fire-pt3 4 print 2
TRANSCRIPT
-
8/2/2019 Fire-Pt3 4 Print 2
1/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 1
DESIGNING FOR FIRE SAFETY
PARTS 3 and 4
ACTIVE SYSTEMS
And
ACCESS for FIRE FIGHTING and RESCUE
Ar Chong Lee SiongAPAM MIFireE MMIArbs
with
Ir Wong See Foong
FIEM MIFireE PEng CEng PJB
A re-visit to the interpretations and applications
of the Uniform Building By-Laws 1984
Uniform Building By-Laws 1984
is a
PRESCRIPTIVE BUILDING CODE
Compliance with this code is a requirement by law
Sets rules and regulations on the application of the code
Provides pre-determined prescriptions
The prescriptions are absolute :
no smaller than..
no bigger than..
no shorter than
no longer than
or
no less than and no more than.
-
8/2/2019 Fire-Pt3 4 Print 2
2/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 2
CONCEPTS OF FIRE SAFETY
1 EVACUATION
2 PASSIVE CONTAINMENT
3 ACTIVE INTERVENTION
4 ACCESS FOR FIRE FIGHTING AND RESCUE
Time
Te
mperature/size
Stage 1
Ignition & growth
Stage 2
development
Stage 3
Full fire
Stage 4
Decay
Flashover
Untenable condition
NATURE OF FIRE
-
8/2/2019 Fire-Pt3 4 Print 2
3/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 3
Active systems for..
EVACUATION
Detection and Alarm
Communication
Smoke control
Portable fire extinguishers
Temperature/size
Time
Untenablecondition
Available Safe Egress Time ASET
detection
alarm
movementTotal
evacuation
ignition
Required Safe Egress Time RSET
Factor of safety:
RSET < 0.75 ASET
-
8/2/2019 Fire-Pt3 4 Print 2
4/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 4
detection
Very early detection
Early detection
Manual detection
alarm
Automatic
Pre alarm
Local / manual
-
8/2/2019 Fire-Pt3 4 Print 2
5/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 5
FIRE DETECTION AND ALARM
System objective are:
To detect outbreak of fire and warn occupants
To activate fire safety systems
To inform Fire Brigade
To monitor fire safety equipment
RELEVANT BY-LAWS
Under UBBL 237, fire alarm systems are requiredfor buildings defined under the 10th Schedule
Under UBBL 238, a fire command center isrequired for all buildings above 30.5 meters orexceeding 9,290 sq. meters in gross area.
-
8/2/2019 Fire-Pt3 4 Print 2
6/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 6
MAIN FIRE ALARM PANELMain fire alarm panel comprises:
Alarm, fault and isolation indication for each zone.
Indicator lights to monitor status of power supplyand fire safety systems such as fire pumps, smokecontrol equipment, carbon dioxide systems, firetank water levels, etc.
Mimic panel to identify location of each zone.
Battery with charger to provide power supply forthe whole system.
FIRE DETECTION DEVICES
Manual break glass for occupants to activatemanually.
Heat detectors to detect heat intensive fires
automatically for spaces up to 9 meters high. Smoke detectors to detect smoke intensive fires
automatically for spaces up to 10 meters high.
Beam (smoke) detectors for high spaces such asatriums up to 25 meters high.
Flame (IR or UV) detectors
-
8/2/2019 Fire-Pt3 4 Print 2
7/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 7
Heat ..or Smoke?
Smoke detectors for electrical rooms and storerooms.
Heat detectors for general areas.
Smoke detectors for areas where rapid heatdevelopment is normal for the function of thespace, or where combustibles may burn with high
release of smokeHeat detectors for areas where smoke may be a
common presence in the space, or wherecombustibles may burn rapidly and efficiently
VOICE COMMUNICATION SYSTEMS
To guide the occupants in an orderly mannerduring evacuation upon detection of fire.
For the firemen to communicate with one anotherduring fire fighting operations.
-
8/2/2019 Fire-Pt3 4 Print 2
8/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 8
RELEVANT BY-LAW
Under UBBL 239, two voice communicationsystem is required for all large buildings and highrise buildings and they are:
Public address system, and
Fire brigade intercommunication system
PORTABLE FIRE EXTINGUISHERS
Intended for use by the occupants during the earlystages of the fire
Under UBBL 227, portable fire extinguishers arerequired for first aid use.
-
8/2/2019 Fire-Pt3 4 Print 2
9/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 9
CLASSES OF FIRES
Class A: Combustible solids like paper, wood
Class B: Inflammable Liquids like kerosene, diesel
Class C: Flammable gases
Class D: Reactive metals like sodium, potassium,
Class E: Ignition of an electrical nature
Class F: Cooking oil fires
TYPES OF EXTINGUISHERS
Water type for Class A fires
Dry powder type for Class A, B, C and F fires
Carbon Dioxide type for Class E fires
Foam type for Class B fires
Dry powder type of 6 kg for general use.
Carbon Dioxide type for electrical rooms
-
8/2/2019 Fire-Pt3 4 Print 2
10/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 10
LOCATION AND SPACING
Beside exit and staircase doors
Generally located within 20 meters of any potentialhazard
Active systems for..
COMPARTMENTATION
Smoke Control
Extinquishment
Manual
Automatic
-
8/2/2019 Fire-Pt3 4 Print 2
11/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 11
SMOKE CONTROLTYPES
Pressurization system to prevent entry of smokeby pressurizing the compartment with air.
Space depressurization system to prevent thespread of smoke by extraction.
Smoke dilution system to remove the smoke by
extraction and make-up of air.
DEPRESSURIZATION SYSTEMS
Typical application are multi-storey officebuildings.
Floor on fire is maintained under negativepressure by extracting the smoke laden air.
Immediate floors above and below are maintainedat positive pressure by supplying air to thesefloors.
-
8/2/2019 Fire-Pt3 4 Print 2
12/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 12
DILUTION SYSTEMS
Typical application are basement car parks andshopping complexes.
Smoke is extracted from zone on fire.
Make-up air is provided to zones adjacent to areaon fire.
HOSE REELS
Intended for the occupants to use during earlystages of the fire
-
8/2/2019 Fire-Pt3 4 Print 2
13/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 13
LOCATION AND SPACING
Near exit and staircase doors
All spaces to be within 36 meters of a hose reel.
No restriction on location of hose reel pumps andtanks.
-
8/2/2019 Fire-Pt3 4 Print 2
14/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 14
SPRINKLER SYSTEM
Intended to detect and extinguish a fire and warnthe occupants to evacuate.
Under UBBL 226, automatic sprinkler systems arerequired for storage and other types of
occupancies where automatic extinguishingsystem is necessary.
-
8/2/2019 Fire-Pt3 4 Print 2
15/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 15
TYPES OF SYSTEMS
Wet pipe system where pipe work is charged withwater at all times.
Dry pipe system where pipe is charged with wateronly after the sprinkler head is activated.
Pre-action system where system is charged withwater after fire is detected but before the sprinklerhead is activated.
Deluge system where water is dischargedsimultaneously from all sprinkler heads uponactivation.
TYPES OF HAZARDS
Light Hazard e.g. apartments, schools
Ordinary Hazards:
OH Group I : Offices, restaurants
OH Group II : Laundries, bakeriesOH Group III : Departmental Stores, Car parks
OH Group IV : Film and television studios
High Hazards:
Process risks
High piled storage risks
-
8/2/2019 Fire-Pt3 4 Print 2
16/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 16
SPRINKLER TANKS
Typical location at ground or first basementalthough no restriction on the location except fordistance from pump.
AREAS EXEMPTED
Transformer Rooms;
Switch gear Rooms;Lift Motor Rooms; and
Toilets;
-
8/2/2019 Fire-Pt3 4 Print 2
17/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 17
INSTALLATION CONTROL VALVE
Water supply to sprinklers feed fromInstallation control valve with alarm gong andshut-off valves.
For life safety systems, Sprinklers are grouped
such that each zone does not have more than200 sprinkler heads with its own flow switch.
-
8/2/2019 Fire-Pt3 4 Print 2
18/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 18
SPRINKLER PIPE WORK
The height between the lowest and highestsprinkler within one stage not to exceed 45 m.
For buildings exceeding 45 m., multiple stages arerequired.
Express risers are permitted to bypass lower
stgages and serve the upper stage.
8. CARBON DIOXIDE EXTINGUISHINGSYSTEM
System using carbon dioxide to extinguish a fireby excluding oxygen from the fire and commonlyused for electrical rooms where water may not besuitable.
The by-law relevant to this system is UBBL 235.
-
8/2/2019 Fire-Pt3 4 Print 2
19/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 19
TYPES OF SYSTEMS
Total Flooding System uses CO2 to displaceoxygen within entire room.
Local Application creates envelope around fire andexclude oxygen around the fire only.
-
8/2/2019 Fire-Pt3 4 Print 2
20/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 20
AUTOMATIC ACTIVATION
Heat and smoke detectors installed to detect fire.
Activation of one detector initiates alarm but notgas discharge.
Activation of any two detectors initiates gasdischarge.
Time delay of 30 sec. before gas discharge.
MANUAL ACTIVATION
Manual activation by pull station in event of
failure of automatic activation. Pull station to be outside of room protected.
Audio and visual warning activated upon gasdischarge to warn occupants from entering.
-
8/2/2019 Fire-Pt3 4 Print 2
21/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 21
Active systems for..
FIRE FIGHTING and RESCUE
Lifts
Risers
Hydrants
FIRE LIFT
Intended to assist the firemen to reach the floors onfire rapidly.
Under UBBL 243, any building exceeding 18.5meters high shall be provided with firemens lift.
-
8/2/2019 Fire-Pt3 4 Print 2
22/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 22
LOCATION AND SPACING
Not more than 61 meters from the furthermostpoint of the floor.
Not more than 61 meters from the main entranceof the building or the fire control room whicheveris nearer.
DESIGN REQUIREMENTS
Lift capacity to be able to carry 550kg. min.
Lift car platform size to be not less than 1.45 sq.
meters. Lift car door to be min. 800 mm clear in width.
Lift to serve all occupied floors.
-
8/2/2019 Fire-Pt3 4 Print 2
23/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 23
FIRE MODE OF OPERATION
Lift to be provided with emergency power foroperation during power failure.
Lift to return to main landing upon detection ofpower failure and remain inoperable until firemenarrive.
Fire switch to be provided at main landing for
firemen to activate the lift for their use.
DRY RISER SYSTEMS
Intended for the firemen to pump water up to thefloors on fire.
Under UBBL 230, dry risers required for allbuildings with topmost floor above 18.3 metersfrom fire appliance access level
-
8/2/2019 Fire-Pt3 4 Print 2
24/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 24
LOCATION AND SPACING
Landing valves located within fire access lobbies.
Provided on every upper floor such that all spacesare within 45 m from a landing valve.
Breeching inlet to be no more than 18 m. from fireappliance access road and not more than 30 metersfrom nearest outdoor hydrant.
-
8/2/2019 Fire-Pt3 4 Print 2
25/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 25
DRY RISER PIPE WORK
Dry riser to be 100 mm dia. If highest outlet is nomore than 23 m. above breeching inlet.
Dry riser to be 150 mm dia. If highest outlet ismore than 23 m. above breeching inlet.
5. WET RISER SYSTEMS
Intended to supply water up to the floors on firefor the firemen to use.
Under UBBL 231, wet risers required for allbuildings with topmost floor above 30.5m. Fromthe fire appliance access level.
-
8/2/2019 Fire-Pt3 4 Print 2
26/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 26
LOCATION AND SPACING
Landing valves located within fire access lobbies.
Provided on every upper floor such that all spacesare within 45 m from a landing valve.
Distance between landing valves on the same floornot to exceed 60 m.
Breeching inlet to be no more than 18 m. from fireappliance access road and not more than 30 metersfrom nearest outdoor hydrant.
-
8/2/2019 Fire-Pt3 4 Print 2
27/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 27
PUMPS AND PIPE WORK
Each stack not to exceed 60 m or 71 m if approvedby the Director General of Fire and Rescue Dept.
Stack height is defined as the height from the wetriser pump to the topmost floor protected.
WET RISER PUMPS AND TANKS
Location of wet riser pumps and tanks restricted toground, first or second basement.
Lowest basement may not be premitted due topossibility of flooding.
-
8/2/2019 Fire-Pt3 4 Print 2
28/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 28
6. DOWNCOMER SYSTEMS
Intended to provide water from roof fire tank tothe floors on fire using static head available.
Only permitted for private residential buildingswhere the topmost floor is no higher than 60 m.above fire appliance access level.
-
8/2/2019 Fire-Pt3 4 Print 2
29/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 29
LOCATION AND SPACING
Landing valves located within fire access lobbies
Provided on every upper floor such that all spacesare within 45 m from a landing valve.
Breeching inlet to be no more than 18 m. from fire
appliance access road and not more than 30 metersfrom nearest outdoor hydrant.
DOWNCOMER TANKS
Tanks located on roof of building for maximum
pressure.
-
8/2/2019 Fire-Pt3 4 Print 2
30/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 30
196, 197 - smoke lobbies, protected lobbies
198, 199, 200, 201 ventilation of stairs
229 fire fighting lobbies
UBBL
Protection of stairs and lobbies
Protection of stairs and lobbies
Protected Lobby : protected lobby separated orisolated from fire and smoke infiltration
Smoke Lobby : a protected lobby primarily toisolate staircases from smoke infiltration
ventilated lobby : protected/smoke lobby bymeans of natural ventilation from outside
Fire Fighting Access Lobby : a protectedlobby designed for fire fighting access
-
8/2/2019 Fire-Pt3 4 Print 2
31/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 31
SMOKE CONTROL SYSTEMS
To control the spread of smoke from the source offire to other occupied spaces and maintainvisibility as much as possible during evacuation.
RELEVANT BY-LAWS
Under UBBL clauses 196 and 197 requires firefighting access lobbies and smoke lobbies to be
pressurized if natural ventilation cannot beprovided.
Under UBBL clauses 200, 201 and 202 requiresescape staircases to be pressurized if naturalventilation cannot be provided.
-
8/2/2019 Fire-Pt3 4 Print 2
32/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 32
STAIRCASE PRESSURIZATION
Entire staircase pressurized with air.
Air pressure within staircase is controlled topermit opening of exit doors without the need ofexcessive force.
LIFT LOBBY PRESSURIZATION
Lift lobbies are individually pressurized with air.
Air pressure within lift lobbies is controlled topermit opening of exit doors without the need ofexcessive force.
-
8/2/2019 Fire-Pt3 4 Print 2
33/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 33
Protected
lobby
requirement
for building >
18m
(By-Law 197)
External wall
Protected
lobby
requirement Building more than
18m above ground
level
No protected
lobby required
Ventilation opening
No protected
lobby required
Omission of
protected lobby
for pressurised
staircase for
buildingsbelow 45m For building
above
18m but below
45m
No protected
lobby
required
Ventilated
opening
Staircase
pressurised
-
8/2/2019 Fire-Pt3 4 Print 2
34/56
-
8/2/2019 Fire-Pt3 4 Print 2
35/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 35
UBBL 229
EXTERNAL FIRE HYDRANTS
System of Pipe work connected to public watermains to provide water for the pumps in the fire
engine.
For industrial plants, fire pumps have to beprovided where flow is unreliable or pressure isinadequate
-
8/2/2019 Fire-Pt3 4 Print 2
36/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 36
RELEVANT BY-LAWS
Under UBBL 225, every building shall beprovided with at least one fire hydrant.
-
8/2/2019 Fire-Pt3 4 Print 2
37/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 37
Hydrants should be located:
i) away from obstructions such as street furniture (benches), phone
booths, etc.
ii) not less than 2,000mm from adjacent buildings and overhangs.
iii) between 610mm to 2,400mm from Fire Appliance Access.
iv) away from risks of vehicular damage.
v) not more than 90m apart from each other (in new buildings adjacent
to existing developments, a new hydrant within 45m radius of the new
building).
-
8/2/2019 Fire-Pt3 4 Print 2
38/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 38
No overhangs
over hydrants
Verandah
Pavement
Access
Hydrant
Building
EMERGENCY POWER SUPPLY
Intended to provide emergency power to operateall fire safety systems.
Under UBBL 253, emergency power is to beprovided for fire pumps, fire lifts, fire alarm,smoke control, emergency lighting, voicecommunication, firemen intercom, etc.
-
8/2/2019 Fire-Pt3 4 Print 2
39/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 39
SOURCES OF EMERGENCY POWER
Standby electrical generator with changeoverswitch activated upon power failure;
Battery banks with charger to maintain them incharged condition.
LOCATION
Generator to be located at ground or first basementfor easy access by firemen.
Outdoor air required to cool diesel enginesradiator.
-
8/2/2019 Fire-Pt3 4 Print 2
40/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 40
INTEGRATION WITH PASSIVE SYSTEMS
Under UBBL clauses 136, limits of dimensions forcompartmentation can be doubled with theprovision of automatic sprinkler system.
INTEGRATION WITH PASSIVE SYSTEMS
Under UBBL clause 202, escape staircases have tobe pressurized if inadequate natural ventilation is
provided.
Likewise under UBBL clause 196(5), smoke lobbieshave to be pressurized or ventilated if naturalventilation is inadequate.
-
8/2/2019 Fire-Pt3 4 Print 2
41/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 41
INTEGRATION WITH PASSIVE SYSTEMS
Under UBBL clauses 250 for smoke venting,mechanically operated smoke vents have to beprovided if there are inadequate openings forsmoke venting.
INTERFACE WITH PASSIVE SYSTEMS
Under UBBL clauses 164(3), fire doors can be heldopen provided the device incorporates a heat
activated mechanism to release the door.
However, this cannot be used for doors toprotected corridors or staircases.
-
8/2/2019 Fire-Pt3 4 Print 2
42/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 42
INTERFACE WITH PASSIVE SYSTEMS
Fire shutters to meet compartmentationrequirements can be left open until activatedby fire alarm.
Glass curtain walls can be utilized to contain
smoke and fire if water spray or water curtainis provided to cool the glass.
FIRE APPLIANCE ACCESS
Refers to an area Access Way specifically allocated for the
parkingof Bomba appliances during fire fighting andrescue operations.
UBBL 140
Access Way (street, road or open space) is to be providedas a proportion of the perimeter of the building, withreference to the volume of the building.
-
8/2/2019 Fire-Pt3 4 Print 2
43/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 43
EXTERNAL ACCESS
Access for emergency and rescue vehicles,equipment and personnel
RoadsPavementsParking
Availability of water :HydrantsStorage tanksLakes, rivers, ponds
And access to fire fighting systems in the premises
Clarity of :Type of building and functionConfiguration of buildingLocation of fire control panelLocation of breaching inlets and pump rooms
AT THE PREMISES
Access into the buildingProtected passageProtected stairsFiremens liftFire fighting lobby
-
8/2/2019 Fire-Pt3 4 Print 2
44/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 44
Pressurised Hydrant System
Sprinkler System
-
8/2/2019 Fire-Pt3 4 Print 2
45/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 45
Dry Riser system
Wet Riser System
-
8/2/2019 Fire-Pt3 4 Print 2
46/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 46
External source of water
Hydrants
Lakes, Ponds, Pools, rivers
Fire Tenders
Fire Fighting Appliance
on Access Way
Internal Systems
Sprinklers
Hose reels
Dry/Wet Risers
Breaching Inlet
Vehicles in use by JBPM :
Motorcycle
Terrain buggy
Rapid Fire Rescue Tender
Fire Rescue Tender
Turntable ladder
Hydraulic platform
Hazmat
-
8/2/2019 Fire-Pt3 4 Print 2
47/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 47
Rapid response motorcycles
Terrain buggy
-
8/2/2019 Fire-Pt3 4 Print 2
48/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 48
Rapid Fire Rescue Tender
Fire Rescue Tender (medium)
-
8/2/2019 Fire-Pt3 4 Print 2
49/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 49
Fire Rescue Tender (light)
HAZMAT tender
-
8/2/2019 Fire-Pt3 4 Print 2
50/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 50
Turntable ladders
Pump tanker
-
8/2/2019 Fire-Pt3 4 Print 2
51/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 51
Hydraulic platforms
Fire appliance
access level and
Access Way
Access Way at upper ground level
-
8/2/2019 Fire-Pt3 4 Print 2
52/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 52
13,000 m3 (1/6)
8,600m3
(1/6)
36,000m3
(1/4)
Access way at appliance access level
Access way at upper ground level
Access road / rampAccess road
/ ramp
Note: Turning provision required for fire appliances if dead end access
exceeds 18 m.
Turning provision can be in the form of hammer-head or turning
circle
Building volume
7,001 cu m
to 28,000 cu m
D
A
B
Isolated site/location
with no adjacent
property/building.
X => 1/6 (A+B+C+D)
Fire appliance
accessX
C
-
8/2/2019 Fire-Pt3 4 Print 2
53/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 53
C => 1/6 (A+B+C+D)
Appliance access from main road is sufficient if the building volume does not exceed
28,000 m3.
In the event the 6 m back lane is accessible by fire fighting appliances and the
building volume exceeds 28,000 m3 but is less than 56,000 m3, then,
A + C => 1/4 (A+B+C+D)
Building volume
7,001 cu m
to 28,000 cu m
City/Built up location
with adjacent buildings D
A
B
C
Accessible perimeter
of building
Main road used for
appliance access
if not less than 12m wide
Pavement
6m back lane
D
A
B
D
A
C
Access
road
> 18m
Building volume
56,001 cu m to
84,000 cu m
min. 6m
B + C => 1/2 (A+B+C+D)
C
Fire appliance access Access road
12m
B
6m back lane
accessible to fire appliance
Pavement
Access road
12mA + C => 1/2 (A+B+C+D)
-
8/2/2019 Fire-Pt3 4 Print 2
54/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 54
D
Fire appliance
access minimum6m width
Building volume
84,001 cu m to
112,000 cu m
A + B + C 3/4 (A+B+C+D)
A
B
C
Access road 12m
D
A
B
Building volume
84,001 cu m to
112,000 cu m
B + C + D => 3/4 (A+B+C+D)
C
Access road 12m
-
8/2/2019 Fire-Pt3 4 Print 2
55/56
ctive Fire Safety Systems 9/29/2011
hong lee siong 55
A
Building
volume
above112,000 cu m
Minimum 6m width
Fire appliance access
D B
C
Access road 12m
W2
(min 6m)
L(13m)
L(13m) min. 6mW1
d1
d2
W = unobstructed width of Appliance Access
L = length of largest Fire Appliance (currently 13m)
d - cut-back distance is obtained by intersecting the imaginary corner of a
building with line A - C
The minimum permissible width of a Fire Appliance Access is 6.0m.
The minimum turning radius around corners of buildings shall be provided as follows:
-
8/2/2019 Fire-Pt3 4 Print 2
56/56
ctive Fire Safety Systems 9/29/2011
Thank you !