  • FIRE REGULATIONS

    (NL, EU)

    note: not included in the reader

    Lecture CIE 5131: Fire safety design

    Dr.ir. IJ.J.van Straalen (TNO) [email protected]

    Ir. A. Breunese (Efectis) [email protected]

  • 2 CIE 5131 Fire Safety Design

    Legislation for fire safety

    Relevant documents (NL)

    Woningwet / Housing Act (1920)

    Bouwbesluit*) / Building Decree (2012)

    NEN / EN documents

    National recommendations of practice (NPR) guidelines

    *) Including Regeling Bouwbesluit 2012

  • 3 CIE 5131 Fire Safety Design

    Bouwbesluit types of rules (1)

    Fire ignition

    Escaping and escape routes

    Smoke production and spread

    Fire spread and controllability

    Resistance to fire

  • 4 CIE 5131 Fire Safety Design

    Bouwbesluit types of rules (2)

    Prevention of ignition

    Choice in materials

    Maintenance

    Escape

    Escape routes

    Information and training

    Smoke production and spread

    Smoke compartments

    Fire spread and controllability

    Sprinklers

    Automatic fire alarm

    Fire compartments

    Fire ventilation

    Resistance to fire: progressive collapse

  • 5 CIE 5131 Fire Safety Design

    Performance requirements

    Principles

    Each requirement specifies

    Subject / Part

    Function

    Acceptable value(s)

    Method to determine the value

    Example:

    In order to limit the reaction to fire, a structural part shall be at least of fire reaction class 4, to be determined using NEN 6065.

    All rules are

    Unambigious

    Quantifiable

  • 6 CIE 5131 Fire Safety Design

    Requirements depend on

    Condition of the structure

    new structure

    existing structure

    Function

    dwelling

    hospital

    office

    shop

    (12 x!)

  • 7 CIE 5131 Fire Safety Design

    Fire ignition and reaction to fire

    Systematic requirements

    Basis: material behaviour

    Properties: Non-combustibility ( NEN 6064) Reaction to fire

    Walls and ceilings ( NEN 6065)

    Floors ( NEN 1775) Other parts such as roofs and chimneys

  • 8 CIE 5131 Fire Safety Design

    Euroclasses (EN 13501-1)

    Classification aspects

    Burning behaviour: heat release (not for Horizontal Flame Spread test & Small Flame test), flame spread

    Smoke production: optical density (SBI & Horizontal Flame Spread test only)

    Flaming droplets: visual observations (SBI & Small Flame test only)

  • 9 CIE 5131 Fire Safety Design

    Euro Class system overview

    Note: For floor coverings (fl), SBI is replaced by Radiant Floor Panel

    Class Test methods Classification aspects

    A1 EN 1716: Calorific value and

    EN 1182: Non-combustibility

    Burning behaviour

    A2 EN 1716: Calorific value or

    EN 1182: Non-combustibility

    Burning behaviour

    and EN 13823: SBI Smoke production

    B/C/D EN 13823: SBI and

    EN ISO 11925: small flame

    Burning behaviour

    Smoke production

    Flaming droplets

    E EN ISO 11925: small flame Burning behaviour Flaming droplets

    F None None

  • 10 CIE 5131 Fire Safety Design

    Euro Class System

    Number of classes

    aspect walls & ceilings floors

    main classes

    burning behaviour

    7 7

    smoke 3 2

    number of

    tests sub classes

    droplets 3 -

    Euro Class System leads to a large number of

    reaction-to-fire classes in order to reduce need for tests, the so called Classification Without Further Testing (= CWFT)* option is introduced in EU regulations.

    * Also referred to as Deemed to Satisfy option

  • 11 CIE 5131 Fire Safety Design

    Smoke production systematic requirements

    Basis: material properties

    Requirements:

    Specific optic density ( NEN 6066)

    Class reaction to fire ( NEN 6065)

  • 12 CIE 5131 Fire Safety Design

    Smoke production requirements for new structures

    Basic requirement: Dspec < 10 m-1

    Escape routes:

    Dspec < 5,4 m-1, in case of class 1 NEN 6065

    Dspec < 2,2 m-1, in case of class 2 NEN 6065

    Note: requirements are for the inside of walls, ceilings etc.

    ID

    I 010

    logwith:

    - I0 is light intensity without smoke

    - I is light intensity with smoke Dspec

    V

    ALD

  • 13 CIE 5131 Fire Safety Design

    Fire spread and controllability

    Systematic requirements

    Basis: structural behaviour

    Properties:

    Resistance against fire spread inside the building Weerstand tegen branddoorslag (WBD) Resistance against fire spread via facades Weerstand tegen brandoverslag (WBO)

    WBDBO NEN 6068

  • 14 CIE 5131 Fire Safety Design

    Branddoorslag en Brandoverslag

    Explanation

    Fire extension A B,C:

    - inside the building

    (branddoorslag)

    - via facade (brandoverslag)

    A

    B

    C

  • 15 CIE 5131 Fire Safety Design

    WBDBO Definitions

    WBD: (fire resistance) ( NEN 6069, -- 71 t/m 73)

    WBO: time after which radiation level > 15 kW/m2 ( NEN 6068)

    WBDBO: min (WBD, WBO)

    Fire compartment: maximum fire extension area within x min.

  • 16 CIE 5131 Fire Safety Design

    Fire spread via facade - assessment

    Verification procedure:

    - determine the most irradiated location for each

    window opening.

    - verify: radiation level < 15 kW/m2

    (zie NEN 6068)

    Support tools:

    - NPR (tables)

    - software (BRANDO e.a.)

  • 17 CIE 5131 Fire Safety Design

    Fire spread quantified requirements

    Range WBDBO: (20), 30 of 60 minutes, i.e.:

    between fire compartments: 60 min.*)

    between fire compartments and shaft: 60 min.

    ...

    Refer to document no. 7 ...

    Max. floor area fire compartment

    Usually: 1000 m2

    Hotel: 500 m2

    *) In case of buildings with a height < 5 m: 30 min.

  • 18 CIE 5131 Fire Safety Design

    Fire spread spiegelsymmetrie

    Country-specific

    Netherlands:

  • 19 CIE 5131 Fire Safety Design

    Resistance to fire Type of requirements

    Basis: structural behaviour

    Properties: structural failure in case of fire exposure

    concrete structures*) ( EN 1992-1-2 and NEN 6071)

    steel structures*) ( EN 1993-1-2 and NEN 6072)

    steel-concrete structures*)( EN 1994-1-2)

    timber structures*) ( EN 1995-1-2 NEN 6073)

    masonry structures*) ( EN 1996-1-2)

    aluminium structures*) ( EN 1999-1-2)

    other structures**) ( NEN 6069) *) assessment via calculations

    **) assessment via experiments (component approach & standard

    temperature-time curve)

  • 20 CT5131 Fire Safety Design

    Resistance to fire quantified requirements

    Escape routes: 30 min.

    Resistance of main load bearing structure:

    dwellings

    red: reduction of 30 min. in case

    the permanent fire density < 500

    MJ/m2

    other buildings

    no sleeping

    other buildings

    sleeping

    no sleeping: office

    school

    shop

    sleeping: hospital

    hotel

    prison

  • 21 CIE 5131 Fire Safety Design

    Resistance to fire: main load bearing

    structure

    main load bearing structure: parts of

    the structure whose collapse may

    result in progressive collapse

  • 22 CIE 5131 Fire Safety Design

    Resistance to fire: main load bearing

    structure (1)

    Blue bracings are part of the

    main load bearing structure

    Blue bracings are not part of the

    main load bearing structure

  • 23 CIE 5131 Fire Safety Design

    Resistance to fire: main load bearing

    structure (2)

    Columns: main load bearing structure*)

    120 min

    Floors: ?

    60 or 120 min

    *) except for columns at the upper floor

    13 m

    WBDBO

  • 24 CIE 5131 Fire Safety Design

    Resistance to fire - summary

    Types of requirements:

    fire spread

    structural failure

    Point of departure Dutch regulations: Standaardbrand

    Levels: (20), 30, 60, 90, 120 min

    Differentiated approach FSE

    (ref.: Part 11)

  • 25 CIE 5131 Fire Safety Design

    Escape and escape possibilities types of requirements

    Basis: human behaviour

    Point of departure: ability to manage for oneself

    Properties:

    number, types and lay-out of escape routes

    dimensions and lay-out of smoke compartments

    capacity of staircases

    ...

  • 26 CIE 5131 Fire Safety Design

    Escape and escape possibilities -

    Quantified requirements

    Basic requirements

    maximum walking distance through smoke: 30 m

    escape time of an entire building: within 15 min

    escaping in two directions min.

  • 27 CIE 5131 Fire Safety Design

    Principle of equivalence (Gelijkwaardigheidsbeginsel)

    Principle: It is allowed to deviate from the performance requirements, provided that alternative measures are taken that result in an

    equivalent safety level

    Motivation: flexibility

    Burden of proof: project developer / owner

    Decision: municipality (Bouw-& Woningtoezicht) input from fire brigade

    Examples: FSE (Chapter 12)

  • 28 CIE 5131 Fire Safety Design

    European regulations

    Aim and lay-out of the regulations

    Aim: remove obstructions for trading building products within EU

    Basis: Recommendations of practice and for building products: EN docs.

  • 29 CIE 5131 Fire Safety Design

    EU versus old Dutch regulations

    Fire testing

    reaction-to-fire Euro classes deviate from current Dutch classes

    resistance-to-fire Fire resistance classes similar to Dutch classes

    Calculation standards resistance-to-fire loads

    concrete Eurocodes - similar to Dutch classes

  • 30 CIE 5131 Fire Safety Design

    Eurocodes Fire - overview

    EC (= EN 1990): Principles & combination of actions

    EC1-1.2 (= EN1991-1.2): Actions NEN 6702

    EC2-1.2 (= EN1992-1-2): Concrete NEN 6071

    EC3-1.2 (= EN1993-1-2): Steel NEN 6072

    EC4-1.2 (= EN1994-1-2): Composite

    EC5-1.2 (= EN1995-1-2): Timber NEN 6073

    EC6-1.2 (= EN1996-1-2): Masonry

    EC9-1.2 (= EN1999-1-2): Aluminium

  • 31 CIE 5131 Fire Safety Design

    Eurocodes Fire Levels

    Tabulated data*)**)

    Simple calculation models**)

    Advanced calculation models***)

    *) not for steel and aluminium (EC3, EC9)

    **) based on standard fire

    ***) FSE; not for masonry (EC6)

    Note: NL approach:

    - only components

    - only standard fire