the vapor phase. If the feed and product streams are liquid, then only the reboiler duty and the condenser duty significantly affect the amount of material in the vapor phase. Condenser duty is usually manipulated to control pressure, unless it represents the limiting capacity constraint or uses a more costly utility than the reboiler. The simplest form of pressure control is at atmospheric pressure to connect the downstream side of the condenser to a suitable vent. This vent may lead directly to the atmosphere or to an inert header. Sometimes an additional vent condenser with a refrigerated coolant is used to minimize product vapor leaving with the inerts.
Page 19: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

CONDENSER DUTY

Qcond = UA(Tp-Tc)

VENT

CONDENSATE

COOLANT

Tc

Tp

19

Presenter
Presentation Notes
The vent allows inerts to enter or leave the condenser as required to change the condenser duty. The condenser duty must satisfy the energy balance in order to keep the pressure constant. Condenser duty can be determined as: Qcond = UA(Tp-Tc) where - Qcond is the condenser duty U is the heat transfer coefficient A is the area available for heat transfer Tp is the condensing temperature Tc is the coolant temperature The area available for condensing vapor can be manipulated by adding or removing inert gas from the tubes. The area of the tubes that is blanked off by the inert gas provides subcooling to the condensate. If more vapor is being created than is being removed, then the pressure will rise and push out inerts until increased area available for condensing restores the energy balance. Conversly, if the pressure is dropping, inerts will enter the condenser until decreased area available for condensing restores the energy balance.
Page 20: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

“BLOCK & BLEED” PRESSURE CONTROL

FC FC LC

VACUUM SOURCE

PC

BLOCK VALVE

BLEE

D VA

LVE

INERTS

20

Presenter
Presentation Notes
For columns operating under vacuum, the vent is connected to some vacuum source such as an steam jet or vacuum pump. A BLOCK and BLEED split-range valve arrangement is often used for pressure control in this case. The BLOCK valve is on the line to the vacuum source and the BLEED valve is on the inert supply line. The split-range is set up such that from 0-50% IVP the BLEED valve closes, and from 50-100% IVP the BLOCK valve opens. Normally, the BLOCK valve will be throttling the flow of naturally occurring inerts to the vacuum source and the BLEED valve will be fully closed. When pressure rises, the BLOCK valve will open further to let more inerts out. When pressure drops, the BLOCK valve will close allowing inerts to accumulate. If the BLOCK valve becomes fully closed, then the BLEED valve begins to open supplementing inerts. If there are sufficient inerts present naturally, then the BLEED valve and inert supply may not be required. For a column operating at very low pressure (< 20 mmHG), the BLOCK valve may be eliminated in order to minimize the pressure drop in the line to the vacuum source. In this case, the BLEED valve continually adds inerts, and the small pressure drop limits the flow out.
Page 21: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MATERIAL BALANCE CONTROL - TYPE 1

FC

FC

FC

FC

FC

LC

LC

TC

21

Presenter
Presentation Notes
Scheme 1 directly adjusts the material balance by manipulation of the distillate flow. If the distillate flow is increased, then the reflux accumulator level controller decreases the reflux flow. As less liquid proceeds to flow down to the sump, the sump level controller decreases the bottoms flow a like amount. The separation is held constant by manually setting the reboiler steam flow to maintain a constant energy per unit feed. This scheme is recommended when the distillate flow is one of the smaller flows in the column, particularly when the reflux ratio is large (R/D > 3). Also, it is important that the reflux accumulator level control can be tightly tuned and that the liquid holdup is not too large (< 5 minutes). This scheme has the least interaction with the energy balance, as it provides a good range of control with only small changes in the distillate flow, and it also provides a form of automatic internal reflux control. If the reflux becomes more subcooled, initially additional vapors will be condensed inside the column. However, the overhead vapors will be reduced by exactly the same amount, and with tight level control, the reflux will then be reduced accordingly. Another advantage of this scheme is that it lends itself readily to the application of feedforward control in order to maintain the D/F ratio for measured changes in feed flow. This feedforward signal would be trimmed by the feedback signal from the temperature controller .
Page 22: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MATERIAL BALANCE CONTROL - TYPE 2

FC

FC

FC

FC

FC

LC

LC

TC

22

Presenter
Presentation Notes
Scheme 2 indirectly adjusts the material balance through the two level control loops. If the reflux flow is increased, then the reflux accumulator level controller decreases the distillate flow. As the additional liquid proceeds to flow down to the sump, the sump level controller increases the bottoms flow a like amount. The separation is held constant by manually setting the reboiler steam flow to maintain a constant energy per unit feed. This scheme is recommended for columns with a small reflux ratio (R/D < 1). This scheme also offers improved dynamics, which may be required, particularly if the column has a large horizontal reflux accumulator.
Page 23: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MATERIAL BALANCE CONTROL - TYPE 3

FC

FC

FC

FC

FC

LC

LC

TC

23

Presenter
Presentation Notes
Scheme 3 indirectly adjust the material balance through the two level loops. If the steam flow is increased, then the sump level controller decreases the bottom flow. As the additional vapors go overhead and condense, the reflux accumulator level control increases the distillate flow a like amount. The separation is held constant by manually setting the reflux flow to maintain a relatively constant energy per unit feed. This scheme is recommended for columns with a small energy per unit feed (V/F < 2). This scheme also offers the fastest dynamics.
Page 24: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

MATERIAL BALANCE CONTROL - TYPE 4

FC

FC

FC

FC

FC

LC

LC

TC

time

response

24

Presenter
Presentation Notes
Scheme 4 directly adjust the material balance by manipulation of the bottom flow. If the bottom flow is decreased, then the sump level controller increases the reboiler steam flow. As the additional vapors go overhead and condense, the reflux accumulator level control increases the distillate flow a like amount. The separation is held constant by manually setting the reflux flow to maintain a relatively constant energy per unit feed. This scheme is recommended when the bottom flow is one of the smaller flows in the column, particularly when the bottom flow is less than 20% of the vapor boilup. This scheme has little interaction with the energy balance, as it provides a good range of control with only small changes in the bottom flow. However, the tuning of the sump level loop usually makes this scheme slower than the others. An inverse response is also possible with this sump level control loop. This type of response occurs when an increase in steam flow temporarily cause the sump level to increase before it begins to decrease. If this occurs, the level loop must be detuned even more. An advantage of this scheme is that it lends itself readily to the application of feedforward control in order to maintain the B/F ratio for measured changes in feed flow. This feedforward signal would be trimmed by the feedback signal from the temperature controller.
Page 25: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

PROCESS SIMULATION

STEADY STATE • PARAMETRIC CASES • CONTROL STAGE LOCATION • SENSITIVITY ANALYSIS • DISTURBANCE ANALYSIS

DYNAMIC • STUDY CONTROL RESPONSE • STARTUP AND SHUTDOWN

25

Presenter
Presentation Notes
HYSYS is a rigorous material and energy balance program which can provide both steady state and dynamic simulations. Parametric steady state cases can provide valuable insight into the operating characteristics of a particular column. HYSYS allows alternative independent parameters and their values to be specified, which makes it easy to study the effect of holding some parameters constant while varying others. Holding product compositions constant while varying feed composition would simulate perfect two point composition control. These parametric cases would indicate how various parameters must change in order to keep the product compositions constant, which can further guide in the selection of the basic column control scheme. Additional parametric steady state cases can be used to locate the control stage, determine the temperature sensitivity and evaluate the effect of disturbances. The basic column control scheme may then be implemented as part of the dynamic model and response studies can further evaluate the effectiveness of the control. Startup and shutdown scenarios may also be studied.
Page 26: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

CONTROL STAGE LOCATION

Benzene-Toluene Column Temperature Profiles

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

70.0 75.0 80.0 85.0 90.0 95.0 100.0 105.0 110.0 115.0 120.0

Temperature, DegC

Stag

e Nu

mbe

r

+1%D/F

-1%D/F

26

Presenter
Presentation Notes
Once a basic column control scheme is chosen, parametric steady state cases, which hold the separation variable constant and adjust the material balance variable, can be used to determine the best control stage location. Temperature profiles from these parametric cases should be plotted together as shown. The best control stage location is where the largest, most symmetrical temperature deviation from the base case occurs. It is recommended that alternative thermowells be installed one stage above and below this location because of uncertainty in tray efficiencies and VLE data.
Page 27: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

TEMPERATURE SENSITIVITY

CONTROL STAGE TEMPERATURE, degF

98

98.2

98.4

98.6

98.8

99

99.2

99.4

99.6

99.8

100

85 90 95 100 105 110

CO

MPO

SITIO

N, w

t%

BOTTOM PRODUCT

DISTILLATE PRODUCT

27

Presenter
Presentation Notes
Product compositions from these same parametric cases can be plotted against the temperature occurring on the uncontrolled control stage as shown. The effect of temperature variations due to measurement errors can be determined in this manner.
Page 28: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

DISTURBANCE ANALYSIS

Benzene-Toluene Column Load Effects

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

-5.0 -4.0 -3.0 -2.0 -1.0 0.0 1.0 2.0 3.0

Delta Temperature, DegC

Tray

Num

ber

28

Presenter
Presentation Notes
Additional parametric cases can evaluate the steady state effect of disturbances on the proposed basic control scheme and control stage location. Temperature deviation profiles as shown illustrate the steady state changes that occur throughout the column at these different disturbance conditions.
Page 29: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

29

REFERENCES

Page 30: Fundamentals of Distillation Column Control CONTROL BASIC – Inventory Control – Composition Control OPTIMIZING – Floating Pressure – Maximum Profit SUBOPTIMIZING – Feedforward

30

REFERENCES