fire-pt3 4 print 2

Upload: simon-lee-s-e

Post on 06-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 Fire-Pt3 4 Print 2

    1/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 1

    DESIGNING FOR FIRE SAFETY

    PARTS 3 and 4

    ACTIVE SYSTEMS

    And

    ACCESS for FIRE FIGHTING and RESCUE

    Ar Chong Lee SiongAPAM MIFireE MMIArbs

    with

    Ir Wong See Foong

    FIEM MIFireE PEng CEng PJB

    A re-visit to the interpretations and applications

    of the Uniform Building By-Laws 1984

    Uniform Building By-Laws 1984

    is a

    PRESCRIPTIVE BUILDING CODE

    Compliance with this code is a requirement by law

    Sets rules and regulations on the application of the code

    Provides pre-determined prescriptions

    The prescriptions are absolute :

    no smaller than..

    no bigger than..

    no shorter than

    no longer than

    or

    no less than and no more than.

  • 8/2/2019 Fire-Pt3 4 Print 2

    2/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 2

    CONCEPTS OF FIRE SAFETY

    1 EVACUATION

    2 PASSIVE CONTAINMENT

    3 ACTIVE INTERVENTION

    4 ACCESS FOR FIRE FIGHTING AND RESCUE

    Time

    Te

    mperature/size

    Stage 1

    Ignition & growth

    Stage 2

    development

    Stage 3

    Full fire

    Stage 4

    Decay

    Flashover

    Untenable condition

    NATURE OF FIRE

  • 8/2/2019 Fire-Pt3 4 Print 2

    3/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 3

    Active systems for..

    EVACUATION

    Detection and Alarm

    Communication

    Smoke control

    Portable fire extinguishers

    Temperature/size

    Time

    Untenablecondition

    Available Safe Egress Time ASET

    detection

    alarm

    movementTotal

    evacuation

    ignition

    Required Safe Egress Time RSET

    Factor of safety:

    RSET < 0.75 ASET

  • 8/2/2019 Fire-Pt3 4 Print 2

    4/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 4

    detection

    Very early detection

    Early detection

    Manual detection

    alarm

    Automatic

    Pre alarm

    Local / manual

  • 8/2/2019 Fire-Pt3 4 Print 2

    5/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 5

    FIRE DETECTION AND ALARM

    System objective are:

    To detect outbreak of fire and warn occupants

    To activate fire safety systems

    To inform Fire Brigade

    To monitor fire safety equipment

    RELEVANT BY-LAWS

    Under UBBL 237, fire alarm systems are requiredfor buildings defined under the 10th Schedule

    Under UBBL 238, a fire command center isrequired for all buildings above 30.5 meters orexceeding 9,290 sq. meters in gross area.

  • 8/2/2019 Fire-Pt3 4 Print 2

    6/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 6

    MAIN FIRE ALARM PANELMain fire alarm panel comprises:

    Alarm, fault and isolation indication for each zone.

    Indicator lights to monitor status of power supplyand fire safety systems such as fire pumps, smokecontrol equipment, carbon dioxide systems, firetank water levels, etc.

    Mimic panel to identify location of each zone.

    Battery with charger to provide power supply forthe whole system.

    FIRE DETECTION DEVICES

    Manual break glass for occupants to activatemanually.

    Heat detectors to detect heat intensive fires

    automatically for spaces up to 9 meters high. Smoke detectors to detect smoke intensive fires

    automatically for spaces up to 10 meters high.

    Beam (smoke) detectors for high spaces such asatriums up to 25 meters high.

    Flame (IR or UV) detectors

  • 8/2/2019 Fire-Pt3 4 Print 2

    7/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 7

    Heat ..or Smoke?

    Smoke detectors for electrical rooms and storerooms.

    Heat detectors for general areas.

    Smoke detectors for areas where rapid heatdevelopment is normal for the function of thespace, or where combustibles may burn with high

    release of smokeHeat detectors for areas where smoke may be a

    common presence in the space, or wherecombustibles may burn rapidly and efficiently

    VOICE COMMUNICATION SYSTEMS

    To guide the occupants in an orderly mannerduring evacuation upon detection of fire.

    For the firemen to communicate with one anotherduring fire fighting operations.

  • 8/2/2019 Fire-Pt3 4 Print 2

    8/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 8

    RELEVANT BY-LAW

    Under UBBL 239, two voice communicationsystem is required for all large buildings and highrise buildings and they are:

    Public address system, and

    Fire brigade intercommunication system

    PORTABLE FIRE EXTINGUISHERS

    Intended for use by the occupants during the earlystages of the fire

    Under UBBL 227, portable fire extinguishers arerequired for first aid use.

  • 8/2/2019 Fire-Pt3 4 Print 2

    9/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 9

    CLASSES OF FIRES

    Class A: Combustible solids like paper, wood

    Class B: Inflammable Liquids like kerosene, diesel

    Class C: Flammable gases

    Class D: Reactive metals like sodium, potassium,

    Class E: Ignition of an electrical nature

    Class F: Cooking oil fires

    TYPES OF EXTINGUISHERS

    Water type for Class A fires

    Dry powder type for Class A, B, C and F fires

    Carbon Dioxide type for Class E fires

    Foam type for Class B fires

    Dry powder type of 6 kg for general use.

    Carbon Dioxide type for electrical rooms

  • 8/2/2019 Fire-Pt3 4 Print 2

    10/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 10

    LOCATION AND SPACING

    Beside exit and staircase doors

    Generally located within 20 meters of any potentialhazard

    Active systems for..

    COMPARTMENTATION

    Smoke Control

    Extinquishment

    Manual

    Automatic

  • 8/2/2019 Fire-Pt3 4 Print 2

    11/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 11

    SMOKE CONTROLTYPES

    Pressurization system to prevent entry of smokeby pressurizing the compartment with air.

    Space depressurization system to prevent thespread of smoke by extraction.

    Smoke dilution system to remove the smoke by

    extraction and make-up of air.

    DEPRESSURIZATION SYSTEMS

    Typical application are multi-storey officebuildings.

    Floor on fire is maintained under negativepressure by extracting the smoke laden air.

    Immediate floors above and below are maintainedat positive pressure by supplying air to thesefloors.

  • 8/2/2019 Fire-Pt3 4 Print 2

    12/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 12

    DILUTION SYSTEMS

    Typical application are basement car parks andshopping complexes.

    Smoke is extracted from zone on fire.

    Make-up air is provided to zones adjacent to areaon fire.

    HOSE REELS

    Intended for the occupants to use during earlystages of the fire

  • 8/2/2019 Fire-Pt3 4 Print 2

    13/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 13

    LOCATION AND SPACING

    Near exit and staircase doors

    All spaces to be within 36 meters of a hose reel.

    No restriction on location of hose reel pumps andtanks.

  • 8/2/2019 Fire-Pt3 4 Print 2

    14/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 14

    SPRINKLER SYSTEM

    Intended to detect and extinguish a fire and warnthe occupants to evacuate.

    Under UBBL 226, automatic sprinkler systems arerequired for storage and other types of

    occupancies where automatic extinguishingsystem is necessary.

  • 8/2/2019 Fire-Pt3 4 Print 2

    15/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 15

    TYPES OF SYSTEMS

    Wet pipe system where pipe work is charged withwater at all times.

    Dry pipe system where pipe is charged with wateronly after the sprinkler head is activated.

    Pre-action system where system is charged withwater after fire is detected but before the sprinklerhead is activated.

    Deluge system where water is dischargedsimultaneously from all sprinkler heads uponactivation.

    TYPES OF HAZARDS

    Light Hazard e.g. apartments, schools

    Ordinary Hazards:

    OH Group I : Offices, restaurants

    OH Group II : Laundries, bakeriesOH Group III : Departmental Stores, Car parks

    OH Group IV : Film and television studios

    High Hazards:

    Process risks

    High piled storage risks

  • 8/2/2019 Fire-Pt3 4 Print 2

    16/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 16

    SPRINKLER TANKS

    Typical location at ground or first basementalthough no restriction on the location except fordistance from pump.

    AREAS EXEMPTED

    Transformer Rooms;

    Switch gear Rooms;Lift Motor Rooms; and

    Toilets;

  • 8/2/2019 Fire-Pt3 4 Print 2

    17/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 17

    INSTALLATION CONTROL VALVE

    Water supply to sprinklers feed fromInstallation control valve with alarm gong andshut-off valves.

    For life safety systems, Sprinklers are grouped

    such that each zone does not have more than200 sprinkler heads with its own flow switch.

  • 8/2/2019 Fire-Pt3 4 Print 2

    18/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 18

    SPRINKLER PIPE WORK

    The height between the lowest and highestsprinkler within one stage not to exceed 45 m.

    For buildings exceeding 45 m., multiple stages arerequired.

    Express risers are permitted to bypass lower

    stgages and serve the upper stage.

    8. CARBON DIOXIDE EXTINGUISHINGSYSTEM

    System using carbon dioxide to extinguish a fireby excluding oxygen from the fire and commonlyused for electrical rooms where water may not besuitable.

    The by-law relevant to this system is UBBL 235.

  • 8/2/2019 Fire-Pt3 4 Print 2

    19/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 19

    TYPES OF SYSTEMS

    Total Flooding System uses CO2 to displaceoxygen within entire room.

    Local Application creates envelope around fire andexclude oxygen around the fire only.

  • 8/2/2019 Fire-Pt3 4 Print 2

    20/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 20

    AUTOMATIC ACTIVATION

    Heat and smoke detectors installed to detect fire.

    Activation of one detector initiates alarm but notgas discharge.

    Activation of any two detectors initiates gasdischarge.

    Time delay of 30 sec. before gas discharge.

    MANUAL ACTIVATION

    Manual activation by pull station in event of

    failure of automatic activation. Pull station to be outside of room protected.

    Audio and visual warning activated upon gasdischarge to warn occupants from entering.

  • 8/2/2019 Fire-Pt3 4 Print 2

    21/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 21

    Active systems for..

    FIRE FIGHTING and RESCUE

    Lifts

    Risers

    Hydrants

    FIRE LIFT

    Intended to assist the firemen to reach the floors onfire rapidly.

    Under UBBL 243, any building exceeding 18.5meters high shall be provided with firemens lift.

  • 8/2/2019 Fire-Pt3 4 Print 2

    22/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 22

    LOCATION AND SPACING

    Not more than 61 meters from the furthermostpoint of the floor.

    Not more than 61 meters from the main entranceof the building or the fire control room whicheveris nearer.

    DESIGN REQUIREMENTS

    Lift capacity to be able to carry 550kg. min.

    Lift car platform size to be not less than 1.45 sq.

    meters. Lift car door to be min. 800 mm clear in width.

    Lift to serve all occupied floors.

  • 8/2/2019 Fire-Pt3 4 Print 2

    23/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 23

    FIRE MODE OF OPERATION

    Lift to be provided with emergency power foroperation during power failure.

    Lift to return to main landing upon detection ofpower failure and remain inoperable until firemenarrive.

    Fire switch to be provided at main landing for

    firemen to activate the lift for their use.

    DRY RISER SYSTEMS

    Intended for the firemen to pump water up to thefloors on fire.

    Under UBBL 230, dry risers required for allbuildings with topmost floor above 18.3 metersfrom fire appliance access level

  • 8/2/2019 Fire-Pt3 4 Print 2

    24/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 24

    LOCATION AND SPACING

    Landing valves located within fire access lobbies.

    Provided on every upper floor such that all spacesare within 45 m from a landing valve.

    Breeching inlet to be no more than 18 m. from fireappliance access road and not more than 30 metersfrom nearest outdoor hydrant.

  • 8/2/2019 Fire-Pt3 4 Print 2

    25/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 25

    DRY RISER PIPE WORK

    Dry riser to be 100 mm dia. If highest outlet is nomore than 23 m. above breeching inlet.

    Dry riser to be 150 mm dia. If highest outlet ismore than 23 m. above breeching inlet.

    5. WET RISER SYSTEMS

    Intended to supply water up to the floors on firefor the firemen to use.

    Under UBBL 231, wet risers required for allbuildings with topmost floor above 30.5m. Fromthe fire appliance access level.

  • 8/2/2019 Fire-Pt3 4 Print 2

    26/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 26

    LOCATION AND SPACING

    Landing valves located within fire access lobbies.

    Provided on every upper floor such that all spacesare within 45 m from a landing valve.

    Distance between landing valves on the same floornot to exceed 60 m.

    Breeching inlet to be no more than 18 m. from fireappliance access road and not more than 30 metersfrom nearest outdoor hydrant.

  • 8/2/2019 Fire-Pt3 4 Print 2

    27/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 27

    PUMPS AND PIPE WORK

    Each stack not to exceed 60 m or 71 m if approvedby the Director General of Fire and Rescue Dept.

    Stack height is defined as the height from the wetriser pump to the topmost floor protected.

    WET RISER PUMPS AND TANKS

    Location of wet riser pumps and tanks restricted toground, first or second basement.

    Lowest basement may not be premitted due topossibility of flooding.

  • 8/2/2019 Fire-Pt3 4 Print 2

    28/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 28

    6. DOWNCOMER SYSTEMS

    Intended to provide water from roof fire tank tothe floors on fire using static head available.

    Only permitted for private residential buildingswhere the topmost floor is no higher than 60 m.above fire appliance access level.

  • 8/2/2019 Fire-Pt3 4 Print 2

    29/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 29

    LOCATION AND SPACING

    Landing valves located within fire access lobbies

    Provided on every upper floor such that all spacesare within 45 m from a landing valve.

    Breeching inlet to be no more than 18 m. from fire

    appliance access road and not more than 30 metersfrom nearest outdoor hydrant.

    DOWNCOMER TANKS

    Tanks located on roof of building for maximum

    pressure.

  • 8/2/2019 Fire-Pt3 4 Print 2

    30/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 30

    196, 197 - smoke lobbies, protected lobbies

    198, 199, 200, 201 ventilation of stairs

    229 fire fighting lobbies

    UBBL

    Protection of stairs and lobbies

    Protection of stairs and lobbies

    Protected Lobby : protected lobby separated orisolated from fire and smoke infiltration

    Smoke Lobby : a protected lobby primarily toisolate staircases from smoke infiltration

    ventilated lobby : protected/smoke lobby bymeans of natural ventilation from outside

    Fire Fighting Access Lobby : a protectedlobby designed for fire fighting access

  • 8/2/2019 Fire-Pt3 4 Print 2

    31/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 31

    SMOKE CONTROL SYSTEMS

    To control the spread of smoke from the source offire to other occupied spaces and maintainvisibility as much as possible during evacuation.

    RELEVANT BY-LAWS

    Under UBBL clauses 196 and 197 requires firefighting access lobbies and smoke lobbies to be

    pressurized if natural ventilation cannot beprovided.

    Under UBBL clauses 200, 201 and 202 requiresescape staircases to be pressurized if naturalventilation cannot be provided.

  • 8/2/2019 Fire-Pt3 4 Print 2

    32/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 32

    STAIRCASE PRESSURIZATION

    Entire staircase pressurized with air.

    Air pressure within staircase is controlled topermit opening of exit doors without the need ofexcessive force.

    LIFT LOBBY PRESSURIZATION

    Lift lobbies are individually pressurized with air.

    Air pressure within lift lobbies is controlled topermit opening of exit doors without the need ofexcessive force.

  • 8/2/2019 Fire-Pt3 4 Print 2

    33/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 33

    Protected

    lobby

    requirement

    for building >

    18m

    (By-Law 197)

    External wall

    Protected

    lobby

    requirement Building more than

    18m above ground

    level

    No protected

    lobby required

    Ventilation opening

    No protected

    lobby required

    Omission of

    protected lobby

    for pressurised

    staircase for

    buildingsbelow 45m For building

    above

    18m but below

    45m

    No protected

    lobby

    required

    Ventilated

    opening

    Staircase

    pressurised

  • 8/2/2019 Fire-Pt3 4 Print 2

    34/56

  • 8/2/2019 Fire-Pt3 4 Print 2

    35/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 35

    UBBL 229

    EXTERNAL FIRE HYDRANTS

    System of Pipe work connected to public watermains to provide water for the pumps in the fire

    engine.

    For industrial plants, fire pumps have to beprovided where flow is unreliable or pressure isinadequate

  • 8/2/2019 Fire-Pt3 4 Print 2

    36/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 36

    RELEVANT BY-LAWS

    Under UBBL 225, every building shall beprovided with at least one fire hydrant.

  • 8/2/2019 Fire-Pt3 4 Print 2

    37/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 37

    Hydrants should be located:

    i) away from obstructions such as street furniture (benches), phone

    booths, etc.

    ii) not less than 2,000mm from adjacent buildings and overhangs.

    iii) between 610mm to 2,400mm from Fire Appliance Access.

    iv) away from risks of vehicular damage.

    v) not more than 90m apart from each other (in new buildings adjacent

    to existing developments, a new hydrant within 45m radius of the new

    building).

  • 8/2/2019 Fire-Pt3 4 Print 2

    38/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 38

    No overhangs

    over hydrants

    Verandah

    Pavement

    Access

    Hydrant

    Building

    EMERGENCY POWER SUPPLY

    Intended to provide emergency power to operateall fire safety systems.

    Under UBBL 253, emergency power is to beprovided for fire pumps, fire lifts, fire alarm,smoke control, emergency lighting, voicecommunication, firemen intercom, etc.

  • 8/2/2019 Fire-Pt3 4 Print 2

    39/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 39

    SOURCES OF EMERGENCY POWER

    Standby electrical generator with changeoverswitch activated upon power failure;

    Battery banks with charger to maintain them incharged condition.

    LOCATION

    Generator to be located at ground or first basementfor easy access by firemen.

    Outdoor air required to cool diesel enginesradiator.

  • 8/2/2019 Fire-Pt3 4 Print 2

    40/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 40

    INTEGRATION WITH PASSIVE SYSTEMS

    Under UBBL clauses 136, limits of dimensions forcompartmentation can be doubled with theprovision of automatic sprinkler system.

    INTEGRATION WITH PASSIVE SYSTEMS

    Under UBBL clause 202, escape staircases have tobe pressurized if inadequate natural ventilation is

    provided.

    Likewise under UBBL clause 196(5), smoke lobbieshave to be pressurized or ventilated if naturalventilation is inadequate.

  • 8/2/2019 Fire-Pt3 4 Print 2

    41/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 41

    INTEGRATION WITH PASSIVE SYSTEMS

    Under UBBL clauses 250 for smoke venting,mechanically operated smoke vents have to beprovided if there are inadequate openings forsmoke venting.

    INTERFACE WITH PASSIVE SYSTEMS

    Under UBBL clauses 164(3), fire doors can be heldopen provided the device incorporates a heat

    activated mechanism to release the door.

    However, this cannot be used for doors toprotected corridors or staircases.

  • 8/2/2019 Fire-Pt3 4 Print 2

    42/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 42

    INTERFACE WITH PASSIVE SYSTEMS

    Fire shutters to meet compartmentationrequirements can be left open until activatedby fire alarm.

    Glass curtain walls can be utilized to contain

    smoke and fire if water spray or water curtainis provided to cool the glass.

    FIRE APPLIANCE ACCESS

    Refers to an area Access Way specifically allocated for the

    parkingof Bomba appliances during fire fighting andrescue operations.

    UBBL 140

    Access Way (street, road or open space) is to be providedas a proportion of the perimeter of the building, withreference to the volume of the building.

  • 8/2/2019 Fire-Pt3 4 Print 2

    43/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 43

    EXTERNAL ACCESS

    Access for emergency and rescue vehicles,equipment and personnel

    RoadsPavementsParking

    Availability of water :HydrantsStorage tanksLakes, rivers, ponds

    And access to fire fighting systems in the premises

    Clarity of :Type of building and functionConfiguration of buildingLocation of fire control panelLocation of breaching inlets and pump rooms

    AT THE PREMISES

    Access into the buildingProtected passageProtected stairsFiremens liftFire fighting lobby

  • 8/2/2019 Fire-Pt3 4 Print 2

    44/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 44

    Pressurised Hydrant System

    Sprinkler System

  • 8/2/2019 Fire-Pt3 4 Print 2

    45/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 45

    Dry Riser system

    Wet Riser System

  • 8/2/2019 Fire-Pt3 4 Print 2

    46/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 46

    External source of water

    Hydrants

    Lakes, Ponds, Pools, rivers

    Fire Tenders

    Fire Fighting Appliance

    on Access Way

    Internal Systems

    Sprinklers

    Hose reels

    Dry/Wet Risers

    Breaching Inlet

    Vehicles in use by JBPM :

    Motorcycle

    Terrain buggy

    Rapid Fire Rescue Tender

    Fire Rescue Tender

    Turntable ladder

    Hydraulic platform

    Hazmat

  • 8/2/2019 Fire-Pt3 4 Print 2

    47/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 47

    Rapid response motorcycles

    Terrain buggy

  • 8/2/2019 Fire-Pt3 4 Print 2

    48/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 48

    Rapid Fire Rescue Tender

    Fire Rescue Tender (medium)

  • 8/2/2019 Fire-Pt3 4 Print 2

    49/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 49

    Fire Rescue Tender (light)

    HAZMAT tender

  • 8/2/2019 Fire-Pt3 4 Print 2

    50/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 50

    Turntable ladders

    Pump tanker

  • 8/2/2019 Fire-Pt3 4 Print 2

    51/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 51

    Hydraulic platforms

    Fire appliance

    access level and

    Access Way

    Access Way at upper ground level

  • 8/2/2019 Fire-Pt3 4 Print 2

    52/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 52

    13,000 m3 (1/6)

    8,600m3

    (1/6)

    36,000m3

    (1/4)

    Access way at appliance access level

    Access way at upper ground level

    Access road / rampAccess road

    / ramp

    Note: Turning provision required for fire appliances if dead end access

    exceeds 18 m.

    Turning provision can be in the form of hammer-head or turning

    circle

    Building volume

    7,001 cu m

    to 28,000 cu m

    D

    A

    B

    Isolated site/location

    with no adjacent

    property/building.

    X => 1/6 (A+B+C+D)

    Fire appliance

    accessX

    C

  • 8/2/2019 Fire-Pt3 4 Print 2

    53/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 53

    C => 1/6 (A+B+C+D)

    Appliance access from main road is sufficient if the building volume does not exceed

    28,000 m3.

    In the event the 6 m back lane is accessible by fire fighting appliances and the

    building volume exceeds 28,000 m3 but is less than 56,000 m3, then,

    A + C => 1/4 (A+B+C+D)

    Building volume

    7,001 cu m

    to 28,000 cu m

    City/Built up location

    with adjacent buildings D

    A

    B

    C

    Accessible perimeter

    of building

    Main road used for

    appliance access

    if not less than 12m wide

    Pavement

    6m back lane

    D

    A

    B

    D

    A

    C

    Access

    road

    > 18m

    Building volume

    56,001 cu m to

    84,000 cu m

    min. 6m

    B + C => 1/2 (A+B+C+D)

    C

    Fire appliance access Access road

    12m

    B

    6m back lane

    accessible to fire appliance

    Pavement

    Access road

    12mA + C => 1/2 (A+B+C+D)

  • 8/2/2019 Fire-Pt3 4 Print 2

    54/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 54

    D

    Fire appliance

    access minimum6m width

    Building volume

    84,001 cu m to

    112,000 cu m

    A + B + C 3/4 (A+B+C+D)

    A

    B

    C

    Access road 12m

    D

    A

    B

    Building volume

    84,001 cu m to

    112,000 cu m

    B + C + D => 3/4 (A+B+C+D)

    C

    Access road 12m

  • 8/2/2019 Fire-Pt3 4 Print 2

    55/56

    ctive Fire Safety Systems 9/29/2011

    hong lee siong 55

    A

    Building

    volume

    above112,000 cu m

    Minimum 6m width

    Fire appliance access

    D B

    C

    Access road 12m

    W2

    (min 6m)

    L(13m)

    L(13m) min. 6mW1

    d1

    d2

    W = unobstructed width of Appliance Access

    L = length of largest Fire Appliance (currently 13m)

    d - cut-back distance is obtained by intersecting the imaginary corner of a

    building with line A - C

    The minimum permissible width of a Fire Appliance Access is 6.0m.

    The minimum turning radius around corners of buildings shall be provided as follows:

  • 8/2/2019 Fire-Pt3 4 Print 2

    56/56

    ctive Fire Safety Systems 9/29/2011

    Thank you !