fisherville senior public school & north west year … · 2019-11-19 · 1. 3. 2. etude...
TRANSCRIPT
All drawings and specifications are the property
the project to ETUDE ARCHITECTS INC.
any other purpose than that for which it was
It shall not be duplicated, used or circulated for
copyright with respect to this document.
issued, and must be returned on completion of
of ETUDE ARCHITECTS INC., who reserves his
NOTES
Contractor shall check and verify all dimensions
Do not scale this drawing. ETUDE ARCHITECTS INC.
ETUDE ARCHITECTS INC. prior to construction.
accepts no responsibility for measurements
scaled from the drawings.
and shall report discrepancies to
3.1.
2.
ETUDE ARCHITECTS INC.
TEL: (416)226-5779 FAX: (416)226-9844 E-mail: [email protected]
30 KERN ROAD, SUITE 106
T O R O N T O , O N T A R I O M 3 B 1 T 1 C A N A D A
DRAWINGS LIST
425 PATRICIA AVENUE, NORTH YORK, ONTARIO M2R 2N1
Toronto
BoardSchoolDistrict TORONTO DISTRICT SCHOOL BOARD
15 OAKBURN CRESCENT, TORONTO, ONT.
the project to ETUDE ARCHITECTS INC.
any other purpose than that for which it was
It shall not be duplicated, used or circulated for
copyright with respect to this document.
issued, and must be returned on completion of
of ETUDE ARCHITECTS INC., who reserves his
ISSUED FOR TENDER
OCTOBER 17, 2019
TENDER #TR-18-1115 (219114)
FISHERVILLE SENIOR PUBLIC SCHOOL &
NORTH WEST YEAR ROUND ALTERNATIVE CENTRE
WINDOW & DOOR REPLACEMENT
PHASE 1
WINDOWS AND DOORS REPLACEMENT - ARCHITECTURAL AS PER DRAWINGS.
SUMMARY OF WORK
ARCHITECTURAL
A100 SITE PLAN, LOCATION PLAN, NOTES & LEGENDS
A101 ELEVATION PHOTOS
A200 KEY PLANS
A201 FLOOR PLANS
A400 BUILDING ELEVATIONS
A600 DEMOLITION & PROPOSED DETAILS
A900 DOOR FINISH SCHEDULES, WINDOW / JAMB / DOOR / FRAME
TYPES AND DETAILS
DETAIL REFERENCE BUBBLE, DETAIL NO.
AND SHEET DRAWN ON.
BUILDING CROSS SECTION, SECTION NO. AND
SHEET DRAWN ON.
WINDOW TYPE REFERENCE
TDSB EXTERIOR DOOR NUMBER
DRAWING SYMBOL LEGEND
ABBREVIATED WORDS ON DRAWINGS ARE LISTED IN THIS SECTION.
REFER TO STRUCTURAL, SITE SERVICES, MECHANICAL & ELECTRICAL DRAWINGS FOR OTHER
ABBREVIATIONS USED.
M. MEN'S
MACH. MACHINE
MCP MODULAR CONTROL PANEL
MECH. MECHANICAL
MIN. MINIMUM
MISC. MISCELLANEOUS
MM MILLIMITERS
M.S. MIDDLE SCHOOL
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO. NUMBER
NTS NOT TO SCALE
O.C. ON CENTER
O.W.S.J. OPEN WEB STEEL JOIST
P. TILE PORCELAIN TILE
PA PUBLIC ADDRESS SYSTEM
PCT PRIVACY CURTAIN TRACK &
CURTAIN
PNL PANEL
PREF PREFERRED
PROP. PROPOSED
PT. PAINT
PTD PAPER TOWEL DISPENSER
REV. REVISED
SCB SLIDING CHALKBOARD
S.C SOLID CORE
SD SOAP DISPENSER
SECT. SECTION
SGL. SINGLE GLAZED
SND SANITARY NAPKIN & TAMPON
DISPOSAL
SPEC. SPECIFICATIONS
SNDISP SANITARY NAPKIN & TAMPON
DISPENSER
SR+C SHOWER ROD AND CURTAIN
S.T STEEL
STRUC. STRUCTURAL
S.U. DOUBLE GLAZED SEALED UNITS
SWB SLIDING WHITEBOARD
STOR. STORAGE
TB TACKBOARD
TC TEACHERS CLOSET
TD TOILET TISSUE DISPENSER
TDD PAPER TOWEL DISPENSER &
DISPOSAL
TG TEMPERED GLASS
TLB TOWEL BAR
TM TILTED MIRROR
T.V. TELEVISION
TYP TYPICAL
UV UNIT VENTILATOR
V VANITY
VCT VINYL COMPOSITE TILE
VEST. VESTIBULE
W. WOMEN'S
WB WHITE BOARD
AFF ABOVE FINISHED FLOOR
ALUM. ALUMINUM
ARCH. ARCHITECTURAL
BD. BOARD
BF BARRIER FREE
BLDG. BUILDING
BLK. BLOCK
CB CHALKBOARD
CH COAT HOOKS
CJ CONTROL JOINT
CONC. CONCRETE
CR COAT RACK
CR+S COAT RACK AND SHELF
CS CONVENIENCE SHELF
CT CERAMIC TILE
C/W COMPLETE WITH
D DRYER
DBL DOUBLE
DC DOOR CONTACT
DF DRINKING FOUNTAIN
DWG. DRAWING
EQ. EQUAL
EQUIP. EQUIPMENT
ELECT. ELECTRICAL
ELEV. ELEVATOR
EXP. EXPOSED
EXIST. EXISTING
EXT. EXTERIOR
FB FIRE BLANKET
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FL FLOOR
FSS FOLDING SHOWER SEAT
GB GRAB BAR
GBF FOLDING GRAB BAR
GBL GRAB BAR "L" SHAPE
GBS SHOWER GRAB BAR
GL GLAZING
GYP. GYPSUM
GW GEORGIAN WIRED GLASS
H/C HANDICAP
HD HAND DRYER
H.M. HOLLOW METAL
HR HOUR
HVT HOMOGENEOUS VINYL TILE
INSUL. INSULATION
INT. INTERIOR
JAN JANITOR
J.S. JUNIOR SCHOOL
LAP LAY-IN ACOUSTIC PANEL
LAV. LAVATORY
LH LEFT HAND
LHR LEFT HAND REVERSE
LWB LIGHT WEIGHT CONCRETE
BLOCK
M MIRROR
1. ALL DEMOLISHED MATERIALS & DEBRIS ARE TO BE DISPOSED BY GENERAL
CONTRACTOR UNLESS OTHERWISE NOTED.
2. OWNER WILL SALVAGE ANY WANTED MATERIAL, EQUIPMENT, ETC. PRIOR TO
CONSTRUCTION START. GENERAL CONTRACTOR TO REPAIR, PATCH & MAKE
GOOD IN A WORKMANLIKE AND WHOLE CONDITION TO THE LIKE OF PRIOR OWNER
SALVAGE.
3. REMOUNT ALL EXISTING TO REMAIN ELECTRICAL WIRING OR ELECTRICAL CONDUITS TO
NEW FINISHED WALL FACE AS INDICATED ON CONTRACT DOCUMENTS, ETC.
4. REPAIR, PATCH & MAKE GOOD ALL EXISTING STRUCTURE AND BUILDING FINISHES THAT
IS DAMAGED AS A RESULT OF CONSTRUCTION.
5. ALL EXISTING MATERIALS AND FINISHES DAMAGED DURING ALTERATIONS & RENEWAL
WORK TO BE RETURNED TO A CONDITION EQUIVALENT TO BEFORE DISTURBANCE. ALL
DAMAGED MATERIALS AND FINISHES TO BE REPLACED WITH MATCHING MATERIAL AND
FINISHES INCLUDING, BUT NOT LIMITED TO, CONSTRUCTION, SIZE, COLOUR AND FINISH.
6. ALL REQUIRED CUTTING & FITTING (INCLUDING ALL STRUCTURAL, ELECTRICAL AND
MECHANICAL) TO BE CONNECTED TO EXISTING WORK, WITH NEW WORK TO BE
PERFORMED AS PART OF THIS CONTRACT AND TO FINISH THE ENTIRE WORK IN A
WORKMANLIKE AND WHOLE CONDITION.
7. ALL WORK TO MAKE GOOD EXISTING; SHALL MATCH EXISTING IN MATERIAL,
CONSTRUCTION AND FINISH INCLUDING PAINT COLOUR BEHIND REMOVED
FITMENTS / MILLWORK UNLESS OTHERWISE SPECIFIED.
8. GENERAL CONTRACTOR TO PERFORM ALL NECESSARY DEMOLITION, ALTERATIONS
AND MAKE GOOD ALL FINISHES AS REQUIRED TO MAKE THIS WORK AS A COMPLETE JOB
(INCLUDING BUT NOT LIMITED TO WORK SHOWN IN DRAWINGS AND SPECIFICATIONS).
9. ALL OPENINGS IN FIRE RATED WALLS, CEILINGS AND FLOORS TO BE RETURNED TO
EQUIVALENT CONDITION BEFORE THE OPENING AND ALL ELECTRICAL AND MECHANICAL
PENETRATIONS TO BE SEALED WITH FIRE STOP MATERIAL AS REQUIRED BY THE O.B.C.
10. ALL EXPOSED ELECTRICAL CONDUITS AND MECHANICAL DUCTS AND PIPES TO BE
PAINT FINISH. COLOURS TO BE SELECTED BY CONSULTANT.
11. CONTRACTOR TO CONTACT ALL AUTHORITIES RESPONSIBLE/ INVOLVED TO
DISCONNECT EXISTING SERVICES (EG. HYDRO, BELL, GAS ETC.)
12. REFER TO STRUCTURAL DRAWING AND SPECIFICATIONS FOR ANY TEMPORARY
SUPPORT PROCEDURES PRIOR TO REMOVAL OF ANY LOAD-BEARING SUPPORTS.
13. INTENT OF DEMOLITION PLANS IS TO MEET ALL THE REQUIREMENTS NEEDED TO
FACILITATE NEW WORK INCLUDING ALL ELEMENTS REQUIRED TO BE DEMOLISHED
THAT ARE NOT INDICATED ON THE FLOOR PLANS.
14. CITY HAS WASTE REMOVAL POLICIES AS PER O-REG`S FOR RECYCLING
MATERIALS IN ACCORDANCE WITH LATEST LEGISLATION.
15. ENSURE ALL DUCT AND DRAIN OPENINGS ARE COVERED AND PROTECTED
DURING DEMOLITION.
16. CONTRACTOR TO REVIEW ASBESTOS MANAGEMENT PROGRAM MANUAL AVAILABLE
FROM HEAD CARETAKER. FOLLOW TDSB PROCEDURE FOR ASBETOS CONTAINING
MATERIAL AS INDICATED IN TENDER DOCUMENTS.
17. ALL WORK TO BE CARRIED OUT IN ACCORDANCE WITH THE LATEST EDITION OF THE
LOCAL, PROVINCIAL AND FEDERAL CONSTRUCTION AND BUILDING CODES, THE NATIONAL
FIRE CODE, THE OCCUPATIONAL HEALTH AND SAFETY ACT, AND ANY OTHER
AUTHORITIES HAVING JURISDICTION.
18. FLASHING REPLACEMENT AND ROOFING WORK REQUIRED DUE TO FLASHING
REPLACEMENT TO BE PERFORMED BY TDSB APPROVED ROOFING CONTRACTOR. ALL
MODIFICATIONS TO EXISTING ROOFING REQUIRED DUE TO FLASHING REPLACEMENT TO
MATCH EXISTING ROOFING SYSTEM. VERIFY WITH TDSB PROJECT SUPERVISOR IF THERE
IS A WARRANTY ON THE EXISTING ROOFING AND UTILIZE THE SAME CONTRACTOR FOR
MODIFICATIONS TO AVOID VOIDING WARRANTY. ALL ROOFING DETAILS, PROCEDURE
AND MODIFICATIONS SHOULD BE APPROVED BY TDSB BUILIDNG ENVELOPE SPECIALIST
ZORAN VODRUS AT 416-948-3053 PRIOR TO COMMENCEMENT.
3
A500
6
A601
1. POURED CONCRETE
OR PRECAST CONCRETE
2. CONCRETE BLOCK
4. (SAND) OR GYPSUM BOARD
5. GRANULAR "A" FILL
7. RIGID INSULATION
8. UNDISTURBED SOIL
9. EXISTING CONST.
11. WOOD BLOCK
10. STEEL
6. GRANULAR "B" FILL
STANDARD ABBREVIATIONS MATERIAL LEGEND DEMOLITION NOTES
GENERAL NOTES
1. GENERAL CONTRACTOR (G.C.) TO VERIFY ALL DIMENSIONS AT SITE. VERIFY ALL SITE
CONDITIONS & REPORT ANY DISCREPANCIES TO THE CONSULTANT. DO NOT SCALE
THESE DRAWINGS.
2. ALL WORK TO BE CARRIED OUT IN ACCORDANCE WITH THE LATEST EDITION OF THE
LOCAL, PROVINCIAL AND FEDERAL CONSTRUCTION AND BUILDING CODES, THE NATIONAL
FIRE CODE, THE OCCUPATIONAL HEALTH AND SAFETY ACT, AND ANY OTHER
AUTHORITIES HAVING JURISDICTION.
3. ALL ROOFING & FLASHING WORK TO BE UNDER CASH ALLOWANCE. REFER TO TENDER
PRICE SCHEDULE AND COORDINATE THIS WORK WITH TDSB ROOFING DEPARTMENT.
NO.
PHOTO REFERENCE NUMBERNO.
ASBETOS NOTES
1. CONTRACTOR TO REVIEW ASBESTOS MANAGEMENT PROGRAM MANUAL AVAILABLE
FROM THE HEAD CARETAKER.
2. FOLLOW TDSB PROCEDURE FOR ASBESTOS CONTAINING MATERIAL, AS INDICATED
IN TENDER DOCUMENTS.
3. PROVIDE HAZMAT REPORTS TO BE PROVIDED AS A CASH ALLOWANCE.
ELEVATION NUMBER
DOOR NUMBER
· CONTRACTOR TO CONFIRM ALL EXISTING OPENINGS DIMENSIONS ON SITE PRIOR TO NEW WINDOWS, CURTAIN WALL, DOORS AND SCREENS FABRICATION.
· CONTRACTOR TO REMOVE COMPONENTS INTERFERING WITH WINDOWS, DOORS AND SCREENS REPLACEMENT AND REINSTALL.
MAKE GOOD ALL DISTURBED AREAS, TO MATCH EXISTING.
· CONTRACTOR TO REMOVE & REINSTALL ALL EXISTING BLINDS/DRAPES IN ALL RELEVANT ROOMS TO FACILITATE WINDOWS REPLACEMENT UNLESS NOTED
OTHERWISE.
· CONTRACTOR TO SUBMIT SHOP DRAWINGS FOR WINDOWS, DOORS AND SCREENS PRIOR TO FABRICATION. SHOP DRAWINGS TO INCLUDE WOOD BLOCKING
FASTENING METHOD AND WINDOWS, CURTAIN WALL, DOORS AND SCREENS FASTENING METHOD. WINDOWS, CURTAIN WALL, DOORS AND SCREENS
FASTENERS TO BE STAINLESS STEEL. REFER TO SPECIFICATIONS. WINDOW, CURTAIN WALL, DOORS AND SCREEN FASTENERS TO BE LOCATED AT JAMBS.
FINAL FASTENERS LOCATIONS AND NUMBER TO BE REVIEWED BY STRUCTURAL ENGINEER PREPARING THE SHOP DRAWINGS.
· ALUMINUM WINDOWS FINISH TO MATCH EXISTING WINDOW COLOUR. (TYPICAL).
· APPLY CONTINUOUS TOE BEAD AT PERIMETER OF GLAZING (TYPICAL).
· PROVIDE INSULATED PANELS WHERE REQUIRED AT PERIMETER OF MECHANICAL PENETRATIONS (ie. A/C, MECHANICAL VENT, ETC.). MODIFY MULLIONS TO
RECEIVE INSULATED PANELS AS REQUIRED.
· GENERAL CONTRACTOR TO PROTECT WINDOWS AT COMPLETION OF INSTALLATION, UNTIL THE PROJECT IS HANDED OVER TO THE OWNER.
· ANY ELECTRICAL ELEMENT WITHIN SPECIFIED SCOPE OF WORK SHALL BE ADDRESSED BY ELECTRICAL CONTRACTOR PRIOR TO PROCEEDING WITH
REMEDIAL OR REPAIR WORK TO EXTERIOR FACADE. REINSTATE ELECTRICAL ELEMENTS TO THEIR EXISTING CONDITIONS UPON COMPLETION OF REMEDIAL
& REPAIR WORK.
· ALL EXIT DOORS ARE TO REMAIN OPERATIONAL FOR DURATION OF REFINISHING/REMEDIAL WORK. EXITS TO REMAIN ACCESSIBLE, SAFE, AND SECURE FOR
DURATION OF WORK. G.C. TO PROVIDE HOARDING AT LOCATIONS, WHERE REQUIRED, COMPLETE WITH OVERHEAD PROTECTION AND LIGHTING.
SUBMIT ENGINEERED SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION AND INSTALLATION OF HOARDING. HOARDING TO BE SECURELY INSTALLED
PRIOR TO COMMENCING ANY WORK. SEE SPEC.
· ALL MATERIALS AND FINISHES AFFECTED BY WORK TO BE MADE GOOD, TO MATCH EXISTING (TYP.)
· BLUESKIN TO BE TERMINATED ONTO THE SOLID MASONRY EXTERIOR WALL. DO NOT TERMINATE BLUESKIN ONTO THE INTERIOR FINISHES.
· MAKE GOOD ALL MATERIAL AND FINISHES AFFECTED BY WORK INCLUDING PLASTER AND/OR DRYWALL.
· INSTALL INSECT SCREENS IN ALL STAFF ROOMS AND DINING / LUNCH ROOM(S) AND ANY ROOM WHERE FOOD IS PREPARED OR SERVED. (TYP.)
· ALL VENT OPENINGS TO COMPLY WITH O.B.C.
SEE SPECIFICATION FOR MORE INFORMATION.
TYPE 1:
OPERABLE SECTIONS OF WINDOW UNIT TOP-HUNG OPEN-OUT VENTS. SUPPLY & INSTALL CONTINUOUSEXTRUDED ALUMINUM HINGES & ROTO OPERATORS WITH DUAL FRICTION ARMS.
TYPE 2:
OPERABLE SECTIONS OF WINDOW UNIT TOP-HUNG OPEN-OUT VENTS. SUPPLY & INSTALL TELEFLEX WINDOWOPERATORS FOR ALL WINDOWS WHERE THE OPERABLE PORTION OF THE WINDOW IS ABOVE 1600mm.
· REFER TO LIST OF UNIT PRICES REQUIRED FOR VARIOUS ITEMS.
· GENERAL CONTRACTOR TO PROVIDE AN 8'-0" HIGH PLYWOOD EXTERIOR HOARDING FOR THE AREA OF WORK AND SCAFFOLDING.
HOARDING TO BE LOCKABLE AND KEPT SAFE AND SECURED AT ALL TIMES.
· GENERAL CONTRACTOR TO PROVIDE INTERIOR HOARDING INSIDE EACH ROOM WHERE WINDOWS ARE TO BE REPLACED. HOARDING TO BE 6'-0" AWAY
FROM THE WINDOWS AND EXTEND FROM FLOOR TO CEILING IN ORDER TO SEPARATE WINDOW WORK AREA FROM THE REST OF THE ROOM.
HOARDING TO BE PLYWOOD OR GYPSUM BOARD. PROTECT ALL INTERIOR FINISHES AND FITMENTS FROM DAMAGE AND DUST. ENSURE DUST CONTROL
MEASURES ARE IN PLACE AT ALL TIMES. MAKE GOOD ALL FINISHES AT COMPLETION AFTER REMOVING HOARDING(S) TO MATCH EXISTING.
· INTERIOR HOARDING TO INCLUDE A PLEXIGLASS PORTION TO PROVIDE NATURAL LIGHT IN EACH ROOM. PLEXIGLASS TO BE MINIMUM 1200MM x 1200MM.
PROVIDE A NUMBER OF PLEXIGLASS INSERTS EQUAL TO THE NUMBER OF WINDOWS IN EACH ROOM. PROVIDE AIR CIRCULATION GRILLS C/W FILTERS
IN HOARDING.
GENERAL NOTE
SCHEDULE OF TENDER PRICES
HOARDING NOTES
HARDWARE TYPES
ALW-1
PLAYING
FIELD
FISHERVILLE SR PS /
NORTH WEST YEAR ROUND ALT CTR
LISSOM
PARK
PATRICIA AVE.
LA
CO
NIA
D
R.
HO
ME
WO
OD
A
VE
.
BR
ILL C
RE
S.
959.71'
N74°07'E
99
.5
5'
N1
5°5
2'W
16.08'
99
.5
5'
N1
5°5
2'W
65.94'
N74°07'E
19
9.2
5'
N1
5°5
2'W
933.8'
N74°07'E
46
0.8
6'
N1
5°5
3'W
PA
RK
IN
G
LO
T
5
6
4A
4
3B 3A
3
2H
2G
2E
2C
2D
2A
2B
2
17
ASPHALT
PLAYGROUND
2F
8 S
PA
CE
S
8 S
PA
CE
S
GARBAGE
PLAYING
FIELD
GREEN
SPACES
SITE PLAN
LOCATION MAP
1 09/26/2019 ISSUED FOR PRE-TENDER CLIENT REVIEW
SITE PLAN, LOCATION PLAN, NOTES & LEGENDS
Toronto
SchoolBoard
District
t. 416-395-4588 / f. 416-395-973415 Oakburn Cres. Toronto, Ontario M2N 2T5
Design & Construction DivisionFacility Services Department
ETUDE ARCHITECTS INC.
No. DATE DESCRIPTION
LOCATION
PROJECT
DRAWING TITLE
TDSB PROJECT No: REVISION No:
DRAWING No:DATE:
SCALE:
DRAWING BY:
APPROVED BY:
FISHERVILLE SR. PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.WINDOW & DOOR REPLACEMENT-PHASE 1
JY
TR-18-1115 (219114)
AS NOTED
A100AM
FISHERVILLE SENIOR PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.425 PATRICIA AVE., NORTH YORK,ONTARIO M2R 2N1
OCTOBER 17, 2019
2 10/17/2019 ISSUED FOR TENDER
3.1 NORTH WALL - TYPICAL WINDOW REPLACEMENTS.
NOTE: REFER TO FLOOR PLANS AND ELEVATIONS FOR DETAILED SCOPE OF WORK.
3.19 EAST WALL- DOOR #6 TO BE MODIFIED.
PHASE 1
3.27 TYPICAL EXISTING HORIZONTAL BLINDS.
3.3 WEST WALL TYPICAL - WINDOW REPLACEMENTS. 3.4 WEST WALL - TYPICAL OPERABLE
WINDOW TO BE REPLACED.
3.2 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.5 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.6 WEST WALL - TYPICAL WINDOW REPLACEMENT. 3.7 WEST WALL - TYPICAL WINDOW
REPLACEMENT.
3.8 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.9 WEST WALL - TYPICAL WINDOW
REPLACEMENT.
3.10 WEST WALL - TYPICAL WINDOW
REPLACEMENT.
3.11 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.14 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.15 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.16 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.18 WEST WALL - TYPICAL WINDOW
REPLACEMENTS.
3.17 WEST WALL - TYPICAL WINDOW REPLACEMENT.
3.21 EAST WALL - TYPICAL WINDOW REPLACEMENTS.
3.13 WEST WALL - TYPICAL WINDOW REPLACEMENT.3.12 WEST WALL - TYPICAL WINDOW
REPLACEMENT.
3.22 EAST WALL - TYPICAL WINDOW
REPLACEMENT.
3.23 EAST WALL - TYPICAL WINDOW REPLACEMENTS. 3.24 EAST WALL - TYPICAL WINDOW
REPLACEMENT.
3.25 EAST WALL - TYPICAL WINDOW REPLACEMENTS.
3.26 EAST WALL - TYPICAL DOOR
REPLACEMENT.
3.28 TYPICAL EXISTING ROLLER SHADES.
3.20 EAST WALL - TYPICAL WINDOW REPLACEMENT.
1 09/26/2019 ISSUED FOR PRE-TENDER CLIENT REVIEW
ELEVATION PHOTOS
KEY PLAN
FISHERVILLE SR PS /
NORTH WEST YEAR ROUND ALT CTR
1
PHASE 1
Toronto
SchoolBoard
District
t. 416-395-4588 / f. 416-395-973415 Oakburn Cres. Toronto, Ontario M2N 2T5
Design & Construction DivisionFacility Services Department
ETUDE ARCHITECTS INC.
No. DATE DESCRIPTION
LOCATION
PROJECT
DRAWING TITLE
TDSB PROJECT No: REVISION No:
DRAWING No:DATE:
SCALE:
DRAWING BY:
APPROVED BY:
FISHERVILLE SR. PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.WINDOW & DOOR REPLACEMENT-PHASE 1
JY
TR-18-1115 (219114)
AS NOTED
A101AM
FISHERVILLE SENIOR PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.425 PATRICIA AVE., NORTH YORK,ONTARIO M2R 2N1
OCTOBER 17, 2019
2 10/17/2019 ISSUED FOR TENDER
LEGEND
REFERENCE NUMBER TO PHOTOS
EXISTING TO REMAIN
AREA OF WIDOWS & DOORS
REPLACEMENTS - PHASE 1
UP
UP
DN
DN
DN
UP
DN
UP
UP
UP
UPUP
UP
DNDN
STAIRS 1
STAIRS 3
STAIRS 4
STAIRS 5
ST
AIR
S 6
STAIRS 7
UP
OPEN COURT
136
CORRIDOR
121
CAFETORIUM
129
STAFF LOUNGE & DINING
121A
STAGE
124
G. W/R
122
B. W/R
120A
LOCKER
120
CARETAKER
120E
CRTKR OFF.
120D
ELECT.
138
TRANS.
139
STOR.
120C
BOILER ROOM
121E
ST.
121C
KITCHEN
121B
120B
INCINERATOR
121D
108
DESIGN & TECH.
110
COMPUTER LAB
108A
STOR.
108C
DUST COL.
118
CORR.
G'S WR
117
G'S CHANGE
116E
116D
INST.
DRY
SHOWERSHOWER
DRY
115
BOY'S CHANGE RM.
115A
ST.
116B
INST.
116C
EQUIPMENT ST.
115
GYMNASIUM
119
CORRIDOR
113
INSTRUMENT. MUSIC
114B
PRAC.
116
STOR.
111
MUSIC
112
STOR.
114A
PRAC.
114
106
CLASSROOM
109
CLASSROOM
123
CTR.
106B
SEMINAR
109A
OFFICE
119
GUIDANCE WORK RM.
127
W.S. W/R
125
M.S. W/R
126
W. W/R
MEN'S W/R
107
CLASSROOM
104
CLASSROOM
102
ART
102A
STOR.103
FAMILY STUDIES
128
130
CONF. ROOM
129
M. WR
129A
W. WR
131
PRINC.
132
GENERAL OFF.
WAITING
132C
KITCH. COPY RM
133C
STO.
133
GUID.
132A
CONF. ROOM
130
CONF.
134
135
HLTH. RM
135B
135A
131A
131B
130
CONF.
130
CONF.
SPECIAL ED.
CLASSROOM
350
ESL
OFFICE
101
UP
STAIRS 2
3A3B
4
4A
5
6
7
1
2
2A
2B
2C
2D
2E
2G
2H
3
2H
3.1
3.17
3.3
3.18
3.5
3.6
3.7
3.2
3.4
3.8
3.9
3.10
3.11
3.13
3.12
3.15
3.14
3.19
3.20
3.21
3.22
3.23
3.24
3.25
3.26
3.16
UP
DN
UP
UP DN
UP
UP
DN
STAIRS 2
STAIRS 3
STAIRS 7
STAIRS 5
STAIRS 7
UP
OPEN TO
STR. BELOW
201
CLASSROOM
203
CLASSROOM
205
CLASSROOM
207
STAFF WORK ROOM
209
SEMINAR ROOM
211
COMPUTER LAB
212
M. WR
216
W. WR
215
W. WR
213
M. WR
208A
OFFICE
208B
LIB. OFF.
208
LIBRARY
208C
SEMINAR
206
CLASSROOM
204
CLASSROOM
217
STAFF WORK ROOM
219
CORR.
202
CLASSROOM
218
STOR.
MECHANICAL FAN ROOM NO.1
221
MECHANICAL FAN ROOM NO.2
PROJ.
ROOF
ROOF
ROOF
208D
SEMINAR
OPEN TO
STR. BELOW
DN
UPPER PART OF
CAFETORIUM
UPPER PART OF
DESIGN & TECH.
UPPER PART OF
GYMNASIUM
UP
STAIRS 6
CORRIDOR
219
STAIRS 1
3.1
3.18
3.5
3.2
3.8
3.10
3.11
3.14
3.21
3.22
3.23
3.25
3.16
STAIRS 1
STAIRS 4
STAIRS 7
DN
DN
DN
ROOF
ROOF
313
CORR.
301
CLASSROOM
303
CLASSROOM
305
CLASSROOM
307
CLASSROOM
309
COMP. CLASSROOM
308
CLASSROOM
310
CLASSROOM
306
CLASSROOM
4
FAN ROOM
315
MECH. ROOM
300
WORK ROOM
ACADEMIC STORAGE
304
SCIENCE CLASS
317
PREP. ROOM
302
SCIENCE CLASS
318
M. WR
322
W. WR
321
W. WR
STAFF WRKRM.
319
M. WR
3.1
3.18
3.5
3.2
3.8
3.10
3.11
3.14
3.21
3.22
3.23
3.25
3.16
1 09/26/2019 ISSUED FOR PRE-TENDER CLIENT REVIEW
FIRST FLOOR KEY PLAN SECOND FLOOR KEY PLAN
THIRD FLOOR KEY PLAN
KEY PLANS
Toronto
SchoolBoard
District
t. 416-395-4588 / f. 416-395-973415 Oakburn Cres. Toronto, Ontario M2N 2T5
Design & Construction DivisionFacility Services Department
ETUDE ARCHITECTS INC.
TRUE
NORTH
DRAWING
NORTH
No. DATE DESCRIPTION
NORTH
LOCATION
PROJECT
DRAWING TITLE
TDSB PROJECT No: REVISION No:
DRAWING No:DATE:
SCALE:
DRAWING BY:
APPROVED BY:
FISHERVILLE SR. PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.WINDOW & DOOR REPLACEMENT-PHASE 1
JY
TR-18-1115 (219114)
AS NOTED
A200AM
FISHERVILLE SENIOR PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.425 PATRICIA AVE., NORTH YORK,ONTARIO M2R 2N1
OCTOBER 17, 2019
2 10/17/2019 ISSUED FOR TENDER
FLOOR PLAN NOTES:
EXISTING WINDOWS AND FRAMES TO BE REPLACED WITH NEW.
REFER TO WINDOW TYPES AND SCHEDULES. GC TO REMOVE AND DISCARD OF EXIST. SECURITY
SCREEN ASSEMBLIES AT FIRST FLOOR LEVEL. PATCH, REPAIR AND MAKE GOOD
AREA AFFECTED BY WORK/ TO MATCH EXISTING.
CONTRACTOR TO CAREFULLY REMOVE EXISTING ROLLER SHADES IN GOOD CONDITION, TO BE
REINSTALLED. CASSETTES AND CHAINS FOR ROLLER SHADES SHOULD NOT TO BE ATTACHED TO NEW
WINDOW FRAMES. REPAIR AND MAKE GOOD AREA AFFECTED BY WORK, TO MATCH EXISTING.
REFER TO SPEC.
CONTRACTOR TO REMOVE AND DISCARD OF EXIST. HORIZONTAL BLINDS AND/ OR ROLLER SHADES
IN POOR CONDITION (SEE FLOOR PLANS). REPLACE WITH NEW TDSB STANDARD ROLLER SHADES.
CASSETTES AND CHAINS FOR ROLLER SHADES SHOULD NOT TO BE ATTACHED TO NEW WINDOW FRAMES.
PATCH, REPAIR AND MAKE GOOD AREA AFFECTED BY WORK TO MATCH EXISTING.
EXISTING DOOR AND FRAME TO BE REPLACED WITH NEW. REFER TO DOOR SCHEDULES.
GC TO REMOVE AND DISCARD OF EXIST. REPLACE WITH NEW DOOR, WITH SOLID PANEL AT BOTTOM.
REFER TO DOOR TYPE SCHEDULE. PATCH, REPAIR AND MAKE GOOD AREA AFFECTED BY WORK,
MATCH EXISTING.
GC TO REMOVE AND DISCARD OF EXISTING ART ROOM DOOR, FRAME, AND TRANSOM TO
BE REPLACED WITH NEW SINGLE ACCESSIBLE DOOR AND SIDELIGHT. REFER TO DOOR SCHEDULE.
GC TO PATCH, REPAIR AND MAKE GOOD AREA AFFECTED BY WORK, TO MATCH EXISTING.
GC TO REMOVE AND DISCARD OF EXISTING PLEXIGLASS AT EXISTING DOORS. INSTALL
NEW SEALED INSULATED GLAZING UNITS WITH TEMPERED GLASS. EXISTING DOORS AND FRAME
TO BE PAINTED. REFER TO DOOR SCHEDULES. GC TO REPAIR AND MAKE GOOD AREA AFFECTED
BY WORK, TO MATCH EXISTING.
GC TO CAREFULLY REMOVE AND RE-INSTALL EXISTING A/C UNITS AND OR MECHANICAL FITMENTS
TO BE RE-INSTALLED UPON COMPLETION OF WORK, TO MATCH EXISTING. PROVIDE INSULATED PANELS
WHERE REQUIRED AT PERIMETER OF MECHANICAL PENETRATIONS. (IE A/C, MECHANICAL VENT, ETC.).
INSECT SCREENS TO BE INSTALLED AT ALL STAFF ROOMS, LUNCH ROOMS, FOOD PREP. AREAS.
TELEFLEX OPERATORS TO BE PROVIDED FOR ALL WINDOWS WITH A SILL HIGHER THAN 1600mm.
1
2
3
4
5
6
7
8
9
LEGEND
REFERENCE NUMBER TO
ELEVATION(S)
REFERENCE NUMBER TO
SECTION(S)
EXISTING TO REMAIN
UP
SPECIAL ED.
CLASSROOM
101
SPECIAL ED.
ESL OFFICE
101
ART
102
STORAGE
102A
CLASSROOM
107
FAMILY
STUDIES
103
MEN'S
WASHROOM
MEN'S
WASHROOM
125
WOMEN'S
WASHROOM
127
WOMEN'S
WASHROOM
GUIDANCE
WORK ROOM
119
OFFICE
109A
CLASSROOM
109
CLASSROOM
106
SEMINAR
ROOM
106B
UP
DN
STAIRS 4
DN
STAIRS 3
STAIRS 2
DN
STAIRS 1
DN
UP
DNDN
UP
STAIRS 1
UP
5
6
7
ALW-1
1
TYP.
4
5
2
ALW-2
ALW-5
ALW-4
ALW-6
ALW-4
ALW-4
ALW-7
ALW-2
ALW-3
ALW-1
ALW-10
ALW-9
ALW-9
ALW-9
ALW-8
ALW-8
1
A400
X
A400
2
A400
3
A400
ALW-11
N.I.C.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
7
7
7
7
7
7
7
8
8
8
8
9
9
9
6
9
CORRIDOR
219
CLASSROOM
201
UP
DN
STAIRS 7
UP
STAIRS 3
STAIRS 2
STAIRS 1
DNUP
OPEN TO BELOW
DN
UP
STAIRS 7
SEMINAR
ROOM
209
CLASSROOM
203
CLASSROOM
205
CLASSROOM
207
COMPUTER
LAB
211
MEN'S
WASHROOM
212
WOMEN'S
WASHROOM
216
OFFICE
208A
LIBRARY
OFFICE
208B
LIBRARY
208
SEMINAR
ROOM
208C
SEMINAR
ROOM
208D
WOMEN'S
WASHROOM
215
MEN'S
WASHROOM
213
MEN'S
WASHROOM
212
CLASSROOM
206
CLASSROOM
204
STAFF
WORK ROOM
217
CLASSROOM
202
STORAGE
218
ALW-1
ALW-12
ALW-1
ALW-1
ALW-4
ALW-1
ALW-1
ALW-4
ALW-1
ALW-1
ALW-1
ALW-1
ALW-8
ALW-4
ALW-4
ALW-1
ALW-1
ALW-1
ALW-8
1
A400
2
A400
3
A400
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
3
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
2
7
9
STAIRS 4
DN
STAIRS 1
DN
STAIRS 7
DN
CLASSROOM
301
CLASSROOM
303
CLASSROOM
305
CLASSROOM
307
COMPUTER
CLASSROOM
309
STAFF
WORK ROOM
MEN'S
WASHROOM
318
WOMEN'S
WASHROOM
322
MEN'S
WASHROOM
319
WOMEN'S
WASHROOM
321
CLASSROOM
308
CLASSROOM
310
CLASSROOM
306
FAN
ROOM
4
MECHANICAL
ROOM
315
ACADEMIC
ROOM
WORK
ROOM
300
SCIENCE
CLASS
304
PREP.
ROOM
317
SCIENCE
CLASS
302
ALW-12
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1
ALW-4
ALW-4
ALW-4
1
A400
2
A400
3
A400
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
1
TYP.
3
3
3
3
2
2
2
2
2
2
2
2
2
2
2
2
FIRST FLOOR PLAN - PHASES 1-3
1 09/26/2019 ISSUED FOR PRE-TENDER CLIENT REVIEW
FLOOR PLANS
Toronto
SchoolBoard
District
t. 416-395-4588 / f. 416-395-973415 Oakburn Cres. Toronto, Ontario M2N 2T5
Design & Construction DivisionFacility Services Department
ETUDE ARCHITECTS INC.
TRUE
NORTH
DRAWING
NORTH
No. DATE DESCRIPTION
NORTH
LOCATION
PROJECT
DRAWING TITLE
TDSB PROJECT No: REVISION No:
DRAWING No:DATE:
SCALE:
DRAWING BY:
APPROVED BY:
FISHERVILLE SR. PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.WINDOW & DOOR REPLACEMENT-PHASE 1
JY
TR-18-1115 (219114)
AS NOTED
A201AM
FISHERVILLE SENIOR PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.425 PATRICIA AVE., NORTH YORK,ONTARIO M2R 2N1
OCTOBER 17, 2019
SECOND FLOOR PLAN - PHASE 1 THIRD FLOOR PLAN - PHASE 1
KEY PLAN
FISHERVILLE SR PS /
NORTH WEST YEAR ROUND ALT CTR
1
PHASE 1
2 10/17/2019 ISSUED FOR TENDER
ALW-4ALW-1 ALW-1
ALW-1 ALW-1
ALW-1
ALW-1
ALW-1 ALW-1 ALW-1
ALW-1ALW-1
ALW-8 ALW-8
ALW-8
ALW-9ALW-9 ALW-9
ALW-8
ALW-4 ALW-4
ALW-4
ALW-10
188.96
FIN. EXISTING FIRST FLOOR
188.42
FIN. EXISTING SECOND FLOOR192.69
FIN. EXISTING THIRDFLOOR196.41
TOP OF EXISTING STRUCTURAL STEEL
200.11
NIC
6
FIN. EXISTING FIRST FLOOR
188.96
4
6
5
ALW-11
ALW-12
188.96
192.69
196.41
200.11
FIN. EXISTING FIRST FLOOR 188.96
FIN. EXISTING SECOND FLOOR 192.69
FIN. EXISTING THIRDFLOOR 196.41
TOP OF EXISTING STRUCTURAL STEEL
200.11
FISHERVILLE SENIOR PUBLIC SCHOOLToronto
BoardSchoolDistrict
ALW-12
ALW-1
ALW-1
ALW-1
ALW-1
ALW-1 ALW-1
ALW-1
ALW-1
ALW-1
ALW-1 ALW-1 ALW-1
ALW-1 ALW-1
ALW-1
ALW-4
188.42
AC
FIN. EXISTING FIRST FLOOR188.96
FIN. EXISTING SECOND FLOOR192.69
FIN. EXISTING THIRD FLOOR196.41
TOP OF EXISTING STRUCTURAL STEEL
200.14
AC
ALW-7
ALW-1
ALW-2 ALW-5ALW-2
ALW-6 ALW-3ALW-4
ALW-4
ALW-4
ALW-4
FIN. EXISTING FIRST FLOOR
188.42
2
1
2
11
2
1
2
1
2
1
3
3
2
1
4
4 5 4
4
4
4
1 1 1 5
ALW-4
2
2AC
AC ACAC
AC AC
AC AC
7
ELEVATION KEY NOTES:
WINDOW REPLACEMENTS:
B) GC TO INSTALL NEW WINDOW AND DOOR ASSEMBLIES AS PER MANUFACTURER'S SPECIFICATION.
PROVIDE FLOOR TO CEILING INTERIOR HOARDING AS PER GENERAL HOARDING NOTES ON
SHEET A100.
C) MAKE GOOD ANY SURFACES AFFECTED BY WORK. REFER TO SPECS AND WINDOW TYPES.
D) PROTECT EXISTING ELECTRICAL CONNECTION(S) INCLUDING RACEWAYS CLOSE TO WINDOW
OPENING(S) FROM ANY DAMAGE.
GC TO REMOVE AND REINSTALL WINDOW MOUNTED MECHANICAL FITMENT(S) INCLUDING A/C AND
EXHAUST FAN(S) ASSEMBLIES TO MATCH EXISTING. PROVIDE INSULATED PANELS WHERE REQUIRED
AT PERIMETER OF PENETRATIONS. MODIFY MULLIONS TO RECEIVE INSULATED PANELS AS REQUIRED.
EXISTING THROUGH WALL AC UNITS TO REMAIN
EXISTING MECHANICAL GRILLES, LIGHTS, SPEAKERS TO REMAIN
EXTERIOR DOOR MODIFICATION AND REPLACEMENTS:
A) GC INSTALL NEW DOORS, SIDELIGHTS, AND FRAMES INCLUDING TRANSOMS.
B) PATCH, REPAIR AND MAKE GOOD AREA AFFECTED BY WORK TO MATCH EXISTING.
EXISTING PLEXI-GLASS GLAZING IN EXISTING DOOR TO BE REMOVED AND REPLACED WITH
INSULATED TEMPERED GLAZING/ CONTRACTOR TO MODIFY / ADD GLASS STOP
TO ACCOMMODATE DOUBLE INSULATED GLASS UNIT.
EXISTING DOOR AND FRAME TO BE PAINTED. COLOUR TO MATCH EXISTING.
EXISTING CONCRETE SILL IN POOR CONDITION AT EXISTING DOOR TO BE REMOVED AND REPLACED.
2
3
1
5
4
6
7
NOTE
- ANY ELECTRICAL ELEMENT WITHIN SPECIFIED SCOPE OF WORK SHALL BE
ADDRESSED BY ELECTRICAL CONTRACTOR PRIOR TO PROCEEDING WITH
REMEDIAL OR REPAIR WORK TO EXTERIOR FACADE. REINSTATE ELECTRICAL
ELEMENTS TO THEIR EXISTING CONDITIONS UPON COMPLETION OF REMEDIAL &
REPAIR WORK.
- ALL EXIT DOORS ARE TO REMAIN OPERATIONAL FOR DURATION OF
REFINISHING/ REMEDIAL WORK. EXITS TO REMAIN ACCESSIBLE, SAFE, AND
SECURE FOR DURATION OF WORK. G.C. TO PROVIDE HOARDING AT LOCATIONS,
WHERE REQUIRED, COMPLETE WITH OVERHEAD PROTECTION AND LIGHTING.
SUBMIT ENGINEERED SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION
AND INSTALLATION OF HOARDING. HOARDING TO BE SECURELY INSTALLED
PRIOR TO COMMENCING ANY WORK. SEE SPEC.
- ALL MATERIALS AND FINISHES AFFECTED BY WORK TO BE MADE GOOD
TO MATCH EXISTING (TYP.)
- CONTRACTOR TO CONFIRM ALL EXISTING OPENINGS DIMENSIONS ON SITE
PRIOR TO NEW WINDOWS FABRICATION.
- CONTRACTOR TO REMOVE COMPONENTS INTERFERING WITH WINDOW
REPLACEMENT, REINSTALL AND MAKE GOOD ALL DISTURBED AREAS
UPON COMPLETION OF WORK.
- ALL VENT OPENINGS TO COMPLY WITH O.B.C.
- NEW ALUMINUM WINDOW COLOUR TO MATCH EXISTING WINDOW COLOUR (TYP.)
- ANY WINDOW WITH A SILL HEIGHT LESS THAN 1070MM TO BE DESIGNED TO MEET
OBC REQUIREMENTS FOR A GUARD INCLUDING PROFILE AND GLAZING.
EAST (COURTYARD) ELEVATION
1 09/26/2019 ISSUED FOR PRE-TENDER CLIENT REVIEW
BUILDING ELEVATIONS
WEST ELEVATION
KEY PLAN
FISHERVILLE SR PS /
NORTH WEST YEAR ROUND ALT CTR
1
PHASE 1
NORTH ELEVATION
Toronto
SchoolBoard
District
t. 416-395-4588 / f. 416-395-973415 Oakburn Cres. Toronto, Ontario M2N 2T5
Design & Construction DivisionFacility Services Department
ETUDE ARCHITECTS INC.
No. DATE DESCRIPTION
LOCATION
PROJECT
DRAWING TITLE
TDSB PROJECT No: REVISION No:
DRAWING No:DATE:
SCALE:
DRAWING BY:
APPROVED BY:
FISHERVILLE SR. PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.WINDOW & DOOR REPLACEMENT-PHASE 1
JY
TR-18-1115 (219114)
AS NOTED
A400AM
FISHERVILLE SENIOR PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.425 PATRICIA AVE., NORTH YORK,ONTARIO M2R 2N1
OCTOBER 17, 2019
2 10/17/2019 ISSUED FOR TENDER
50+
/-
240+/-
CAREFULLY REMOVE EXISTING
WINDOW AND FRAME/ PREPARE
EXISTING SUBSTRATE TO
RECEIVE NEW WINDOW
TYPE ON A900 (TYP.)
25+/-
EXIST. PRECAST
TERRRAZO SILL
TO REMAIN
EXISTING TO REMAIN
EXIST. PRECAST
CONCRETE PANEL
TO REMAIN
CAREFULLY REMOVE EXISTING
WINDOW ASSEMBLY/ PATCH/
REPAIR & MAKE GOOD AREA
AFFECTED BY WORK. TO MATCH
EXISTING/ PREPARE TO
RECEIVE NEW WINDOW
ASSEMBLY (TYP.)
EXISTING STRUCTURE AND
CEILING ASSEMBLY TO REMAIN/
PATCH REPAIR AND MAKE GOOD
AREA AFFECTED BY WORK/ TO
MATCH EXISTING (TYP.)
EXISTING TO REMAIN
CONTRACTOR TO CAREFULLY REMOVE EXISTING
ROLLER SHADES IN GOOD CONDITION - TO BE REINSTALLED/
REMOVE AND DISCARD OF EXIST. HORIZONTAL BLINDS AND/
OR ROLLER SHADES IN POOR CONDITION (SEE FLOOR PLANS)
TO BE REPLACED WITH NEW TDSB STANDARD ROLLER SHADES.
EXTERIOR
INTERIOR
EXIST. TERRAZZO SILL TO
REMAIN/ GC TO CAREFULLY
REMOVE AND RE-INSTALL SILL/
MAKE GOOD ALL MATERIALS
DOUBLE GLAZING
IN FIXED WINDOW
FRAME
LINE OF EXISTING
WINDOW ASSEMBLY
TO BE REMOVED
13
3+
/-
16
0+
/-
SELF ADHESIVE AIR/
VAPOUR BARRIER
MEMBRANE BLUESKIN
BY HENRY/ TYPICAL
EXIST.
TO
REMAIN
EXISTING STRUCTURE AND CEILING ASSEMBLY TO
REMAIN/ PATCH REPAIR AND MAKE GOOD AREA
AFFECTED BY WORK/ TO MATCH EXISTING (TYP.)
96+/-
133
EXISTING BRICK
TO REMAIN
NEW DOUBLE GLAZING
IN FIXED ALUMINUM
WINDOW FRAME
EXIST. PRECAST
CONCRETE PANEL
TO REMAIN
SEALANT & BACKER
ROD TYPICAL
SELF ADHESIVE AIR/ VAPOUR
BARRIER MEMBRANE BLUESKIN
BY HENRY/ TYPICAL
LINE OF EXISTING WINDOW
FRAME TO BE REMOVED
EXISTING TO REMAIN
NEW OR EXISTING ROLLER SHADE TO BE INSTALLED/
SEE FLOOR PLANS FOR NOTES/ CASSETTE FOR BLINDS
TO BE FASTENED TO WALL OR CEILING - DO NOT ATTACH
CASSETTE OR CHAIN TO WINDOW FRAME (TYP.)
EXIST. PRECAST
TERRRAZO SILL
TO REMAIN
133
NEW DOUBLE GLAZING
IN FIXED ALUMINUM
WINDOW FRAME
SEALANT & BACKER
ROD/ TYPICAL
EXISTING TO REMAIN
ALUMINUM PANNING TO
MATCH WINDOW FRAME
COLOUR/ SEALANT AND
BACKER ROD AT
TOP AND BOTTOM
PREFINISHED EXTRUDED
ALUM. FLASHING &
SILL C/W UPTURN
DAM AT ENDS
SELF ADHESIVE AIR/ VAPOUR
BARRIER MEMBRANE
BLUESKIN BY HENRY/ TYPICAL
FILL ALL VOIDS WITH FOAM
INSULATION (TYP)
SEALANT & BACKER
ROD/ TYPICAL
LINE OF EXISTING WINDOW
FRAME TO BE REMOVED
PROPOSED ALUMINUM
ENTRY DOOR FRAME/
AND SIDE LIGHT/ REFER
TO DOOR SCHEDULE
EXIST. PRECAST
CONCRETE PANEL
TO REMAIN
EXISTING BRICK TO
REMAIN/ PATCH/ REPAIR
AND MAKE GOOD ALL
SURFACES AFFECTED BY
WORK/ TO MATCH
EXISTING (TYP.)
PROPOSED FIXED
TRANSOM IN ALUMINUM
FRAME/ REFER TO
DOOR SCHEDULE
SELF ADHESIVE
AIR/ VAPOUR
BARRIER
MEMBRANE
BLUESKIN BY
HENRY/ TYPICAL
NEW ROLLER SHADE TO BE
INSTALLED/ CASSETTE FOR
BLINDS TO BE FASTENED TO
WALL OR CEILING - NOT
ATTACHED TO WINDOW OR
DOOR FRAME (TYP.)
EXISTING ELECTRICAL
RACEWAY TO BE CAREFULLY
REMOVED AND RE-INSTALLED
EXISTING STRUCTURE/ WOOD
PANELING AND GLUED ON CEILING
TO REMAIN/ MODIFY CEILING AS
REQUIRED TO ACCOMMODATE
NEW WINDOW AND BLIND
INSTALLATION/ PATCH REPAIR AND
MAKE GOOD AREA AFFECTED BY
WORK/ TO MATCH EXISTING (TYP.)
jh jh
PROPOSED ALUMINUM
ENTRY DOOR FRAME/
AND SIDE LIGHT/ REFER
TO DOOR SCHEDULE
EXTERIOR INTERIOR
EXISTING FIN. FLOOR
AND BASE TO REMAIN/
PATCH/ REPAIR AND
MAKE GOOD ALL
SURFACES AFFECTED
BY WORK/ TO MATCH
EXISTING (TYP.)
EXISTING BLOCK TO
REMAIN PATCH/ REPAIR
AND MAKE GOOD ALL
SURFACES AFFECTED
BY WORK/ TO MATCH
EXISTING (TYP.)
EXISTING CONC. PAD
TO REMAIN/ PATCH/
REPAIR AND MAKE
GOOD ALL SURFACES
AFFECTED BY WORK/
TO MATCH EXISTING
(TYP.)
LINE OF EXISTING
DOOR FRAME
SELF ADHESIVE AIR/
VAPOUR BARRIER
MEMBRANE BLUESKIN
BY HENRY/ TYPICAL
EXISTING TO
REMAIN
jh
EXISTING BRICK
TO REMAIN
NEW DOUBLE GLAZING
IN OPERABLE
OPEN-OUT VENT IN
ALUMINUM WINDOW
FRAME
EXISTING STRUCTURE AND CEILING ASSEMBLY TO
REMAIN/ PATCH REPAIR AND MAKE GOOD AREA
AFFECTED BY WORK/ TO MATCH EXISTING (TYP.)
SEALANT & BACKER
ROD TYPICAL
96+/-
133
SEE PLANS FOR ROOMS TO RECEIVE
INSECT SCREENS
SELF ADHESIVE AIR/ VAPOUR BARRIER
MEMBRANE BLUESKIN BY HENRY/ TYPICAL
EXIST. PRECAST
CONCRETE PANEL
TO REMAIN
EXISTING TO REMAIN
NEW OR EXISTING ROLLER SHADE TO BE INSTALLED/ SEE FLOOR PLANS
FOR NOTES/ CASSETTE FOR BLINDS TO BE FASTENED TO WALL OR
CEILING - DO NOT ATTACH CASSETTE OR CHAIN TO WINDOW FRAME (TYP.)
EXIST. PRECAST
TERRRAZO SILL
TO REMAIN
SEALANT & BACKER
ROD/ TYPICAL
EXISTING TO REMAIN
ALUMINUM PANNING TO
MATCH WINDOW FRAME
COLOUR/ SEALANT AND
BACKER ROD AT
TOP AND BOTTOM
PREFINISHED EXTRUDED
ALUM. FLASHING &
SILL C/W UPTURN
DAM AT ENDS
SELF ADHESIVE AIR/ VAPOUR
BARRIER MEMBRANE
BLUESKIN BY HENRY/ TYPICAL
FILL ALL VOIDS WITH FOAM
INSULATION (TYP)
NEW DOUBLE GLAZING IN
OPERABLE OPEN-OUT VENT IN
ALUMINUM WINDOW FRAME
SEE PLANS FOR ROOMS TO
RECEIVE INSECT SCREENS
jh
SEALANT & BACKER
ROD/ TYPICAL
EXISTING BRICK
TO REMAIN
NEW DOUBLE GLAZING
IN FIXED ALUMINUM
WINDOW FRAME
SEALANT & BACKER
ROD TYPICAL
133
SELF ADHESIVE AIR/
VAPOUR BARRIER
MEMBRANE BLUESKIN
BY HENRY/ TYPICAL
EXISTING TO
REMAIN
MODIFY EXISTING GLUED ON
CEILING TILES TO ACCOMMODATE
NEW WINDOW FRAME
NEW OR EXISTING ROLLER SHADE TO
BE INSTALLED/ SEE FLOOR PLANS FOR
NOTES/ CASSETTE FOR BLINDS TO BE
FASTENED TO WALL OR CEILING -
DO NOT ATTACH CASSETTE OR CHAIN
TO WINDOW FRAME (TYP.)
SOLID BIRCH GUARD
WITH STAIN FINISH
152
38
150 x 19MM CHANNEL
SECURED TO ANGLES
64 x 64 x 6.4MM STEEL ANGLE
SECURED TO WALL AT BOTH
ENDS/ STEEL ANGLE NOT TO
BE SECURED TO WINDOW
FRAME/ ANGLE TO BE PAINTED
TO MATCH WINDOW FRAME
NOTE:
TO BE ALIGNED WITH
MULLION AT 1100MM A.F.F./
CONTRACTOR TO SUBMIT
SHOP DRAWINGS
1100
A.F
.F
.
NEW DOUBLE GLAZING
IN FIXED ALUMINUM
WINDOW FRAME
312
LINE OF EXISTING WINDOW
FRAME TO BE REMOVED
133
NEW DOUBLE GLAZING
IN FIXED ALUMINUM
WINDOW FRAME
EXISTING BRICK
TO REMAIN
SEALANT & BACKER
ROD TYPICAL
INSULATED METAL
PANEL TO MATCH
WINDOW FRAME
COLOUR
PREFINISHED EXTRUDED
ALUM. FLASHING &
SILL C/W UPTURN
DAM AT ENDS
EXISTING TO
REMAIN
EXTERIOR
INTERIOR
EXIST. TERRAZZO SILL TO
REMAIN/ GC TO CAREFULLY
REMOVE AND RE-INSTALL SILL/
MAKE GOOD ALL MATERIALS
LINE OF EXISTING
WINDOW ASSEMBLY
TO BE REMOVED
13
3+
/-
24
0+
/-
SELF ADHESIVE AIR/
VAPOUR BARRIER
MEMBRANE BLUESKIN
BY HENRY/ TYPICAL
jh
DOUBLE GLAZING IN
OPERABLE OPEN-OUT
WINDOW FRAME
EXIST.
TO
REMAIN
jh
EXTERIOR
INTERIOR
DOUBLE GLAZING
IN OPERABLE
OPEN-OUT
WINDOW FRAME
DOUBLE GLAZING
IN FIXED WINDOW
FRAME
EXIST. TERRAZZO SILL
TO REMAIN/ GC TO
CAREFULLY REMOVE
AND RE-INSTALL SILL/
MAKE GOOD ALL
MATERIALS
DOUBLE GLAZING
IN FIXED WINDOW
FRAME
LINE OF EXISTING
WINDOW ASSEMBLY
TO BE REMOVED
EXTERIOR
INTERIOR
jh
EXISTING BRICK
TO REMAIN
NEW DOUBLE GLAZING
IN FIXED ALUMINUM
WINDOW FRAME
SEALANT & BACKER
ROD TYPICAL
96+/- 133
NEW DOUBLE GLAZING
IN OPERABLE
OPEN-OUT VENT IN
ALUMINUM WINDOW
FRAME
SEE PLANS FOR
ROOMS TO RECEIVE
INSECT SCREENS
SELF ADHESIVE AIR/ VAPOUR
BARRIER MEMBRANE
BLUESKIN BY HENRY (TYP.)
EXISTING TO
REMAIN
NEW OR EXISTING ROLLER SHADE TO BE
INSTALLED/ SEE FLOOR PLANS FOR NOTES/
CASSETTE FOR BLINDS TO BE FASTENED TO
WALL OR CEILING - DO NOT ATTACH CASSETTE
OR CHAIN TO WINDOW FRAME (TYP.)
EXISTING STRUCTURE/ WOOD
PANELING AND GLUED ON CEILING TO
REMAIN/ MODIFY CEILING AS
REQUIRED TO ACCOMMODATE NEW
WINDOW AND BLIND INSTALLATION/
PATCH REPAIR AND MAKE GOOD
AREA AFFECTED BY WORK/ TO
MATCH EXISTING (TYP.)
DEMOLITION SECTION DETAIL AT SILL
DEMOLITION SECTION DETAIL AT CEILING ASSEMBLY
1 09/26/2019 ISSUED FOR PRE-TENDER CLIENT REVIEW
NOTE:
· GC TO SUBMIT SHOP DRAWINGS DESIGNED, REVIEWED AND STAMPED BY A
PROFESSIONAL ENGINEER LICENSED TO PRACTICE IN PROVINCE OF ONTARIO.
(TYP.)
· INSTALL INSECT SCREENS IN ALL STAFF ROOMS AND DINING / LUNCH ROOM(S)
AND ANY FOOD PREP. ROOMS. (TYP.)
· MAKE GOOD ALL FINISHES DISTURBED BY CONSTRUCTION TO MATCH EXISTING.
(TYP.)
DEMOLITION & PROPOSED DETAILS
KEY PLAN
FISHERVILLE SR PS /
NORTH WEST YEAR ROUND ALT CTR
1
PHASE 1
WINDOW JAMB-FIXED (TYP.)
PROPOSED SECTION DETAIL AT SILL
PROPOSED SECTION DETAIL AT CEILING ASSEMBLY
PROP. TRANSOM & DOOR HEAD DETAIL
PROPOSED DOOR SILL DETAIL
PROPOSED SECTION DETAIL AT SILL
PROPOSED SECTION DETAIL AT CEILING ASSEMBLY
PROPOSED SECTION DETAIL AT CORRIDOR WINDOWS
PROPOSED GUARD DETAIL AT CORRIDOR
PROPOSED SILL DETAIL AT CORRIDOR
WINDOW JAMB (TYP.) MULLION (TYP.)
MULLION-FIXED (TYP.)
PROP. SECTION DETAIL AT TRANSOM
Toronto
SchoolBoard
District
t. 416-395-4588 / f. 416-395-973415 Oakburn Cres. Toronto, Ontario M2N 2T5
Design & Construction DivisionFacility Services Department
ETUDE ARCHITECTS INC.
No. DATE DESCRIPTION
LOCATION
PROJECT
DRAWING TITLE
TDSB PROJECT No: REVISION No:
DRAWING No:DATE:
SCALE:
DRAWING BY:
APPROVED BY:
FISHERVILLE SR. PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.WINDOW & DOOR REPLACEMENT-PHASE 1
JY
TR-18-1115 (219114)
AS NOTED
A600AM
FISHERVILLE SENIOR PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.425 PATRICIA AVE., NORTH YORK,ONTARIO M2R 2N1
OCTOBER 17, 2019
2 10/17/2019 ISSUED FOR TENDER
879+
/-
2108+
/-
TO
M
AT
CH
E
XIS
TIN
G D
IM
.737+
/-
FIN. FLOOR
FIN. FLOOR
FIXED
FIXED
OPEN-
OUT
FIXED
OPEN-
OUT
50
550 1848+/- 550
50
3150+/-
TO MATCH EXISTING DIM.
50
(CLASSROOM 101
CLASSROOM 102
FAMILY STUDIES 103
CLASSROOM 109
CLASSROOM 202
CLASSROOM 203
CLASSROOM 204
CLASSROOM 206
TYPE ALW-1
50
550
50
1358+
/-
50
LIBRARY 208
COOMP. LAB. 211
CLASSROOM 301
CLASSROOM 303
CLASSROOM 305
CLASSROOM 307
CLASSROOM 308
CLASSROOM 309
CLASSROOM 310)
8
A600
5
A600
10
A600
50
7
A600
4
A600
6
A600
3
A600
4
A600
50
2987+
/-
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
SIM
NOTES:
- CONTRACTOR TO VERIFY ALL DIMENSIONS AT SITE PRIOR
TO FABRICATION.
- GC TO VISIT SITE AND VERIFY PANNING REQUIREMENTS
PRIOR TO BID SUBMISSION.
- REFER TO FLOOR PLANS FOR LOCATIONS, WHERE EXISTING
ROLLER SHADES ARE TO BE REMOVED, WHERE
NEW ROLLER SHADES ARE SUPPLIED AND INSTALLED OR
EXISTING ROLLER SHADES ARE RE-INSTALLED.
REFER TO SPECIFICATIONS.
- INSTALL INSECT SCREENS IN ALL STAFF ROOMS AND DINING /
LUNCH ROOM(S) AND ALL ROOMS WHERE FOOD IS PREPARED.
(TYP.)
- GC TO SUBMIT SHOP DRAWINGS DESIGNED, REVIEWED AND
STAMPED BY A PROFESSIONAL ENGINEER LICENSED TO
PRACTICE IN PROVINCE OF ONTARIO. (TYP.)
- MAKE GOOD ALL FINISHES DISTURBED BY CONSTRUCTION
TO MATCH EXISTING. (TYP.)
- ALL WINDOWS AND GLAZING WITH A SILL HEIGHT OF LESS
THAN 1000MM TO BE DESIGNED AS A GUARD AND TO MEET
OBC REQUIREMENTS.
NOTES:TYPICAL
-DOOR / DOOR FRAMING CONTRACTOR TO VERIFY ALL DIMENSIONS AND DOOR SWINGS ON-SITE (DOOR OPENINGS, ETC). -ALL LOCK CORES TO MATCH SCHOOL EXIST. LOCKING SYSTEM. HANDLES TO BE LEVER STYLE. -REFER TO DOOR AND HARDWARE SPECIFICATIONS. -KICK PLATE TO BE STAINLESS STEEL.
FIRST FLOOR DOOR SCHEDULE
DOOR
NO.
FROM TO
DOORS FRAMES AND SCREENS HARDWARE REMARKS REV.
SW
IN
G
TY
PE
HE
IG
HT
WID
TH
TH
IC
KN
ES
S
MA
TE
RIA
L
FIN
IS
H
GL
AZ
IN
G
TY
PE
MA
TE
RIA
L
FIN
IS
H
JA
MB
T
YP
E
TH
RE
SH
OL
D T
YP
E
EL
EC
TR
IC
AL
D
EV
IC
E
FIR
E R
AT
IN
G L
AB
EL
LO
CK
S
ET
LA
TC
H S
ET
PR
IV
AC
Y S
ET
PA
SS
AG
E S
ET
CL
OS
ER
ST
OP
PA
NIC
D
EV
IC
E
PU
LL
/P
US
H
WE
AT
HE
R S
TR
IP
PIN
G
ST
AIN
LE
SS
S
TE
EL
KIC
KP
LA
TE
AU
TO
MA
TIC
D
OO
R
OP
ER
AT
OR
6 EXIT STAIR #6 EXTERIOR EXISTING
EXISTING PLEXIGLASS TO BE REMOVED. REPLACE WITH NEW DOUBLE GLAZING.
EXISTING DOOR AND FRAME TO BE PRIMED AND PAINTED
102 ART ROOM EXTERIOR RHR D2 2100 965 45 HM PT
TG
SU
F2 HM PT J ALUM - - Δ - - - Δ Δ - Δ Δ Δ -
109 CLASSROOM 109 EXTERIOR RHR D1 2070 914 45 HM PT
TG
SU
F1 HM PT J ALUM - - Δ - - - Δ Δ Δ - Δ Δ -
R.H./L.H.
L.H.R. R.H.R.
L.H. R.H.
DOOR SWINGS
TG : TEMPERED PLATE GLASS
ST. : STEELS.W.C.: SOLID WOOD CORE
H.M. : HOLLOW METAL
F.C. : FOAM CORE
ALUM.: ALUMINUM
SU : DOUBLE GLAZED SEALED UNITS
R.H.R./L.H.R.
G. : GLAZED
PT. : PAINTED
DC : DOOR CONTACT
ADO : AUTOMATIC DOOR OPENER
DADC : DOOR ALARM DOOR CONTACT
FG : FIRE RATED GLASS
L.H./R.H./R.H.
L.H.R./R.H.R./R.H.R.
50
70+/-
1084+/-
TO MATCH EXISTING DIM.
914
TO MATCH
EXISTING DIM.
F1
CLASSROOM #109
F2
ART ROOM #102
30
43
+/-
TO
M
AT
CH
E
XIS
TIN
G
1930 +/-
TO MATCH EXISTING DIM
50
84
3+
/-
50
21
00
501830+/-
50
780+/- 1000
10
02
07
0
50
50
FIN. FLOOR
21
70
+/-
tT
O M
AT
CH
E
XIS
TIN
G
AC AC
(FAMILY STUDIES 203)
TYPE ALW-2
OPEN-
OUT
OPEN-
OUT
FIXED FIXED
FIN. FLOOR
FIN. FLOOR
87
9+
/-
21
08
+/-
TO
M
AT
CH
E
XIS
TIN
G D
IM
.7
37
+/-
29
87
+/-
50
550 1848+/- 550
50
3150+/-
TO MATCH EXISTING DIM.
50
50
55
0+
/-
50
48
0+
/-
50
50
82
8
FIXED
RE-INSTALL
EXISTING A/C UNIT/
FILL GAPS WITH
SOLID INSULATED
PANEL (TYP.)
50
50
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
AC
(CLASSROOM 107)
TYPE ALW-3
FIXED FIXED
879+
/-
2108+
/-
TO
M
AT
CH
E
XIS
TIN
G D
IM
.737+
/-
2987+
/-
50
550 1848+/- 550
50
3150+/-
TO MATCH EXISTING DIM.
50
50
550+
/-
50
480+
/-
50
50
828
FIN. FLOOR
FIN. FLOOR
OPEN-
OUT
OPEN-
OUT
FIXED
FIXED
6
A600
6
A600
FIXED
FIXED
SIM
50
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
87
9+
/-
21
08
+/-
73
7+
/-
29
87
+/-
50 1231+/-50
551 50
FIXED
FIXED
OPEN-
OUT
(FAMILY STUDIES 103
CLASSROOM 109
GUIDANCE 119
CLASSROOM 206
STAFF WORK RM. 207
OFFICE 208A
PREP. RM. 317
STAFF WORK RM.-3RD FLR.)
TYPE ALW-4
1932
TO MATCH EXISTING DIM.
50
55
0+
/-
50
13
58
50
FIN. FLOOR
FIN. FLOOR
50
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
(FAMILY STUDIES 103)
TYPE ALW-5
AC
879+
/-
2108+
/-
737+
/-
2987+
/-
50 1231+/-50
550 50
FIXED
FIXED
OPEN-
OUT
1932
TO MATCH EXISTING DIM.
50
550+
/-
50
828
50
FIN. FLOOR
FIN. FLOOR
480+
/-
50
50
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
879+
/-
2108+
/-
737+
/-
2987+
/-
50 53850
550 50
636+/-
50
550+
/-
50
1358
50
1932
TO MATCH EXISTING DIM.
AC
(CLASSROOM 107)
TYPE ALW-6
FIXED
FIXED
FIXED
50
479
50
1478
50
FIN. FLOOR
FIN. FLOOR
OPEN-
OUT
50
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
(CLASSROOM 109)
TYPE ALW-7
OPEN-
OUT
FIXED
21
08
+/-
87
9+
/-
29
88
+/-
50 551
2015+/-
TO MATCH EXISTING
501364+/-
50
10
0
13
58
+/-
50
55
05
0
FIXED
FIN. FLOOR
FIN. FLOOR
73
7+
/-
15
A900
17
A900
SIM
EXISTING CONCRETE SILL
TO BE REMOVED AND
NEW PRECAST CONCRETE
SILL TO BE INSTALLED
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
(CLASSROOM 106
SEMINAR ROOM 208D
STAIR 3 AT 3RD FLOOR LEVEL)
TYPE ALW-8
1289+
/-
50
1139+
/-
50
3533+
/-
2244+
/-
RO
OM
106
50
3150+/-
TO MATCH EXISTING
FIXEDOPEN-
OUT
OPEN-
OUT
737+
/-
FIN. FLOOR AT
CLASSROOM 106
FIN. FLOOR
550 1849+/- 550 50
50
50
FIN. FLOOR AT
SEMINAR ROOM 208D
1688+
/-
AT
R
OO
M 208D
9
A600
50
PROVIDE TYPE 2 HARDWARE:
OPERABLE SECTIONS OF WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY & INSTALL TELEFLEX WINDOW
OPERATORS FOR ALL WINDOWS WHERE THE OPERABLE
PORTION OF THE WINDOW IS ABOVE 1600mm.
(CLASSROOM 104
ART ROOM 102)
TYPE ALW-9
FIXED
OPEN-
OUT
OPEN-
OUT
FIXED
FIXED FIXED
29
84
+/-
50
50
3150+/-
TO MATCH EXISTING
550 50 1848+/-
50
55050
73
7+
/-
41
5+
/-
50
13
58
+/-
50
55
0
50
25
23
+/-
46
1+
/-
FIN. FLOOR
FIN. FLOOR
16
A600
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
(ART ROOM 102)
TYPE ALW-10
2984+
/-
50
740+
/-
415+
/-
50
1358+
/-
50
550
50
2573+
/-
461+
/-
FIN. FLOOR
FIN. FLOOR
FIXED
FIXED
OPEN-
OUT
FIXED
501830+/-
50
50
PROVIDE TYPE 1 HARDWARE:
OPERABLE SECTIONS OF
WINDOW UNIT TOP-HUNG
OPEN-OUT VENTS. SUPPLY &
INSTALL CONTINUOUS
EXTRUDED ALUMINUM
HINGES & ROTO OPERATORS
WITH DUAL FRICTION ARMS.
(CORRIDOR 1ST FLOOR)
TYPE ALW-11
FIXED FIXED FIXED
FIN. FLOOR
FIN. FLOOR
2714+
/-
1010
1500+
/-
1214+
/-
50
1350+
/-
50
50
949+/- 50 949+/- 50 949+/- 50
3048
13
A600
50
7
A600
FIXED FIXED FIXED
FIXED FIXED FIXED
(CORRIDOR 219
CORRIDOR 319)
TYPE ALW-12
FIN. FLOOR
FIN. FLOOR
26
86
+/-
10
38
11
00
+/-
50
15
11
+/-
50
76
8+
/-
50
949+/- 50 949+/-50
949+/- 50
3048
29
33
8
5
A600
11
A600
12
A600
13
A600
914+/-
TO MATCH EXISTING
150
20
70
+/- T
O M
AT
CH
E
XIS
TIN
G
614 150
15
07
23
26
07
57
18
0
D1
CLASSROOM #109
SOLID
PANEL
D2
ART ROOM #102
965
150665
150
15
07
53
21
00
26
07
57
18
0
D3 & F3 - EXISTING
EXIT #6
25
40
+/-
15
28
+/-
82
50
914+/-
50
914+/-
50
914+/-
5082
15
1+
/-
15
0+
/-
18
5+
/-
41
3+
/-
26
5+
/-
3107+/-
EXISTING PLEXIGLASSS
GLAZING TO BE REMOVED
AND REPLACED WITH
INSULATED GLAZING WITH
TEMPERED GLASS /
CONTRACTOR TO MODIFY
/ ADD GLASS STOP TO
ACCOMMODATE DOUBLE
INSULATED GLASS UNIT
EXISTING FRAME
TO BE RE-PAINTED
26
91
+/-
150
614
150150
614
150 150
614
150
10
67
10
67
LINES OF
EXISTING
DOORS AND
FRAMES
TO BE
REMOVED
SEALANT AND
BACKER ROD AT
PERIMETER -
BOTH SIDES.(TYP.)
PROPOSED
ALUMINUM ENTRY DOOR
AND FRAME/ REFER TO
DOOR SCHEDULE
EXIST. TO
REMAIN
J2
EXIT TO COURTYARD
ART ROOM 102
INTERIOR
SELF ADHESIVE AIR/
VAPOUR BARRIER
MEMBRANE BLUESKIN
BY HENRY/ TYPICAL
ALUMINUM PANNING TO
MATCH WINDOW FRAME
COLOUR/ SEALANT AT
PERIMETER
EXTERIOR
INTERIOR
LINES OF EXISTING
DOOR AND FRAME
TO BE REMOVED
EXISTING CONC.
SILL BELOW
IN POOR
CONDITION/ TO
BE REPLACED/
MATCH EXISTING
EXISTING TO
REMAIN
J1
CLASSROOM 109
SEE DOOR SCHEDULE
SEALANT & BACKER ROD
AT BOTH SIDES (TYP.)
ALUMINUM PANNING TO MATCH
WINDOW FRAME COLOUR/
SEALANT AT PERIMETER
SELF ADHESIVE AIR/
VAPOUR BARRIER
MEMBRANE BLUESKIN
BY HENRY/ TYPICAL
70
ALUMINUM PANNING TO
MATCH WINDOW FRAME
COLOUR/ SEALANT AT
PERIMETER
PROPOSED
ALUMINUM ENTRY DOOR
AND FRAME/ REFER TO
DOOR SCHEDULE
DOUBLE GLAZING
IN FIXED WINDOW
FRAME
LINES OF
EXISTING
DOORS AND
FRAMES
TO BE
REMOVED
PROPOSED
ALUMINUM
ENTRY DOOR
AND FRAME/
REFER TO DOOR
SCHEDULE
SIDELIGHT
EXIT TO COURTYARD
ART ROOM 102
EXTERIOR
INTERIOR
WINDOW ELEVATION - TYPE ALW-1
QUANTITYTYPE
ALW-1 27
WINDOW QUANTITIES:
JAMB TYPE
DOOR TYPE FRAME TYPES
1 09/26/2019 ISSUED FOR PRE-TENDER CLIENT REVIEW
NOTE:
GC TO SUBMIT SHOP DRAWINGS DESIGNED, REVIEWED AND STAMPED BY A
PROFESSIONAL ENGINEER LICENSED TO PRACTICE IN PROVINCE OF ONTARIO. (TYP.)
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-2 2
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-3 1
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-4 10
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-5 1
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-6 1
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-7 1
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-8 4
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-9 3
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-10 1
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
QUANTITYTYPE
ALW-11 1
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
WINDOW ELEVATION - TYPE ALW-2 WINDOW ELEVATION - TYPE ALW-3 WINDOW ELEVATION - TYPE ALW-4 WINDOW ELEVATION - TYPE ALW-5
WINDOW ELEVATION - TYPE ALW-6 WINDOW ELEVATION - TYPE ALW-7 WINDOW ELEVATION - TYPE ALW-8 WINDOW ELEVATION - TYPE ALW-9 WINDOW ELEVATION - TYPE ALW-10
WINDOW ELEVATION - TYPE ALW-11 WINDOW ELEVATION - TYPE ALW-12
DOOR FINISH SCHEDULES, WINDOW / JAMB / DOOR / FRAMETYPES AND DETAILS
DOOR JAMB TYPE JAMB TYPE
Toronto
SchoolBoard
District
t. 416-395-4588 / f. 416-395-973415 Oakburn Cres. Toronto, Ontario M2N 2T5
Design & Construction DivisionFacility Services Department
ETUDE ARCHITECTS INC.
No. DATE DESCRIPTION
LOCATION
PROJECT
DRAWING TITLE
TDSB PROJECT No: REVISION No:
DRAWING No:DATE:
SCALE:
DRAWING BY:
APPROVED BY:
FISHERVILLE SR. PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.WINDOW & DOOR REPLACEMENT-PHASE 1
JY
TR-18-1115 (219114)
AS NOTED
A900AM
FISHERVILLE SENIOR PUBLIC SCHOOLNORTH WEST YEAR ROUND ALT. CTR.425 PATRICIA AVE., NORTH YORK,ONTARIO M2R 2N1
OCTOBER 17, 2019
QUANTITYTYPE
ALW-12 2
REMARKS
GC TO VERIFY WINDOW QUANTITIES
AND DIMENSIONS AT SITE.
TOTAL NUMBER OF WINDOWS TO BE REPLACED = 54
2 10/17/2019 ISSUED FOR TENDER