FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD I JOIST F4543.03 STC 63 IIC 56 CONSTRUCTION Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Johns Manville R-13 Fiberglass Insulation Weyerhaeuser TrusJoist 360 TJI Joist RSIC-1 Installed @ 24"x48" Clark Dietrich 087F125-18 Furring Channel @ 24" O.C. 2 Layers Type C Gypsum Panel STC 63 Test Number F4543.03 IIC 56 ©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710 RSIC® is a registered Trade Mark of PAC International, LLC. STC IIC

Upload: others

Post on 15-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • FLOOR CEILING ASSEMBLY

    DIRECT FIX TO WOOD I JOIST

    F4543.03 STC 63 IIC 56

    CONSTRUCTIONMetroflor Commonwealth Commercial Luxury Resilient TileHacker Industries, Inc. Firm-Fill Gypsum ConcreteHacker Industries, Inc. Firm-Fill SCM-250 Sound Control MatOriented Strand Board SheathingJohns Manville R-13 Fiberglass InsulationWeyerhaeuser TrusJoist 360 TJI JoistRSIC-1 Installed @ 24"x48"Clark Dietrich 087F125-18 Furring Channel @ 24" O.C.2 Layers Type C Gypsum Panel

    STC 63Test Number F4543.03 IIC 56

    ©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710RSIC® is a registered Trade Mark of PAC International, LLC.

    STC

    IIC

  • 130 Derry Courtaa

    York, PA 17406aa

    p. 717.764.7700

    f. 717.764.4129www.archtest.com · www.intertek.com/building

    Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips

    Ceiling Isolation: 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel

    Ceiling: 15.9 mm Type C Gypsum Panel

    Ceiling: 15.9 mm Type C Gypsum Panel

    Reference should be made to Intertek-ATI Report F4543.03-113-11 for complete test specimen

    description. This page alone is not a complete report.

    Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete

    Subfloor Underlayment: 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat

    Subfloor: 18.8 mm Oriented Strand Board Sheathing

    Insulation: 88.9 mm Johns Manville R-13 Fiberglass Insulation

    Joist: 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist

    Test Specimen Identification:

    Floor Topping: 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile

    Specimen Type: Weyerhauser TJI Assembly - 302 mm

    Overall Size: 3023 mm by 3632 mm

    STC 63

    IIC 56

    Series/Model: FIRM-FILL® Brand Gypsum Concrete and FIRM-FILL® SCM-250

    Sound Control Mat - Metroflor® Commonwealth Commercial Luxury Resilient Tile

    F4543.03-113-11-R2

    ACOUSTICAL PERFORMANCE TEST REPORT

    ASTM E 90 AND ASTM E 492

    Rendered to

    HACKER INDUSTRIES INC.

  • 130 Derry Courtaa

    York, PA 17406aa

    p. 717.764.7700

    f. 717.764.4129www.archtest.com · www.intertek.com/building

    ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)

    ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in

    Sound Insulation Test Methods

    Test Procedure

    All testing was conducted in the VT test chambers at Intertek-ATI located in York,

    Pennsylvania. The microphones were calibrated before conducting the tests.

    The airborne transmission loss test was conducted in accordance with the ASTM E 90 test

    method using the single direction method. Two background noise sound pressure level and five

    sound absorption measurements were conducted at each of five microphone positions. Four

    sound pressure level measurements were made simultaneously in both rooms, at each of five

    microphone positions.

    Test Methods

    The acoustical tests were conducted in accordance with the following standards. The equipment

    listed in the attachments meets the requirements of the following standards.

    ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound

    Transmission Loss of Building Partitions

    ASTM E 413-10, Classification for Rating Sound Insulation

    ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound

    Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine

    Report Date 03/03/16

    Revision Date 04/29/16

    Project Scope

    Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct

    airborne sound transmission loss and impact sound transmission tests. The complete test data is

    included as attachments to this report. The client provided the test specimen. The specimen was

    constructed on the date of testing.

    Newport Beach, California 92660

    Report F4543.03-113-11

    Test Date 02/04/16

    Page 1 of 5

    Acoustical Performance Test Report

    HACKER INDUSTRIES INC.

    1600 Newport Center Drive, Suite 275

    F4543.03-113-11-R2

  • TJI Joist57.2 by 3023 301.6 Weyerhaeuser TrusJoist® 360 21.2 lin m 4.46 kg/m

    Note: Fastened to perimeter frame on 610 mm centers

    2962 by 584 88.9 Johns Manville R-13 10.98 m² 1.25 kg/m²

    Note: Laid directly over furring/hat channels.

    Oriented Strand

    Board Sheathing

    1219 by 2438 18.8 N/A 10.98 m² 10.25 kg/m²

    Note: Fastened to joists with 76 mm by 3 mm framing nails on 203 mm centers along perimeter and

    305 mm centers in the field.

    Fiberglass Insulation

    Sound Control Mat1219 by 3023 6.4

    Hacker Industries, Inc. FIRM-

    FILL® SCM-25010.98 m² 0.49 kg/m²

    Note: Installed per manufacturer's specifications with seams overlapping and taped

    Gypsum Concrete3632 by 3023 25.4

    Hacker Industries, Inc. FIRM-

    FILL® Brand10.98 m² 48.82 kg/m²

    Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a

    closed cell foam perimeter isolation. The product name was specified by client.

    Luxury Resilient

    Tile

    457.2 by 457.2 3.0Metroflor® Commonwealth

    Commercial10.98 m² 5.22 kg/m²

    Note: Adhered to the subfloor topping with Mannington MT-711 Pressure Sensitive Adhesive.

    Adhesive was spread with a 1.6 mm U-notch trowl and allowed to cure to the manufacturer's

    specifications.

    Test Specimen Materials and Installation Details

    MaterialDimensions

    (mm)

    Thickness

    (mm)Manufacturer and Series Quantity

    Average

    Weight

    Average Relative Humidity 51% Average Relative Humidity 68%

    Test Calculations

    The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated

    in accordance with ASTM E 413 and ASTM E 989, respectively.

    Test Conditions

    Source Room Receive Room

    Average Temperature 24°C Average Temperature 17.3°C

    Page 2 of 5

    Test Procedure (Continued)

    The impact sound transmission test was conducted in accordance with the ASTM E 492 test

    method. Two background noise sound pressure level, two sound pressure level measurements

    with the tapping machine operating at each position specified by ASTM E 492, and five sound

    absorption measurements were conducted at each of five microphone positions.

    The air temperature and relative humidity conditions were monitored and recorded during all

    measurements.

    F4543.03-113-11-R2

  • Comments

    The total weight of the floor/ceiling assembly was 1096.3 kg. Intertek-ATI will store samples

    of the test specimen for four years. A photograph of the test specimen is included in the

    attachments. A drawing of the test specimen is included in the attachments.

    Gypsum Panel1219 by 3023 15.9 Type C 10.98 m² 11.9 kg/m²

    Note: Fastened to the furring channels on 305 mm centers with 41.3 mm Type S bugle head screws.

    Seams and perimeter sealed with Pecora AC-20 FTR Acoustical Sealant.

    Gypsum Panel1219 by 3023 15.9 Type C 10.98 m² 11.9 kg/m²

    Note: Fastened to the furring channels on 305 mm centers with 25.4 mm Type S bugle head screws.

    Furring/Hat Channel3658 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m

    Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center.

    Isolation Clips76.9 by 35.6 28.0 PAC International RSIC-1 Classic 24 clips 0.06 kg/clip

    Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.

    F4543.03-113-11-R2

    Page 3 of 5

    Test Specimen Materials and Installation Details (Continued)

    MaterialDimensions

    (mm)

    Thickness

    (mm)Manufacturer and Series Quantity

    Average

    Weight

  • Technician II - Acoustical Testing Project Manager - Acoustical Testing

    Attachments (7 Pages): This report is complete only when all attachments are included.

    * Stated by Client/Manufacturer

    N/A - Non Applicable

    Intertek-ATI will service this report for the entire test record retention period. Test records,

    such as detailed drawings, datasheets, representative samples of test specimens, or other

    pertinent project documentation, will be retained by Intertek-ATI for the entire test record

    retention period. The test record retention period ends four years after the test date.

    This report does not constitute certification of this product nor an opinion or endorsement by

    this laboratory. It is the exclusive property of the client so named herein and relates only to the

    specimen tested. This report is intended to help in the client’s quality assurance program, but it

    does not represent a continuous or exhaustive evaluation of the specimen tested or of other

    products or materials that were not evaluated. The statements and data provided herein do not

    constitute approval, disapproval, certification, or acceptance of performance or materials.

    This report may not be reproduced, except in full, without the written approval of

    Intertek-ATI.

    FOR INTERTEK-ATI:

    David M. Dacheux Jordan Strybos

    F4543.03-113-11-R2

    Page 4 of 5

  • This report produced from controlled document template ATI 00629(d), Revised 02/09/15.

    R2 04/29/16 Page 3 Clip spacing installation note corrected

    R0 03/03/16 N/A Original Report Issue

    R1 03/10/16 All pagesJob extension number changed per

    client's request

    F4543.03-113-11-R2

    Page 5 of 5

    Revision Log

    Revision Date Page(s) Description

  • Test Chambers

    VT Receive Room Volume 157.31 m³

    VT Source Room Volume 190 m³

    Page 1 of 7

    Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 11/15

    * The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

    Source Room Microphone Scantek 378B20 63741 04/15

    Source Room Environmental

    IndicatorComet T7510 63812 11/15

    Source Room Microphone PCB Piezotronics 378B20 63740 04/15

    Source Room Microphone PCB Piezotronics 378B20 63742 04/15

    Source Room Microphone PCB Piezotronics 378B20 63738 04/15

    Source Room Microphone PCB Piezotronics 378B20 63739 04/15

    Receive Room Environmental

    IndicatorComet T7510

    63810

    63811

    10/15

    10/15

    Receive Room Microphone PCB Piezotronics 378B20 63746 05/15

    Receive Room Microphone PCB Piezotronics 378B20 63747 05/15

    Receive Room Microphone PCB Piezotronics 378B20 63744 05/15

    Receive Room Microphone PCB Piezotronics 378B20 63745 05/15

    Microphone Calibrator Norsonic 1251 Y002919 07/15

    Receive Room Microphone Scantek 378B20 63748 05/15

    Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *

    F4543.03-113-11-R2

    Attachments

    Instrumentation

    Instrument Manufacturer Model ATI NumberDate of

    Calibration

  • STC Rating (Sound Transmission Class)

    Deficiencies (Sum of Deficiencies)

    Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

    2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

    3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

    ATI 00614 Revised 02/09/15 Page 2 of 7

    25

    63

    0.70 -

    10000 11.0 30.8 92 10 79 0.40 -

    8000 11.2 24.8 97 14 81

    0.50 -

    6300 9.8 18.3 98 18 78 0.70 -

    5000 8.7 14.3 104 28 75

    0.40 0

    4000 9.4 12.2 104 31 73 0.40 0

    3150 9.1 10.3 103 33 72

    0.30 0

    2500 10.0 9.6 102 35 69 0.30 0

    2000 13.6 8.6 104 37 69

    0.50 0

    1600 20.0 7.8 104 38 69 0.40 0

    1250 24.0 7.8 104 40 67

    0.50 1

    1000 24.6 7.7 104 44 64 0.40 2

    800 23.9 7.8 105 44 64

    0.30 1

    630 24.7 7.9 106 44 65 0.50 0

    500 26.6 8.1 104 45 62

    0.60 4

    400 22.1 8.5 104 48 59 0.50 3

    315 24.0 10.4 106 52 55

    1.20 3

    250 27.5 11.4 104 52 53 1.00 3

    200 25.5 10.4 105 57 50

    1.10 3

    160 30.2 8.2 108 65 45 2.00 5

    125 35.9 9.7 106 64 44

    4.40 -

    100 40.2 11.9 106 66 41 1.90 -

    80 55.6 17.2 108 67 41

    -

    63 48.3 25.8 101 61 38 3.20 -

    (dB) Limit Deficiencies

    50 51.0 24.5 101 64 35 4.80

    SPL SPL SPL Confidence of

    (Hz) (dB) (m²) (dB) (dB)

    Technician David M. Dacheux

    FreqBackground

    AbsorptionSource Receive Specimen

    TL

    95% Number

    Client Hacker Industries Inc.

    Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

    mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

    Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

    Gypsum Panel

    Specimen Area 10.98 m²

    F4543.03-113-11-R2

    AIRBORNE SOUND TRANSMISSION LOSS

    ASTM E 90

    Test Date 02/04/16

    Data File No. F4543.03

  • Specimen Area 10.98 m²

    Technician David M. Dacheux

    ATI 00614 Revised 02/09/15 Page 3 of 7

    Data File No. F4543.03

    Client Hacker Industries Inc.

    Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

    mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

    Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

    Gypsum Panel

    F4543.03-113-11-R2

    AIRBORNE SOUND TRANSMISSION LOSS

    ASTM E 90

    Test Date 02/04/16

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    63

    125

    250

    500

    100

    0

    200

    0

    400

    0

    800

    0

    Sou

    nd

    Tra

    nsm

    issi

    on

    Loss

    (d

    B)

    Frequency (Hz)

    Airborne Sound Transmission Loss

    Specimen TL

    Contour Curve

  • IIC Rating (Impact Insulation Class)

    Deficiencies (Sum of Deficiencies)

    56

    28

    Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

    ATI 00615 Revised 02/09/15 Page 4 of 7

    10000 7.3 31.4 13 0.3 -

    8000 7.7 24.9 14 0.5 -

    6300 8.0 18.3 17 0.9 -

    5000 7.0 14.5 24 0.7 -

    4000 10.7 12.1 27 0.8 -

    3150 6.3 10.3 31 0.3 0

    2500 7.6 9.6 38 0.4 0

    2000 12.8 8.6 43 0.4 1

    1600 19.0 7.8 46 0.2 1

    1250 21.0 7.8 52 0.3 4

    1000 20.4 7.7 56 0.3 5

    800 20.7 7.7 59 0.3 7

    630 20.7 8.0 56 0.5 3

    500 21.2 8.0 54 0.2 0

    400 18.9 8.6 53 0.9 0

    315 21.5 10.6 53 1.5 0

    250 26.9 11.3 53 0.8 0

    200 23.8 10.1 53 0.6 0

    160 28.2 8.8 59 1.1 3

    125 33.0 10.1 58 2.1 2

    100 39.4 12.3 58 2.0 2

    80 48.0 19.0 59 2.4 -

    63 44.8 29.8 63 3.3 -

    50 48.8 25.8 67 4.0 -

    (Hz) (dB) (m²) (dB) Limit Deficiencies

    Technician David M. Dacheux

    Freq Background SPL AbsorptionNormalized Impact

    SPL

    95% Number

    Confidence of

    Client Hacker Industries Inc.

    Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

    mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

    Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

    Gypsum Panel

    Specimen Area 10.98 m²

    F4543.03-113-11-R2

    IMPACT SOUND TRANSMISSION

    ASTM E 492

    Test Date 02/04/16

    Data File No. F4543.03

  • Technician David M. Dacheux

    ATI 00615 Revised 02/09/15 Page 5 of 7

    Client Hacker Industries Inc.

    Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand GypsumConcrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

    mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

    Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

    Gypsum Panel

    Specimen Area 10.98 m²

    F4543.03-113-11-R2

    IMPACT SOUND TRANSMISSION

    ASTM E 492

    Test Date 02/04/16

    Data File No. F4543.03

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    1100

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    63

    125

    250

    500

    100

    0

    200

    0

    400

    0

    800

    0

    Imp

    act

    In

    sula

    tion

    Cla

    ss (

    IIC

    )

    So

    un

    d P

    ress

    ure

    Lev

    el (

    dB

    )

    Frequency (Hz)

    Impact Sound Transmission

    Normalized Impact SPL

    Contour Curve

  • Page 6 of 7

    Close-Up of Test Specimen

    F4543.03-113-11-R2

    Photograph

  • Page 7 of 7

    5-Insulation

    6-Joist

    7-Ceiling Isolation

    8-Ceiling

    1-Floor Topping

    2-Subfloor Topping

    3-Subfloor Underlayment

    4-Subfloor

    Drawing

    F4543.03-113-11-R2

    2016-04-29T05:56:48-0400Sobell, Janine

    2016-04-29T06:23:39-0400David Dacheux

    2016-05-02T09:46:28-0400Jordan Strybos