    Specifications

    Issue/Rev. 0.6 (2/08) Bulletin SS03010

    Smith MeterValves

    Model 215 Wafer Sphere3"-12" Digital Control Valve

    The Smith MeterModel 215 Digital Control Valveisa high-performance, wafer-sphere valve with a solenoid-

    controlled pneumatic/hydraulic actuator.When used in conjunction with one of the Smith MeterElectronic Valve Controllers (e.g., Model SS1, Accu-Load, or MiniLoad), a Model 215 Valve provides precise,trouble-free, low pressure drop, preset loading, and/orflow control of virtually any flowing liquid. The Model215 is particularly well suited for applications on heavyfuel oils or lube oils where viscosity limits the use ofhydraulic valves.

    Features

    Operation is independent of fluid viscosity andpressureto assure proper control under virtually alloperating conditions.

    Wide fluid compatibilitycan be assured by properselection of valve-wetted materials.

    Fail-safe operationsince valves are spring-loadedfail-to-close.

    Pre-wired, explosion-proof junction boxsuppliedas standard.

    Main valve meets NACE MR-01-75 requirements.

    Options

    Pneumatic or Hydraulic Actuation.

    Pressure regulator.

    Pressure gauge.

    Limit switches.

    Hydraulic Power Pack.

    Customer to ConnectAir or Hydraulic Supply

    Pressure Gauge (Optional)

    N.C.

    Solenoid N.O.Solenoid

    NeedleValve

    LimitSwitch

    (Optional)

    To Atmosphere(Air)

    To Tank(Hydraulic)

    NeedleValve

    Note:Valve normally closed.

    PressureRegulator

    (Optional)

    Figure 1 Model 215 Valve Schematic

    Operation

    The valve schematic in Figure 1illustrates the simplicityof the solenoid-controlled actuator system of the Model215 Valve. The normally closed (N.C.) and normallyopen (N.O.) solenoids, located on the pressure andrelief lines (respectively) of the actuator, control theoperation of the valve. Opening the pressure line andclosing the relief line, by energizing both solenoids,allows high pressure air or hydraulic fluid to enter theactuator, pushing the diaphragm and opening the valve.Conversely, de-energizing both solenoids allows thehigh pressure in the actuator to relieve to atmosphereor back to the hydraulic reservoir, permitting the actuatorspring to close the valve. Closing off both the pressureand relief lines (energizing the N.O. solenoid only) locksthe valve in place. The needle valve settings control thevalve opening and closing speeds.

    3" Model 215

    The Most Trusted Name In Measurement

  • 8/12/2019 fmc - LCV

    2/4

    Page 2 SS03010 Issue/Rev. 0.6 (2/08)

    Specifications (For standard Wafer Sphere Type215 Valve)

    Main Valve

    Type: High-performance, wafer-sphere valve standard.

    Sizes: 3" to 12", installed between Class 150 ANSI RFcompanion flanges (supplied by others).

    Operating Pressures: 285 psig (Class 150 ANSI) standard. Other pressures available on request.

    Operating Temperatures: -20F (-29C) to 100F (38C)1.

    Materials of Construction:

    Body Carbon SteelDisk and Shaft Stainless SteelSeat TFE (Teflon)Other materials available on request.Meets NACE MR-01-75 requirements.

    Actuator

    Type: Spring diaphragm

    Materials of Construction:

    Body Carbon steelDiaphragm Buna-N

    Air Supply: Clean, dry air or gaseous nitrogen.

    Hydraulic Supply: Clean Hydraulic Fluid, Dextron II orequivalent.

    Operating Pressure: 100 psig maximum, 60-85 psignormal.

    Operating Temperature: -20F (-29C) to 150F (68C).

    Needle Valve

    Material: Brass standard Stainless Steel optional

    Tubing and Fittings

    Material: Steel standardStainless Steel optional

    Optional Equipment

    Pressure Regulator: 0-250 psi (air only)

    Pressure Gauge: 0-160 psiOptional Limit Switches: Two SPDT, UL-listed, CSAcertified FM approved. (NEMA 4, 7 Groups C andD, and 9 Groups E, F, and G) for combined water-tight and hazardous location design. Switches arerated at 15A with 125/250 Vac and 0.5A dc resistive.

    Hydraulic Power Pack

    110/240 VAC 50/60 Hz Single Phase.

    1 HP Explosion Proof Motor Class I, Div. IGroups C&D.

    3.0 GPM gear pump for fast response.

    Hydraulic Supply and Return Manifolds Drivesup to 6 valve actuators (Ref. Smith 215 SeriesValves). Size 3/8" SAE for supply and 1/2" SAEfor return.

    5 Gallon Reservoir with top filler/breather, drainplug and sight-level (small footprint).

    Supply Pressure Regulator with adjustable setpoint 0 to 200 psig with liquid filled gauge.

    On Demand Pump activates only when valvecontrol is needed, used in conjunction with anAccuLoad or other preset controller.

    * Consult factory on valves larger than 4".

    Solenoids

    Explosion-proof, UL-listed and CSA-certified for NEMA

    4 and 7, Groups C and D, for use in watertight andhazardous locations.

    Type: 2-way normally closed on pressure line 2-way normally open on exhaust line

    Materials of Construction:

    Standard Brass with Buna-N diskOptional Stainless Steel with Viton disk for service

    in corrosive atmosphere

    Operating Pressure: 85 psi maximum

    Operating Temperature: -40F (-40C) to 180F (82C)

    Voltage: Standard 102-120 Vac 60 Hz 94-110 Vac 50 Hz

    204-240 Vac 60 Hz 188-220 Vac 50 Hz Optional 20-25 Vdc 10.2-12.6 VdcOther voltages, consult factory

    Applications: Open or closed position indication forsignaling devices, panel light operation, etc.

    Valve open position limiting to facilitate prompt valveclosure in dedicated service where an SS1 Controlleror AccuLoad is not required.

    1 Higher temperatures available with decrease in maximumworking pressure.

  • 8/12/2019 fmc - LCV

    3/4

    Issue/Rev. 0.6 (2/08) SS03010 Page 3

    Dimensions

    Inches (mm)

    Typical Actuator Number2

    Air of Preset Swept Deliveries Valve Volume per Cylinder Size A B C D E F G H J L Cv (in3) of GN

    23

    1.9" 1.1" 5.0" 2.9" 1.7" 10.9" 8.2" 4.4" 8.9" 21.9" 3" 165 66 3,000 (49) (27) (127) (73) (42) (277) (207) (113) (227) (558)

    2.1" 1.2" 6.2" 3.8" 1.7" 11.4" 8.2" 4.9" 8.9" 21.9" 4" 400 66 3,000 (54) (30) (157) (95) (42) (290) (207) (125) (227) (558)

    2.3" 1.9" 8.5" 5.6" 2.1" 13.2" 8.3" 5.9" 10.9" 24.2" 6" 1,050 133 1,500 (57) (33) (216) (142) (53) (337) (212) (149) (273) (616)

    2.5" 1.4" 10.6" 7.4" 2.7" 15.4" 8.8" 7.6" 12.6" 26.4" 8" 2,200 265 750 (64) (35) (270) (188) (67) (391) (222) (194) (319) (670)

    2.8" 1.6" 12.8" 9.3" 3.4" 18.8" 9.2" 9.2" 15.0" 30.4" 10" 3,300 531 375 (71) (41) (324) (236) (86) (478) (235) (235) (381) (786)

    3.2" 1.9" 15.0" 11.2" 1.8" 18.6" 9.2" 10.8" 15.0" 30.4" 12" 5,100 531 375 (81) (48) (381) (284) (44) (471) (235) (273) (381) (786)

    Inches (mm)

    Note: Dimensions Inches to the nearest tenth (millimeters to the nearest whole mm), each independently dimensioned from respectiveengineering drawings.

    G

    E

    C

    A

    H

    B

    F

    J

    7.7" (195)Constant

    D (Dia.)

    L

    11.25" (285.8)

    Constant

    2 Based on using air at a rate of one full actuation at 45 psig for each preset delivery.3 One standard cylinder of gaseous nitrogen (GN

    2) contains 300 standard cubic feet.

  • 8/12/2019 fmc - LCV

    4/4

    Editorial change included in SS03010 Issue/Rev. 0.6 (2/08): Page 1: EDITORIAL CHANGE footnote (1) moved from page 1 to page 2.

    Printed in U.S.A. 2/08 FMC Technologies Measurement Solutions, Inc. All rights reserved. SS03010 Issue/Rev. 0.6 (2/08)

    Visit our website at www.fmctechnologies.com/measurementsolutions

    The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currentlyin effect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.

    Headquarters:500 North Sam Houston Parkway West, Suite 100, Houston, TX 77067 USA, Phone: +1 (281) 260-2190, Fax: +1 (281) 260-2191

    Gas Measurement Products:Houston, TX USA+1 (281) 260-2190Thetford, England +44 (1842) 82-2900Kongsberg, Norway+47 (32) 286-700Buenos Aires, Argentina+54 (11) 4312-4736

    Integrated Measurement Systems:Corpus Christi, TX USA+1 (361) 289-3400Kongsberg, Norway+47 (32) 286-700San Juan, Puerto Rico +1809(787) 274-3760United Arab Emirates, Dubai+971 (4) 331-3646

    Liquid Measurement Products:Erie, PA USA+1 (814) 898-5000Los Angeles, CA USA+1 (310) 328-1236Slough, England +44 (1753) 57-1515Ellerbek, Germany+49 (4101) 304-0Barcelona, Spain+34 (93) 201-0989Moscow, Russia+7 (495) 564-8705Melbourne, Australia+61(3) 9807-2818

    Beijing, China +86 (10) 6500-2251Singapore +65 6861-3011Chennai, India +91 (44) 450-4400