SULTANATE OF OMAN DIRECTORATE GENERAL OF CIVIL DEFENCE FIRE SAFETY REQUIREMENTS PART TWO VEHICLE SERVICE STATIONS

Upload: others

Post on 11-Mar-2020

24 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

SULTANATE OF OMAN DIRECTORATE GENERAL OF CIVIL DEFENCE

FIRE SAFETY

REQUIREMENTS

PART TWO

VEHICLE SERVICE STATIONS

Page 2: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

1

SAFETY REQUIREMENTS FOR SERVICE STATIONS

1. DEFINITIONS

1.1 Service Station: A site where liquids used as motor fuel are stored, and

dispensed from fixed equipment into the fuel tanks of Motor Vehicles.

Facilities may be included for the sale of accessories, greasing, changing

oil and washing, the repair of tires, replacement of batteries and similar

minor maintenance requirements for motor vehicles. It may also include

facilities for storage and retaining of kerosene and for vending of small

quantities of refreshments.

1.2 Tanker: A vehicle comprising a traction unit whether rigid, articulated or

including a trailer.

1.3 Dispenser: A measuring or metering unit used for the dispensing of

Petroleum Products from the storage tank.

1.4 Concerned Authority: An organization having responsibility for any of the

following in connection with the service station.

a. Approval of location.

b. Approval of plans before construction work commences.

c. Issue of license to start construction work.

d. Approval of the completed work.

e. Issue of license to operate.

1.5 Responsible Person: A person who has the control of the day-to-day

Running of the service station.

1.6 Dangerous Occurrence: An event which may lead to fire or similar

hazardous circumstances.

1.7 H a z a r d o u s Areas:

A- Zone " 0" and area i n which a flammable gas/air mixture is

continuously present or is present for long period.

B- Zone "1" an area in which a flammable gas/air mixture is likely to

occur at any time during normal operations.

C- Zone "2" an area in which a flammable gas/air mixture is not likely to

occur in normal conditions and if it does it will only exist for a short

period of time.

1.8 A Non-Hazardous Area:

A safe area which f o r m s no part of the classified hazardous area

according to item 1.7

Page 3: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

2

1.9 Intrinsically Safe Circuit: An electrical circuit which, when installed and

operated under the specified conditions, on any electrical spark occurring

in normal working, is incapable of causing ignition of a flammable

petrol/air mixture.

1.10 Intrinsically Safe Apparatus: An electrical apparatus, so constructed

that when installed and operated under the specified conditions, on any

electrical sparking occurring in normal working, either in the apparatus or

in the circuit associated with it, is incapable of causing an ignition of a

flammable petrol/air mixture. ··

1.11 Self Service Station: A site where the motor fuel is dispensed from fixed

equipment into the fuel tanks of motor vehicles by persons other than the

service station attendant.

1.12 Watch room: A small room used by a supervisor or an employee whose

career is connected by filling operations. The room may also be used for

marketing and storing the necessary parts of vehicles. 2. LICENSING

2.1 It is not permitted to establish a petrol filling station until obtaining a

certificate of license from Ministry of Petroleum & Minerals (Department of

Petroleum Products Affairs), after the approvals from the following

authorities:

A- Ministry of Housing

B- Town Planning Authority- wall of the area.

C- Royal Oman Police (Directorate General of Operations, Directorate

General of Civil Defense, Directorate General of Traffic).

D- Any other concern authority

2.2 The appl icat ion shall b e submitted to the Ministry of Petroleum

(Department of Petroleum Product Affairs) according to the procedures

followed, by completing the application form prepared for this purpose.

The following documents shall be attached.

A- Copy of the ownership certificate

B- Copy of the site plan (kooky)

C- Plans of the site showing buildings to be erected thereto, together

with the location of any buildings in proximity to the site. The plans

shall have sufficient details to enable site location to be identified

and shall indicate the purposes for which the building will be used.

D- A written obligation by the owner to follow all safety requirements.

Page 4: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

3

2.3 All the safety rules mentioned in these requirements are intended for

Application to new petrol service stations, but it can be introduced into

Existing stations if its safety situation needs, and also in case of major

changes to its design by the owner.

3. Planning OF SERVICE STATIONS

3.1 location of Site

a. Any site selected for a service station should be such that adequate

space is available to permit safe location of tanks, vent pipes, tank

filling points, tank vehicle offloading stands, pumps and dispensers and

buildings, in relation both to the operation of service station and to the

safety of adjacent premises, should comply with the requirements in

this code and also to regulations and instructions of other concerned

authorities.

b. The site should allow safe entry, access and parking for customers

vehicles ca l l i ng f o r fuelling and other services a n d for road tank

vehicles supplying the service station, particularly making allowance for

coincident arrivals, according to the instructions of the Directorate

General of Traffic

3.2 layouts

A- General Design.

The buildings, operating areas and equipment of the service station,

including any to which the public have access, should be laid out in

such a manner as to ensure maximum safety and efficiency of

operation of the service station.

B - Safety Distances.

a. Tank filling points, tank vents, tank vehicle offloading stands, pumps

and dispensers should be located so that an accumulation of

petroleum vapor is unlikely, and at adequate distances so that no

hazardous atmosphere is likely to reach any source of ignition. They

should be sited at adequate distances from any opening in a building

or access to a below ground area, basement or cellar.

b. Tank openings, pumps and dispensers should be located so that their

centre lines are not less than 4.25m from any fixed source of ignition

or from the boundary of the premises.

4. TANKS

4.1 The following requirements should apply when installing the tanks:

A -Tank construction material should be compatible with all grades of

motor fuels. Tanks should be built to approve standards.

Page 5: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

4

B -The tank shall be suitable protected against corrosion or made from

Corrosion resistant material.

C -Tanks should be provided with connections for filling, drawing, gauging

and venting. There should be no openings to the tanks other than

those necessary for filling, gauging and venting.

D -The filling/dipping pipe should be carried down to within 40mm of tank

bottom. The suction pipe should terminate not less than 12mm above

the bottom of the filling/dipping pipe so as to maintain a liquid seal.

4.2 Tank Vents

a. Each tank or each compartment of a multi-compartment tank should

have a vent pipe not less than 40 mm in size. Tanks o r tank

compartments should be independently vented; vents from more than

one tank or compartment should not be connected into a common vent

pipe. Where vapor balancing facilities are fitted, the vent pipes to tanks

containing t h e same product may be manifold to allow for one

common vapor hose connection, according to the approved standards.

b. The upper end of the vent pipe should discharge upwards in the open

air at a greater height than the possible liquid level in any tank vehicle

filling the tank. This height should be at least 3.75m above ground level

and should not be located within 1.5m of opening windows or other

openings of any building.

c. The open end of the vent pipe should be provided with an open mesh

cap or screen, of metal or plastic, sufficient to prevent the entry of birds

or leaves. The mesh of the screen should not be finer than 6mm. The

screen should be of a material resistant to corrosion.

d. There should be no entry to basements, cellars or areas below ground

level within 1.5m of a point vertically below a vent discharge point.

e. Vent pipe outlets should be at least 1.5m from the boundary of the

service station, except where the boundary is a solid wall extending

down to ground level and 1.5m beyond the vent pipe outlet in every

other direction. Consideration should be given to the nature of the

adjoining property when deciding the proximity of vent pipes t o

boundaries.

f. The vapor from vent pipes is heavier than air and flammable. No fixed

source of ignition should be permitted in the immediate area of vent

pipe outlets.

Page 6: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

5

4.3 Tank gauging facilities:

a. If the measuring is by means of a dipstick, and the means of a direct

filling pipe, the same pipe shall be used for gauging, a steel plate of

adequate size and of the same thickness as the tank shall be welded to

the bottom of the tank immediately below the filling pipe.

b. Offset fill pipe: Where a separate dip pipe is provided there should be a

spring loaded shut off device or other approved means of closure.

4.4 The following requirements should app l y w h e n installing the

underground tanks:

a. Tank filling points, tank vents, tank vehicle offloading stands should be

located so that an accumulation of petroleum vapor is unlikely, and at

adequate distances so that no hazardous atmosphere is likely to reach

any source of ignition. They should be sited at adequate distances from

any opening in a building or access to a below-ground area, basement

or cellar.

b. Tank openings, should be located so that their centre lines are not less

than 4.25m from any fixed source of ignition from the boundary of the

premises o r building opening, and should c o m p l y w i t h the safety

distances determined by Directorate General of Civil Defense according

to the fire risks of the surrounding areas.

c. The area in which an underground tank is installed shall be such that

while motor fuels are being discharged from the tanker into the

storage tank, the tanker shall be wholly within the boundaries of the

service station.

4.5 Tank protection against corrosion

a. Buried steel tanks should be adequately protected against corrosion

having regard to the type of soil, water table and other prevailing

conditions in the area where the tank is to be installed.

bowered the tank is constructed in steel and fully protected against

possible soil corrosion it may be installed in a simple excavation back­

filled with clean sand. The sand surround should not be less than

150mm thick and should be completely surround the tank except for the

Manhole opening.

c. Where the tank is constructed in steel and is not fully protected against

possible soil corrosion, it should be installed in a fine concrete satisfying

the following requirements:

- Grade designation - 30

- Type of cement- sulphate resisting Portland.

- Nominal maximum size of aggregate- 20mm.

- Method of compaction- needle vibration.

Page 7: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

6

Before the tank is installed all rust or scale should be removed from the external surface immediately before applying the protective fin­ is, which may consist of one coat of red lead primer followed by one liberal coat of bitumen or two coats of bituminous paint or other suitable protective materials. The fine concrete surround should have a minimum thickness of 150mm and should surround the tank completely except for the manhole opening.

d. Where the tank is not constructed in steel special consideration should be given to the method of installation.

4.6 After lowering into the excavation and before it is surrounded by con­ Crete or sand, the tank shall be subjected to an internal air pressure of 0.7 Bar (10 psi) for not less than 24 hours or filled with water and sub­

Jest to a hydrostatic pressure of 0.7 bar (10 psi) for not less than 60 minutes to ensure that there is no leakage from the tank and its con­ section.

4.7 The excavation above tank and its surrounding shall be filled with clean sand, or other suitable non-corrosive materials to the appropriate­ ate level.

The manhole, filling, suction and venting connections, shall be en­ closed in a sturdily constructed brick or concrete chamber. The cover to the chamber shall be raised 25mm above forecourt level and ramped.

4.8 Where there is vehicular movement in the areas over the tank, this area shall be covered with reinforced concrete or asphaltic concrete to the required level. The reinforced shall extend at least 300mm horrid­ tonally in all directions beyond the plane of the tank.

5. PUMPS AND DISPENSING SYSTEMS.

5.1 The following requirements shall be fulfilled:

a. Pumps may be located in the dispensing units on the forecourt, or they may be located elsewhere and transfer product to individual or multiple dispensing units.

Bit is recommended that dispensing units should be located on a slightly raised island on the forecourt or otherwise protected from damage by collision from vehicles.

c. Diesel dispensers should be installed on special separate islands, with­ adequate distances from petrol dispensers. This is to provide safety movement for trucks or vehicles calling for fuelling with diesel. These vehicles are often used for the transportation of dangerous materials. This will ensure that there is no risk of interruption or danger to other vehicles movement in the station area.

Page 8: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

7

D Pumps located remote from the dispensing units should be pro­ Tested against physical damage.

E.Pumps and dispensing units should be designed, constructed and tested to accepted engineering standards.

f. Pumps and dispensing units should be adequately secured in posi­ tion. Each suction pipe riser should terminate in a shallow liquid­ tight pit beneath the pump it serves. The pit should be constructed with walls and floor of concrete not less than 150mm in thickness. It should be as shallow as is practicable and in no case deeper than is necessary to accommodate the flexible connection between the suction pipe riser and the pump. The ground enclosed within the pump housing should otherwise be paved with concrete.

great power operated pump shall be fitted with either a limiting de­ vice or a preset device to prevent a continuous out flow of more than 100 liters for Class 1 Product and 150 liters for others in one operation.

h. A control shall be provided to permit the pump to operate only when the nozzle is removed from its normal position and the switch on the pump is manually actuated. This control shall also stop the pump when the nozzle is returned to its normal position.

I. The maximum bypass pressure of the pump shall not exceed 2 bars.

Golf a sight glass unit is fitted; it shall be capable of withstanding hay Prostatic pressure of 5 bars.

Kithara shall be adequate flow of ventilating air across the dispenser unit and the total effective area of ventilation openings shall not be less than 80 cm2.

I. Dispensing hose should be to approve standards. It should be capable of withstanding a test pressure of 5 bars, sufficiently flexible to allow easy handling, and should be of material compatible with the product being handled. The cover shall be smooth and resistant to weathering and abrasion.

5.2 Hose Nozzles A - The nozzle shall be provided with an automatic cut-off to prevent

spillage due to blow-back or to overfilling and the maximum flu­ write to operate the cut-off shall not be more than one half of the flow rate for which the retaining latch open device is currently Set.

B - An attendant operated pumps no stop or catch shall be provided on the nozzle which would keep the nozzle valve open, unless all The following conditions are satisfied:

- Provision shall be made to ensure that the nozzle is not dis­ placed from the filling pipe of a vehicle during normal filling operations.

Page 9: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

8

- In the event of the nozzle falling out of the filling pipe of the vehicle,

the operat ing lever o f the nozz le valve shall automatically be

released from the retaining latch upon impact of the nozzle with the

vehicle or the ground, and the flow of petrol shall stop immediately.

- The nozzle shall be attached to the delivery hose in such a manner

that in the event of a vehicle moving while the nozzle remains in the

filling pipe, the flow of petrol will stop and the nozzle becomes

released from the delivery assembly before damage to the control

valve, coupling, delivery hose or pump can occur. 5.3 D i s p e n s i n g Unit and Nozzle in Self Service Stations.

In addition to the above, the following requirements shall be fulfilled;

A. For se l f -service operation particular attention should be paid t o

surrounding r isks and to the layout of the premises t o afford ease of

entry and exit for customers' vehicles to and from the forecourt area.

Local conditions may make a site unsuitable for self-service.

B. In self-service stations supervision shall be exercised at all times by an

attendant stationed at the control point where the individual petrol pump

and the forecourt emergency switches are located.

C. Petrol pumps and adjacent dispensing areas shall be clearly and readily

visible from the control point so that no obstacle except for vehicles

being fuelled is liable to be placed or to come between the dispensing

areas on the control point.

D.Communication shall be able to be made at all times without difficulty,

between the attendants having to leave the control point.

E. In self-service stations where coin-operated or card-operated petrol

pumps are installed, there shall be at least one forecourt attendant on

duty while the station is open to the public.

F. Provision shall be made for rendering inoperat ive a n y device on

the nozzle which would keep the nozzle valve open.

Gather minimum flow rate to operate the cut-off shall be not more than 9

liters per minute.

H. After the cut-off has operated, it shall not be possible to re-establish

flow without first returning the nozzle control lever to the 'off' position.

I. The nozzle shall be fitted with a device to prevent delivery unless either

the nozzle is properly located or the spout is pointing down.

Page 10: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

9

6. PIPES AND FITTINGS

a. The pipes, valves and fittings together with any jointing materials, shall be

compatible with and not affected by motor fuels.

Pipes and their joints shall not become damaged or leak under stresses

induced by thermal expansion or other forces occurring in normal service.

They shall withstand the stresses t e m p e r a t u r e s arising during

f i r e exposure or be suitably protected against these.

b. Sufficient number of valves shall be provided in piping systems for the

efficient and safe operation, during normal operation and in the event of

any damage.

c. Piping s ub jec ted to external c o r r o s i o n shall be painted o r

suitably protected against corrosion.

d. Pipe lines and connections shall be subject to an internal pressure of 0.7

bar (10 psi), for not less than 10 minutes, to ensure that there is no leak

on the pipe lines before they are covered with concrete or sand.

Underground pipe lines shall be substantially supported and covered in

not less than 150mm of fine concrete or protected by stone slabs. Where

there is vehicular movement over the pipelines, the area shall be covered

with reinforced concrete or to be installed in pipe trenches and fixed steel

cover, or to be provided by a steel sleeve around the buried pipes.

e. Any trench in which pipes are laid shall be of dimensions adequate to

permit access to valves and fittings.

7. ELECTRICALINSTALLATION

7.1 The following requirements should apply when installing electrical

wiring:

a. Wiring shall be installed, so far as is practicable, in positions which wi l l

prevent its exposure to mechanical damage or to the effect of heat,

corrosive substances or solvents. If such exposure is unavoidable,

appropriate measures shall be taken to protect the wiring.

b. Where cables in a conduit pass through a floor, wall, partition or ceiling,

the' hole provided for the conduit shall be filled with cement or similar

non-combustible material to the full thickness of the floor, wall, partition

or ceiling, through which it passes.

c. All equipment, connections and wiring, the function of which is not clear,

shall be clearly marked to indicate its function.

d. The overhead power supply line shall be terminated outside the Zone 1

and Zone 2 areas.

e. Fuses or circuit-breakers shall not be situated within the housing of.

The petrol pumps.

Page 11: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

10

f. Socket outlets and plugs in Zone I areas shall be of flameproof design

and the flexible cable shall be suitably protected with a flexible metallic

screen sheathed overall.

g. Sockets outlets and plugs in Zone 2 areas shall be of a type specifically

designed for use in Zone 2 areas such as interlocked plugs and sockets

with mercury-in-glass switches or enclosed make-brake micro switches.

Socket outlets of flameproof design may also be used.

h. Electrical equipment, apparatus and wiring, installed within the danger

area, shall be to the appropriate Zone requirements, as mentioned in

Table (7.1}.

I. Electrical equipment which is not intrinsically safe shall not be

connected in the same circuit with intrinsically safe equipment.

j. Portable and mobile apparatus, other than hand lamps supplied by

flexible cables, shall be provided with earth-leakage circuit-breakers.

k. Portable and lamps used in Zone 1 and 2 areas, shall be of flameproof

or intrinsically safe type and shall not operate at a voltage exceeding

50v. to earth.

I. Joints in conduits shall be made water tight. Conduits passing from a

safe area to a hazardous area shall be provided with a flameproof

sealing box or any other approved sealants protection, at the point

where the conduit enters the dangerous area.

7.2 D i s p e n s e r Circuits

A. Single dispenser:

- The dispenser shall be provided with two circuits to control individually

the dispenser motor and its integrated lighting.

B. Dual dispensers:

- Dual dispensers shall be provided with three separate sub-circuits, one

for each separate pump motor and one for the integral lighting.

- Each sub-circuit shall be protected by a suitable circuit-breaker of a

fuse of suitable current carrying capacity.

7.3 Emergency switch

In addition to the main switch controlling the electrical installation of the

service station, a separate emergency switch shall be provided in the

circuit to isolate the electricity supply from all petrol pumps and integral

pump lighting. It shall be so located and positioned as to be readily visible

and easily accessible a n d at a safe distance f r o m any opening to

a storage tank, any petrol pump or venting pipe.

Page 12: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

11

7.4 Earthling

A- The metal enclosure of all electrical equipment, conduits, junction's

boxes and metal sheathing of cable, shall be properly earthed.

B - Earth leakage circuit breakers o f the current opera t ed or

voltage operated type shall be used.

7.5 Lighting and Ventilation

A - Lighting in the service station shall be adequate for the tasks to be

performed, but in any case the intensity of light in the forecourt and

lubrication area shall be not less than 100 lox at floor level.

8 - Lamps and lamp holders shall be of totally enclosed type within the

dangerous areas.

C -Service Station buildings should be provided with active and suitable

adequate ventilation.

7.6 The motor generator room:

The motor/generator working on oil (if any) shall be housed in a separate

room, specially constructed for this purpose at adequate safety distance

from any opening to a storage tank or any petrol pump. 8. SAFETY PRECAUTIONS TO BE OBSERVED DURING OPERATIONS

8.1 Tanker Off-loading:

a. The tanker shall be completely within the boundary o f the service

station. It shall be so positioned that it can be driven directly from the

site in the event of a dangerous occurrence.

b. The handbrake shall be on and inadvertent movement of the tanker

shall be prevented.

c. Any static electrical charge on the tanker shall be discharged in a safe

manner before delivery of petrol into the storage tank.

d. No other vehicle movement shall be permitted within 4.5m from the

tanker discharge manifold during offloading.

e. The tanker and the storage tank shall be gauged to make sure the tank

can receive the quantity to be delivered.

f. The vicinity of vents shall be checked for possible sources of ignition.

Page 13: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

12

g. The driver of the tanker shall stay in the vicinity of the valve at the point

where the delivery hose is connected to the tanker. If there is evidence

of liquid petrol being ejected, the delivery shall be stopped.

h. At the end of delivery, the storage tank shall be gauged and the filling

pipe cap and manhole chamber cover replaced.

8.2 Fuelling Of Motor Vehicles:

a. The engine of the vehicle shall be switched off.

b. The delivery hose nozzle shall be inserted firmly into the filling pipe of

the vehicle and its contact with the pipe shall be maintained until the

completion of delivery. Care shall be exercised to prevent spillage of

petrol during filling.

c. The delivery hose shall not be twisted or stretched a n d it shall be

replaced in its normal position after delivery has been completed.

8.3 Filling of Portable Containers:

a. Class I Petroleum should only be filled into an approved type of

portable container, and the container should be securely closed

immediately after the filling is completed. On no account should an

open type of vessel be used.

b. Hose nozzles, whether manual or automatic, should be held open

manually during the filling of a portable container.

c. Containers should be clearly marked with the name of the product with

which they are filled, and in the case of Class I Petroleum the marking

should be in accordance with any statutory regulations. 9. FIRE PRECAUTIONS

9.1 Bui lding requirements:

A- Service station buildings s h o u l d be constructed generally o f

non­ combustible materials to conform to local building regulations.

Flooring material should be oil and water-resistant and as far as

possible provide a non-slip surface.

B - Buildings should be adequately ventilated. The type and location of

heating apparatus should be such that there will be no possibility of a

source of ignition in a hazardous area, either during normal operations

or in the event of a spillage on the forecourt.

Page 14: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

13

C - Doors should be provided and located so as to provide a ready means

of escape in the event of tire. Any means provided t o r bolting o r

locking the doors should be such that they can easily be opened from

the inside at all times when the service station is open for business. 9.2 Firefighting equipments:

Adequate equipment and materials to fighting the initial stages of a tire

shall be provided in the service station and other buildings within the

service station boundary.

The following is recommended as a guide to the amount of tire fighting

equipment:

A. An ample supply of clean dry sand to be provided at suitable places.

B. Dry Powder extinguishers of 12 keg capacity (minimum)

4 dispensers or less - 2 extinguishers 5-8 dispensers 3 extinguishers

And one more extinguisher for every additional 3 dispensers.

Cythera shall be at least one 12 kg. Capacity (minimum) dry chemical fire

extinguisher near the petrol tank opening and one near the entrance of

the generator room (if any).

D.As recommended by the Directorate General of Civil Defense, provision

may be made t o an adequate supply of water, f r o m hyd r an t s

connected to the main town supply line or from an overhead water tank

provided within the station. Fire hydrants should be from approved type

and similar to the type used by the Directorate General of Civil Defense.

E. All tire fighting equipment should be located where it is, and will remain,

accessible a n d unobstructed. It should be ensured that everyone

concerned knows where it is. Extinguishers should not be covered up,

nor should things be hung from them so that taking them down would

be difficult. They should be suitably mounted so as to protect them from

deterioration.

F. Fire extinguishers, a n d any other firef ighting equipment provided,

should be regularly inspected, tested and maintained to manufacturer's

recommendations.

Extinguishers should be sealed, where provision is made for sealing, to

indicate that they have not been discharged. A record of inspections

and tests should be kept in a register, and the date of inspection shown

on the appliance.

Page 15: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

14

9.3 Sources of Ignition Should Be Avoided:

a. Smoking shall not be permitted any where inside Zone 1 and Zone 2

areas of the service station.

b. Sources of ignition such as open flames, cutting and welding etc. shall

not be introduced into dangerous areas; hot surfaces, frictional heat,

sparks, etc. shall be eliminated from such areas; the danger of

spontaneous combustion shall be avoided.

c. Accidental spillage of petrol shall be removed immediately.

d. Petrol shall never be used for cleaning.

e. Extra care shall be taken when fuelling recreational vehicles fitted with

gas fuelled stoves, refrigerators, water heaters or similar appliances. 10. HOUSE-KEEPING

a. Tools not in use shall be kept on a tool-board provided for the purpose.

b. All floors shall be maintained in a clean and non-slip condition.

c. Rubbish shall not be allowed to accumulate and all dirty rags and empty

oil cans shall be collected and placed in suitable rubbish containers.

d. Any waste material such as oil shall be disposed of in a safe manner;

such material shall not be dumped into a sewer or septic tank, not spread

over the ground

11. SERVICES

a. Correct types of tools shall be used. Worn or ragged tools shall not be

used. Electrical tools should be suited to the zone classification of the

area in which they are to be used.

b. Checking and Exchanging Oil:

- Raise the bonnet to a safe position and secure it.

- Switch off the engine.

- Remove any spill after topping up or changing the oil.

12. TRAINING

a. Service station attendants shall be trained in the use of fire extinguishers

and the procedure to be adopted in the case of fire or other similar

emergency.

Page 16: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

15

b. Service station shall be provided wi th a facility to call Civil Defense

parties, telephone numbers of Directorate General of Civil Defense and

the Royal Oman Police shall be displayed in a prominent place.

c. Service station attendants shall be trained in the safe use of pumps and

other equipment, and in the prevention of any dangerous occurrence. 13. PERSONNEL PROTECTION

a. Suitable personnel protection equipment such as gloves, goggles, safety

glasses, s a f e t y shoes, aprons, etc. shall be provided to

personnel, depending on the nature of the work.

b. Any unsafe condition w h i c h can cause accidents, shall be reported

immediately and the necessary corrective action taken as soon as

possible.

c. All operational and maintenance work shall be planned and supervised by

a responsible person who shall ensure that all necessary precautions are observed.

d. Any defects in the machinery shall be attended to immediately and it shall

not be used until the defect is rectified.

e. Precautions shall be taken to avoid hazards and any required protective

equipment shall be worn.

f. Clothing's oiled with petrol or any other flammable material, shall be

removed immediately and any area of the body affected, shall be washed

thoroughly. Loose or torn clothing shall not be worn by any person working

in the service station.

g. Substances, which can cause dermatitis or skin burns, shall be washed

immediately from any affected area of the body and any necessary first

aid treatment shall be rendered.

h. Any accident causing injuries shall be attended immediately by the first­

aid personnel; if hospitalization of the injured person is necessary, it shall

be affected without delay.

I. A first-aid box, equipped for the treatment of minor injuries and burns shall

be available in each service station. At least one person shall be trained in

first aid treatment.

14. GENERAL REQUIREMENTS

a. Car washing facilities, shall be as far as possible from dispensing units

Page 17: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

16

With an adequate safety d is tance . Car wash design w o u l d keep

traff ic flows separate and offloading points well clear of everything.

b. Ground shall be sloped from office building towards washing facilities.

c. Entrances and Exits shall be marked clearly "Entrance o n l y " and "Exit

only". Signs shall comply with standards and requirements of Ministry of

Communication and Royal Oman Police, Directorate General of Traffic.

d. Suitable directional signs or markings should be provided for traffic flow to

and from the refueling islands and for inter-station traffic.

e. Drainage:

- Provision should be made to prevent the escape of product f rom the

premises into any water course, public drain or sewer or into or on to

adjoining property. Surface water which is liable to be contaminated

with petroleum may be required to be passed through an interceptor

before draining from the premises.

- Provision should be made either by grading, drainage galleys or raised

sills at entrances to buildings, or other means to prevent any spillage

from the forecourt are draining on to any adjacent building. 15. NOTICES, MARKING AND OPERATING INSTRUCTIONS

a. The following warning notices in Arabic and English shall be as approved

standard and displayed in a prominent position:

® S

C1 vile Def once, _, •:'-'l...:•

999 '\ '\ '\

b. T h e following n o t i c e shall be conspicuously displayed adjacent t o

the emergency switch in Arabic and English. "EMERGENCY SWITCH"

c. Tanks shall have an information plate indicating the kind of fuel stored in

each tank.

d. A copy of the license issued rye the authority, setting out the conditions

tube observed by persons employed shall be displayed in a prominent

position.

Page 18: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

17

TABLE 7.1

ELECTRICAL EQUIPMENT IN CLASSIFIED AREAS WITHIN SERVICE

STATIONS

Factor

BURIED TANK

Fill opening or any other

opening to the tank

Above-ground offset

filling connection tight fill

Vent discharge opening

DISPENSING UNITS

Extent of Classified Area Zone

Classification

Up to 1 m above ground level within a horizontal radius 2 Of 1.5m from the edge of the manhole and down to

ground level.

Any chamber or pit in the Zone 2 area which does not 1

include an opening to a storage tank.

Any manhole chamber containing a normal sealed 1

opening to a storage tank.

Up to 0.5m above the fill connection within a horizontal 2

Radius of 1.5m from the connection and down to ground level. Within 1.5m of the open end of the vent extending in all directions. 1

Within 1.5m of any other part of the vent riser pipe. 2

Within housing of dispensing unit 1

Any pit, box or space below forecourt or surrounding ground level, 1

any part of which is within a Zone 1 or Zone 2 classified area.

To a distance of 3m from the centre line of the dispensing unit 2

to a height of 1.25m above ground level and then reducing

Uniformly between 3m and 4.25m from the centre line to reach

ground level at 4.25m.

When a dispenser is fitted with a sight glass and a flexible hose 2

then, if the connection joints are outside the housing of the

Dispenser, a hazardous area exists forming a cylinder down to

Ground level (or to meet the Zone 2 area defined for the

dispenser itself) the radius of the cylinder being 0.75m.

This cylinder extends upwards above the sight glass and hose

joint connections for 150mm.

When a dispenser has a radial arm mounted immediately 2

above the dispenser-carrying joints for sight glasses and/or

Those connections- then the conditions set down in the above

Paragraph applies saving that the radius of the Zone 2

cylinder is 0.75m from the center of the sight glass and/or

hose connection plus the radius of the radial arm.

When a dispenser has a flexible hose depending from a fixed 2

high level point at which joints for the hose and/or a sight glass

Are made (at a height not greater than 2.5m above ground

level) then a Zone 2 area exists forming a cylinder down to ground

level (or to meet the Zone 2 area defined for the dispenser itself)

the radius of the cylinder being 0.75m. This cylinder extends

upwards above the sight glass and hose joint connections

For 150 mm.

Page 19: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

18

TABLE 7.1

ELECTRICAL EQUIPMENT IN CLASSIFIED AREAS WITHIN SERVICE STATIONS

Factor Extent of Classified Area Zone

Classification

LIGHT FITTING

MOUNTED ABOVE

A DISPENSER

Connected to the dispenser in a manner which allows the

passage of vapor from inside the dispenser housing into the

light fitting.

If within the Zone 2 area created by any configuration of 2

Dispenser unit above.

REMOTE PUMP

OUTDOOR

Within the housing of the pump and any pit, box or space 1

below ground level within a horizontal distance of 1.5m

From the pump housing.

Within 1.5m of the pumping housing extending in all horizontal 2

directions and down to ground level.

INSPECTION PITS Pits in maintenance or inspection bays or within a Zone 2 area 1

Very large pits or sub-level inspection bays situated in non- 2

hazardous areas where good permanent ventilation obtains.

SALES, STORAGE,

RESTROOM$ AND

KIOSK

If there is any opening to these rooms within a Zone 2 classified 2

areas, the whole area of the room, up to a height of 1.25m.

Note: Where a source of hazard can give rise to both a Zone 1 and a Zone 2 area, it should not be

implied that Zone 2 is an extension of Zone 1. It is important to understand that the conditions

which give rise to a Zone 1 or a Zone 2 are quite different. (See 1.7 to 1.9- Definitions)

Page 20: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

19

Raised or Double soil Man lid Concrete

Forecourt Chamber Level Cast in place

150mm.

Tank

' ', ''\

I

'

Expansion Joint.

Number dependant

on size of tank

Reinforced Concrete Base.

FIG. 1 TANKS INSTALLED IN FINE CONCRETE

Vent Pipe ----...1

Raised or Double sealmanlid.

Dip I Fill pipe.

Concrete

Suction Pipe. Brick Chamber or Concrete cast in place

228 mm.Thick Brickwork. (Waterproof rendered.) Concrete

cover reinforced as necessary.

Sandinfill.

228mm. Thick Brickwork. (Waterproof rendered.)

Impact plate Foot valve

and Strainer. Reinforced Conaete Base.

Concrete Cradle.

FIG. 2. TANKS INSTALLED IN BRICK AND CONCRETE VAULT

Page 21: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

20

l

I

DIVISON 1 AREA

DIVISION 2AREA

f Height to top.

of pump Housing o

Wr 1

h.2

i5 m

ev.

: :r:grealer. FORECOURT LEVEL

--

PUMP HOUSING t

PUMPS ISLAND

OJ

PUMPS

FIG. 3. LIMITES OF DANGEROUS AREAS FOR PUMPS AND PUMP ISLAND.

Page 22: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

21

4.25M·---+-I-+---3.00M.-!

1.25.M.

FORECOURT

LEVEL

Tank

DIVISON

1 AREA

DIVISION

2AREA

DIVISION

1 AREA

DIVISION

2AREA

FIG. 4. LIMITS OF DANGEROUS

AREA FOR TANK OPENING

VENT PIPE

FORECOURT

LEVEL

f---<---1.50 M. ---H

FIG. 5. LIMITS OF DANGEROUS AREA FOR VENT PIPE.

Page 23: FIRE SAFETY REQUIREMENTS - PDO Safety Requirements Part...filling points, tank vehicle offloading stands, pumps and dispensers and buildings, in relation both to the operation of service

1\) 1\)

1 - Shed

2 - Office and shop

3 - Air Sign

4 - No Smoking sign

5 - Direction Entrance sign

6 - Site Name sign

- Litter Bin

Notice: