fire/alarm/security/communications - rexel · it’s why companies turn to emerson network ......

44
Fire/Alarm/Security/Communications Product Catalog Surge Protection For Business-Critical Continuity TM

Upload: duongnguyet

Post on 09-Sep-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Fire/Alarm/Security/CommunicationsProduct Catalog

FPO

Surge Protection For Business-Critical ContinuityTM

Page 2: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Protection Against Damage, Disruption, and Costly Downtime of your …

Mission-Critical Equipment … Today’s advanced commercial/residential fire, alarm, security and telecommunication systems are more sophisticated than ever before. In a nanosecond, transients can disrupt, disable and ruin your mission-critical equipment. It’s why companies turn to Emerson Network Power Surge Protection for their line of surge suppression and filtering products to protect sensitive equipment from excessive maintenance costs, damage and costly downtime.

Emerson Network Power’s comprehensive portfolio includes products for Data/Signal Line Protection, AC Power Surge Protection, and Filtering/Line Conditioning. Plus, all of our engineered power-quality solutions are backed by a dedicated team of power-quality specialists who are available to share their applications and integration knowledge with you. We’re here to help!

Why take chances by putting the security of your mission-critical equipment at risk? Turn to Emerson Network Power Surge Protection products for peace of mind.

To learn more about the world’s most trusted lineup of multi stage, hybrid, solid state, power quality products, call us toll-free at 800-288-6169, or visit our Web site at www.emersonnetworkpower.com/surge.

Page 3: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Table of ContentsApplication Product Page #

CCTV SySTemS Application Drawing 2Zone/Loop/Data Edco™ PC642 Series 3120 VAC Heavy Duty 120 Volt AC Edco™ HSP Series 4Plug-in Surge Protection/Active Tracking™ Filter Islatrol™ SP-6TVN 5CCTV & Data Applications/Coax Edco™ CX Series 6Closed Circuit TV Protection Edco™ CCTV-1 7One- and Two-Pair Signal Line Protection Edco™ FAS-1 and FAS-2 Series 7Two-Pair Signaling Circuit Protector (Modular) Edco™ PHC Series 8 CAT6/CAT5 Power Over Ethernet Edco™ CAT6-5POE Series 9Channel Rackmount Edco™ RM-CX06-16R 9

Fire AlArm Application Drawing 10Zone/Loop/Data Edco™ PC642 Series 11Two-Pair SLC Loop Protector (Modular) Edco™ SLCP Series 12Two-Line Telephone Protection (Modular) Edco™ PC2-TEL 12Two-Pair Signaling Circuit Protector (Modular) Edco™ PHC Series 13120 VAC Heavy Duty 120 Volt AC Edco™ HSP Series 14120/240 VAC Heavy Duty (Parallel) PowerSure™ EMC-240B 15One- and Two-Pair Signal Line Protection Edco™ FAS-1 and FAS-2 Series 16Medium Duty 120 VAC — Single Phase PowerSure™ FAS-120AC 17

BurglAr 12VDC Application Drawings 18One- and Two-Pair Signal Line Protection Edco™ FAS-1 and FAS-2 Series 19Plug-in Surge Protection (Active Tracking™ Filter) Islatrol™ SP-6TVN 20RJ11/RJ31X Telephone Protection Edco™ FAS-TEL and FAS-31XT 21Single-Pair Medium Duty Low Voltage Zone/Horn/Strobe/Data Edco™ TER Series 22Two-Line Telephone Protection (Modular) Edco™ PC2-TEL 22

ACCeSS CONTrOlApplication Drawing 23Electric Door Suppressor Edco™ EL-EDS 24Two-Pair Data/Signal Line Power Edco™ 5W8-30 25RJ11/RJ31X Telephone Protection Edco™ FAS-TEL and FAS-31XT 26120 VAC Heavy Duty 120 Volt AC Edco™ HSP Series 27Zone/Loop/Data Edco™ PC642 Series 28Data Circuit Protection Edco™ LCDP 29

COmmuNiCATiONSOne- and Two-Pair Signal Line Protection Edco™ FAS-1 and FAS-2 Series 30DIN Rail Protection Edco™ DRS (DC) Series 31High Frequency Coax Protector — N-Type Edco™ CX-HFN 32High Frequency Coax Protector — F-Type Edco™ CATV-DF 32Intercom/Speaker Punch Block Protection (Parallel) Edco™ OPX Series 33Intercom/Speaker Punch Block Protection (Series) Edco™ PB Series 34Telecom/Punch Block Protection Edco™ H Series 35Data/Signal Line/Punch Block Protection Edco™ COHP Series 36Fits Standard 66MI-50 Punch Down Blocks Edco™ MGB Ground Rail 36RJ11/RJ31X Telephone Protection Edco™ FAS-TEL and FAS-31XT 37Multi-Channel Rackmount Edco™ RM-CAT6-POE Series 38Data Circuit Protection Edco™ LCDP 38 RJ-45 Telephone/Data Edco™ RJA-RJD Series 39Terminating Assembly Edco™ TBLK Assembly 40CAT6/CAT5 Power Over Ethernet Edco™ CAT6-5POE Series 40Key Systems Edco™ MOD-12 41

Page 4: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

VideoHead-End

EquipmentRack

Multiplexer

SP 1or

SP 2AC Power

Video

Power

Video

Power

RS-485, RS-422 (PTZ)

Power Over Ethernet (POE)

SP 3

SP 5

SP 3

SP 5

SP 6

SP 7 SP 7

SP 6

SP 5

SP 4

SP 5

SP 4

Legend

SP 1 ... HSP121BT-1RUSP 2 ... SP-6TVNSP 3 ... CX06-Mor ...... RM-CX06-16R (16 ch.)SP 4 ... CX06-MI

SP 5 ... FAS-1-043HC (2.5A)or ...... PHC-043* (5A)SP 6 ... PC642C-008LC*SP 7 ... CAT6-5 POE-FF or -MF *Needs PCB1B Base

Exterior FixedCamera

Exterior Camerawith PTZ

Exterior POECamera

For POE with PTZcontact Edco

2

Protecting CCTV Systems Application Drawing

CCTV Systems

Page 5: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

3

CCTV Systems

edco™ PC642 Series Zone/Loop/DataThe Edco PC642 Series surge suppressor is a two-pair (four-wire) module

implementing three-stage hybrid technology. This module addresses

over-voltage transients with gas tubes and silicon avalanche components.

In addition, sneak and fault currents are mitigated with resettable fuses (PTCs).

The PTCs increase resistance by several orders of magnitude when over-currents

exceed safe levels. A normal state resumes when over-currents are removed.

The ability to self-restore in this manner significantly increases suppressor

performance and survivability.

The Edco PC642 Series card edge module is gold plated, double sided, and is

designed to mate with the Edco PCB1B gold-plated female terminal connector.

When snapped together, the data circuits “pass thru” the protector in a serial

fashion from the four “Field Side” terminals to the four “Electronics Side”

terminals. Terminals 1 or 10 of the Edco PCB1B must be attached to Building-

Approved Ground per Edco Technical Bulletin # 2015.

Features ■ Three-stage hybrid protection

■ Sneak/fault current protection

■ Resettable fusing — PTCs

■ Low capacitance option

■ Plug-in module

■ Fast response time

■ Requires Edco PCB1B base

■ Order PC642PTU — an invaluable troubleshooting tool

■ 5 year warranty

eDCO PCB1B BASe SOlD SePArATely

OPTiON:DiN rAil KiT AVAilABleOrDer PArT # 11604KiT-PC

general Technical SpecificationsMaximum Operating Voltage 5, 12, 18, 24, 30, 36, 43, 52, 180 VDC

Clamping Voltage 8, 15, 20, 30, 36, 43, 50, 60, 200* VDC

Operating Current 0.15A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology GDT, SAD, w/Series PTC

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2H x 1W x 2.5L (PC642 + PCB1B Base)

Weight 1 oz

Certification UL 497B

* PC642C-200 is not UL certified

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of continuously supplying more than 150 milliamperes.

Terminal Assignments

PCB1B:

Unprotected Pair 2

Unprotected Pair 1

Protected Pair 2

Protected Pair 1

Keying Pin

Even TerminalsOdd Terminals

Field SideElectronics Side

9

7

5

3

1

10

8

6

4

2

1.0

{ }

}{ 2.125" 2.4"

Ground Terminal 1 Or 10 To Building-Approved Ground

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Ordering information

PC642

PCB1B

APPliCATiON:

RS485, RS422: PC642C-008LC & PCB1B

RS423, Token Ring: PC642C-008LC & PCB1B

RS232: PC642C-020 & PCB1B

E-Net, 10 Base T: PC642C-030LC & PCB1B

4–20 ma: PC642C-036 & PCB1B

How To Specify The Appropriate model

-

Voltage Clamp

60 Volts50 Volts43 Volts36 Volts30 Volts

15 Volts8 Volts

2 0 0

PC642C

20 Volts

**200 Volts0 6 0 0 5 0 0 4 3

0 3 0 0 2 0

0 3 6

0 1 5 0 0 8

no suffixstage 2 clampeach line-to-groundstage 2 clampline-to-line only

stage 2 clamp line-to-lineand each line to ground

D

Xlow capacitance option stage2 clamp line-to-line and eachline to ground

**Not UL Listed

LC

Page 6: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

4

CCTV Systems

edco™ HSP Series120 VAC Heavy Duty 120 Volt ACThe Edco HSP Series is an advanced three-stage hybrid, solid state power-

line protector. Features such as noise filtering, common mode and normal

mode suppression, nanosecond reaction time, power line tracking, and

compression screw terminations make the Edco HSP Series an excellent

choice in commercial and industrial applications.

The Edco HSP Series offers a replaceable fuse designed to remove the load

(protected equipment) from the line if the unit is either overloaded or

the internal protection fails. This feature prevents surges from entering

equipment through a failed protector not noticed by the user.

Maximum Operating Voltage 120 VAC

Clamping Voltage 325 VAC

Operating Current 15A

I-Nominal (In) 3 kA

Total Peak Surge Current 39 kA (8 x 20 µs)

Operating Frequency 47–63 Hz

EMI Attenuation (100 kHz to 100 MHz) > 40 dB

SPD Technology Metal Oxide Varistors (MOVs) w/ L-C Filter

Modes Of Protection Line-to-Neutral, Line-to-Ground, Neutral-to-Ground

Status Indication Power On & MOVs functional

Connection Type 3 Position, 20A Terminal Block w/Compression Screws Terminals Accept Up To 14 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) HSP121BT-1RU 1.8H x 2.9W x 5.3L HSP-121A 2.95H x 4.95W x 3L

Weight 10 oz

Certifications HSP121BT-1RU ANSI/UL1449 Third Edition, Type 4 HSP121A ANSI/UL1449 Third Edition, Type 2

general Technical Specifications Dimensions

Features ■ Fast response time

■ Failure indicator

■ Power line tracking

■ Filtering

■ Polycarbonite NEMA 4X enclosure (HSP121A)

■ Three-stage hybrid design

■ Replaceable fuse

■ 1/2" or 3/4" knockouts for nipple conduit connectors (HSP121A)

■ 5 year warranty

GND

N

AC

GND

N

AC

3/4" Conduit Fitting 3/4" Conduit Fitting

1/2" Conduit Fitting 1/2" Conduit Fitting

Mounting – HSP121AHoles 3/16" Dia.

Mounting – HSP121BT-1RUHoles 3/16" Dia.

Light On – NormalLight Off – Requires Service

eDCO HSP121BT-1ru

eDCO HSP121A

Page 7: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

5

CCTV Systems

islatrol™ SP-6TVNPlug-in Surge Protection/Active Tracking™ FilterThe Islatrol SP-6TVN is an industrial-strength surge suppression/filtering device

that plugs into a standard duplex receptacle. It features uniquely designed

repositionable outlets and protects against damaging power disturbances

traveling through your wiring into your electrical outlets.

Features ■ Plugs into standard 120V, 15A

electrical outlet

■ Total peak surge current capacity of 39 kA

■ Cables for telephone, video, and data connectors included

■ Repositionable outlets rotate to accommodate available space

■ Perfect for tight spaces, behind furniture

and appliances

■ Intelligent monitoring against improper wiring/grounding

■ 60 dB maximum high frequency

■ Operational indicator lamp

■ 5 year warranty

general Technical Specifications

AC Power Protection

Nominal Operating Voltage 120 VAC, Single Phase

Operating Voltage Range 120 VAC +/- 10%

Operating Frequency Range 47–63 Hz

Rated Output 15A

ANSI/IEEE C62.41 Category Category A & B

Connection Type (6) 5-15R Receptacles and 5-15P Plug

Phase Configuration 2 Wire + Gnd

Size 7.5 x 4.75 x 1.75 (Inches)

Enclosure High Impact Plastic

Weight 2.0 lbs (0.9 kgs)

Modes Of Protection L – N, L – G, N – G

Indication of Suppression Status Status Indicator

Response Time < .5 ns Normal Mode

Certification ANSI/UL 1449 Third Edition Type 3

Warranty 5 Year

maximum Continuous Operating Voltage (mCOV)

Line To Neutral 130 VAC

Peak Surge Current (8 x 20 ms)

Line To Neutral 13 kA

Line To Ground 13 kA

Neutral To Ground 13 kA

Total 39 kA

ANSi/ieee C62.41 Cat A ringwave (6 kV, 200A, 100 kHz)

Normal Mode 265V

Common Mode 290V

ANSi/ieee C62.41 Cat B ringwave (6 kV, 500A, 100 kHz)

Normal Mode 275V

Common Mode 290V

Frequency response

Normal Mode 60 dB Maximum, Forward/Reverse, 100 kHz to 50 MHz

Common Mode 40 dB Maximum, Forward/Reverse, 5 MHz to 50 MHz

low Voltage Protection Video 1 & 2 Phone Network

Connection Type Type “F” Type RJ-11 Type RJ-45

Cables Provided 6 (2x) Type “F” RJ-11 Male RJ-45 Male 6' Ends 6' Ends Ends

Peak Surge Current 5 kA 2 kA 3 kA (8 x 20 µs) (10 x 1000 µs) (8 x 20 µs)

Capacitance <12 pf <50 pf <70 pf

Protection Level L-G T-R, T-G, R-G L-G (8 Lines)

Clamping Voltage (DC) 145 V 270-350 V 30 V

Attenuation 1 dB @ 2 Ghz N/A N/A

rePOSiTiONABle OuTleTS

Page 8: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

6

edco™ CX SeriesCCTV & Data Applications/CoaxThe Edco CX Series Surge Protective Devices (SPDs) implement three-stage

hybrid technology. The SPDs address over-voltage transients with a primary

Gas Discharge Tube (GDT), and secondary Silicon Avalanche Diode (SAD)

components. Over-current protection, e.g. sneak and fault currents, are

mitigated with solid-state resettable fuses —PTCs. The Edco CX Series SPDs

are designed in accordance with NFPA 780 (2004 edition) requirements,

with up to 20 kA of surge current capability. The Edco CX06-MI model has an

isolated ground and is recommended for use at the camera end.

Features ■ Sneak/fault current protection

■ Low insertion loss

■ Shielded case

■ CX06-MI has an isolated ground

■ 5 year warranty

general Technical SpecificationsMaximum Operating Voltage 5 VDC

Clamping Voltage 6 VDC

Operating Current 0.17A

Peak Surge Current 20 kA (8 x 20 µs)

Frequency Range 0 to 20 MHz

Insertion Loss < 1 dB at 20 MHz

SPD Technology GDT, SAD, w/Series PTC

Connection Type BNC, 50/75 Ohms

Operating Temperature -40°C to +85°C

Dimensions (Inches) M = 1.5H x 1W x 3.25L MI = 1.5H x 1W x 4L SBL = 1.7H x 1.4W x 2.8L

Weight M = 2.3 oz MI = 3 oz

Certification UL 497B

Head End CX06-M

Camera End CX06-MI CX06-MI-SBL

• Other configurations available — please consult factory

Ordering information

CCTV Systems

OPTiON:DiN rAil KiT AVAilABleOrDer PArT # 11604KiT-CX

CX06-mi-SBl installation

Page 9: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ FAS-1 and FAS-2 SeriesOne- and Two-Pair Signal Line Protection

The Edco FAS-1 and Edco FAS-2 Series are multi-stage one-pair or two-pair surge

suppressors designed for high-exposure applications. These products were

specifically designed to meet multiple, low voltage, protection applications in the

fire and security industries.

Features ■ Lightning protection for low voltage

■ Data/signal lines

■ Multi stage protection

■ Common mode and differential protection mode

■ Automatic recovery

■ 5 year warranty

Maximum Operating Voltage 15, 24, 36, 52 VDC

Clamping Voltage 18, 33, 43, 60 VDC

Operating Current 2.5A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 10 MHz

Insertion Loss < 0.1 dB at 10 MHz

SPD Technology GDT, SAD, w/Series Inductor

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 12 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) FAS-1 = 1.5H x 1.5W x 2.8L FAS-2 = 2H x 2W x 2.8L

Weight FAS-1 = 3.5 oz FAS-2 = 7 oz

Certification UL 497B

FAS-1-018 HC (One-pair) 12 VDC Use FAS-2-018 HC (Two-pair)

FAS-1-033 HC (One-pair) 24 VDC Use FAS-2-033 HC (Two-pair)

FAS-1-043 HC (One-pair) 24 VAC Use FAS-2-043 HC (Two-pair)

FAS-1-060 HC (One-pair)* 48V Systems Use FAS-2-060 HC (Two-pair)*

*Not UL listed

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of continuously supplying more than 2.5 amperes.

general Technical Specifications Ordering informationinstallationUnprotected Or Field Side

Protected Equipment

Ground Lug

Equi

p. Line

10–14 AWG

Features ■ Automatic recovery

■ Low insertion loss

■ Easily installed

■ Shielded case

■ Miniature size

■ 5 year warranty

Maximum Operating Voltage 5 VDC

Clamping Voltage 90 VDC (Spark Over Voltage)

Operating Current 1A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 1 GHz

Insertion Loss < 0.5 dB at 500 MHz <1.0 dB at 900 MHz

SPD Technology Gas Discharge Tube (GDT)

Connection Type BNC, 75 Ohm

Operating Temperature -40°C to +85°C

Dimensions (Inches) 0.6H x 0.6W x 2.0L

Weight 1 oz

general Technical Specifications

7

edco™ CCTV-1 Closed Circuit TV ProtectionThe Edco CCTV-1 application is specifically designed for lightning protection on

closed circuit TV systems. The protector is easily installed with standard type BNC

coax connectors. The Edco CCTV-1 offers low loss, even at frequencies approaching

500 Mhz. This is important for error-free data communication applications.

CCTV Systems

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Page 10: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

8

CCTV Systems

edco™ PHC SeriesTwo-Pair Signaling Circuit Protector (modular)The Edco PHC Series is designed to protect two pairs of wires specifically

for alarm and security systems where operating currents can be as high

as 5 amps. Electrically, the Edco PHC Series is a rugged series hybrid

implementing a staged complement of MOVs, copper wound inductors and

Silicon Avalanche Diodes. This design reduces series resistance to 0.2 Ohms

per pair. These products are intended to mate with an Edco PCB1B

gold-plated female terminal connector.

The Edco PHC modules plug into a base assembly (Edco PCB1B). The base

assembly can be mounted to any flat surface and should be located as close

as practical to the protected equipment. Terminal 1 and/or terminal 10

should be connected to Building-Approved Ground with 12- or 10-gauge

solid wire.

general Technical Specifications Ordering information How To Specify The Appropriate model

Features ■ Three-stage protection

■ Differential protection

■ Common mode protection

■ Plug-in module

■ Automatic recovery

■ Fast response time

■ Continuous current up to 5 Amps

■ UL 497B listed

■ Requires Edco PCB1B base

■ Order PC642PTU — an invaluable troubleshooting tool

■ 5 year warranty

Maximum Operating Voltage 12, 18, 24, 36, 52, 70, 120 VDC

Clamping Voltage 15, 20, 30, 43, 60, 100, 150 VDC

Operating Current 5A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 10 MHz

Insertion Loss < 0.1 dB at 10 MHz

SPD Technology MOV, SAD, w/Series Inductor

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 3.7H x 1.75W x 2.375L (PHC + PCB1B Base)

Weight 8 oz

Certification UL 497B

24V Horn, Strobe, Bell PHC-043 & PCB1B

70V Speaker Lines PHC-SP70 & PCB1B

eDCO PCB1B BASe SOlD SePArATely

PCB1B:

Unprotected Pair 2

Unprotected Pair 1

Protected Pair 2

Protected Pair 1

Keying Pin

Even TerminalsOdd Terminals

Field SideElectronics Side

9

7

5

3

1

10

8

6

4

2

1.0

{ }

}{ 2.125" 2.4"

Ground Terminal 1 Or 10 To Building-Approved Ground

Terminal Assignments

Voltage Clamp

* Not UL listed

Applications Part Number

Dimensions

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

eDCO PCB1B BASe SOlD SePArATely

Page 11: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Maximum Operating Voltage 5 VDC

Clamping Voltage 6 VDC

Operating Current 0.15A

Peak Surge Current 20 kA (8 x 20 µs)

Frequency Range 0 to 100 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology GDT, SAD, w/Series PTC

Connection Type BNC, 50/75 Ohm

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.75H x 19W x 2.0D (1U)

Weight 3.2 lbs

Certification UL 497B

edco™ rm-CX06-16r Channel RackmountThe Edco RM-CX06-16R Surge Protective Device (SPD) is a 16 channel coax SPD

implementing three-stage hybrid technology. The SPD addresses over-voltage

transients with a primary Gas Discharge Tube (GDT), and secondary Silicon

Avalanche Diode (SAD) components. Over-current protection, e.g., sneak and

fault currents, are mitigated with new solid-state resettable fuses — PTCs. The

Edco RM-CX06-16R SPD is designed in accordance with NFPA 780 (2004 edition)

requirements, with up to 20 kA of surge current capability.

general Technical Specifications

Features ■ Sneak/fault current protection

■ Low insertion loss

■ Shielded case

■ 16 channel

■ 1 year warranty

9

edco™ CAT6-5POe Series CAT6/CAT5 Power Over EthernetThe Edco CAT6-5POE Series is designed to work on Category 5 Power-Over-

Ethernet transmission lines as well as Category 6 applications. Ideal to protect

expensive equipment against surges and transients entering a building on

exposed transmission lines. Available in both female to female and male to

female RJ-45 connectors.

Features ■ Exceeds CAT5 & 6 transmission values

■ CAT5 POE compatible

■ CAT6 compatible

■ Applications up to 60 VDC @ 300 mA

■ 1 year warranty

Maximum Operating Voltage 60 VDC

Clamping Voltage 65 VDC

Operating Current 300 mA

Peak Surge Current 60A (10 x 1000 µs)

Frequency Range 0 to 250 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode (SAD)

Connection Type RJ-45 Jacks

Operating Temperature -40°C to +85°C

Dimensions (Inches) 0.8H x 1.0W x 2.3L (FF) 0.8H x 1.0W x 3.0L (MF)

Weight 1 oz

RJ-45 (Female-Female) CAT6-5POE-FF

RJ-45 (Male-Female) CAT6-5POE-MF

general Technical Specifications

CCTV Systems

Page 12: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Fire AlarmPanel

(24 VDC Typical)

AC Power

SLC Loop — Penetrating Exterior

RS-485 Network — Exterior

Post Indicator Valve Circuit — Exterior

Notification Appliance Circuit — Exterior

Printer Circuit To Guard House

LegendSP 1 .... FAS-120ACSP 2 .... HSP-121BT1RUSP 3 .... PC2-TEL*SP 4 .... SLCP-43*SP 5 .... PC642C-008LC*

SP 6 .... FAS-1-033HCSP 7 .... PHC-043*SP 8 .... PC642C-020*SP 9 .... EMC-240BSP 3

(Over 1000 feet need protection at wall penetration point)

SP 4

SP 5

SP 6

SP 7

SP 8(RS-232 Typical)

SP 8

SP 7

SP 5

SP 4

*Needs PCB1B Base

TelephoneLine

SP 6

SP 1or

SP 2or

SP 9

10

Fire Alarm

Protecting Fire Alarm Systems Application Drawing

Page 13: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

11

edco™ PC642 Series Zone/Loop/DataThe Edco PC642 Series surge suppressor is a two-pair (four-wire) module

implementing three-stage hybrid technology. This module addresses

over-voltage transients with gas tubes and silicon avalanche components.

In addition, sneak and fault currents are mitigated with resettable fuses

(PTCs). The PTCs increase resistance by several orders of magnitude when

over-currents exceed safe levels. A normal state resumes when over-currents

are removed. The ability to self-restore in this manner significantly increases

suppressor performance and survivability.

The Edco PC642 card edge module is gold plated, double sided, and

is designed to mate with the Edco PCB1B gold-plated female terminal

connector. When snapped together, the data circuits “pass thru” the protector

in a serial fashion from the four “Field Side” terminals to the four “Electronics

Side” terminals. Terminals 1 or 10 of the Edco PCB1B must be attached to

Building-Approved Ground per Edco Technical Bulletin # 2015.

Features ■ Three-stage hybrid protection

■ Sneak/fault current protection

■ Resettable fusing — PTCs

■ Low capacitance option

■ Plug-in module

■ Fast response time

■ Requires Edco PCB1B base

■ Order PC642PTU — an invaluable troubleshooting tool

■ 5 year warranty

eDCO PCB1B BASe SOlD SePArATely

general Technical SpecificationsMaximum Operating Voltage 5, 12, 18, 24, 30, 36, 43, 52, 180 VDC

Clamping Voltage 8, 15, 20, 30, 36, 43, 50, 60, 200* VDC

Operating Current 0.15A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology GDT, SAD, w/Series PTC

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2H x 1W x 2.5L (PC642 + PCB1B Base)

Weight 1 oz

Certification UL 497B

* PC642C-200 is not UL certified

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of continuously supplying more than 150 milliamperes.

Terminal Assignments

Ground Terminal 1 Or 10 To Building-Approved Ground

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Ordering information

APPliCATiON:

RS485, RS422: PC642C-008LC & PCB1B

RS423, Token Ring: PC642C-008LC & PCB1B

RS232: PC642C-020 & PCB1B

E-Net, 10 Base T: PC642C-030LC & PCB1B

4–20 ma: PC642C-036 & PCB1B

How To Specify The Appropriate model

**200 Volts**Not UL Listed

Voltage Clamp

Fire Alarm

OPTiONDiN rAil KiT AVAilABleOrDer PArT # 11604KiT-PC

Page 14: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Features ■ Compatible with SLC circuits

■ Line-to-ground protection

■ State-of-the-art silicon technology

■ Over-current protection

■ 497B UL listed

■ Requires Edco PCB1B base

■ PC642PTU (Pass Thru Unit) available for troubleshooting

■ 5 year warranty

edco™ SlCP Series Two-Pair SLC Loop Protector (Modular)The Edco SLCP Series are four-wire modules designed to protect signaling

line circuits (SLC). The device has 0 ohms of resistance and offers line-to-

ground protection.

eDCO PCB1B BASe SOlD SePArATely

Maximum Operating Voltage 5, 12, 18, 24, 32, 36, 48, & 52 VDC

Clamping Voltage 8, 15, 20, 30, 36, 43, 50, & 60 VDC

Operating Current 1A

Peak Surge Current 250A (8 x 20 µs)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode (SAD)

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2H x 1W x 2.5L (SLCP + PCB1B Base)

Weight 1 oz

Certification UL 497B

general Technical Specifications Ordering information

edco™ PC2-Tel Two-Line Telephone Protection (Modular)The Edco PC2-TEL is a solid state, two-line telephone interface protector

module. This unit is specifically designed to protect both phone lines

required by commercial fire panels.

Features ■ Tip-to-ring protection

■ Tip- and ring-to-ground protection

■ Over-current protection

■ Resettable solid state fuses — PTC

■ UL listed 497A

■ Requires PCB1B base

■ PC642PTU (Pass Thru Unit) available for trouble shooting

■ 5 year warranty

Maximum Operating Voltage 250 VDC

Clamping Voltage 270 VDC

Operating Current 0.15A

Peak Surge Current 160A (10 x 1000 T & R To Ground)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Series PTC and Silicon Avalanche Diode (SAD)

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2H x 1W x 2.5L (PC2TEL + PCB1B Base)

Weight 1 oz

Certifications UL 497A, CUL

eDCO PCB1B BASe SOlD SePArATely

general Technical Specifications

12

Fire Alarm

0 0 8

0 1 5

0 2 0

0 3 0

0 3 6

0 4 3

0 5 0

0 6 0

8 Volts

15 Volts

20 Volts

30 Volts

36 Volts

43 Volts

50 Volts

60 Volts

S L C P

ClampingVoltage

Page 15: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ PHC Series Two-Pair Signaling Circuit Protector (Modular)The Edco PHC Series is designed to protect two pairs of wires specifically

for alarm and security systems where operating currents can be as high

as 5 amps. Electrically, the Edco PHC Series is a rugged series hybrid

implementing a staged complement of MOVs, copper wound inductors and

Silicon Avalanche Diodes. This design reduces series resistance to 0.2 Ohms

per pair. These products are intended to mate with an Edco PCB1B

gold-plated female terminal connector.

The Edco PHC modules plug into a base assembly (Edco PCB1B). The base

assembly can be mounted to any flat surface and should be located as close

as practical to the protected equipment. Terminal 1 and/or terminal 10

should be connected to Building-Approved Ground with 12- or 10-gauge

solid wire.

general Technical Specifications Ordering information

Features ■ Three-stage protection

■ Differential protection

■ Common mode protection

■ Plug-in module

■ Automatic recovery

■ Fast response time

■ Continuous current up to 5 Amps

■ UL 497B listed

■ Requires Edco PCB1B base

■ Order PC642PTU — an invaluable troubleshooting tool

■ 5 year warranty

Maximum Operating Voltage 12, 18, 24, 36, 52, 70, 120 VDC

Clamping Voltage 15, 20, 30, 43, 60, 100, 150 VDC

Operating Current 5A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 10 MHz

Insertion Loss < 0.1 dB at 10 MHz

SPD Technology MOV, SAD, w/Series Inductor

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 3.7H x 1.75W x 2.375L (PHC + PCB1B Base)

Weight 8 oz

Certification UL 497B

24V Horn, Strobe, Bell PHC-043 & PCB1B

70V Speaker Lines PHC-SP70 & PCB1B

eDCO PCB1B BASe SOlD SePArATely

PCB1B:

Unprotected Pair 2

Unprotected Pair 1

Protected Pair 2

Protected Pair 1

Keying Pin

Even TerminalsOdd Terminals

Field SideElectronics Side

9

7

5

3

1

10

8

6

4

2

1.0

{ }

}{ 2.125" 2.4"

Ground Terminal 1 Or 10 To Building-Approved Ground

Terminal Assignments

0 1 5

0 2 0

0 3 0

0 4 3

0 6 0

S P 7 0

1 3 0 R M S

15 Volts

20 Volts

30 Volts

43 Volts

60 Volts

*100 Volts

*150 Volts

*Not UL Listed

(For Horn, Bell, Strobes)

(For 120V Signal Lines)

Voltage ClampP H C

Applications Part Number

Dimensions

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

How To Specify The Appropriate model

13

Fire Alarm

Page 16: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Maximum Operating Voltage 120 VAC

Clamping Voltage 325 VAC

Operating Current 15A

I-Nominal (In) 3 kA

Total Peak Surge Current 39 kA (8 x 20 µs)

Operating Frequency 47–63 Hz

EMI Attenuation (100 kHz to 100 MHz) > 40 dB

SPD Technology Metal Oxide Varistors (MOVs) w/ L-C Filter

Modes Of Protection Line-to-Neutral, Line-to-Ground, Neutral-to-Ground

Status Indication Power On & MOVs functional

Connection Type 3 Position, 20A Terminal Block w/Compression Screws Terminals Accept Up To 14 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) HSP121BT-1RU 1.8H x 2.9W x 5.3L HSP-121A 2.95H x 4.95W x 3L

Weight 10 oz

Certifications HSP121BT-1RU ANSI/UL1449 Third Edition, Type 4 HSP121A ANSI/UL1449 Third Edition, Type 2

general Technical Specifications Dimensions

Fire Alarm

14

edco™ HSP Series120 VAC Heavy Duty 120 Volt ACThe Edco HSP Series is an advanced three-stage hybrid, solid state power-

line protector. Features such as noise filtering, common mode and normal

mode suppression, nanosecond reaction time, power line tracking, and

compression screw terminations make the Edco HSP Series an excellent

choice in commercial and industrial applications.

The Edco HSP Series offers a replaceable fuse designed to remove the load

(protected equipment) from the line if the unit is either overloaded or

the internal protection fails. This feature prevents surges from entering

equipment through a failed protector not noticed by the user.

Features ■ Fast response time

■ Failure indicator

■ Power line tracking

■ Filtering

■ Polycarbonite NEMA 4X enclosure (HSP121A)

■ Three-stage hybrid design

■ Replaceable fuse

■ 1/2" or 3/4" knockouts for nipple conduit connectors (HSP121A)

■ 5 year warranty

GND

N

AC

GND

N

AC

3/4" Conduit Fitting 3/4" Conduit Fitting

1/2" Conduit Fitting 1/2" Conduit Fitting

Mounting – HSP121AHoles 3/16" Dia.

eDCO HSP121BT-1ru

eDCO HSP121A

Mounting – HSP121BT-1RUHoles 3/16" Dia.

Light On – NormalLight Off – Requires Service

Page 17: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

PowerSure™ emC-240B120/240 VAC Heavy Duty (Parallel)The PowerSure EMC-240B surge suppressor is designed to protect AC

distribution panel circuits or 120V power supplies feeding sensitive

electronic equipment. Electrically, the unit incorporates MOV and thermal

fusing technology. The PowerSure EMC-240B is designed to be installed in

parallel on standard single phase 120/240 VAC (3W + G) or single phase

120 VAC (2W + G) circuits.

Features ■ Fast response time

■ 40 kA per phase capacity

■ Failsafe and fused

■ Operational status indicators

■ ANSI/UL 1449 Third Edition Type 2

■ 5 year warranty

general Technical SpecificationsMaximum Operating Voltage 120/240 VAC

I Nominal (In) 3 kA

Operating Current NA, Parallel

Total Peak Surge Current 80 kA (8 x 20 µs)

Operating Frequency 47–63 Hz

EMI Attenuation (100 kHz to 100 MHz) > 40 dB

SPD Technology Metal Oxide Varistors (MOVs)

Modes Of Protection Line-to-Line Line-to-Neutral

Status Indication Power On & MOVs Functional

Connection Type Wire Leads

Operating Temperature -40°C to +85°C

Dimensions (Inches) 4.6H x 2.2W x 2.8L

Weight 13.5 oz

Certification ANSI/UL 1449 Third Edition, Type 2

Fire Alarm

15

installation

L

N120 V

Ground

EMC-240B

BlackBlackWhiteGreen

N L

EMC-240B

BlackBlackWhiteGreen

120 V

120 V

Ground

L1

240 V

L2

N

L2 N L1

4.5

2.8 2.2

18

120 VAC Service 120/240 VAC Service

EMC-240B

BlackBlackWhiteGreen

240 V

240 V

L1

240 V

L2

GND

L2 GND L1

240 V AC Service

Caution:Installation and service should be performed by qualified electricians only.

Before installing EMC, remove all electrical power from circuits.

Connect on load side of main breakers. Use two dedicated 30A circuit breakers.

mechanical

2.8" 2.2"

4.5"

18"

Page 18: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ FAS-1 and FAS-2 SeriesOne- and Two-Pair Signal Line Protection

The Edco FAS-1 and Edco FAS-2 Series are multi stage one-pair or two-pair surge

suppressors designed for high exposure applications. These products were

specifically designed to meet multiple low voltage protection applications in the

fire and security industries.

Features ■ Lightning protection for low voltage

■ Data/signal lines

■ Multi stage protection

■ Common mode and differential protection mode

■ Automatic recovery

■ 5 year warranty

Maximum Operating Voltage 15, 24, 36, 52 VDC

Clamping Voltage 18, 33, 43, 60 VDC

Operating Current 2.5A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 10 MHz

Insertion Loss < 0.1 dB at 10 MHz

SPD Technology GDT, SAD, w/Series Inductor

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 12 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) FAS-1 = 1.5H x 1.5W x 2.8L FAS-2 = 2H x 2W x 2.8L

Weight FAS-1 = 3.5 oz FAS-2 = 7 oz

Certification UL 497B

FAS-1-018 HC (One-pair) 12VDC Use FAS-2-018 HC (Two-pair)

FAS-1-033 HC (One-pair) 24VDC Use FAS-2-033 HC (Two-pair)

FAS-1-043 HC (One-pair) 24VAC Use FAS-2-043 HC (Two-pair)

FAS-1-060 HC (One-pair)* 48V Systems Use FAS-2-060 HC (Two-pair)*

* Not UL listed

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of continuously supplying more than 2.5 amperes.

general Technical Specifications Ordering informationinstallation

< 3

Unprotected Or Field Side

Protected Equipment

Ground Lug

10–14 AWG

Equi

p. Line

16

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Fire Alarm

Page 19: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Fire Alarm

17

Features ■ LED indicator

■ Fast response time

■ Thermal fuse

■ L-G, L-N, & N-G protection

■ Compact size

■ Liquid tight conduit fitting

■ ANSI/UL 1449 Third Edition Type 2

■ 5 year warranty

PowerSure™ FAS-120ACMedium Duty 120 VAC — Single PhaseThe PowerSure FAS-120AC surge suppressor is designed to protect AC distribution

panel circuits or 120V power supplies feeding sensitive electronic equipment.

Electrically the unit incorporates MOV and thermal fusing technology. This device is

designed to be installed in parallel on standard single phase 120 VAC

(L, N, G) circuits.

Installation can be close-nipple up to a distribution panel/circuit or hardwired in

parallel up to power supply input terminal screws. Be sure to dress leads as short

as possible.

general Technical Specifications

Part Number PowerSure FAS-120AC

Maximum Operating Voltage 120 VAC

SPD Location Type Type 2

I-Nominal (In) 3 kA

Operating Current NA

Peak Surge Current 6.5 kA/Mode, 13 kA/Phase, 15.5 kA/Total

Operating Frequency 47–63 Hz

EMI Attenuation NA

SPD Technology MOVs

Modes of Protection L-N, L-G, N-G

Status Indication Power On & MOVs Functional

Connection Type Wire Leads

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2.5H x 1.5W x 3.0L

Weight 4 oz

Certification ANSI/UL 1449 Third Edition, Type 2

mounting

1.5"

Ø0.1860

2.5"

3"

Caution:This product should be installed and serviced by qualified service technicians or personnel only.

Remove power before installation or service.

Page 20: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

18

Burglar 12VDC

Protecting Burglar Alarm Systems Application Drawings

Commercial

residential

Page 21: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ FAS-1 and FAS-2 SeriesOne- and Two-Pair Signal Line Protection

The Edco FAS-1 and Edco FAS-2 Series are multi stage one-pair or two-pair surge

suppressors designed for high-exposure applications. These products were

specifically designed to meet multiple, low voltage, protection applications in the

fire and security industries.

Features ■ Lightning protection for low voltage

■ Data/signal lines

■ Multi stage protection

■ Common mode and differential protection mode

■ Automatic recovery

■ 5 year warranty

Maximum Operating Voltage 15, 24, 36, 52 VDC

Clamping Voltage 18, 33, 43, 60 VDC

Operating Current 2.5A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 10 MHz

Insertion Loss < 0.1 dB at 10 MHz

SPD Technology GDT, SAD, w/Series Inductor

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 12 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) FAS-1 = 1.5H x 1.5W x 2.8L FAS-2 = 2H x 2W x 2.8L

Weight FAS-1 = 3.5 oz FAS-2 = 7 oz

Certification UL 497B

FAS-1-018 HC (One-pair) 12VDC Use FAS-2-018 HC (Two-pair)

FAS-1-033 HC (One-pair) 24VDC Use FAS-2-033 HC (Two-pair)

FAS-1-043 HC (One-pair) 24VAC Use FAS-2-043 HC (Two-pair)

FAS-1-060 HC (One-pair)* 48V Systems Use FAS-2-060 HC (Two-pair)*

*Not UL listed

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of continuously supplying more than 2.5 amperes.

general Technical Specifications Ordering informationinstallation

< 3

Unprotected Or Field Side

Protected Equipment

Ground Lug

10–14 AWG

Equi

p. Line

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

19

Burglar 12VDC

Page 22: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Burglar 12VDC

20

islatrol™ SP-6TVNPlug-in Surge Protection (Active Tracking™ Filter)The Islatrol SP-6TVN is an industrial-strength surge suppression/filtering device

that plugs into a standard duplex receptacle. It features uniquely designed

repositionable outlets and protects against damaging power disturbances

traveling through your wiring into your electrical outlets.

Features ■ Plugs into standard 120V, 15A

electrical outlet

■ Total peak surge current capacity of 39 kA

■ Cables for telephone, video, and data connectors included

■ Repositionable outlets rotate to accommodate available space

■ Perfect for tight spaces, behind furniture

and appliances

■ Intelligent monitoring against improper wiring/grounding

■ 60 dB maximum high frequency

■ Operational indicator lamp

■ 5 year warranty

general Technical Specifications

AC Power Protection

Nominal Operating Voltage 120 VAC, Single Phase

Operating Voltage Range 120 VAC +/- 10%

Operating Frequency Range 47–63 Hz

Rated Output 15A

ANSI/IEEE C62.41 Category Category A & B

Connection Type (6) 5-15R Receptacles and 5-15P Plug

Phase Configuration 2 Wire + Gnd

Size 7.5 x 4.75 x 1.75 (Inches)

Enclosure High Impact Plastic

Weight 2.0 lbs (0.9 kgs)

Modes Of Protection L – N, L – G, N – G

Indication Of Suppression Status Status Indicator

Response Time < .5 ns Normal Mode

Certification ANSI/UL 1449 Third Edition Type 3

maximum Continuous Operating Voltage (mCOV)

Line To Neutral 130 VAC

Peak Surge Current (8 x 20 ms)

Line To Neutral 13 kA

Line To Ground 13 kA

Neutral To Ground 13 kA

Total 39 kA

ANSi/ieee C62.41 Cat A ringwave (6 kV, 200A, 100 kHz)

Normal Mode 265V

Common Mode 290V

ANSi/ieee C62.41 Cat B ringwave (6 kV, 500A, 100 kHz)

Normal Mode 275V

Common Mode 290V

Frequency response

Normal Mode 60 dB Maximum, Forward/Reverse, 100 kHz to 50 MHz

Common Mode 40 dB Maximum, Forward/Reverse, 5 MHz to 50 MHz

low Voltage Protection Video 1 & 2 Phone Network

Connection Type Type “F” Type RJ-11 Type RJ-45

Cables Provided 6 (2x) Type “F” RJ-11 Male RJ-45 Male 6' Ends 6' Ends Ends

Peak Surge Current 5 kA 2 kA 3 kA (8 x 20 µs) (10 x 1000 µs) (8 x 20 µs)

Capacitance <12 pf <50 pf <70 pf

Protection Level L-G T-R, T-G, R-G L-G (8 Lines)

Clamping Voltage (DC) 145 V 270–350 V 30 V

Attenuation 1 dB @ 2 Ghz N/A N/A

rePOSiTiONABle OuTleTS

Page 23: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Maximum Operating Voltage 12, 24, 43, 52, 180, 220, & 220 VDC

Clamping Voltage 15, 30, 50, 60, 200, 270 & 300 VDC

Operating Current 0.15A

Peak Surge Current 160A (10 x 1000 µs T & R to Ground)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode w/ Series PTC

Connection Type Terminal Block w/Compression Lugs In/ RJ Connector Out

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1H x 2W x 2L

Weight 2 oz

Certifications UL 497A, CUL

Ordering informationFAS-TEL-060T Digital Phone

FAS-TEL-200T Analog Phone/Fax/Modem

FAS-31XT Alarm System Phone

FAS-TEL-DSL DSL

Features ■ <1 nanosecond response time

■ Solid-state silicon breakover technology

■ Low capacitance

■ Over current protection

■ UL 497A listed

■ Line-to-line protection

■ Line-to-ground protection

■ Polyswitch resettable fuses — PTCs

■ 5 year warranty

edco™ FAS-Tel and FAS-31XTRJ11/RJ31X Telephone Protection

The Edco FAS-TEL and Edco FAS-31XT are single-pair telephone or data line

protectors that implement advanced two-stage hybrid design. These units

address over-voltage transients with silicon breakover devices, while sneak and

fault currents are mitigated with PTC technology which consists of solid state

resettable fuses.

The Edco FAS-31XT replaces the RJ31X jack with a protected version. Four screw

terminals are provided to wire the protector in the same manner as a standard

RJ31X jack.

The Edco FAS-TEL is nearly identical to the Edco FAS-31XT except with out the

shorting bars. Two screw terminals are provided to connect the incoming

telephone line to the protector. Protected equipment such as modems are

plugged into the female modular jack on the Edco FAS-TEL.

general Technical Specifications

21

Burglar 12VDC

270 Volts

300 Volts

0 1 5

0 3 0

0 5 0

0 6 0

2 0 0

15 Volts

30 Volts

50 Volts

60 Volts

200 Volts

ClampingVoltage F A S - T E L - T

F A S - T E L - D S L

F A S - 3 1 X T

How To Specify The Appropriate model

Page 24: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Burglar 12VDC

22

general Technical Specifications

edco™ Ter SeriesSingle-Pair Medium Duty Low Voltage Zone/Horn/Strobe/DataThe Edco TER surge suppressor directly installs onto electronic circuit wiring

terminal screws. This close proximity preserves Edco TER’s response time,

clamping level and ground reference by elimi nating lead lengths. The Edco

TER’s miniature size fits directly inside fire or security panels, CCTV housings

and other system electronic enclosures. These features maximize surge

suppression performance while reducing hardware and labor costs to install.

Features ■ Fits Euro style and barrier strip terminals

■ Automatic recovery

■ Single-pair protection

■ High energy silicon avalanche technology

■ UL 497B listed

■ Operating current > 2 Amps

■ Compact size: 1.3" x 0.4" x 2" (HxWxL)

■ 5 year warranty

Maximum Operating Voltage 15, 30, 40 VDC

Clamping Voltage 18, 33, 43 VDC

Operating Current 0.09A

Peak Surge Current (10 x 1000 µs) 018 = 215A, 033 = 108A, 043 = 81A

Frequency Range 0 to 20 MHz

Insertion Loss <0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode (SAD)

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 12 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.3H x 0.4W x 2.0L

Weight 0.6 oz

Certification UL 497B

Fits in Series With Circuits Wires At The Terminal Screws

Zone, Buss, Loop, Data, Receive, Bell, Horn, Strobe, Pan/Tilt & CCTV

TER-018 (For 12 VDC Systems)

TER-033 (For 24 VDC Systems)

TER-043 (For 24 VDC Systems)

general Technical Specifications Ordering information

edco™ PC2-Tel Two-Line Telephone Protection (Modular)The Edco PC2-TEL is a solid state, two-line telephone interface protector

module. This unit is specifically designed to protect both phone lines required by

commercial security panels.

Features ■ Tip-to-ring protection

■ Tip- and ring-to-ground protection

■ Over-current protection

■ Resettable solid state fuses — PTCs

■ UL listed 497A

■ Requires PCB1B base

■ PC642PTU (Pass Thru Unit) available for troubleshooting

■ 5 year warrantyeDCO PCB1B BASe SOlD SePArATely

Maximum Operating Voltage 250 VDC

Clamping Voltage 270 VDC

Operating Current 0.15A

Peak Surge Current 160A (10 x 1000 T & R To Ground)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Series PTC and Silicon Avalanche Diode (SAD)

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2H x 1W x 2.5L (PC2TEL + PCB1B Base)

Weight 1 oz

Certifications UL 497A, CUL

Page 25: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Protecting Access Control Systems Application Drawing

AccessControl

Panel

RS-485/RS-422 Circuit

Electric Strike orMaglock Circuit

Card Reader (Wiegand)

Circuit for Device Outside of Building

Door LockPower Supply

Dial-UpCom

LAN/WAN

AC PowerGate Position Switch

Gate Lock/Control

To Head-End or Other

Control Panels

SP 1

SP 8

SP 7

SP 1 SP 5 SP 6

SP 2

SP 3

SP 4

SP 5

SP 3

SP 4

SP 2

SP 1 .... HSP-121BT1RUSP 2 .... PC642C-008LC*SP 3 .... EL-EDSSP 4 .... 5W8-30*SP 5 .... FAS-1-xxxHCSP 6 .... FAS-2-xxxHCSP 7 .... LCDP-xxxSP 8 .... FAS-31XT

*Needs PCB1B Base

Legend

Access Control

23

Page 26: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

24

Access Control

The diagram below illustrates the proper installation of the Edco EL-EDS. For each maglock or electric strike circuit, you will need to install a suppressor (1) across the relay contacts and (2) across the leads connected to the lock solenoid (locate as close as possible to the solenoid). The suppressor wires can be installed without regard to polarity. If your package does not contain two (2) devices, contact your distributor.

installation

edco™ el-eDSElectric Door Suppressor The Edco EL-EDS suppressor kit is intended for installation with electrical

switching devices that are connected through a relay contact on typical access

control panels.

The Edco EL-EDS protects against electrical anomalies (transients) that are

generated as a result of the collapsing electrical field of an electromagnetic

switching device (maglock or electric strike). The Edco EL-EDS provides

protection for both relay contacts and control panel.

Maximum Operating Voltage 52 VDC

Clamping Voltage 56 VDC

Operating Current NA

Peak Surge Current 500 A

Frequency Range 0 to 20 MHz

Insertion Loss <0.1 dB at 20 MHz

SPD Technology SAD w/Filtering Capacitor

Connection Type Wire Leads

Operating Temperature -40˚C 10 +85˚C

Dimensions (Inches) 8 L

Weight 1 oz

Warranty 5 years

general Technical Specifications

Features ■ <1 Electromagnetic protection

■ 2 devices per package

■ Relay contact and control panel protection

■ 5 year warranty

Page 27: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ 5W8-30 Two-Pair Data/Signal Line Power The Edco 5W8-30 is an access control protection module designed for

typical Wiegand outputs for access devices. This is a 5-wire module that

accommodates low voltage data lines for 5 VDC circuits. Fifth wire power

protection will allow up to 24 VDC.

In addition, sneak and fault currents are mitigated with resettable fuses

(PTCs). The PTCs increase resistance several orders of magnitude when over-

currents exceed safe levels. A normal state resumes when over-currents are

removed. The ability to self restore in this manner significantly increases

suppressor performance and survivability.

Features ■ Automatic recovery

■ Fast response time

■ Resettable fusing — PTCs

■ Plug-in module

■ Data and power protection combined

■ Sneak/fault current protection (data only)

■ Silicon avalanche technology

■ Requires Edco PCB1B base

■ PC462 PTU (Pass Thru Unit) available for troubleshooting

■ 5 year warranty

Maximum Operating Voltage 5 VDC (Data) & 24 VDC (Power)

Clamping Voltage 8 VDC (Data) & 30 VDC (Power)

Operating Current 0.15A

Peak Surge Current Data = 125A (10 x 1000 µs) Power = 500 A (8 x 20 µs)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.15dB at 20 MHz

SPD Technology MOV, SAD, w/ Series PTC

Connection Type Terminal Block w/compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2H x 1W x 2.5L (5W8-30 + PCB1B Base)

Weight 1 oz

general Technical Specifications installation

eDCO PCB1B BASe SOlD SePArATely

Note: The hybrid design of this product includes series resistance. Do not use this device if data pairs are capable of continuously supplying more than 150 milliamperes.

Ground Terminal To Building-Approved Ground (Preferably AC Power Safety Ground)

DC Power — T-Tap PositiveCommon Wire Here

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

25

Access Control

Page 28: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

26

Access Control

Maximum Operating Voltage 12, 24, 43, 52, 180, 220, & 220 VDC

Clamping Voltage 15, 30, 50, 60, 200, 270 & 300 VDC

Operating Current 0.15A

Peak Surge Current 160A (10 x 1000 µs T & R to Ground)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode w/ Series PTC

Connection Type Terminal Block w/Compression Lugs In/ RJ Connector Out

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1H x 2W x 2L

Weight 2 oz

Certifications UL 497A, CUL

Ordering informationFAS-TEL-060T Digital Phone

FAS-TEL-200T Analog Phone/Fax/Modem

FAS-31XT Alarm System Phone

FAS-TEL-DSL DSL

Features ■ <1 nanosecond response time

■ Solid-state silicon breakover technology

■ Low capacitance

■ Over current protection

■ UL 497A listed

■ Line-to-line protection

■ Line-to-ground protection

■ Polyswitch resettable fuses — PTCs

■ 5 year warranty

edco™ FAS-Tel and FAS-31XTRJ11/RJ31X Telephone Protection

The Edco FAS-TEL and Edco FAS-31XT are single-pair telephone or data line

protectors that implement advanced two-stage hybrid design. These units

address over-voltage transients with silicon breakover devices, while sneak and

fault currents are mitigated with PTC technology which consists of solid state

resettable fuses.

The Edco FAS-31XT replaces the RJ31X jack with a protected version. Four screw

terminals are provided to wire the protector in the same manner as a standard

RJ31X jack.

The Edco FAS-TEL is nearly identical to the Edco FAS-31XT except with out the

shorting bars. Two screw terminals are provided to connect the incoming

telephone line to the protector. Protected equipment such as modems are

plugged into the female modular jack on the Edco FAS-TEL.

general Technical Specifications How To Specify The Appropriate model

270 Volts

300 Volts

0 1 5

0 3 0

0 5 0

0 6 0

2 0 0

15 Volts

30 Volts

50 Volts

60 Volts

200 Volts

ClampingVoltage F A S - T E L - T

F A S - T E L - D S L

F A S - 3 1 X T

Page 29: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ HSP Series120 VAC Heavy Duty 120 Volt ACThe Edco HSP Series is an advanced three-stage hybrid, solid state, power-

line protector. Features such as noise filtering, common mode and normal

mode suppression, nanosecond reaction time, power line tracking, and

compression screw terminations make the Edco HSP Series an excellent

choice in commercial and industrial applications.

The Edco HSP Series offers a replaceable fuse designed to remove the load

(protected equipment) from the line if the unit is either overloaded or

the internal protection fails. This feature prevents surges from entering

equipment through a failed protector not noticed by the user.

Maximum Operating Voltage 120 VAC

Clamping Voltage 325 VAC

Operating Current 15A

I-Nominal (In) 3 kA

Total Peak Surge Current 39 kA (8 x 20 µs)

Operating Frequency 47–63 Hz

EMI Attenuation (100 kHz to 100 MHz) > 40 dB

SPD Technology Metal Oxide Varistors (MOVs) w/ L-C Filter

Modes Of Protection Line-to-Neutral, Line-to-Ground, Neutral-to-Ground

Status Indication Power On & MOVs functional

Connection Type 3 Position, 20A Terminal Block w/Compression Screws Terminals Accept Up To 14 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) HSP121BT-1RU 1.8H x 2.9W x 5.3L HSP-121A 2.95H x 4.95W x 3L

Weight 10 oz

Certifications HSP121BT-1RU ANSI/UL1449 Third Edition, Type 4 HSP121A ANSI/UL1449 Third Edition, Type 2

general Technical Specifications Dimensions

Mounting – HSP121BT-1RUHoles 3/16" Dia.

Light On – NormalLight Off – Requires Service

Features ■ Fast response time

■ Failure indicator

■ Power line tracking

■ Filtering

■ Polycarbonite NEMA 4X enclosure (HSP121A)

■ Three-stage hybrid design

■ Replaceable fuse

■ 1/2" or 3/4" knockouts for nipple conduit connectors (HSP121A)

■ 5 year warranty

27

Access Control

GND

N

AC

GND

N

AC

3/4" Conduit Fitting 3/4" Conduit Fitting

1/2" Conduit Fitting 1/2" Conduit Fitting

Mounting – HSP121AHoles 3/16" Dia.

eDCO HSP121BT-1ru

eDCO HSP121A

Page 30: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

28

Access Control

edco™ PC642 Series Zone/Loop/DataThe Edco PC642 Series surge suppressor is a two-pair (four-wire) module

implementing three-stage hybrid technology. This module addresses

over-voltage transients with gas tubes and silicon avalanche components.

In addition, sneak and fault currents are mitigated with resettable fuses (PTCs).

The PTCs increase resistance by several orders of magnitude when over-currents

exceed safe levels. A normal state resumes when over-currents are removed.

The ability to self-restore in this manner significantly increases suppressor

performance and survivability.

The Edco PC642 Series card edge module is gold plated, double sided, and is

designed to mate with the Edco PCB1B gold-plated female terminal connector.

When snapped together, the data circuits “pass thru” the protector in a serial

fashion from the four “Field Side” terminals to the four “Electronics Side”

terminals. Terminals 1 or 10 of the Edco PCB1B must be attached to Building-

Approved Ground per Edco Technical Bulletin # 2015.

Features ■ Three-stage hybrid protection

■ Sneak/fault current protection

■ Resettable fusing — PTCs

■ Low capacitance option

■ Plug-in module

■ Fast response time

■ Requires Edco PCB1B base

■ Order PC642PTU — an invaluable troubleshooting tool

■ 5 year warranty

eDCO PCB1B BASe SOlD SePArATely

OPTiON:DiN rAil KiT AVAilABleOrDer PArT # 11604KiT-PC

general Technical SpecificationsMaximum Operating Voltage 5, 12, 18, 24, 30, 36, 43, 52, 180 VDC

Clamping Voltage 8, 15, 20, 30, 36, 43, 50, 60, 200* VDC

Operating Current 0.15A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology GDT, SAD, w/Series PTC

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 10 AWG

Operating Temperature -40°C to +85°C

Dimensions (Inches) 2H x 1W x 2.5L (PC642 + PCB1B Base)

Weight 1 oz

Certification UL 497B

* PC642C-200 is not UL certified

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of supplying more than 150 milliamperes continuously.

Terminal Assignments

PCB1B:

Unprotected Pair 2

Unprotected Pair 1

Protected Pair 2

Protected Pair 1

Keying Pin

Even TerminalsOdd Terminals

Field SideElectronics Side

9

7

5

3

1

10

8

6

4

2

1.0

{ }

}{ 2.125" 2.4"

Ground Terminal 1 Or 10 To Building-Approved Ground

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Ordering information

PC642

PCB1B

APPliCATiON:

RS485, RS422: PC642C-008LC & PCB1B

RS423, Token Ring: PC642C-008LC & PCB1B

RS232: PC642C-020 & PCB1B

E-Net, 10 Base T: PC642C-030LC & PCB1B

4–20 ma: PC642C-036 & PCB1B

How To Specify The Appropriate model

-

Voltage Clamp

60 Volts50 Volts43 Volts36 Volts30 Volts

15 Volts8 Volts

2 0 0

PC642C

20 Volts

**200 Volts0 6 0 0 5 0 0 4 3

0 3 0 0 2 0

0 3 6

0 1 5 0 0 8

no suffixstage 2 clampeach line-to-groundstage 2 clampline-to-line only

stage 2 clamp line-to-lineand each line to ground

D

Xlow capacitance option stage2 clamp line-to-line and eachline to ground

**Not UL Listed

LC

Page 31: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

general Technical Specifications

Maximum Operating Voltage 5, 12, 24, 48, 65 VDC

Clamping Voltage 8, 15, 30, 60, 75 VDC

Operating Current 1.5A

Peak Surge Current (10 x 1000 µs) 008 = 125A, 015 = 72A, 030 = 22A, 060 = 18A, POE*=15A

Frequency Range 0 to 100 MHz

Insertion Loss < 0.1 dB at 50 MHz

SPD Technology Silicon Avalanche Diode (SAD)

Connection Type RJ-45 Jacks

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.0H x 2.5W x 4.25L

Weight 3 oz

Certification UL 497B

* LCDP-POE is not UL certified

The user equipment plugs into the LCDP’s equipment (protected) side, and the LCDP’s line (unprotected) side is connected to the incoming line. All 8 conductors are protected. The green ground wire must be bonded to the protected equipment power ground (third wire, green wire safety ground). Do not add length to the ground wire, since it must be kept as short as possible.

Ordering information

Model Clamping Voltage

LCDP-008 8 Volts

LCDP-015 15 Volts

LCDP-030 30 Volts

LCDP-060 60 Volts

LCDP-POE* 75 Volts

installation

Features ■ <1 nanosecond response time

■ Line-to-line protection

■ Low capacitance

■ RJ-45/4 pair protection (8 wire)

■ Silicon avalanche design

■ Line-to-ground protection

■ 5 year warranty

edco™ lCDPData Circuit ProtectionThe Edco LCDP Series is designed to conveniently protect 8 wire, low voltage, data

circuits and employs two RJ-45 jacks for easy installation. The Edco LCDP utilizes

silicon avalanche (solid-state) suppression technology and exhibits very low

capacitance to accommodate high data rates. This unit supports high-speed data

rates of over 100 Mbps.

Access Control

29

Page 32: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

30

edco™ FAS-1 and FAS-2 SeriesOne- and Two-Pair Signal Line Protection

The Edco FAS-1 and Edco FAS-2 Series are multi stage one-pair or two-pair surge

suppressors designed for high-exposure applications. These products were

specifically designed to meet multiple, low voltage, protection applications in the

fire and security industries.

Features ■ Lightning protection for low voltage

■ Data/signal lines

■ Multi stage protection

■ Common mode and differential protection mode

■ Automatic recovery

■ 5 year warranty

Maximum Operating Voltage 15, 24, 36, 52 VDC

Clamping Voltage 18, 33, 43, 60 VDC

Operating Current 2.5A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 10 MHz

Insertion Loss < 0.1 dB at 10 MHz

SPD Technology GDT, SAD, w/Series Inductor

Connection Type Terminal Block w/Compression Lugs Terminals Accept Up To 12 AWG

Operating Temperature -40 C to +85 C

Dimensions (Inches) FAS-1 = 1.5H x 1.5W x 2.8L FAS-2 = 2H x 2W x 2.8L

Weight FAS-1 = 3.5 oz FAS-2 = 7 oz

Certification UL 497B

FAS-1-018 HC (One-pair) 12VDC Use FAS-2-018 HC (Two-pair)

FAS-1-033 HC (One-pair) 24VDC Use FAS-2-033 HC (Two-pair)

FAS-1-043 HC (One-pair) 24VAC Use FAS-2-043 HC (Two-pair)

FAS-1-060 HC (One-pair)* 48V Systems Use FAS-2-060 HC (Two-pair)*

*Not UL listed

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of continuously supplying more than 2.5 amperes.

general Technical Specifications Ordering informationinstallation

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

< 3

Unprotected Or Field Side

Protected Equipment

Ground Lug

10–14 AWG

Equi

p. Line

Page 33: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

31

Maximum Nominal Surge Peak Current Typ Maximum Nominal Part Peak Signal Breakdown 1p 10 x 1000 µs 8 x 20 µs Cap Continuous Series Number Voltage Voltage Current Waveform (pf) Current (ma) Resistance

DRS-008 6 8 >100 10 kA 1500 150 5 Ohms

DRS-015 12 15 >100 10 kA 1500 150 5 Ohms

DRS-232 15 22 >100 10 kA 1500 150 5 Ohms

DRS-030 24 30 >100 10 kA 1500 150 5 Ohms

DRS-036 30 36 >100 10 kA 1500 150 5 Ohms

DRS-043 35 43 >100 10 kA 1500 150 5 Ohms

DRS-050 43 50 >100 10 kA 1500 150 5 Ohms

DRS-060 52 60 >100 10 kA 1500 150 5 Ohms

*DRS-175 200 250 >10 8 kA 1500 150 5 Ohms

**DRS-130 170 200 >10 8 kA 1500 5000 None

*Not UL 4978 Listed

**Warning!! DRS-130RMS is for discrete signal use only. Do not use DRS-130RMS on 120 VAC power lines. This unit is a non-hybrid, MOV design, rated above 5A operational current and can withstand greater than eight occurrences of a 10 kA (8 x 20 µs) waveform, and greater than 1,000 occurrences of a 200A 10 x 1000 µs waveform.

general Technical Specifications Dimensional Diagrams

Features ■ Low-voltage data surge protection

■ Three-stage hybrid protection

■ Sneak/fault current protection with resettable fuses—PTCs

■ Low profile packaging

■ UL 497B listed

■ Easy installation

■ Fits standard 35 mm DIN rail

■ Fast response time < 1 nanosecond

■ 5 year warranty

edco™ DrS (DC) SeriesDIN Rail Protection The Edco DRS (DC) Series is a DIN rail mountable, single-pair surge suppression

module implementing three-stage hybrid technology. This module addresses

over-voltage transients with gas tubes and silicon avalanche components. In

addition, sneak currents are mitigated with resettable fuses (PTCs). The PTCs

increase resistance several orders of magnitude when over-currents exceed safe

levels. A normal state resumes when over-currents are removed. The ability

to self-restore in this manner significantly increases suppressor performance

and survivability.

The Edco DRS (DC) Series mounts onto a standard 35 mm industrial DIN rail.

There are three “Field Side” and three “Electronics Side” screw terminals. One

is reserved for a shield. Three electrically tied ground terminals are provided for

grounding the Edco DRS (DC) Series unit to Building-Approved Ground. Shield is

isolated from ground.

For a 2-terminal version without a shield, order the Edco DRS-XXX-2.

DrS-XXX-2 (2 Terminal Version)

DrS-XXX

Page 34: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ CATV-DFHigh Frequency Coax Protector — F-TypeThe Edco CATV–DF surge protectors are designed to protect sensitive electronic

equipment from damage due to excessive voltage or currents generated by

lightning or static buildup.

Applications include direct broadcast satellite systems, HDTV, and cable modems.

The Edco CATV–DF offers low signal loss at frequencies up to 2 gigahertz.

Incorporates GDT (gas discharge tube) technology.

Maximum Operating Voltage 25 VDC

Clamping Voltage 150 VDC (Spark Over Voltage)

Operating Current 1A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 2 GHz

Insertion Loss < 1.0 dB at 1 GHz < 2.0 dB at 2 GHz

SPD Technology Gas Discharge Tube (GDT)

Connection Type Type F Female

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.25H x 2.5W x 4L

Weight 3 oz

Maximum Operating Voltage 130 VDC

Clamping Voltage 150 VDC (DC Spark Over Voltage)

Operating Current 1A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 4 GHz

Insertion Loss < 0.5 dB 2 to 3 GHz

SPD Technology Gas Discharge Tube (GDT)

Connection Type Female N-Type

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.25H x .875W x 2.5L

Weight 4 oz

general Technical Specifications

Features ■ Automatic recovery

■ Low insertion loss

■ Shielded case

■ Easily installed

■ 5 year warranty

general Technical Specifications

edco™ CX-HFNHigh Frequency Coax Protector — N-TypeThe Edco CX-HFN surge protectors are designed to protect sensitive

electronic equipment from damage due to excessive voltage or currents

generated by lightning or static buildup.

The Edco CX-HFN offers low signal loss at frequencies up to 3 gigahertz.

The Edco CX-HFN accommodates both bulkhead mount and stud mount.

The input and output connections are interchangeable.

Ordering informationCX-HFN-FM Female to Male

CX-HFN-FF Female to Female

Communications

32

Page 35: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Maximum Operating Voltage 12, 24, 42, 12, 35 VDC

Clamping Voltage 15, 30, 48, 15, 56 VDC

Operating Current 2A

Peak Surge Current 015 =125A, (10 x 1000 µs) 030 = 71A, 048 = 45A, CLN = 125A, SPK = 500A, 8 x 20 µs

Frequency Range 0 to 20 MHz

Insertion loss < 0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode (SAD), OPX-SPK Model Uses MOV

Connection Type Clip

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.25H x 0.375W x 2.0L

Weight 1 oz

Certification UL 497B

edco™ OPX SeriesIntercom/Speaker Punch Block Protection (Parallel) Medium Exposure ApplicationsThe Edco OPX Series surge protectors are specifically designed for medium-

exposure applications. Thus, the protectors can be used on pairs inside a building

or leaving the build ing, in conduit up to 500 feet. These protectors are intended

to be used in conjunction with the Edco MGB Ground Rail and a standard MI-50

Punch Down Block.

The Edco OPX Series offers several, distinct advan tages over other current

technologies. Among the advantages are low cost, no series resis tance, and

durable solid-state construction.

general Technical Specifications

Test Points

MI-50 Block

installation

Features ■ Over-current protection

■ Replaces bridging clips on MI-50 block

■ UL 497B listed

■ Utilizes MGB grounding rail

■ Test point accessible

■ 5 year warranty

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Communications

33

0 1 5

0 3 0

0 4 8

C L N

S P K

15 Volts

30 Volts

48 Volts

15 Volts (Call-In Circuit)

56 Volts (Speaker Circuit)

ClampingVoltage

O P X

How To Specify The Appropriate model

Page 36: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

34

Features ■ Over current protection

■ Replaces bridging clips on M1-50 bock

■ UL 497B listed

■ Utilizes MGB grounding rail

■ Test point accessible

■ 5 year warranty

Maximum Operating Voltage 12, 56 VDC

Clamping Voltage 21, 70 VDC

Operating Current 0.15A

Peak Surge Current PBCLN = 0.2 kA, PBSPK = 0.5 kA (10 x 1000 µs)

Frequency Range 0 to 20 MHz

SPD Technology PBCLN = SAD w/Series PTC, PBSPK = MOV w/Series PTC

Insertion Loss < 0.1 dB at 20 MHz

Connection Type Clip

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.25H x 0.4W x 2.8L

Weight 1 oz

Certification UL 497B

Ordering informationPBCLN Call-In Circuit

PBSPK Speaker Circuit

Test Points

MI-50 Block

See Technical Bulletin # 2017

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of continu ously supplying more than 150 mA.

general Technical Specifications installation

TTA-2: Test Point Plug Available

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

edco™ PB SeriesIntercom/Speaker Punch Block Protection (Series)The Edco PB modules are solid-state protectors for intercom extension pairs.

As a new alternative to the “OPX,” the standard EDCO intercom protector, the PB

adds fusing and a new component layout. These hybrid protectors are intended

to be used in conjunction with the EDCO MGB ground rail and a standard MI-50

punch down block. The PB modules feature solid-state resettable fuses (PTCs)

between the protected equipment and the over voltage clamping components.

This unique design prevents problems with “All-Call” in the event of catastrophic

protector failure.

Patented Technology

Page 37: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

edco™ H SeriesTelecom/Punch Block Protection Advanced Ultra High Speed TechnologyThe Edco H Series modules are ultra high speed, fused, solid state, secondary

protectors for KEY/PABX systems. The units are available in three different

clamping voltages. The Edco H Series is constructed with solid state silicon

foldback technology, polyswitch resettable fuses — PTCs — and failure fuses.

These protection modules are intended to be used in conjunction with proper

primary protectors (UL 497A). The protective elements switch from the normal

high-impedance state to a low-impedance state upon a detection of a surge,

then switch back to high impedance after the surge has passed. The Edco

H Series single-pair modules fit onto a standard Edco MI-50 split block and

replace bridging clips. In addition, these modules require the Edco MGB Ground

Rail for each Edco MI-50 block used.

Maximum Operating Voltage 50, 180, 230 VDC

Clamping Voltage 65, 200, 270 VDC

Operating Current 0.15A

Peak Surge Current 160A (10 x 1000 µs T & R to Ground)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Silicon Breakover Device w/Series PTC

Connection Type Clip

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.25H x 0.4W x 2.8L

Weight 1 oz

Certifications UL 497A, CUL

Ordering informationHCO Central Office/Trunk

HAE Analog Extension

HDE Digital Extensions

MI-50 Block

Unprotected Side — Terminate Field Side Wiring Coming IntoBuilding On The “Unprotected Side”

general Technical Specifications installation

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Patented Technology

Communications

35

Page 38: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

36

edco™ COHP SeriesData/Signal Line/Punch Block Protection High-Exposure ApplicationsThe Edco COHP modules are three-stage hybrid protectors for low-voltage data and

telecommunications applications. The modules address over-voltage transients with

gas tubes and silicon avalanche components. In addition, sneak and fault currents

are mitigated with resettable fuses (PTCs). Intended to be used on pairs without

the presence of ring ing voltage. The Edco COHP modules are designed for data and

control applications as an isolated loop circuit protector.

Features ■ Replaces bridging clips on MI-50 Block

■ <1 nanosecond response time

■ Line-to-line protection

■ Line-to-ground protection

■ Utilizes MGB grounding rail

■ Rugged, three electrode, gas tube, first stage

■ Silicon avalanche hybrid technology

■ Polyswitch resettable fusing — PTCs

■ 5 year warranty

edco™ mgB ground railFits Standard 66MI-50 Punch Down Blocks Split Block VariationsThe Edco MGB Ground Rail — designed to fit standard 66MI-50 Punch Down Blocks.

Allows Edco’s H Series, COHP, OPX, PB Series and other similar surge suppressors to

access ground when snapped onto the 66MI-50 Punch Down Block. The Standard

66MI-50 Block is capable of accommodating up to 25 Edco surge suppressors.

MI-50 Block

Edco Recommends A 10AWG Wire To

Building-Approved Ground —Keep Short

Protected Unprotected

U.S. Patent No. 4,703,983

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Maximum Operating Voltage 6, 12, 20, 24,

43, 52 VDC

Clamping Voltage 8, 15, 20, 30, 50, 60 VDC

Operating Current 0.15A

Peak Surge Current 10 kA (8 x 20 µs)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology GDT, SAD, w/ Series PTC

Connection Type Clip

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.25H x 0.4W x 2.8L

Weight 1 oz

Certification UL 497B

Model Clamping Voltage

COHP-008 8 Volts

COHP-015 15 Volts

COHP-020 20 Volts

COHP-030 30 Volts

COHP-050 50 Volts

COHP-060 60 Volts

general Technical Specifications Ordering information

Page 39: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Features ■ <1 nanosecond response time

■ Solid-state silicon breakover technology

■ Low capacitance

■ Over current protection

■ UL 497A listed

■ Line-to-line protection

■ Line-to-ground protection

■ Polyswitch resettable fuses — PTCs

■ 5 year warranty

Maximum Operating Voltage 12, 24, 43, 52, 180, 220, & 220 VDC

Clamping Voltage 15, 30, 50, 60, 200, 270 & 300 VDC

Operating Current 0.15A

Peak Surge Current 160A (10 x 1000 µs T & R to Ground)

Frequency Range 0 to 20 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode w/ Series PTC

Connection Type Terminal Block w/Compression Lugs In/ RJ Connector Out

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1H x 2W x 2L

Weight 2 oz

Certifications UL 497A, CUL

Ordering informationFAS-TEL-060T Digital Phone

FAS-TEL-200T Analog Phone/Fax/Modem

FAS-31XT Alarm System Phone

FAS-TEL-DSL DSL

general Technical Specifications

edco™ FAS-Tel and FAS-31XTRJ11/RJ31X Telephone ProtectionThe Edco FAS-TEL and Edco FAS-31XT are single-pair telephone or data line

protectors that implement advanced two-stage hybrid design. These units

address over-voltage transients with silicon breakover devices, while sneak

and fault currents are mitigated with PTC technology which consists of solid state

resettable fuses.

The Edco FAS-31XT replaces the RJ31X jack with a protected version. Four screw

terminals are provided to wire the protector in the same manner as a

standard RJ31X jack.

The Edco FAS-TEL is nearly identical to the Edco FAS-31XT except with out the

shorting bars. Two screw terminals are provided to connect the incoming

telephone line to the protector. Protected equipment such as modems are

plugged into the female modular jack on the Edco FAS-TEL.

Communications

37

How To Specify The Appropriate model

270 Volts

300 Volts

0 1 5

0 3 0

0 5 0

0 6 0

2 0 0

15 Volts

30 Volts

50 Volts

60 Volts

200 Volts

ClampingVoltage F A S - T E L - T

F A S - T E L - D S L

F A S - 3 1 X T

Page 40: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

38

Maximum Operating Voltage 5, 12, 24, 48, 65 VDC

Clamping Voltage 8, 15, 30, 60, 75 VDC

Operating Current 1.5A

Peak Surge Current (10 x 1000 µs) 008 = 125A, 015 = 72A, 030 = 22A, 060 = 18A, POE*=15A

Frequency Range 0 to 100 MHz

Insertion Loss < 0.1 dB at 50 MHz

SPD Technology Silicon Avalanche Diode (SAD)

Connection Type RJ-45 Jacks

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.0H x 2.5W x 4.25L

Weight 3 oz

Certification UL 497B (*except LCDP-POE)

edco™ lCDPData Circuit ProtectionThe Edco LCDP Series is designed to conveniently protect 8 wire, low-voltage data circuits and employs two RJ-45 jacks for easy installation. The Edco LCDP utilizes silicon avalanche (solid-state) suppression technology and exhibits very low capacitance to accommodate high data rates. This unit supports high-speed data rates of over 100 Mbps.

edco™ rm-CAT6-POe SeriesMulti-Channel RackmountThe Edco RM-CAT6-POE Series is a modular, high speed, data-line protector

that utilizes a three-stage hybrid design technology. This unit addresses high-

energy voltage transients that can damage expensive computer equipment.

Ideal for network switches and hubs, the Edco RM-CAT6-POE Series is easily

mounted in close proximity to the protected equipment.

general Technical Specifications

Features ■ Exceeds Category 6 transmission values

■ Compact 1U rack size

■ Replaceable surge modules

■ Low insertion loss

■ Offered in 16 or 48 channel protection*

■ Three-stage hybrid

■ Meets POE requirements

■ 1 year warranty

*Other configurations available. Consult factory.

Maximum Operating Voltage 57 VDC

Clamping Voltage 68 VDC

Frequency Range 0-250 MHz

Operating Current 0.15A

SPD Technology GDT, SAD, W/Series PTC

Modes of Protection Signal High-Low Signal High-Ground, Signal Low-Ground

Peak Surge Current 10 kA (8 x 20 µs)

Insertion Loss <0.1dB

VSWR <1.2

Operating Humidity 0-95% Non-Condensing

Operating Temperature -40°C to +85°C

Input Connection Type RJ-45

Output Connection Type RJ-45

Mounting Rackmount

Enclosure Type Painted Steel

Dimensions 1.75Hx19Wx6.3D

Weight 5.5 lbs.

Features ■ <1 nanosecond response time

■ Line-to-line protection

■ Low capacitance

■ RJ-45/4 pair protection (8 wire)

■ Silicon avalanche design

■ Line-to-ground protection

■ 5 year warranty

general Technical SpecificationsThe user equipment plugs into the LCDP’s equipment (protected) side, and the LCDP’s line (unprotected) side is connected to the incoming line. All 8 conductors are protected. The green ground wire must be bonded to the protected equipment power ground (third wire, green wire safety ground). Do not add length to the ground wire, since it must be kept as short as possible.

Ordering informationLCDP-008 8 Volts

LCDP-015 15 Volts

LCDP-030 30 Volts

LCDP-060 60 Volts

LCDP-POE 75 Volts

installation

mODel SHOWN 48 CAT6-POe

Page 41: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

39

edco™ rJA-rJD SeriesRJ-45 Telephone/DataThe Edco RJA and Edco RJD Series are four-pair telephone/data-line protectors

that implement advanced, two stage, hybrid design. These units address

over voltage transients with silicon breakover devices, while sneak and fault

currents are mitigated with PTC technology, which consists of solid state

resettable fuses.

The Edco RJA and Edco RJD Series incorporate Edco RJ-45 female jacks in and

out. The Edco RJA voltage clamp is set for C.O. Trunks and analog telephone

extensions (with ring in voltage), and the Edco RJD voltage clamp is set for

digital extensions (no ring in voltage).

Features ■ <1 nanosecond response time

■ Solid-state resettable fuses — PTCs

■ Silicon breakover technology

■ Low capacitance

■ Line-to-line protection

■ Tip- and ring-to-ground protection

■ CAN/CSA C22.2, No. 226-92 compliant

■ UL 497A listed

■ 4 pair protection

■ 5 year warranty

general Technical Specifications

Maximum Operating Voltage 48, 220 VDC

Clamping Voltage 55, 280 VDC

Operating Current 0.15A

Peak Surge Current 200 A (10 x 1000 µs)

Frequency Range 0 to 50 MHz

Insertion Loss < 0.1 dB at 50 MHz

SPD Technology Silicon Breakover Devices w/Series PTC

Connection Type RJ-45 Jacks

Operating Temperature -40°C to +85°C

Dimensions (Inches) 1.0H x 2.5W x 4.25L

Weight 3 oz

Certifications UL 497A, CUL

Analog Phone RJA-45

Digital Phone RJD-45

Gnd.

Building-Approved

Ground

Ordering informationinstallation

The Edco RJA and Edco RJD Series are intended for indoor use only and shall be employed on the equipment side of a listed primary telephone protector.

Page 42: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

40

edco™ TBlK AssemblyTerminating AssemblyThe Edco TBLK is a high-density assembly designed to house up to 12 or 25

individual Edco surge protec tion modules. Standard Edco H Series, COHP,

OPX, PB Series, and other similar modules (separately ordered) are suitable

for the Edco TBLK assembly. The Edco TBLK is capable of terminating solid or

strand ed 26 to 14 AWG wire using compression terminal screws.

edco™ CAT6-5POe Series CAT6/CAT5 Power Over EthernetThe Edco CAT6-5POE Series is designed to work on Category 5 Power-Over-

Ethernet transmission lines as well as Category 6 applications. Ideal to protect

expensive equipment against surges and transients entering a building on

exposed transmission lines. Available in both female to female and male to

female RJ-45 connectors.

Features ■ Exceeds CAT5 & 6 transmission values

■ CAT5 POE compatible

■ CAT6 compatible

■ Applications up to 60 VDC @ 300 mA

■ 1 year warranty

Dimensions

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Operating Voltage 60 VDC

Clamping Voltage 65 VDC

Operating Current 300 mA

Peak Surge Current 60A (10 x 1000 µs)

Frequency Range 0 to 250 MHz

Insertion Loss < 0.1 dB at 20 MHz

SPD Technology Silicon Avalanche Diode (SAD)

Connection Type RJ-45 Jacks

Operating Temperature -40°C to +85°C

Dimensions (Inches) 0.8H x 1.0W x 2.3L (FF) 0.8H x 1.0W x 3.0L (MF)

Weight 1 oz

RJ-45 (FF) CAT6-5POE-FF

RJ-45 (MF) CAT6-5POE-MF

general Technical Specifications Ordering information

Page 43: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

Communications

41

1. Basic internal surge protection (standard)2. Plug-in hybrid surge protection

Tip/ring Or Data Protection1. Incoming C.O. lines use HCO 2. Analog extensions use HAE3. Digital extensions use HDE

AC Protection Options

To AC Building-Approved Ground

Cable Shield Ground

MGB Ground Rail

ChassisGround

MOD-12

HAE or HDE(One Per Extension)

66 Block

HCO(One Per CO TRUNK)

Existing Telco PrimaryProtection Demarc

CO TRUNKS

KSUHAE

HDE

Application Diagram

Features ■ 1 to 12 pair expansion

■ Replaceable single-pair protection modules

■ Punch down block (66 type)

■ Test points

■ Protective transparent cover

■ UL 1363 listed

■ 5 year warranty

edco™ mOD-12 Key SystemsThe Edco MOD-12 Tip/Ring protection for Key/PBX Systems. This innovative

design creates an automatic ground window, thus eliminating the problem of

ground potential difference.

Edco H Series Protector Modules readily snap onto the Edco MOD-12. Protection

is expandable from 1 to 12 pairs in single-pair increments and is field upgradable.

In addition, test points are provided on each pair.

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Ordering informationMOD-12 Base Assembly

Page 44: Fire/Alarm/Security/Communications - Rexel · It’s why companies turn to Emerson Network ... Electric Door Suppressor Edco™ EL-EDS 24 ... designed to mate with the Edco PCB1B

emerson Network Power. The global leader in enabling Business-Critical ContinuityTM.

AC PowerConnectivity

DC Power

HeadquartersSurge Protection100 Emerson ParkwayBinghamton, NY 13905T: 607-721-8840T: 800-288-6169F: 607-722-8713E: [email protected]

Embedded Computing

Monitoring

Outside PlantPower Switching & Controls

Precision Cooling

emersonNetworkPower.com/surge

Racks and Integrated CabinetsServices

Surge Protection

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. © 2010 Emerson Electric Co.

While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

SL-50200 Rev.1 8/10 Printed in USA

Embedded Power