fp+ operation manual om-fp+ rev105

Upload: henrycervantes4

Post on 08-Aug-2018

244 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    1/37

    FP+ Series:Dedicated Touring Ampliers

    Rev. 1.0.5Item no. OM-FP+

    Operation Manual

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    2/37

    2 FP+ Series Operation Manual

    1 CONTENTS .................................................................................................................................................2

    2 APPROVALS ................................................................................................................................................4

    3 WARNINGS .................................................................................................................................................4

    3.1 Explanation o graphical symbols ........................................................................................................4

    3.1.1 WARNING ................................................................................................................................4

    3.1.2 CAUTION..................................................................................................................................4

    3.2 Important Saety Instructions ..............................................................................................................4

    3.3 User responsibility ...............................................................................................................................5

    3.3.1 Mains connection grounding ....................................................................................................5

    3.3.2 Speaker output hazard ..............................................................................................................5

    3.3.3 Radio intererence ....................................................................................................................5

    3.3.4 Speaker damage .......................................................................................................................5

    3.3.5 Maintenance .............................................................................................................................5

    4 WELCOME ...................................................................................................................................................64.1 Introduction ..........................................................................................................................................6

    4.2 Main Features ......................................................................................................................................6

    4.2.1 Patented Class TD amplier and Regulated Switch Mode Power Supply (R.SMPS ) ..........6

    4.2.2 Amplier gain ...........................................................................................................................6

    4.2.3 Voltage Peak Limiter (VPL) .....................................................................................................6

    4.2.4 Protection and perormance optimization .................................................................................6

    4.2.5 NomadLink / Ethernet control and monitoring network ..........................................................7

    5 INSTALLATION ...........................................................................................................................................8

    5.1 Unpacking ............................................................................................................................................8

    5.2 Mounting .............................................................................................................................................8

    5.2.1 Rear support bracket ................................................................................................................85.3 Cooling .................................................................................................................................................9

    5.4 Operating voltage ................................................................................................................................9

    5.5 Grounding ............................................................................................................................................9

    6 quICk GuIdE OVERVIEW .......................................................................................................................10

    6.1 Front Panel overview .........................................................................................................................10

    6.1.1 Power on/o and remote switch ............................................................................................10

    6.1.2 Front Panel LEDs ...................................................................................................................10

    6.2 Rear Panel overview ..........................................................................................................................11

    6.2.1 Network and conguration section ........................................................................................ 12

    6.2.2 The DIP-switch eatures .........................................................................................................126.2.3 Input and Output connectors..................................................................................................13

    6.3 Nomadlink / Ethernet network setup .................................................................................................14

    7 OPERATION ANd PERORMANCE ........................................................................................................15

    7.1 Introduction ........................................................................................................................................15

    7.2 Operation precautions .......................................................................................................................15

    7.3 Signal fow and headroom .................................................................................................................15

    7.3.1 Signal fow blocks ...................................................................................................................15

    1 CONTENTs

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    3/37

    FP+ Series Operation Manual 3

    7.3.2 Headroom, sensitivity and VPL / Gain settings ......................................................................16

    7.4 Audio Input and Output connections .................................................................................................17

    7.4.1 Balanced Input connections ...................................................................................................17

    7.4.2 Unbalanced Input connection .................................................................................................17

    7.4.3 Speakon Output connections .................................................................................................177.4.4 Binding Post ( BP ) Output connectors ...................................................................................18

    7.4.5 Output bridge mode ...............................................................................................................19

    7.4.6 Amplier Gain .........................................................................................................................19

    7.4.6.1 Channel gain / Level ( Front-panel pots ) .......................................................................19

    7.4.6.2 Amplier sensitivity .......................................................................................................19

    7.4.7 Output Voltage Peak Limiter, (VPL) ........................................................................................20

    7.4.8 Output Current Peak Limiter (CPL) .........................................................................................20

    7.5 Protection, aults and warnings .........................................................................................................21

    7.5.1 Introduction ............................................................................................................................21

    7.5.2 Sae Operating Area Detector (SOAD) ...................................................................................21

    7.5.3 Very High Frequency (VHF) protection ...................................................................................217.5.4 DC protection .........................................................................................................................21

    7.5.5 High-impedance warning (open load) .....................................................................................22

    7.5.6 Low-impedance protection (short circuit) ...............................................................................22

    7.5.7 Temperature protection ..........................................................................................................22

    7.5.8 Power Average Limiter (PAL) .................................................................................................22

    7.5.9 Sot-Start ................................................................................................................................22

    7.6 Front Panel monitoring and adjustments ...........................................................................................23

    7.6.1 Level indicators .......................................................................................................................23

    7.6.2 Level adjust ............................................................................................................................23

    7.6.3 Mute indication .......................................................................................................................23

    7.6.4 Perormance, Warning and Fault indicators ............................................................................24

    7.7 NomadLink network and DeviceControl sotware .............................................................................24

    7.7.1 NomadLink network in the ampliers ....................................................................................24

    7.7.2 Connection and setup.............................................................................................................25

    7.7.3 NomadLink network cable lengths .........................................................................................25

    7.7.4 Ethernet network cable lengths .............................................................................................26

    7.7.5 DeviceControl sotware ..........................................................................................................26

    8 APPENdIx .................................................................................................................................................27

    8.1 Maintenance ......................................................................................................................................27

    8.2 FAQ ....................................................................................................................................................27

    8.3 Additional documentation ..................................................................................................................27

    8.4 Current Draw and Thermal Dissipation specications .......................................................................28

    9 TEChNICAL SPECIICATIONS ............................................................................................................... 35

    10 WARRANTY ..............................................................................................................................................36

    CONTENTs 1

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    4/37

    4 FP+ Series Operation Manual

    This equipment conorms to the requirements o the EMC Directive 2004/108/EC and the requirements o the Low Voltage Directive 2006/95/EC.

    Standards applied: EMC Emission EN55103-1, E3

    EMC Immunity EN55103-2, E3, with S/N below 1% at normal operation level.

    Electrical Saety EN60065, Class I

    This equipment is tested and approved according to the U.S. saety standard ANSI/ UL 60065 and Canadian saety standard CSA C22.2 NO. 60065. ETL

    made the tests and they are a Nationally Recognized Testing Laboratory (NRTL).

    3.1 Eplanation o grapical symbols

    The lightning symbol within a triangle is intended to alert the user to the presence o un-insulated dangerous voltages within the units chassis that may be o

    sucient magnitude to constitute a risk o electric shock to humans.

    The exclamation point within a triangle is intended to alert the user to presence o important operating and service instructions in the literature accompanying the

    product.

    3.1.1 WARNING

    3.1.2 CAuTION

    3.2 Important Saety Instrctions

    Beore using your FP+ Series product, be sure to careully read the applicable items o this Operation Manual and the Saety Instructions.

    1. Keep this manual or uture reerence.

    Heed all warnings.2.

    Follow all instructions.3.

    Do not use this unit near water.4.

    Do not spill water or other liquids into or on the unit. Do not operate the unit while wet or standing in liquid.5.

    Clean only with dry cloth.6.

    Do not block the air intake or exhaust ports. Install the unit in accordance with the instructions.7.

    Do not operate the unit near heat producing devices such as radiators, heat registers, stoves or other apparatus that produce heat. Always operate the unit with the chassis ground wire connected to the8.

    electrical saety earth. Do not deeat the saety purpose o a grounding-type plug. A grounding-type plug has two pins and a third grounding prong. The third prong is provided or your saety. I the provided

    plug does not t into your outlet, consult an electrician or replacement o the obsolete outlet.Connect only to AC power outlets rated 100-120 V or 200-240 V, 50- 60 Hz as dictated by the units voltage conguration.9.

    Do not use this unit i the power cord is broken or rayed. Protect the power cord rom being walked upon or pinched, particularly at the plug and the point where it exits rom the apparatus.10.

    Only use accessories specied by the manuacturer.11.

    The unit is intended to use in a 19 rack. Follow the mounting instructions. When a rack on wheels is used, use caution when moving the loaded rack to avoid injury rom tipping over.12.

    Unplug this apparatus during lightning storms or when unused or long periods o time.13.

    Do not connect the units outputs in parallel or series with any other units output. Do not connect the units output to any other voltage source, such as battery, mains source, or power supply, regardless14.

    o whether the unit is turned on or o.

    Do not run any o the units outputs back into another channels input.15.

    Reer all servicing to qualied service personnel. Servicing is required when the apparatus has been damaged in any way such as:16.

    Power-supply cord or plug is damaged.

    Liquid has been spilled into the unit

    An object has allen into the unit

    The unit has been exposed to rain or moisture

    The unit does not operate normally

    The unit was dropped or the chassis is damaged

    17. Do not remove top or bottom covers. Removal o the covers will expose hazardou s voltages. There are no user serviceable parts inside and removal may void the warranty.

    18. An experienced user shall always supervis e this proessional audio equipment, especially i inexperien ced adults or minors are using the equipment.

    19. The mains plug is used as the disconnect device and shall remain readily accessible. I the mains plug is not readily accessible due to mounting in a 19 rack, then the mains plug or the entire rack must be

    readily accessible.

    20. The US National Dierencescl.16.3 requires that network cables must be fame rated VW-1.

    2 APPROVALs

    3 WARNINGs

    To reduce risk o re or electric shock, do not expose this apparatus to rain or moisture.

    Do not expose this system/apparatus to dripping or splashing and ensure that no objects lled with liquids, such as vases, are placed on the apparatus.

    Lappareil ne doit pas tre expos des egouttements deau ou des claboussures et de plus quaucun objet rempli de liquide tel que des vases ne doit pas tre

    plac sur lappareil.

    This apparatus must be connected to a mains socket outlet with a protective

    earthing connection.

    Cet appareil doi t tre raccord une prise de courant qui est branche la terre.

    The mains plug is used as a disconnect device and shall remain readily operable.

    Lorsque la prise du rseau dalimentation est utiliss comme dispositi de dconnexion, ce dispositi doit demeur aisment accessible.

    To reduce the risk o re or electric shock, do not remove screws. No user-serviceable parts inside. Reer servicing to qualied service personnel

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    5/37

    FP+ Series Operation Manual 5

    WARNINGs 3

    3.3 user responsibility

    3.3.1 Mains connection groning

    Your ampliier must be connected to a

    grounded socket outlet.

    3.3.2 Speaer otpt azar

    Power ampliers are capable o producing

    hazardous output voltages. To avoid electrical

    shock, do not touch any exposed speaker wiring

    while the amplier is operating. The external wiring

    connected to the speaker terminals shall be installed

    by a qualied instructed person or ready-made leads

    or cords o appropriate capacity shall be used.

    As the amplier outputs produce high voltage,do

    not connect or disconnect speaker cables when

    the mains power is on. Also, attach the saety cover

    on the speaker terminals or sae operation and to

    comply with electrical product approvals.

    3.3.3 Raio intererence

    A sample o this product has been tested and complies

    with the limits or the European Electro Magnetic

    Compatibility (EMC) directive. This equipment has

    also been tested and ound to comply with the limits

    or a Class B digital device, pursuant to Part 15 o

    the FCC Rules. These limits are designed to provide

    reasonable protection against harmul intererencerom electrical equipment. This product uses radio

    requency energy and i not used or installed in

    accordance with these operating instructions, may

    cause intererence to other equipment, such as radio

    receivers. However, there is no guarantee that inter-

    erence will not occur in a particular installation.

    I this equipment does cause harmul intererence

    to radio or television reception, which can be deter-

    mined by turning the equipment on and o, the user

    is encouraged to try to correct the intererence by

    one or more o the ollowing measures:

    Reorient or relocate the antenna.

    Increase the separation between the equipment

    and receiver.

    Connect the equipment to an outlet on a circuit

    dierent rom that to which the receiver is

    connected.

    Check i the aected unit complies with the EMC limits

    or immunity, (CE-labeled). I not, address the problem

    with the manuacturer or supplier. All electrical products

    sold in the EC must be approved or immunity against

    electromagnetic elds, high voltage fashes, and radio inter-

    erence.

    Consult the dealer or an experienced Radio/TVtechnician or help.

    3.3.4 Speaer amage

    Your amplier is very powerul and can be

    potentially dangerous to bothloudspeakers and

    humans alike. Many loudspeakers can be easily

    damaged or destroyed by overpowering them. Always

    check the speakers continuous and peak power

    capabilities. Although the ampliers attenuators can

    be used to reduce the overall gain,an increase o the

    input signal can result in ull output power, which

    may cause damage to connected speakers.

    3.3.5 Maintenance

    For sae and reliable operation, the dust covers behind

    the ront panel should be cleaned regularly. I the dust

    lters are not maintained there will be saety risks.

    For example the unit can ignite the dust and a re

    will occur due to high internal temperatures. There

    is also a risk that the unit will malunction since it is

    dependent on constant airfow rom ront to rear. I

    the dust lters are not clean and the unit malunc-

    tions, any resultant problems will not be covered by

    the warranty.

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    6/37

    6 FP+ Series Operation Manual

    4 WELCOME

    4.1 Introction

    Thank you or choosing Lab.gruppen FP+ Series

    power ampliers or your sound reinorcement sys-

    tem. We are condent that you will be pleased withthe perormance, conguration fexibility, reliability,

    and long-term durability oered by the FP+ Series

    products.

    This manual provides a comprehensive guide to the

    eatures and unctionality o FP+ Series ampliers.

    Please read through it to become ully acquainted

    with the many conguration options and multiple

    layers o protection circuitry. To acilitate timely

    installation and use o this FP+ Series product, we

    have included a Quick Guide Overview (section 6).

    This brie summary, in conjunction with Installation(section 5), contains the basic inormation needed

    to saely install the amplier and place it in service.

    However, we highly recommend reading through this

    manual in its entirety, beginning with Main Features

    and Technologies and continuing through Operation

    and Perormance. As you become thoroughly amiliar

    with all aspects o operation, you may learn o eatures

    or options that will aect your choices on amplier

    modes or loudspeaker system conguration.

    The Lab.gruppen FP+ Series builds on the oundation

    o the road-tested P Series, with the same sonic

    signature powerul, tight bass and transparent

    high requency response. In addition, the FP+ Series

    ampliers establish new benchmarks or extremely

    high power and channel density, and also oer the

    benets o remote computer monitoring and control

    via the NomadLink network.

    4.2 Main eatres

    The FP+ Series incorporates a number o sophisti-

    cated technologies many o them proprietary toLab.gruppen to ensure the best possible per-

    ormance and many years o reliable operation.

    Familiarizing yoursel with these technologies will

    prove invaluable in setting up and optimizing your

    loudspeaker system.

    4.2.1 Patente Class Td amplier anReglate Switc Moe Power Spply(R.SMPS)

    Lab.gruppens patented Class TD technology

    combines the exceptional eciency o a Class D

    amplier with the high sonic quality associated withClass B designs. Class TD also incorporates the same

    basic concepts behind Class H designs, but here they

    are rened and pushed to a higher level to achieve

    greater eciency.

    The Class TD output sections work in concert with

    Lab.gruppens unique, Regulated Switch Mode

    Power Supply (R.SMPS) to create a superior overall

    power amplier topology. R.SMPS ensures stable,

    ull output power over an extremely wide range o

    mains voltage levels. Sagging or fuctuating mains

    voltage will not aect the power output delivered tothe loudspeakers.

    4.2.2 Amplier gain

    For greater fexibility in system integration, FP+ Series

    ampliers allow gain adjustment rom +23 dB to +44

    dB in 3 dB steps. This eature accommodates any

    combination o input device and loudspeaker type.

    For example, i the input signal is weak, the gain can

    be boosted to maintain maximum power output while

    avoiding a poor signal-to-noise ratio. This gain adjust-

    ment eature makes it easier to achieve an optimal

    balance between headroom and noise foor.

    4.2.3 Voltage Pea Limiter (VPL)

    The Voltage Peak Limiter (VPL) eature allows

    user adjustments that determine maximum volt-

    age output, thus matching the amplier to the

    connected speaker load. Regardless o load impe-

    dance, the VPL eature can be set to ensure that

    neither temperature nor current limitations are

    exceeded beore reaching the desired voltage

    threshold.

    4.2.4 Protection an perormanceoptimization

    Appropriate and reliable power amplication is vital to

    any audio system. Inadequate or aulty power ampli-

    cation could cause damage to the loudspeakers, or in

    some cases to the power ampliers themselves. To

    prevent any damage or costly service interruptions,

    FP+ Series ampliers oer advanced eatures to

    protect both internal circuits and any connected loads.

    These eatures even protect the mains use that, in

    extreme cases, could be overloaded.

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    7/37

    FP+ Series Operation Manual 7

    Following are short descriptions o standard built-in

    FP+ Series protection eatures:

    CPL , (Current Peak Limiter) ensures that the am-

    pliers output does not exceed the sae current

    handling parameters o amplier components.Temperature protection ensures that theamplier will not be damaged by exceeding

    thermal limits.

    PAL , (Power Average Limiter) limits the maximum

    average power consumption according to the

    power supply and mains-breaker capabilities.

    Vh , (Very High Frequency) protection circuitsmute the output o the amplier when non-

    dynamic continuous signals above 10 kHz are

    detected.

    dC protection ensures destructive DC signals

    will not appear at the amplier outputs. I suchconditions occur an internal use opens and ault

    indication is displayed.

    Low-impeance (short circuit) protection pro-vides a ault warning indication and shuts down

    the output stage when, or example, an input

    signal is present and a malunctioning cable or

    driver is short circuiting the output.

    hig-impedance warning reports an alert when,

    at the same time, output signal is high and no

    current draw is measured. This situation might

    occur when no speakers are connected, or when

    a driver is blown.

    Low inrus current ensures that the mainsbreaker will not trip when several power

    ampliers are turned on simultaneously.

    4.2.5 NomaLin / Eternet control anmonitoring networ

    The NomadLink network allows easy setup, monito-

    ring, and control o FP+ Series power ampliers and

    other Lab.gruppen NomadLink-enabled ampliers.

    The patented network topology provides automatic

    detection and addressing o multiple ampliers,

    and is controlled rom a PC via the optional NLB

    60E NomadLink Bridge & Network Controller usingstandard TCP/IP communication. Phantom powering

    through the network cables enables the sotware

    to detect devices that are not currently turned on

    or connected to the mains. This ensures very high

    reliability and redundancy levels while allowing con-

    nected ampliers to remain on standby with no power

    consumption.

    Cable connections can be daisy-chained or easier

    system setup. This also reduces total component

    costs, simplies installation, and makes daily opera-

    tion more convenient. There is no need to create

    a star topology using many switches as with, or

    example, an Ethernet system. Individual amplieraddresses do not need to be manually entered; you

    will automatically know where an individual amplier

    resides in the network.

    A daisy chain network loop, in combination with

    the automatic addressing o devices, enables

    Lab.gruppens proprietary DeviceControl sotware

    to automatically create a precise picture o all con-

    nected devices and their relative position in the chain.

    By quickly creating a clear overview o the entire

    system conguration, DeviceControl provides fexible

    control o very large amplier systems. Set-up time isminimized, and critical inormation is readily available

    or monitoring perormance and solving problems

    during operation.

    Via NomadLink, you can monitor all metering data

    as well as all aults and warning indications simulta-

    neously. NomadLink also allows you to remotely

    control power on and power o, as well as engage

    Mute and Solo unctions on individual channels.

    WELCOME 4

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    8/37

    8 FP+ Series Operation Manual

    Figure 5.2b: Use washer or xed installation

    Figure 5.2c: Use tube or slide-on installation.

    5 INsTALLATION

    5.1 unpacing

    Careully open the shipping carton and check or any

    noticeable damage. Every Lab.gruppen amplier is

    tested and inspected beore leaving the actory andshould arrive in perect condition. I any damage

    is discovered, please notiy the shipping company

    immediately. Only the consignee may institute a claim

    with the carrier or damage incurred during shipping.

    Save the carton and packing materials or the carriers

    inspection. Should you ever need to ship the amplier,

    always use the original packaging materials.

    5.2 Monting

    Free airfow rom ront-to-rear o the amplier must

    be possible. Thereore, no doors or rack-lids should

    be mounted in ront o or behind the ampliers.

    Ampliers may be stacked directly on top o each

    other. There is no need or spacing in between units,

    though this might enable more convenient installation

    o cabling on the rear panel.

    It is recommended that rear supports be mounted or

    maximum long-term stability. Rear support brackets

    are included.

    Figure 5.2a: Rear support mounting hardware

    2x2x

    2x

    2x

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    9/37

    FP+ Series Operation Manual 9

    5.3 Cooling

    The amplier uses a orced-air cooling system with

    air fow rom ront to rear, maintaining a low operating

    temperature within dened limits. Front-to-rear air-fow is preerred as cooler air is present at the ront in

    nearly all applications. (This allows higher continuous

    power levels without encountering thermal problems.)

    Never attempt to reverse the airfow. The amplier

    modules require a pressure chamber between the

    ans and heatsink, and this eect unctions only in

    one direction.

    Make sure that there is an adequate air supply in ront

    o the amplier, and that the rear o the amplier has

    sucient space to allow the exhaust to escape. I

    the amplier is rack-mounted, do not use covers ordoors on the ront or rear o the rack.

    Should a heat sink overheat, the temperature

    sensing circuits will mute the overheating channel.

    I the power supply overheats, another sensing

    circuit will mute all output channels until the power

    supply cools to sae operating temperature. An early

    warning beore shut down will be indicated on the

    ront panel LEDs, and a warning will be sent through

    the NomadLink network.

    Always make sure that the dust-lters behind the

    detachable ront panel are clean to ensure maximum

    possible airfow.

    I the amplier malunctions due to dirty

    dust lters, any required repairs are not

    covered by the warranty.

    5.4 Operating voltage

    The label placed to the right o the mains

    cable on the rear o the amplier indicates theAC mains voltage or which the amplier is wired

    and approved: 115 V or 230 V. Connect the power

    cable only to the AC source type reerred to on the

    label. The warranty will not cover damage caused by

    connecting to an incorrect type o AC mains.

    Lab.gruppen switch mode ampliers use primary

    switching. Because the mains power is rectied

    directly in ront o the transormer, the amplier is

    insensitive to mains requency. It may be connected

    to 50 or 60 Hz sources, and actually will operate on

    line requencies rom DC to 400 Hz.

    I the power plug mounted at the actory is notappropriate or your country, it can be removed and

    the proper connector wired in its place as ollows:

    BLACK or BROWN LIVE

    WHITE or BLUE NEUTRAL

    GREEN or GREEN/YELLOW EARTH(GROUND)

    I you are not 100% condent o your

    competence to replace the mains plug, engage

    qualied personnel to do the job.

    Once a suitable AC supply is connected, the

    amplier can be turned on using the ront panel

    power switch. The amplier then goes through a

    sot-start sequence as it sel-checks its circuits. The

    ans will blow at high speed beore dropping to idle,

    and the power LED will illuminate.

    Inrush power is controlled and limited during sot-

    start, enabling multiple ampliers to be powered up

    simultaneously.

    5.5 Groning

    There is no ground lit switch or terminal on the

    FP+ Series ampliers. The signal ground is always

    foating, via a resistor, to chassis and thereore the

    grounding system is automatic.

    In the interests o saety, never disconnect the earth

    (ground) pin on the AC power cord.

    Use balanced input connections to avoid hum and

    intererence.

    INsTALLATION 5

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    10/37

    10 FP+ Series Operation Manual

    6 QUICK GUIDE OVERVIEW

    The ampliers ront panel presents the perormance

    and ault condition indicators, power and remote

    switches, and a removable dust-lter cover. Level

    potentiometers provide individual attenuation or the

    amplier channels. Range is 0 dB to - innity. (The

    12 oclock position indicates -10 dB attenuation.) Aconvenient label strip with writing surace is provided

    adjacent to each level potentiometer.

    To remove the dust-lter covers, loosen the thumb-

    screws located underneath the ront handles. This

    allows removal o the dust-lters or cleaning. The

    covers may be made tamper resistant by replacing

    the thumbscrews with Philips head or saety Torx

    screw. Thread size is M3.

    The amplier never should be operated

    without the dust-lters in place.

    6.1.1 Power on/o an remote switc

    The Power on/o switch is located on the right side.

    A second switch, labeled REMOTE, is above the

    Power switch. When the Remote switch is on (with

    mains connected and power on/o switch on), the

    yellow LED above it will illuminate indicating that

    external power on/o commands rom the NomadLink

    network connection will switch the amplier on or

    o. When Remote is activated the amplier will not

    switch on until a Power On command is receivedrom the network. When the remote switch is o,

    it is not possible to switch amplier power on or o

    using NomadLink network control.

    6.1.2 ront-panel LEds

    The ront-panel LED area includes the ollowing

    indicators per channel:

    VHF

    TEM

    NOMAD LINK

    BRIDGE C+D

    S IG - 2 0 - 15 - 1 0 - 4 VPLCPL

    S IG - 2 0 - 15 - 1 0 - 4 VPLCPL

    BRIDGE A+B MUTE

    MUTE

    S IG - 2 0 -1 5 - 10 - 4 V PL C PL

    S IG - 2 0 -1 5 - 10 - 4 V PL C PL

    HI-IMP

    HI-IMP

    HI-IMP

    HI-IMP

    CLIP

    CLIP

    CLIP

    CLIP

    VHF

    TEM

    VHF

    TEM

    VHF

    TEM

    PWR

    PALFP10000Q

    -10dB

    -inf 0

    -10dB

    -inf 0

    -10dB

    -inf 0

    -10dB

    -inf 0

    channelA

    B channel

    Cchannel

    Dchannel

    FP SERIES

    R

    POW

    POW

    6.1 ront-Panel overview

    Figure 6.1.2a: Front panel LED eld (per-channel)

    Vhf - Very High Frequency protection active (output muted)(Yellow constant)

    TEM - Temperature warning (Yellow fashing)TEM - Temperature mute (Yellow constant)MuTE - Channel muted via NomadLink network or dueto a ault condition (Red)

    CPL - Current Peak Limiter (CPL) active (Orange fashing)CPL - (Orange constant with output muted): Low impe-dance / short circuit detection ault

    VPL - Voltage Peak Limiter (VPL) active

    SIG

    - Signal levels - 40 dB (Sig) to 4 dBhi-Imp - High-impedance/open load detected (Orange)Brige - Bridge mode operation (Yellow)

    .When no VPL, CPL or PAL indicators are illumi-

    nated, and the VPL DIP-switch is set to maximum

    at the specied nominal load, the amplier

    channel is able to deliver maximum rated output

    power

    (PWR) Power on (Green)

    (PAL) Power Average Limiter active

    (Red)

    NomadLink network active (Blue)

    Figure 6.1.2b: Front panel global LED eld

    When the network is connected, the blue

    NomadLink LED will illuminate even when mains

    power is not connected. NomadLink receives

    phantom power rom the network as supplied

    by the NLB 60E.

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    11/37

    FP+ Series Operation Manual 11

    QUICK GUIDE OVERVIEW 6

    6.2 Rear-Panel overview

    SPEAKER OUTPUTSBALANCED INPUTS

    CH DCH D CH C+D CH BCH B CH A+BCH C CH A

    XLR PIN 1-SCRN PIN 2-POS PIN 3-NEG

    44dB

    41dB

    38dB

    35dB

    32dB

    29dB

    26dB

    23dB

    150V

    121V

    101V

    83V

    70V

    56V

    47V

    38V

    BRIDGE

    1+:+

    2- :-

    1+ CH D+

    1- CH D-

    1+ CH C+

    1- CH C-

    2+ CH D+

    2- CH D-

    1+ CH B+

    1- CH B-

    1+ CH A+

    1- CH A-

    2+ CH B+

    2- CH B-

    Ser.N:o Removed!

    WIRING

    NORMAL:CLASS2

    BRIDGED:CLASS3

    Must be grounded/earthedMade in Sweden

    200-240V 50-60Hz :2500WFP 10000Q

    DIP-switches

    or adjusting key

    eatures

    (See below)

    XLR connectors or

    inputs and loop thru

    Mains input 115 V

    or 230 V operation

    (Not selectable)

    NomadLink net-

    work In and Out on

    EtherCon-housed

    RJ45 connections

    4 channel version

    shown with Neutrik

    Speakon output

    connectors

    Rear view o two-channel model tted with Binding Post connectors

    Rear view o two-channel model tted with Speakon connectors

    Rear view o our-channel model tted with Binding Post connectors

    SPEAKER OUTPUTSBALANCED INPUTS

    CH DCH D CH C+D CH BCH B CH A+BCH C CH A

    XLR PIN 1- SCRN PI N2-POS PIN 3-NEG

    44dB

    41dB

    38dB

    35dB

    32dB

    29dB

    26dB

    23dB

    150V

    121V

    101V

    83V

    70V

    56V

    47V

    38V

    BRIDGE

    1+:+

    2 - : -

    1+ CHD+

    1- CHD-

    1+ CHC+

    1- CHC-

    2+ CHD+

    2- CHD-

    1+ CHB+

    1- CHB-

    1+ CHA+

    1- CHA-

    2+ CHB+

    2- CHB-

    Ser.N:o Removed!

    WIRING

    NORMAL:CLASS2

    BRIDGED:CLASS3

    Mustbe grounded/earthedMade in Sweden

    200-240V 50-60Hz :2500WFP 10000Q

    Rear view o our-channel model tted with Speakon connectors

    Figure 6.2: Two- and our-channel speaker output connector options (not applicable to all models)

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    12/37

    12 FP+ Series Operation Manual

    6 QUICK GUIDE OVERVIEW

    6.2.1 Networ an Congration section

    Four-channel model shown. Two-channel versions

    have VPL and Bridge Mode switches or channels

    A and B only. All models have dierent VPL values.

    Functions are otherwise identical.

    44dB

    41dB

    38dB

    35dB

    32dB

    29dB

    26dB

    23dB

    150V

    121V

    101V

    83V

    70V

    56V

    47V

    38V

    Figure 6.2.2a: Rear panel DIP-switch eld

    6.2.2 Te dIP-switc eatres

    The ollowing eatures may be adjusted using the

    DIP-switches on the rear panel o the amplier.

    Gain - Globally set or all channels, rom +23 dB to+44 dB in 3 dB steps.

    Option active - Not currently implemented.

    an Masked - When on, engages the intelligentan eature; an speed is lowered when no signal is

    present.

    Brige A+B an C+d - Switches the channel pairsinto bridge mode operation An automatic -6 dB gain

    compensation is applied.

    VPL - The Voltage Peak Limiter provides optimumpeak voltage settings or each channel. Level selec-

    tions vary by model within the FP+ Series.

    Mode - Select VPL mode to either Hard or Sotoperation. For channels driving sub-wooers and

    low-requency drivers, it is recommended to use

    the Hard setting or optimal operation. For mid- and

    high- requency drivers, always select Sot.

    VPL in Stanar Moe

    P 14000 P 13000 P 9000 P 7000 P 4000 P 10000q P 6000q

    195 V 195 V 170 V 155 V 121 V 150 V 101 V170 V 170 V 140 V 121 V 101 V 121 V 83 V

    140 V 140 V 116 V 101 V 83 V 101 V 70 V

    116 V 116 V 100 V 83 V 70 V 83 V 56 V

    100 V 100 V 80 V 70 V 56 V 70 V 47 V

    80 V 80 V 66 V 56 V 47 V 56 V 38 V

    66 V 66 V 54 V 47 V 38 V 47 V n/a

    54 V 54 V n/a 38 V n/a 38 V n/a

    VPL in Brige Moe

    P 14000 P 13000 P 9000 P 7000 P 4000 P 10000q P 6000q

    195 V 390 V 340 V 310 V 242 V 300 V 202 V

    170 V 340 V 280 V 242 V 202 V 242 V 166 V

    140 V 280 V 232 V 202 V 166 V 202 V 140 V

    116 V 232 V 200 V 166 V 140 V 166 V 112 V

    100 V 200 V 160 V 140 V 112 V 140 V 94 V

    80 V 160 V 132 V 112 V 94 V 112 V 76 V

    66 V 132 V 108 V 94 V 76 V 94 V n/a

    54 V 108 V n/a 76 V n/a 76 V n/a

    Table 6.2.2b: VPL voltage selections in Standard Mode

    Table 6.2.2c: VPL voltage selections in Bridge Mode

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    13/37

    FP+ Series Operation Manual 13

    6.2.3 Inpt an Otpt connectors

    All FP+ Series ampliers are equipped with balanced XLR-F input connectors. two-channel models also oer

    parallel (loop-thru) XLR-M output connectors or daisy-chaining multiple ampliers rom the same signal

    source.

    All FP+ Series ampliers except the FP 9000, FP 13000 and FP 14000 oer a choice o either binding post(BP) or Neutrik NL4FC Speakon output connectors (SP). The FP 9000, FP 13000 and FP 14000 are oered

    with BP connectors only as the potential maximum output current exceeds the recommended limits or the

    Speakon connectors.

    For specic conguration and wiring inormation, see section 7.4.

    QUICK GUIDE OVERVIEW 6

    Audio inputs - our-channel models Audio inputs and loop-thru connectors -

    two-channel models

    Speakon outputs - our-channel models

    Speakon outputs - two-channel models Binding Posts - two-channel models

    Binding Post outputs - our-channel model

    Figure 6.2.3a: Two- and our-channel input connector congurations

    Figure 6.2.3b: Two- and our-channel speaker output congurations

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    14/37

    14 FP+ Series Operation Manual

    6.3 NomaLin / Eternetnetwor setp

    The amplier includes, as a standard eature, internalacilities or the NomadLink monitoring and control

    network. All eatures o the NomadLink network are

    accessible via a PC running Lab.gruppens proprietary

    DeviceControl sotware. A single rackspace NLB 60E

    NomadLink Bridge & Network Controller accepts the

    TCP/IP data stream rom the computer and converts it

    to the NomadLink protocols. Even when no computer

    is connected, the NLB 60E can initiate stand-alone

    power on/o and muting unctions, as well as report

    any ault or warning conditions.

    The PC is connected to the NLB 60E using a

    standard Ethernet interace and a crossed Cat-5 cable(peer-to-peer setup). I a HUB or switch is in the

    network, standard straight Cat-5 cables must be

    used. The ront and rear Ethernet connections on

    the NLB 60E can be used individually, but only one

    PC at a time running DeviceControl can access the

    subnet.

    Many newer laptop computers will allow

    peer-to-peer connection with the NLB 60E

    using a standard straight Cat-5 cable in-

    stead o a crossed Cat-5 cable.

    The deault xed TCP/IP address o the NLB 60E is

    192.168.1.166. The subnet mask is 255.255.255.0.

    For urther details, please reer to instructions

    supplied with the NLB 60E unit.

    The NomadLink connections use standard straight

    Cat-5/RJ45 equipped cables. For a saer mechanical

    connection it is possible to use Neutrik EtherCon

    XLR-type housings on the cables.

    US National Dierences cl.16.3 requiresthat NomadLink network cables must be

    rated VW-1.

    The OUT port rom the NLB 60E must be connected

    to the IN port o the rst amplier. The OUT port

    rom the rst amplier in turn connects to the next

    ampliers IN port to orm a daisy-chain The OUT

    port on the last amplier is connected to the IN port

    on the NLB 60E to close the loop.

    There are electrical limitations to cable

    lengths on a NomadLink network, both interms o total cable length in the loop and

    between any two devices. Read the

    Operation and Perormance chapter in this manual,

    or the instructions supplied with the NLB 60E, to

    ensure the network is congured within these

    parameters.

    Although the network will unction as an

    open loop under most circumstances, it is

    strongly recommended that the loop be

    closed by connecting the last ampliers

    OUT port to the NLB 60Es IN port. Doing so will

    improve redundancy and communication speed.

    External contact closures and 24 V low/high triggers

    can be connected to the GPI connectors on the NLB

    60E or control o re-alarm systems or external

    power sequencers. For more details read the instruc-

    tions supplied with the NLB 60E.

    6 QUICK GUIDE OVERVIEW

    SPEAKER OUTPUTSBALANCED INPUTS

    CHDCH D CH C+D CH BCHB CH A+BCH C CH A

    X LR P IN 1 -S CR N P IN 2 -P OS P IN 3 -N EG

    44dB

    41dB

    38dB

    35dB

    32dB

    29dB

    26dB

    23dB

    150V

    121V

    101V

    83V

    70V

    56V

    47V

    38V

    BRIDGE

    1+:+

    2-:-

    1+ CHD+

    1- CHD -

    1+ CHC+

    1- CHC-

    2+ CHD+

    2- CHD -

    1+ CHB+

    1- CHB-

    1+ CHA+

    1- CHA-

    2+ CHB+

    2- CHB-

    Ser.N:o Removed!

    WIRING

    NORMAL:CLASS2BRIDGED:CLASS3

    Mustbe grounded/earthedMade inSweden

    200-240V 50-60Hz :2500WFP10000Q

    IN OUT

    NOMADLINK

    IN OUT

    NOMADLINK

    NOMADLINKIN OUTETHERNET

    GENERALPURPOSEINPUT,GPI

    ETHERNET

    "Crossed" RJ45 cable:

    Between NLB 60E and PC.

    "Straight" RJ45 cable:

    Between Ethernet switch or hub and NLB 60E.

    "Straight" RJ45 cables:

    Between NLB 60E and amplifiers, and fromamplifier to amplifier in a subunit.

    NOTE: Connection can be made to either

    the front or rear panel or the NLB 60E.Although two computers may be connectedto the NLB 60E simultaneously, only one isallowed access to the subnet at a time.

    Figure 6.3:NomadLink network wiring conguration

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    15/37

    FP+ Series Operation Manual 15

    Overall amplier input gain is adjusted using the

    input stage DIP-switches. Please note that the gain

    setting is global, aecting all channels. Following

    the input stage, the dedicated level control on each

    channel allows signal attenuation rom 0 dB to minus

    innity.

    The Current Peak Limiter (CPL) section dynamically

    limits the input signal based on three parameters:

    sensed current level, eedback rom the output stage,

    and sensed voltage clip rom the VPL (and output

    amplier voltage clip i Sot Clip is activated). This

    ensures that power output is maintained within the

    design limits o the amplier.

    The adjustable Voltage Peak Limiter (VPL) sets the

    maximum output voltage and thereore also the

    maximum output power. Eight dierent voltagestages are available using the DIP-switches on the

    rear panel o all models, except the FP 9000 and FP

    4000 that both have seven stages and the FP 6000Q

    which provides six voltage stages.

    The sophisticated output section monitors aults

    and generates appropriate warnings, which are

    displayed on the amplier ront panel and transmitted

    through the NomadLink network. These alerts allow

    the operator to adjust system settings and thereby

    avoid problems. In the rare event that conditions are

    extraordinarily severe, the amplier will shut down

    until the ault or problem setting has been rectiedor adjusted. These sensing circuits are also employed

    to eed back voltage and current level inormation,

    via a side chain, to the limiters. Sensing circuits

    also transmit local amplier module temperature

    and power supply temperature to the appropriate

    protection mechanisms. Read the Protection, Faults

    and Warnings section or urther details.

    7.1 Introction

    The ollowing sections provide comprehensive

    inormation on amplier connection, setup, operation,

    and perormance. The detailed inormation includedhere is essential to realizing the ull unctionality o the

    FP+ Series ampliers.

    7.2 Operation precations

    Make sure that the Power switch and the Remote

    switch on the amplier ront panel are set to

    o beore making any input, output or network

    connections, and also beore manipulating the

    DIP-switches on the rear panel.Make sure that the AC mains voltage is correct

    and matches the voltage printed on the rear panel

    o the amplier (115 V or 230 V).

    Make sure that no signal is present at the input

    to the amplier when powering up. An input

    signal could produce an unintentionally loud initial

    volume rom the speakers.

    7.3 Signal fow an earoom

    7.3.1 Signal fow blocs

    All FP+ Series ampliers have the same signal fow,

    and the same eature sets. The only internal dier-

    ences are in the maximum output current per channel

    and VPL settings.

    The input stage o all FP+ Series ampliers has a

    high sensitivity to provide ample system headroom.

    This in eect means that the input stage is almost

    impossible to clip.

    OPERATION AND PERFORMANCE 7

    Figure 7.3.1: FP+ Series signal fow diagram

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    16/37

    16 FP+ Series Operation Manual

    7.3.2 hearoom, sensitivity an VPL / Gainsettings

    The input amplier and limiter system is designed

    to accommodate extremes o perormance. Typi-

    cally, exceeding maximum input by much as +10 dB

    will only result in a 1% increase in distortion. Theollowing schematics illustrate how the adjustable

    VPL and Gain circuitry aect input sensitivity and

    output power.

    The tables to the let o the illustration 7.3.2 below

    show input sensitivity or a FP 13000 with a 2 ohm

    load and 195 V peak (max.) and 54 V peak (min.) re-

    spectively or the eight dierent gain stages between

    +23 dB and +44 dB. The resulting output power is

    displayed in dBu, Vrms and watts in the tables to the

    ar right. Complete input sensitivity tables or all VPL

    and Gain settings or all FP+ Series models can beound at www.labgruppen.com.

    The headroom available through the input stage to

    the clip limiter is shown by the dotted lines as +10

    dB at 195 V peak and +16.1 dB at 54 V peak. These

    lines illustrate the additional signal level that can be

    accepted at the input beore any signicant distortion

    will appear at the input stage.

    I you use the level potentiometer in the

    signal chain to reduce the level by an amount

    greater than the headroom relative to input

    sensitivity, AND you drive the amplier

    to clip level, you are in danger o clipping the input

    stage beore the current or voltage peak limiters are

    activated.

    When bridging two channels, you must

    add +6 dB to the input sensitivity to achieve

    maximum output voltage due to theautomatic -6 dB gain compensation

    inserted by the amplier.

    7 OPERATION AND PERFORMANCE

    Figure 7.3.2: FP 13000 VPL and GAIN settings

    Gain set to:(DIP-switches)

    + 44 dB+ 41 dB

    + 38 dB+ 35 dB+ 32 dB

    + 29 dB+ 26 dB+ 23 dB

    Voltage PeakLimiter set to:(DIP-switches)

    195 Vpeak

    170 Vpeak140 Vpeak116 Vpeak100 Vpeak80 Vpeak66 Vpeak

    54 Vpeak

    InputsensitivitydBu / Vrms

    1,0 / 0,87

    4,0 / 1,237,0 / 1,7

    10,0 / 2,5

    13,0 / 3,516,0 / 4,919,0 / 6,9

    22,0 / 9,8

    Hard/Soft switch

    Gain select switches Front panelpotentiometer

    DynamicGain reduction

    VPL select switches

    Class TD

    Voltage Clip sensing

    Current clip sensing

    Monitoring LevelTemperatureFault/Warning

    Control Mute

    + 10 dB headroom to cliprelative to input sensitivity *)

    Outputpower

    dBu / Vrms

    45,0 / 138

    43,8 / 12042,1 / 9940,5 / 82

    39,2 / 7137,3 / 5735,6 / 47

    33,9 / 38

    Gain set to:(DIP-switches)

    + 44 dB+ 41 dB

    + 38 dB+ 35 dB+ 32 dB

    + 29 dB+ 26 dB

    + 23 dB

    InputsensitivitydBu / Vrms

    -10,1 / 0,24-7,1 / 0,34-4,1 / 0,5

    -1,1 / 0,71,9 / 1,04,9 / 1,4

    7,9 / 1,910,9, / 2,7

    + 16,1 dB headroom to cliprelative to input sensitivity*)

    VPL set to 54 VPEAK

    VPL set to 195 VPEAK

    Input Amplifier Level Control Clip Limiter Voltage Peak Limiter Output Power Amplifier

    *) Headrom limited to +5dB at Gain set to +23 dB at Max. VPL

    Complete tables for all VPLsettings can be found at:www.labgruppen.com

    Output Power@ 2 Ohm

    Watt

    6.500 W

    6.500 W4.970 W3.540 W

    2.550 W1.850 W1.330 W

    960 W

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    17/37

    FP+ Series Operation Manual 17

    7.4 Aio Inpt an Otptconnections

    7.4.1 Balance Inpt connections

    Figure 7.4.1a: Audio inputs - our-channelmodels

    Figure 7.4.1a: Audio inputs and loop-thruconnectors - two-channel models

    The XLR input connectors are electronically ba-

    lanced, and wired according to the IEC 268 standard

    (pin 2 = hot). XLR input connectors should be wired

    as ollows:

    Pin 1 Ground/shield

    Pin 2 Hot (+)

    Pin 3 Cold (-)

    Figure 7.4.1c: Balanced XLR wiring schematic

    When linking the same source signal to

    several input channels, be aware that there

    is a limit to the number o channels an

    output source can drive. A typical output

    source (e.g. a DSP crossover unit) can drive up to

    our amplier channels beore external line-driversmight be required to buer the signal.

    7.4.2 unbalance Inpt connections

    Figure 7.4.2: Unbalanced XLR wiring schematic

    To connect an input to an unbalanced source, it is

    possible to connect pins 1 and 3 in the XLR plug at

    the amplier end o the cable. However, a better

    method is to connect pin 3 to the shield at the source

    end o the cable, as this usually results in better hum

    and noise rejection. Balanced input connections are

    recommended whenever possible.

    7.4.3 Speaon Otpt connections

    Reer to the instructions in this section i your amplier

    is equipped with the Speakon output connectors.

    Figure 7.4.3a: Speakon outputs - two-channelmodels

    Figure 7.4.3b: Speakon outputs - our-channelmodels

    OPERATION AND PERFORMANCE 7

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    18/37

    18 FP+ Series Operation Manual

    Two-cannel ampliers Two-channel ampliersare wired in the ollowing manner. The right Speakon

    connector, Channel A+B, provides outputs or both

    Channel A and Channel B. This output is useul when

    wiring the amplier or bridged mono operation. See

    section 7.4.6. The let Speakon connector providesan output or Channel B only.

    Connect the + and loudspeaker cables as shown

    in the illustrations below.

    Channel A and B into two

    separate Speakons

    Channel A and B into one

    Speakon (Stereo and Bi-amp)

    Bridge mono

    Figure 7.4.3c: Speakon wiring schematic

    our-cannel amplifers Additional connectorsare provided or Channel C and Channel D. Channel

    C unctions as Channel A above, and Channel D as

    Channel B above.

    7.4.4 Bining Post (BP) Otpt connectors

    Reer to the instructions in this section i your amplier

    is equipped with Binding Post output connectors.

    Figure 7.4.4a: Binding Post outputs -two-channel models

    Figure 7.4.4b: Binding Post outputs -our-channel models

    Connect the positive (+) loudspeaker cable to the

    positive (+) red terminals. Connect the negative (-)

    loudspeaker cable to the negative (-) black terminals.

    For bridge mode, connect the positive (+) terminal

    on Channel A to the positive (+) loudspeaker cable

    and the negative (-) terminal on Channel B to the

    negative (-) loudspeaker cable.

    Channels C and D on our-channel versions are

    connected in the same manner. For bridge mode,

    connect the positive (+) terminal on Channel C to the

    positive (+) loudspeaker cable and the negative (-)

    terminal on Channel D to the negative (-) loudspeaker

    cable.

    The outputs on all FP+ Series ampliers

    produce high voltage. Do not connect ordisconnect the loudspeaker cables while the mains

    power is on. Never operate the amplier with any

    portion o bare loudspeaker wire exposed. Also, at-

    tach the saety cover (4-channel Speakon

    versions only) on the speaker terminals or sae op-

    eration and to comply with electrical product

    approvals.

    7 OPERATION AND PERFORMANCE

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    19/37

    FP+ Series Operation Manual 19

    Never connect an output terminal to ground,

    or to any other input or output. Observe

    relative loudspeaker polarity: loudspeakers

    connected in reverse polarity will exhibit

    degraded perormance, particularly in bass requen-

    cies, and may be damaged as a consequence.

    Use a high-quality stranded loudspeaker

    cable, and keep cable runs as short as

    possible.

    7.4.5 Otpt brige moe

    It is possible to bridge channels in two-channel ver-

    sions, or in pairs o two (A+B and C+D) in our-channel

    versions. When bridged, the input source must be

    connected to input A (A+B) or C (C+D) respectively.

    Output speaker cables must be connected to the

    plus pole on channel A or C and the minus pole onB or D.

    The main benet o bridging the output is a doubling

    o output voltage. Bridging can be used to turn a

    our-channel FP 10000Q amplier, or example into

    a three-channel amplier with 2 x 1300 W and 1 x

    4200 W at 8 ohms or 2 x 2100 W and 1 x 5000 W

    at 4 ohms

    Most power amplier designs, when bridged, auto-

    matically introduce a +6 dB input gain boost which

    can lead the user to conclude that said amplierdelivers more than double the power when in

    bridge mode. This is clearly not the case, as the

    gain boost articially enhances perceived power at

    the cost o headroom. The FP+ Series ampliers

    work on globally set constant gain, and automatically

    compensate the input gain by -6 dB. For example, i

    the amplier is congured in a three-channel mode,

    then the selected gain is maintained rom input to

    output on all channels.

    7.4.6 Amplier Gain

    All FP+ Series ampliers eature adjustable input gain.

    This versatility enables the amplier to accommodate

    a multitude o system congurations with various

    input sources and speaker layouts. Amplier gain is

    set globally or all channels. The range is +23 dB to

    +44 dB in 3 dB steps. Individual channel ne level

    adjustment is available using the potentiometers on

    the ront panel.

    The unique adjustable input gain eature o the

    FP+ Series makes it easier to attain the optimum

    balance between headroom and signal-to-noise ratio

    in the signal path. A weak signal at the input might

    require the gain to be raised in order to achieve maxi-

    mum output power with the lowest signal-to-noiseratio. A hot input signal, however, would require

    a lowering o the gain to avoid sending the amplier

    into Voltage or Current clipping. See Appendix to

    review the table containing Gain versus VPL setting

    implications or input sensitivity and output power.

    Bridge mode operation automatically compensates

    by -6 dB, keeping all channels at the same gain.

    7.4.6.1 Cannel gain/level (ront-panel pots)

    Individual channel gain (level) may be adjusted using

    the potentiometers located on the ront panel. Rangeis rom 0 dB to -innity in 31 steps. The attenuation

    is logarithmic, with the 12 oclock position indicating

    -10 dB.

    I the level control is used to attenuate to a

    lower level than the headroom relative to

    input sensitivity AND the amplier input is

    driven into clip, there is a danger o clipping

    the input stage beore the current or voltage peak

    limiters are activated.

    7.4.6.2 Amplier sensitivity

    Sensitivity is dened as how many Volts (rms) or

    dBu (reerred to 0.775 Vrms) are required to achieve

    ull (maximum) output power. As the output power

    varies with the load impedance, 4 ohms is usually

    the common reerence. Since FP+ Series ampliers

    are capable o providing multiple maximum output

    power levels through use o the VPL eature, many

    sensitivity calculations may be required or a single

    amplier. We recommend use o the DeviceControl

    sotware to simpliy this process. DeviceControls

    Device View page, used in combination with the DIP-

    switch settings display, will automatically produce

    a sensitivity calculation rom the given data (VPL,

    Gain and load).

    OPERATION AND PERFORMANCE 7

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    20/37

    20 FP+ Series Operation Manual

    7.4.7 Otpt Voltage Pea Limiter (VPL)

    Voltage Peak Limiter (VPL) is a unique eature in

    FP+ Series ampliers. It is used to select the maxi-

    mum power available on each output channel. VPL

    levels are set using the rear-panel DIP-switches; eight

    level positions are oered on all models except theFP 6000Q, which oers six).

    P 13000

    V pea Vrms

    195 138

    170 121

    140 99

    116 82

    100 71

    80 57

    66 47

    54 38

    P 14000

    V pea Vrms

    195 138

    170 121

    140 99

    116 82

    100 71

    80 57

    66 47

    54 38

    P 7000

    V pea Vrms

    155 110

    121 86

    101 72

    83 59

    70 50

    56 40

    47 33

    38 27

    P 9000

    V pea Vrms

    170 121

    140 99

    116 82

    100 71

    80 57

    66 47

    54 38

    P 10000q

    V pea Vrms

    150 106

    121 86

    101 72

    83 59

    70 50

    56 40

    47 33

    38 27

    P 4000

    V pea Vrms

    121 86

    101 72

    83 59

    70 50

    56 40

    47 33

    38 27

    P 6000q

    V pea Vrms

    101 72

    83 59

    70 50

    56 40

    47 33

    38 27

    The values or VPL are displayed as maximum Voltage

    Peak. To translate Voltage Peak into Vrms, you must

    divide the Voltage Peak values by 1.41 (see table).

    The VPL allows you to set the correct maximum

    output peak power or optimum perormance with

    the connected speakers. The correct setting dependson the system type and the specic load connected

    to the channel. Since each channel can be congured

    to deliver either very high voltage peak power OR

    high current draw at low-impedances, it is important

    to set the VPL correctly.

    I you choose a lower VPL setting, you only reduce

    the maximum output voltage. At the same time, this

    allows more current headroom or low-impedance

    loads. The amplier thus runs at higher eciency,

    with a signicantly reduced risk o going into thermal

    protection.

    7.4.8 Otpt Crrent Pea Limiter (CPL)The Current Peak Limiter (CPL) ensures that the

    amplier will not be damaged by orcing the amplier

    to deliver current levels to the outputs that exceed the

    physical limits o the transistors. The CPL keeps the

    amplier within the Sae Operating Area (SOA).

    The CPL is non-adjustable and has dierent limit

    values depending on model type.

    CPL activity is indicated by illumination o an orange

    LED or each channel on the ront panel. Warningsalso are shown in the DeviceControl sotwares

    GUI.

    A steadily illuminated orange CPL LED (with MUTE

    illuminated) indicates a short circuit situation (or very

    low-impedance). The output will mute or 6 seconds

    beore measuring the output impedance again. This

    will continue until the short circuit is xed, at which

    time the output will automatically un-mute. An input

    signal must be present to allow detection o short

    circuit or low-impedance conditions.

    The problem can be solved by checking

    input and output cables and examining the

    state o the loudspeaker load. I there is no

    short circuit present, then the condition may

    be rectied by lowering the VPL or input levels.

    7 OPERATION AND PERFORMANCE

    Table 7.4.7: V peak to Vrms tables or theFP+ Series

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    21/37

    FP+ Series Operation Manual 21

    7.5 Protection, alts anwarnings

    7.5.1 IntroctionThe FP+ Series ampliers incorporate a sophisticated

    and comprehensive set o protection eatures. Faults

    and warnings are indicated on the ront panel and

    reported via the NomadLink network or indication

    on the DeviceControl GUI.

    7.5.2 Sae Operating Area detector (SOAd)

    The Sae Operating Area Detector (SOAD) compares

    output voltage against output current to ensure that

    the output transistors are working inside their sae

    operating area.

    The SOAD provides ault monitoring and input to

    the Current Peak Limiter (CPL). The SOAD has no

    dedicated indicator, and its operation is revealed only

    in conjunction with eatures such as the CPL.

    7.5.3 Very hig reency (Vh) protection

    All FP+ Series ampliers include protection circuits

    that detect continuous Very High Frequency content

    in the input signal. The detection begins at ap-

    proximately 10 kHz and moves upwards to include

    ultrasonic signal. I VHF signals are detected, the

    output will mute or 6 seconds beore re-measuring.Once no continuing VHF signal is detected, the output

    un-mutes and returns to normal operation.

    This eature recognizes that continuous ull-scale VHF

    signals do not appear in natural sources such as

    music. Any such signals can thereore be considered

    as a ault when present. VHF protection is essential

    in avoiding damage to high requency drivers.

    The VHF protection operational area is dependent

    on output power level and requency. The illustration

    below shows a decreasing threshold on the output

    power level, starting at approximately 10 kHz andrising with a -6 dB slope. This denes the VHF protec-

    tion area. When continuous output power above

    the threshold line is detected the VHF protection

    becomes active.

    20 Hz 10 kHz 20 kHz 30 kHz

    - 6 dB slope

    VHF protectionoperation area

    Max. Peakoutput power

    Max. Continousoutput power

    utputower

    Attack timeVHF protection

    Slow

    Fast

    20 Hz 10 kHz 20 kHz 30 kHz

    Figure 7.5.3: VHF protection attack time vs

    output power/requency

    The Attack time or the VHF protection is increa-

    singly shorter at higher requencies. For example, an

    ultrasonic continuous signal will cause the outputs to

    mute rapidly, where it will take several milliseconds

    or a 10 kHz continuous signal to trigger the output

    mute. This is shown in the illustration above.

    The VHF protection is NOT a limiter and does not

    alter the ampliers requency response. It is imple-

    mented solely to detect continuous VHF content. The

    amplier will always pass VHF peaks at ull power,

    with no eect on musical transients.

    The VHF protection is indicated by a yellow LED on

    the amplier ront panel, with output muting or 6

    seconds when in action. It is reported as a ault via the

    NomadLink network on the DeviceControl GUI.

    I you bench test the amplier using a

    continuous, ull scale sine-wave input above

    10 kHz, the VHF protection will activate and

    prevent measurement o ull peak output

    power. (Output will be muted long beore maximum

    output power is attained.) To measure the true peakoutput power, use a burst signal.

    7.5.4 dC protection

    DC protection is implemented on each output

    to prevent damage to connected loudspeakers.

    DC present at the output will trigger muting and

    illuminate the ault LED indicator. Any DC present

    at the output indicates a hardware malunction that

    requires servicing o the amplier.

    OPERATION AND PERFORMANCE 7

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    22/37

    22 FP+ Series Operation Manual

    7.5.5 hig-impeance warning (open loa)

    A high-impedance (open load) condition is indicated

    when an input signal above approximately -29 dB

    is detected and no unctioning loudspeakers are

    connected to the amplier. The ault in indicated

    by a orange Sig/Hi-imp LED. The indicator is greenwhen a valid load is present under the same input

    signal conditions

    Since the Hi-impedance detection

    initially triggers only when the input signal

    rises above -29 dB, it might cause the

    indicator to rst turn green, and then red,

    even in situations where no speaker is connected.

    7.5.6 Low-impeance protection warning

    A low impedance or short circuit ault is detected

    when current draw is high (Current Peak Limiteractive) and when, simultaneously, output signal

    is low (-4 dB LED does not illuminate). When this

    occurs, the amplier protects the output stage

    rom damage by muting the output signal and

    bypassing the circuits. Indication o this ault is a

    constant orange illumination o the Current Peak

    Limiter (CPL) LED on the ront panel. The protection

    will sequence at 6 second intervals to re-measure

    conditions. I the low-impedance ault is no longer

    detected, the amplier will un-mute.

    I the CPL turns constant orange, the outputis muted, and the -4 dB signal LED is ON,

    then the amplier has gone into maximum

    current protection. This situation is caused

    by an excessive input signal and is not due to a short

    circuit. Turn down the input signal to avoid or

    remedy this situation.

    7.5.7 Temperatre protection

    Thermal measurement points are provided on each

    output channel as well as on the power supply. These

    indicators will, i the pre-specied temperature level

    is exceeded, give a high temperature warning. Thiswarning condition is indicated by a fashing TEM LED

    on the ront panel, and it is reported on the Device

    Control GUI via the NomadLink network.

    As the amplier approaches a thermal protection

    threshold, the warning LED sequence will start with

    short on-time bursts. I the amplier continues

    to overheat and approaches the temperature limit,

    the fashing sequence will be dened by longer and

    longer on-time bursts until the protection mode is

    activated.

    I the temperature becomes too high to continue

    sae operation, the overheated output channel(s)

    will be muted until the temperature returns to anacceptable level.

    Fully active temperature protection (with muting) is

    indicated by a constantly illuminated TEM LED. It

    will also be indicated as a ault via the NomadLink

    network on the DeviceControl GUI.

    Temperature measurements will continue at 6

    second intervals. The output will un-mute when the

    channel or power supply returns to a sae operating

    temperature.

    7.5.8 Power Average Limiter (PAL)

    The Power Average Limiter (PAL) controls the

    current-drawing relationship between the power

    supply and the mains inlet. PAL limits the maximum

    average power consumption according to the power

    supply capabilities, ensuring that the PSU will not

    overload. In addition, in the larger models that

    potentially could pull more current rom the mains

    than the mains uses are specied to handle (more

    than 16 A), PAL limits the ampliers maximum

    current draw to prevent blowing the mains use.

    7.5.9 Sot-Start

    High powered ampliers with inadequate inrush

    limiting can pull considerable current rom the

    mains at turn-on. This can result in tripping o ast-

    acting mains breakers. Such is not the case with

    FP+ Series ampliers. The FP+ Series ampliers

    have very low inrush power as the capacitors are

    charged slowly and in a controlled manner ensuring

    that breakers will not trip.

    Several ampliers will, under normal conditions, be

    able to be powered up simultaneously. I you do

    experience problems powering up multiple ampli-

    ers simultaneously, use the NomadLink network

    and/or the NLB 60E to establish a power sequence

    with a preset delay between the start-up o each

    subsequent amplier.

    7 OPERATION AND PERFORMANCE

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    23/37

    FP+ Series Operation Manual 23

    7.6 ront-panel monitoring anajstments

    7.6.1 Level inicators

    Figure 7.6.1: Front panel LED eld (per-channel)

    The ront-panel displays an array o ten LED indica-

    tors or level and status monitoring o each amplier

    channel. Indications related to signal levels are as

    ollows:

    Orange CPL (Current Peak Limiter) fashing

    Indicates that output signal has reached the limit

    o the output devices and limiting is in eect.

    Red VPL/CLIP Indicates that signal has reached

    maximum output voltage. (Maximum voltage is

    determined by rear-panel VPL settings.)

    Green SIG to -4 Indicates output signal levelsin normal operating range

    SIG + hI-IMP (green/orange) Indicates inputsignal above 44 dB. Should the SIG indicator

    turn red, this indicates a high-impedance

    or open connection has been detected at theoutput. Possible aults include a disconnected

    cable or malunctioning loudspeaker. (In some

    cases a normal condition, such as a sub-bass

    enclosure with high-impedance at a certain

    requency, can trigger this indication.) I the -10

    dB LED illuminates AND the HI-IMP LED turns

    orange, then the amplier has detected an open

    load (no loudspeaker connected).

    More detailed signal indications are available using

    the DeviceControl sotware application.

    7.6.2 Level ajst

    Level adjust potentiometers (one per channel) are

    located on the ront panel adjacent to the LED display.

    The potentiometers operational range is 0 dB to

    minus innity in 31 steps. Attenuation is logarithmic,

    with -10 dB at the 12 oclock position. See table or

    levels at other increments.

    OPERATION AND PERFORMANCE 7

    Step Attenation

    1 (Min) -In. dB

    2 -60.5. dB

    3 -48.3 dB

    4 -33.9 dB5 -25.8 dB

    6 -21.6 dB

    7 -19.2 dB

    8 -17.4 dB

    9 -16.0 dB

    10 -14.7 dB

    11 -13.7 dB

    12 -12.7 dB

    13 -12.1 dB

    14 -11.3 dB

    15 -10.6 dB

    16 -10.0 dB

    17 -9.3 dB

    18 -8.7 dB19 -8.1 dB

    20 -7.4 dB

    21 -6.8 dB

    22 -6.1 dB

    23 -5.3 dB

    24 -4.5 dB

    25 -3.6 dB

    26 -2.7 dB

    27 -1.7 dB

    28 -0.7 dB

    29 -0.3 dB

    30 -0.2 dB

    31 (Max) -0.0 dB

    Table 7.6.2: Attenuation or ront panel poten-tiometers in steps-to-dB levels

    Note that it is not possible to adjust individual chan-

    nel attenuation rom the NomadLink network or

    elsewhere on the amplier.

    7.6.3 Mte inication

    Individual channel Mute is indicated by illumination

    o the red MUTE LED provided or each channel. I

    only the red MUTE LED is illuminated and all other

    indications are normal, then the channel has beenmuted by a command rom the NLB 60E ront panel

    or the DeviceControl application. Otherwise, an il-

    luminated MUTE LED could indicate a ault condition

    (see below).

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    24/37

    24 FP+ Series Operation Manual

    7 OPERATION AND PERFORMANCE

    7.6.4 Perormance, Warning an altinicators

    Global Inicators:

    Figure 7.6.4a: Front panel global LED eld

    Power on/o (green) indicates that mains poweris switched on.

    NomadLink (blue) indicates that the network

    is connected. The NomadLink LED will light up

    even beore the mains power is connected and

    switched on as it takes phantom power rom the

    network cable.

    PAL , Power Average Limiter (red), indicatesthat the amplier is limiting because the power

    supply and/or the mains-inlet use has reached

    maximum capability.

    Cannel Inicators:

    Figure 7.6.4b: Front panel LED eld(per-channel)

    Brige moe (yellow) indicates i two channelsare bridged using the DIP-switch on the rear

    panel.

    CPL, Current Peak Limiter (orange), whenfashing indicates the maximum possible current

    draw has been reached.

    CPL, Current Peak Limiter (orange), when con-stant indicates excessive current draw caused

    by a short circuit on the output or very low

    operational impedance. MUTE LED will illuminate

    and the output will mute or 6 seconds beore

    re-measuring the output impedance. This will

    continue until the short circuit is removed. CPL

    remains constant orange in a ault condition only

    when an input signal is present.

    Temperature (yellow) warning is indicatedby a fashing LED. I the amplier goes into

    thermal protect (output muted), the TEM LEDilluminates constant yellow and the red MUTE

    LED illuminates.

    Vh, Very High Frequency protection (yellow)

    indicates that potentially harmul continuous high

    requencies have been detected on the input

    signal. The output is muted (MUTE LED on).

    hardware ault is indicated when both the CPL

    and TEM, VHF and MUTE indicators light up

    simultaneously. The amplier requires servicing

    beore placing back in operation.

    7.7 NomaLin networ andeviceControl sotware

    7.7.1 NomaLin networ in te ampliers

    Figure 7.7.1: NomadLink Network RJ45connectors

    All FP+ Series ampliers are equipped with the

    proprietary NomadLink network interace. This

    includes two EtherCon housed RJ45 connections:

    one IN and one OUT.

    Use standard straight Cat-5 Ethernet cables with

    RJ45 connectors to connect the amplier to the NLB

    60E or to daisy-chain multiple ampliers.

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    25/37

    FP+ Series Operation Manual 25

    It is very important that two IN or two OUT

    ports are NEVER connected to each other.

    This will cause the NomadLink communi-

    cation and DeviceControl to exhibit erratic

    behavior and display inaccurate data. However, this

    situation will not damage the amplier circuitry.

    Up to 60 ampliers can be connected to one NLB

    60E in a daisy-chain or closed loop.

    When the NLB 60E is powered up, the NomadLink

    network receives phantom power. This causes the

    blue NomadLink LED on the amplier ront panel

    and the NomadLink LED on the rear panel to light

    up. NomadLink is active even when the amplier has

    mains power disconnected or is not yet powered

    up.

    The amplier does not have a stand-by power

    supply or the network. The network is solely

    powered rom the NLB 60E. Should an amplier ail

    or be inadvertently disconnected rom the mains,

    network integrity is ully maintained and all ampliers

    remain visible on the system.

    7.7.2 Connection an setp

    The NomadLink network requires use o an NLB

    60E NomadLink Bridge & Network Controller. The

    NomadLink network is established by connecting the

    NLB 60E OUT port to the rst ampliers IN port.Then a daisy-chain is established by connecting the

    rst ampliers OUT port to the next ampliers IN

    port, and so on. I a closed loop network is desired

    or improved redundancy (highly recommended), the

    last ampliers OUT port must be connected to the

    NLB 60Es IN port.

    For all connections, straight Cat-5 RJ45-equipped

    Ethernet cables should be used.

    To ensure ull perormance o your NLB 60E

    NomadLink Bridge & Network Controllerwith the expanded range o FP+ Series

    ampliers, as well as ull compatibility with

    Lab.gruppens third party control protocol, please be

    sure that you are using the most up-to-date rmware.

    This is available or download at:

    www.labgruppen.com/index.php/support/sot-

    ware_rmware/

    OPERATION AND PERFORMANCE 7

    Please register at the website to gain access, and to

    allow us to inorm you when updates are available.

    Optimal NomadLink perormance can only

    be assured when using Cat-5 cables.

    However, as NomadLink is only using twowires + ground or communication and

    phantom power it is possible to create converters

    rom RJ45 to, or example, XLR connectors using

    2-wire shielded cable. The NomadLink network can

    then be operated using a standard tie-line in a

    multicore signal distribution system. See the drawing

    below or an example o how to create a

    converter.

    Figure 7.7.2: NomadLink RJ45 to XLR wiringschematic

    I any cable ormat or connection other than

    Cat-5 (or better) and RJ45 is utilized,

    network perormance may be compro-

    mised. In this event Lab.gruppen cannot

    guarantee that the NomadLink network will be ullyoperational.

    7.7.3 NomaLin networ cable lengts

    In situations where the ampliers and the NLB 60E

    will be positioned in dierent locations at some

    distance rom each other, or where groups o

    ampliers within a single subnet with up to 60 units

    will be installed with a distance in between, these

    general rules may be considered:

    Below are typical examples o NomadLink network

    setups:

    Rle 1: The maximum cable length in betweenany two devices may not exceed 300 meters /

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    26/37

    26 FP+ Series Operation Manual

    980 eet.

    Rle 2: In a non-closed-loop daisy-chained subnet the total maximum cable length is 400 meters / 1300eet.

    Rle 3: In a closed-loop subnet the total maximum cable length is 700 meters / 2300 eet.

    7.7.4 Eternet networ cable lengtsThe connection between the NLB 60E and your PC is a standard Ethernet network running the TCP/IP protocol.

    Cable distances between NLB 60E and your PC ollow standard rules or Ethernet systems.

    Contact your IT expert or more details.

    7.7.5 deviceControl sotware

    DeviceControl is Lab.gruppens proprietary sotware application or monitoring and controlling networked

    FP+ Series and other Lab.gruppen NomadLink-ready power amplier. DeviceControl runs on a Windows PC,

    which connects via Ethernet to the NLB 60E NomadLink Bridge & Network Controller. DeviceControl provides

    comprehensive monitoring o amplier status as well as control o amplier power on/o and individual channel

    mute and solo unctions.

    Please review the DeviceControl Operation Manual or more detailed inormation.

    7 OPERATION AND PERFORMANCE

    Figure 7.7.5a: NomadLink daisy chain conguration

    Figure 7.7.5b: NomadLink closed loop conguration

    Figure 7.7.5c: NomadLink closed loop daisy chain conguration

    Figure 7.7.5d. NomadLink dual daisy chain closed loop conguration

  • 8/22/2019 FP+ Operation Manual OM-FP+ Rev105

    27/37

    FP+ Series Operation Manual 27

    8.1 Maintenance

    During normal operation your FP+ Series amplier

    will provide trouble-ree service. The only user main-

    tenance required is to periodically vacuum clean theoam dust-lters behind the ront grille.

    In some extreme cases it may be necessary or

    authorized service personnel to clean the inside o

    the amplier. These conditions usually occur ater

    prolonged use in extreme environments such as

    those using cracked oil smoke machines. I you

    are using your amplier in a heavy duty application,

    it is recommended to have your amplier serviced

    every 3 years purely as a preventative action.

    8.2 Aq

    Following are common questions asked about

    Lab.gruppen FP+ Series power ampliers together

    with helpul answers.

    q: What is the input sensitivity o the ampliers?A: Input sensitivity is calculated rom the ampliergain, maximum output voltage and load. As gain and

    output voltage is adjustable in FP+ Series ampliers,

    you need to look this inormation up in a table ound in

    the Appendix section o this manual. Input sensitivity

    also is automatically calculated in the DeviceControl

    sotware application.

    q: What are the maximum cable lengths allowed

    when using the NomadLink network?

    A: NomadLink uses a daisy-chain topology toconnect ampliers and an NLB 60E in a network.

    Standard RJ45-equipped Cat-5 cables are used

    throughout. The daisy chain may be made into

    a closed-loop by connecting a return cable to the

    NLB 60E rom the last amplier.

    General rules o cable lengths:

    The maximum cable length in between any

    two devices may not exceed 300 meters / 980

    eet.

    In a non-closed-loop daisy-chained subnet the

    maximum cable length is 400 meters / 1300

    eet.

    In a closed-loop subnet the maximum cable

    length is 700 meters / 2300 eet.

    Exceeding these limits may result in lost contact

    with the devices, or loss o phantom powering due

    to cable resistance.

    q: How long can cable-runs be on the Ethernet

    network connecting the NLB 60E to the PC?A: On the Ethernet side, normal Ethernet cable limits

    apply. This is typically a maximum o 80 meters / 300

    eet between each device. Follow standard instal-

    lation procedures or Ethernet. Distances beyond

    100 meters may require use o a repeater, a ormat

    converter, or optical cables.

    q: Why is the NomadLink network a closed-loop

    topology?

    A: Technically speaking, the closed loop isoptional. The purpose o closing the loop is primarily to

    provide a secondary path to the ampliers. I cablesare broken or disconnected in either direction, all

    ampliers still may be addressed by the network.

    q: How can I be sur