FILTEMCAC Single Phase Filters FT110/FT111 Series
Features and Benefits
Typical Applications
Electrical Schematics
Rated current: 0.5A~300A
Various terminals: wire, solder lug, stud, terminal
blocks, etc
Optional medical versions(H type)
Custom specific versions available on request
General purpose AC filters with good attenuation performance at frequency range 150KHz~30MHz.
Compact structure, high performance-cost ratio, easy to install, safe and reliable.
FT110 and FT111 series are one-stage common mode filters with almost the same filtering effect,
only slight difference according to different current.
High voltage versions above 380VAC are also available.
Electrical & electronic equipment
Consumer goods
Household appliance
Medical device
Office automation equipment
Datacom equipment
Introduction
Lc
C x
L
N
G
L'
N '
C y
C y
Lc
C x1
L
N
G
L'
N '
C y
C y
R C x2
FT110 FT111
Technical Data
Tabulates
Rated Voltage: VR 110/250VAC
Operating Frequency: fR 50/60Hz
Rated Current: IR 0.5~300A@40℃
Test Voltage: Vtest 1760VDC, 3S(line-line); 2000VAC, 3S(line-ground)
Climatic Category(IEC 60068-1) 25/085/21(-25℃ /+85℃ Damp heat test for 21 days)
Part No.Rated
Current [A]
Leakage Current [mA]250VAC/50Hz
@20℃
Terminals
Weight [g]
-S -L -W -T
FT110-1 1 <0.6 --- --- ○ --- 65
FT110-3 3 <0.6 --- --- ○ --- 65
FT110-6 6 <0.6 --- --- ○ --- 65
FT110-10 10 <0.6 --- ○ --- --- 75
FT111-6 6 <1.0 M4 ○ --- --- 140
FILTEMCAC Single Phase Filters FT110/FT111 Series
Part No.Rated
Current [A]
Leakage Current [mA]250VAC/50Hz
@20℃
Terminals
Weight [g]
-S -L -W -T
FT111-10 10 <1.0 M4 ○ --- --- 170/140
FT111-20 20 <1.0 M4 ○ --- --- 170/140
FT111-30 30 <1.0 M6 --- --- ○ 320/220
FT111-40 40 <3.0 M6 --- --- ○ 550/400
FT111-50 50 <3.0 M6 --- --- ○ 600/550
FT111-60 60 <3.0 M6 --- --- ○ 600/700
FT111-80 80 <3.0 M8 --- --- ○ 1400/1600
FT111-100 100 <3.0 M8 --- --- ○ 1400/1650
FT111-120 120 <3.0 M8 --- --- ○ 1400/1650
FT111-150 150 <3.0 M10 --- --- ○ 1900/2100
FT111-200 200 <3.0 M10 --- --- ○ 1900/2300
FILTEMCAC Single Phase Filters FT110/FT111 Series
Insertion Loss(dB)
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
FILTEM
CR
100dB
80
60
40
20
030M10M
H z
150K 1M
100dB
80
60
40
20
030M10M
H z
150K 1M
FT110-1 FT110-3 FT110- 6 FT110- 10
100dB
80
60
40
20
030M10M
H z
150K 1M
FT111- 6 FT111- 10
100dB
80
60
40
20
030M10M
H z
150K 1M
FT111- 40 FT111- 50
100dB
80
60
40
20
030M10M
H z
150K 1M
FT111- 60 FT111- 80
100dB
80
60
40
20
030M10M
H z
150K 1M
FT111- 100 FT111- 120
100dB
80
60
40
20
030M10M
H z
150K 1M
FT111- 150 FT111- 200
100dB
80
60
40
20
030M10M
H z
150K 1M
FT111- 20 FT111- 30
common mode differential mode
Note: Insertion loss is tested with a system of empty load and 50Ω-50Ω according to UL1283 Standard. The actual effect
please follow the field data of real application.
FILTEMCAC Single Phase Filters FT110/FT111 Series
R
FILTEMC
33±1
46±1
54±0.5
63 M
AX.
23 M A X.
2- 4.0±0.5
56 M A X.
13±0.5
6±0.5
26±0.5
6.3*0.8±0.2
7.3±0.2
Outline Drawing and Dimensions(mm)
FT110-1/3/6 FT110-10
FT111-6/10/20 FT111-6/10
FT111-20 FT111-30
FILTEMCR
FILTEMCR
150 M IN .
51 M
AX
23 M A X.45 M A X.
29±1
40±0.5
2-3.5*4.5±0.5
15±0.5
8±0.5
BU
YEG N
BN
BU
BN
150 M IN .
FILTEMCR
51±1
52 M
AX.
30 M A X.
63±0.5
74 M A X.
10±0.5
22±0.5
4.5±0.5
25±0.5
6.3*0.8±0.2
7.3±0.2
74 M A X.
FILTEMCR2- 4.5±0.5
4-M 4
51±1
63±0.5
52 M
AX.
9±0.5
20±0.5
30 M A X.87 M A X.
3.4±0.5
25±0.5
FILTEMCR2- 4.5±0.5
4-M 4
51±1
63±0.5
52 M
AX.
9±0.5
20±0.5
30 M A X.86 M A X.
2.5±0.5
25±0.5
R
FILTEMC
52 M
AX.
39 M A X.
2- 5±0.5
75±0.5
106 M A X.
25±0.5
9±0.5
25±0.5
4-M 6
4.2±0.5
FILTEMCR
FILTEMCR
63±1
FILTEMCAC Single Phase Filters FT110/FT111 Series
FT111-40/50/60 FT111-80/100/120
FT111-200 FT111-150
FT111-40 FT111-30
R
FILTEMC
139 M A X.
50±0.5
80±1
107 M
AX.
6±0.5 4±0.5
3.8±0.5
95±0.5
42±0.5
44 M A X.
20±0.5
4-M 6
96±1
FILTEMCR
FILTEMCR
103.5±0.5
58 M
AX.
92±1
2-5*6.7±0.5
M 4
37±0.5
10±0.5
31.5±0.5
46 M
AX.
124 M A X.
Outline Drawing and Dimensions(mm) of Terminal Block Series
FILTEMCR
120±2
80±0.5
187 M A X.
115±1
100±2
6±0.5
52 M A X.
28±0.5
66±0.5
132 M
AX.
9±0.5
4-M 8
10±0.5
4±0.5
R
FILTEMC
150±2
90±0.5
226 M A X.
105±2
137 M
AX.
6.5±0.5
10.1±0.5
50±0.5
15±0.5
35±0.5
62 M A X.
120±1
4.5±0.5
4-M 10
R
FILTEMC
150±2
90±0.5
225 M A X.
105±2
137 M
AX.
6.5±0.5
9.7±0.5
50±0.5
15±0.5
35±0.5
62 M A X.
120±1
4.5±0.5
4-M 10
FILTEMCR
FILTEMCR
2- 5±0.5
52 M
AX.
75±0.5
86 M A X.
39 M
AX.
M 4
10±0.5
20.5±0.5
30.5±0.5
63±1
86 M A X.
FILTEMCAC Single Phase Filters FT110/FT111 Series
FT111-60
FT111-100 FT111-80
FT111-120/150 FT111-200
FILTEMCR
FILTEMCR1
0±0.5M 4
120±1
172 M A X.
100±2
4.5±0.5
45±0.5
62 M
AX.
62 M
AX.
12.1±0.5
40.4±0.5
FILTEMCR
FILTEMCR
184±1
102 M
AX.
80±0.5
6.5±0.5
M 4
62 M
AX.
40.4±0.5
232 M A X.
12.1±0.5160±2
50±0.5
FILTEMCR
FILTEMCR
184±1
102 M
AX.
80±0.5
6.5±0.5
50±0.5
M 4
240 M A X.
160±2
48.5±0.5
62 M
AX.
15.1±0.5
FILTEMCR
FILTEMCR
12±0.5
102 M
AX.
6.5±0.5
225±1
80±0.5
288 M A X.
200±2
102 M
AX.
M 6
18.8±0.5
54±0.5
FT111-50
FILTEMCR
FILTEMCR
10±0.5
M 4
10±0.5
120±1
133 M A X.
100±2
4.5±0.5
45±0.5
62 M
AX.
31.5±0.5
62 M
AX.
M 6
12±0.5
240±2 25±0.5
100.7±0.5
152 M
AX.
172 M
AX.
145±0.5
342 M A X.
R
FILTEMC
R
FILTEMC
265±1
8.5±0.5
FILTEMCAC Single Phase Filters FT110/FT111 Series
1. Storage of EMI Filters:
2. Installation of EMI Filters:
EMI filters mustn't be left out in the heat of the sun or exposed to the rain, it should be stored in warehouse
with good ventilation, surrounding temperature between -30℃ and +65℃ , the highest relative air humidity
lower than 90%, and no corrosive liquid or gas.
EMI filters should be installed at power input, and the line inside the chassis be as short as possible to
reduce radiated interference.
Both input and output lines of EMI filters neither be intersected nor be tied up by string.
Make sure the mounting flange fully grounded, and keep the ground cable as short as possible if filters are
connected to other equipment.
If the terminal is stud, please use two spanners to fasten the screw nut when connecting to avoid stud
rotating and thus causing changes to the internal circuit and consequently leading to filters arcing, short
circuit, broken down or the filtering effect worsened. First use spanner1 to fix the screw nut near the metal
case, then use spanner2 to tighten the screw nut in front( shown as Figure1), otherwise the terminals may
be damaged. Apply the same for the connection of other phases.
Important Notes on EMI Filter Application
(Figure1)
Keep the tools fastening the stud be vertical to the metal case of filter when installing terminal block filters
( shown as Figure2 ), must not tilt( shown as Figure3 ), otherwise the terminal blocks may be damaged.
FILTEMCAC Single Phase Filters FT110/FT111 Series
(Figure2) (Figure3)
3. Reminding and Warning:
Please read all the safety warnings and instructions before installing filters and putting them into use:
Contact information of Tech. Dept.:
T: 0086-531-58622887
F: 0086-531-58622899
A: Building 20, Xinmao Qilu Science and
Technology City, No. 1 Zidong Road,
Tianqiao District, Jinan 250119, China
Contact information of Sales:
T: 0086-531-58622888
F: 0086-531-58622886
Skype: [email protected]
Web.: www.filtemc.com
Don't take terminals as supporting point when moving filters to avoid the terminals distortion, loosening or
broken.
The protective earth connections shall be the first to be made when the EMC filter is installed and the last to
be disconnected.
Filters generate leakage current, please make sure they are well grounded before putting into operation.
If the rated current is higher than 50A, we recommend grounding by the earth terminals but not only through
the metal case of filters.
Danger of electric shock: EMC filters contain components that store an electric charge. Dangerous voltages
can continue to exist at the filter terminals for longer than five minutes even after the power has been
switched off.
The working conditions of EMI filter should comply with the technical parameters stated on the label, over
voltage or overload could cause damage to filters. It is suggested to take proper over current protection
measures.
Current drop occurs when the surrounding temperature rise, fail to follow the current drop requirement may
lead to impermissible exceeding of the component temperature, as a result the service life of filters will be
shortened after long time running.