fft aura fence operations manual v2.0
TRANSCRIPT
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
1/90
FFT Aura Fence
Operations Manual
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
2/90
The information in this document is subject to change without notice. No part of this document may be reproduced or transmitted
in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Future Fibre
Technologies Pty. Ltd. Future Fibre Technologies Pty. Ltd. may have patents or pending patent applications, trademarks,
copyrights, or other intellectual property rights covering subject matter in this document. The furnishing of this document does
not transfer rights or license to these patents, trademarks, copyrights, or other intellectual property except as expressly provided
in any written license agreement from Future Fibre Technologies Pty. Ltd.
2013 Future Fibre Technologies Pty. Ltd. All rights reserved.
Printed in Australia.
Document Title: FFT Aura Fence Operations Manual
Document Number: M903 3713 022, Version 2.0, FOSS 3 v1.20.5.91, Strain 7
Future Fibre Technologies Pty. Ltd., the Future Fibre Technologies logo, FFT, FFT Secure Zone, FFT Secure Fence, FFT Secure
Link, FFT Secure Pipe, FOSS, FOSL, FOSF, FOPSS, FFT CAMS, FFT TAZ, FFT Locator, FFT Microstrain/Locator and Foptic
are either registered trademarks or trademarks of Future Fibre Technologies Pty Ltd. Incorporated in Australia, the USA and/or
other countries. Microsoft, MS, MS-DOS and Windows are registered trademarks of Microsoft Corporation. Fujikura FSM-60S
Fusion Splicer is a product of Fujikara Limited. Joint closure instructions reprinted with permission of Tyco International Limited
(TE Electronics) and Channell Commercial Corporation, USA. Westover FM-C320 Fibre Microscope is a product of Westover
Scientific (JDSU). Alazar is a trademark of AlazarTech, USA. Basik is a trademark of NKT Electronics Co. Ltd, China. NI is a
trademark of National Instruments, USA. Adlink is a trademark of ADLINK Technology Inc. Helios Web Interface (HWI) is a
product of Fotech Solutions Ltd.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
3/90
Contents iii
Contents
1.0 Company information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Company overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Contact details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 FFT terminology and acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.0 Important product and safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 FFT product disclaimers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Laser safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Reminders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.0 FFT Aura system overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2 System outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.3 Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.4 System performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.5 FFT Aura Fence deployment options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.5.1 Fence-mounted fibre . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.5.2 Resilience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.0 FFT Aura Fence sensing controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145.1 Connect cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.2 Front panel information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5.3 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
6.0 Configuring the hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.1 Datasheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
6.2 Start the laser and detection system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
6.3 System shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.4 Tuning FFT Aura to the sensing fibre . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.0 Web Configuration Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.1 Logging into the FFT Aura HWI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
7.2 Main screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.3 Main Configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
7.3.1 Colour map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7.3.2 Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
7.3.3 Print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.4 Waterfall display / Sound field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
7.5 Configuration menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
7.6 System health . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
7.7 Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
4/90
iv FFT Aura Fence Operations Manual
7.8 Admin Configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.8.1 Hardware properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.8.2 Fibre processing properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407.8.3 Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.8.4 View FDEL properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.9 Level Crossings in HWI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.9.1 Signal Filtering and Level Crossings Counts . . . . . . . . . . . . . . . . . . . . 53
7.9.2 Dynamic Threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
8.0 FFT Aura Fence Alarming Module: FOSS 3 Configuration . . . . . . . . . . . . . . . 62
8.1 Level Crossings in FOSS 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.1.1 FOSS 3 Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.1.2 FOSS 3 Classification Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
8.1.3 FOSS 3 Diagnostic Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Appendix A Setting the IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
A.1 Change the controllers IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
A.2 Change the front panel display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
5/90
Company information 1
1.0 Company information
1.1 Company overview
Future Fibre Technologies (FFT) manufactures and markets a range of fibre optic intrusion
detection and location systems for fences, pipelines, perimeters and other assets that are, quite
simply, the worlds most effective solution for securing high value assets and critical
infrastructure.
FFTs core products include:
FFT Aura
FFT CAMS
FFT Secure Fence
FFT Secure Link
FFT Secure Pipe
FFT Secure Point
FFT Secure Zone
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
6/90
2 FFT Aura Fence Operations Manual
1.2 Contact details
Americas Washington DC
Future Fibre Technologies (US) Inc
800 West El Camino Road
Mountain View CA 94040
USA
Toll free: +1 (877) 650 8900
Outside USA: +1 (650) 903 2222
Fax: +1 (435) 417 6671
Email: [email protected]: www.fftsecurity.com
Future Fibre Technologies (US) Inc.
11350 Random Hills Road, Suite 800
Fairfax, VA 22030
USA
Toll free: +1 (877) 650 8900
Outside USA: +1 (650) 903 2222
Fax: +1 (435) 417 6671
Email: [email protected]: www.fftsecurity.com
Australia Europe
Future Fibre Technologies Pty Ltd
10 Hartnett Close
Mulgrave
VIC 3170
Australia
Phone: +61 (3) 9590 3100
Fax: +61 (3) 9560 8000
Email: [email protected]
Web: www.fftsecurity.com
Future Fibre Technologies Pty Ltd
3000 Hillswood Drive, Hillswood Business Park
Chertsey, Surrey KT16 0RS
England
Phone: +44 (0)1932 895 317Fax: +44 (0)1932 895 318
Email: [email protected]
Web: www.fftsecurity.com
Middle East India
Future Fibre Technologies MENA FZ-LLC
Building 11 Office G08
Dubai Internet CityUnited Arab Emirates
Phone: +971 4 4345361
Fax: +971 4 4393406
Email: [email protected]
Web: www.fftsecurity.com
Future Fibre Technologies
M-12/23, DLF City Phase 2
Gurgaon, Haryana 122 002India
Phone: +91 124 4087020
Fax: +91 124 4087019
Email: [email protected]
Web: www.fft security.com
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
7/90
FFT terminology and acronyms 3
2.0 FFT terminology and acronyms
Acronym Description
API Application Programming Interface.
ARaD Alarm Recognition and Discrimination.
Area Name
(User defined)
Can be made up of multiple zones. This term is used only for establishing views
in FFT CAMS, for example, North Fence, Boundary Road Fence, etc.
Barriers
(User defined)
Refers to type of barrier on the perimeter or the various multiple lines of defence,
for example, Chain mesh Outer Fence, Below Ground Sensor, Sterile Zone,
Barbwire, Gates, Taut Wire Inner Fence, PIR, VMD, CCTV, etc.
BGS Below Ground Sensor.
Channel Each independent sensing cable monitored by a Controller. Microstrain/Locator
has one channel.
408/408 systems have up to eight channels. The FFT Secure Zone system has up
to 16 channels.
Channel Alarms Disabled
Alarm
The alarm channel has been disabled in FOSS, that is, the perimeter covered by
that channel is no longer supervised.
CNCD Control and Command.
Controller Sector
(User defined)
A single sensing controller (a PC running FOSS) that can control multiple zones.
The sector may either be the complete perimeter or one section of the perimeter.
It contains all the channels and zones monitored by an individual FOSS
Controller.
DAS Distributed Acoustic System.
Device Not Responding
Alarm
An external device to FFT CAMS, for example, PLC, camera, etc. is not
responding.
DST Daylight Saving Time.
DWDM Dense Wavelength Division Multiplexing. DWDM works by combining and
transmitting multiple signals simultaneously at different wavelengths on the same
fibre.
End Element Defines and terminates the end of the sensing cable for FFT Secure Zone systems.
End Sensor Defines and terminates the end of the sensing cable.
FDEL Function Detect Event Locator.
Feeder Cable An insensitive singlemode lead-in cable connecting the sensing controller to thesensing cable. Used in all FFT products.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
8/90
4 FFT Aura Fence Operations Manual
FFT CAMS Central Alarm Monitoring System software that can be used on any computer on
the sensing network. Used to integrate and centralise the information and signals
from each of the sensing controllers on the network, including specific third-partyequipment.
FFT Secure Fence Fibre optic perimeter security detection and location system.
FFT Secure Fence 108 8-channel fibre optic perimeter security detection system with a maximum range
of 10 km for each individual channel.
FFT Secure Fence 408 8-channel fibre optic perimeter security detection system with a maximum range
of 40 km for each individual channel.
FFT Secure Link Fibre optic network security monitoring system.
FFT Secure Pipe Fibre optic pipeline security monitoring system detecting third-party interference
and tampering.
FFT Secure Point Fibre optic perimeter protection of utility substations, solar farms, storage yards,
pumping stations, block valve sites, etc.
FFT Secure Zone Fibre optic zone-based intrusion detection system for relatively short fence
perimeters.
Fibre Break Alarm An alarm that indicates that a fibre has been broken or cut.
FOSS Fibre Optic Sensing System software used to operate the FFT sensing controller.
FOSS Degraded Alarm An alarm that indicates that the FOSS software is running degraded. Normally
this will require the FOSS PC to be restarted.
FOSS Unit Shutting
Down
The FOSS unit has been shut down.
GIU Gate isolator unit. Allows gates to be defined within the locating system as
separate zones from the fence sensor; allows the gate to be isolated and not
generate alarms.
GUI Graphical User Interface.
GUID Global Unique Identifier a unique identifier for an alarm.
KVM Keyboard, Video and Mouse console.
Laser Off Alarm An alarm that can be raised to indicate that the laser has been turned off. For
example, this happens when an operator opens the configuration dialog on a
FOSS unit configured as a locator.
Laser Shutdown Alarm An alarm that indicates that the laser temperature has exceeded a set shutdown
level. A technician should verify why the temperature in the room with the FOSS
PC/unit has increased.
Laser TemperatureWarning
An alarm that indicates that the laser temperature has exceeded a set warninglevel. It should be monitored from there on as it might keep increasing or it might
decrease.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
9/90
FFT terminology and acronyms 5
LED Light Emitting Diode.
Locator Disabled ForChannel Alarm
FOSS indicates that the given channel is a locator channel, whereas FFT CAMShas it configured as an FFT Secure Zone channel. This is a configuration error.
Locator Fault Alarm A system alarm that can be raised by a Locator system. This alarm type normally
reflects that the installation of the FOSS unit is faulty. Please contact FFT.
Loss of Communications A system alarm that can be raised by either an FFT Secure Zone or a Locator
system. It indicates that FOSS has not replied to the heartbeat sent by FFT CAMS
within a set timeout period. The network connection should be verified between
FOSS and FFT CAMS.
M/L Microstrain Locator.
Multimode (MM) Multimode fibre optic cable.
OTDR Optical Time Domain Reflectometer. An instrument used to test fibre systems
and locate losses and reflections.
RFU Reserved for Future Use.
Sensing Controller The industrial computer that houses the FFT sensing hardware and software.Controls and monitors the fibre optic sensing cable, detecting events and
intrusions.
SDK Software Development Kit. An interface provided to access the services of
FFT CAMS.
Singlemode (SM) Singlemode fibre optic cable.
Start Element Defines the beginning of the sensing cable for that zone for FFT Secure Zone
systems.
Start Sensor Defines the beginning of the sensing cable. Prior to the start sensor, the lead-in
cable is insensitive.
Stealth Alarm An intrusion alarm that normally reflects a short duration impact on the perimeter.
System Shutdown Error
Alarm
FFT CAMS did not shutdown properly.
Threshold Count Alarm An intrusion alarm that normally reflects a longer duration impact on the
perimeter.
UPS Uninterruptable Power Supply.
UTC Coordinated Universal Time or Universal Time Coordinated.
Zones
(User defined)
Refers to the localised breakdown of the individual sections of the barrier being
monitored. Can be either (FFT Secure Zone, 8-channel, strain) hardware or
software (M/L) zones.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
10/90
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
11/90
Important product and safety information 7
3.3 Reminders
Always turn off the laser and sensing controller whenever installation or maintenanceon the fibre is taking place or whenever a connector is disconnected or a fibre broken.
Before you inspect fibre connectors, ensure that the laser LED is OFF.
Neverinspect fibre connectors with a fibre scope with laser on.
Always inspect the connectors or adapters before you clean them.
Always clean then reinspect the connector before making the connection.
Always use the connector housing to plug or unplug a fibre never pull on the fibre.
Always keep a protective cap on any unplugged fibre connectors.
Always store unused protective caps in a resealable container to prevent the possibilityof transferring dust to the fibre. Locate the containers near the connectors for
easy access.
Never use alcohol or wet cleaning without a way to insure that it does not leave residue
on the endface. This residue can cause performance degradation of the system.
Never look into a fibre while the system lasers are on.
Never clean bulkheads or receptacle devices without a way to inspect them.
Never touch the endface of the fibre connectors.
The information in this document is subject to change without notice and
may not be construed in any way as a commitment by FFT.
While FFT makes every effort to ensure the accuracy and contents of the
document it assumes no responsibility for any errors that may appear.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
12/90
8 FFT Aura Fence Operations Manual
4.0 FFT Aura system overview
4.1 Introduction
FFT Aura is a fibre optic based distributed acoustic sensing system. This system comprises
a sensing controller and a fibre optic cable. Where possible, the system may be operated on
existing fibre cables to turn existing infrastructure into a highly accurate distributed sensing
system.
When installed on a fence, FFT Aura is distributed, providing detection at every point along
the fibre. The system is capable of highly accurate sensing with accuracy of up to 6 metres and
a range of 16 kilometres from the sensing controller.
The system is acoustic and operates by detecting all seismic and acoustic events on the fibre
cable. The system provides continuous detection and monitoring in all weather conditions,
being immune to electromagnetic (EM) and radiofrequency (RF) interference and being
capable of being run alongside high voltage power cables.
FFT Aura operates using a modified and highly controlled variant of an Optical Time Domain
Reflectometry (OTDR) instrument. For buried applications, the system requires no specially
manufactured fibre and operates with a standard telecommunications grade fibre optic cable.
The FFT Aura sensing controller is connected to one end of the fibre optic cable and sends apulsed laser light into the fibre. The fibre type required is a standard telecommunications grade,
singlemode (SM) fibre. The fibre is inert and no power is required along the entire sensing
length, only at the sensing controller.
4.2 System outline
The FFT Aura system comprises three major elements:
Sensor: singlemode fibre optic cable, designed for specific application
Sensing controller: rack-mountable unit, monitors up to 16 km of connected fibre Alarm Processing server: a server for analysis and generation of alarms.
4.3 Technology
FFT Aura is a phase-sensitive OTDR-based sensing system employing one singlemode fibre
within a sensing cable. Using a coherent laser, pulses of light are propagated down the fibre.
The natural Rayleigh scattering process in optical fibres causes a small portion of this light to
scatter or reflect back towards a detector, which is also appropriately placed next to the source
to receive the scattered signals. Using this technique a series or array of distributed sensingchannels or microphones are sequentially set up along the sensing fibre. By detecting and
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
13/90
FFT Aura system overview 9
monitoring the backscattered signal as well as its pulse timing information, a perturbation on
the sensing cable can be detected and located to a high precision.
Figure 4-1 Principles of FFT Aura
When installed on a perimeter fence, FFT Aura provides real-time monitoring of the fence,
detecting intrusion events such as climbs or cutting. Signal characterisation and analysis
techniques are used to provide an operator or security team with highly accurate positional and
threat information, allowing for a swift and informed response. This provides a monitoring
capability for security and maintenance events.
Mechanical vibrations easily generate detectable changes in the interferometric signal and
allow for the generation of maps of vibration signals along the sensing cable, up to a maximum
range of 16 kilometres from the sensing controller. This is then translated, using real-time
software, to generate maps and customisable alarm signals for display and transmission to
monitoring equipment.
To reduce nuisance alarms, the system includes a fast electronic processor to automatically
distinguish between intrusion and non-intrusion disturbances.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
14/90
10 FFT Aura Fence Operations Manual
4.4 System performance
FFT Aura can be deployed in a number of applications, including:
Perimeter security fence-mounted system
Perimeter security below ground, covert system
Pipeline security/leak detection above ground and below ground deployments
Linear asset security buried using new or existing fibre optic cables.
This manual is only concerned with the FFT Aura fence-mounted applications. For
information on other applications, please contact FFT.
The key features of FFT Aura for fence-mounted applications are:
fully distributed sensing over entire fibre cable length of up to 16 kilometres
perimeter fence-mounted location accuracy of within 6 metres
FFT Aura is capable of setting hundreds of individually tunable zones on the fibre for:
- prioritisation of key threat areas
- desensitisation of non-core areas
- tuning to detect specific events and filter against non-threat events
- accounting for specific environmental conditions
- allowing for multiple installation configurations- setting of specific detection parameters, including time.
software configurable zones may be from 6 metres to several kilometres in length
real-time detection, location and notification to any desired monitoring location,
including to mobile security personnel
no field electronics or power required to the cable
sensitivity at acoustic frequencies greater than 3 kHz to 9 kHz, depending on sensor
cable length
low maintenance requirements capable of integration with CCTV via FFT CAMS
probability of detection (POD) is high due to intelligent signal processing and analysis
of disturbances
no false alarms due to intelligent signal processing and analysis of disturbances.
nuisance alarm rate (NAR) is minimal due to multi-parameter intelligent signal
analysis, discarding non-intrusion and environmental events
no seasonal calibration or adjustments are required.
In addition to the performance features detailed above, FFT Aura is capable of performingintelligent acoustic signature analysis to detect and classify or ignore specific events. For
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
15/90
FFT Aura system overview 11
fence-mounted systems, a level crossings (LC) algorithm is used to eliminate unwanted
background noise and minimise false alarms. This could include concentrations of strong wind,
incidents of rain or hail against the overhead cables, traffic noise or the energy of passingtrains.
The system is also capable of classifying specific events, including security events, such as
digging, or climbing.
FFT Aura is not affected by changes in fibre length along the length of the sensor and it is
immune to radio frequency interference (RFI) and electromagnetic interference (EMI),
external jamming and is intrinsically safe (IS). There are no electrical or active electronics
installed in the field. Multiple controller units can be installed on a single fibre optic cable at
suitable junction points and be networked together to monitor the entire length of the asset.
The FFT Aura sensing controller contains the electronics and software required to
continuously monitor, in real time for the detection of intrusion events over the entire length
of the fibre optic sensing cable. The system will raise an alarm when an intrusion is detected,
calculate and display the location of the intrusion event.
4.5 FFT Aura Fence deployment options
4.5.1 Fence-mounted fibre
When mounted on fences, FFT Aura will detect vibrations that may be caused by, but not
limited to:
physical action against the fence, including cutting or lifting
attempts to climb the fence or ladders being placed against the infrastructure
movements around the fence, including footsteps and vehicles.
FFT Aura is capable of monitoring an entire perimeter fence with a single fibre, which may be
mounted on fences or walls, and may also be buried to provide additional protection on key
threat areas.
When FFT Aura is deployed as a fence-mounted fibre optic cable intrusion detection sensor
system based on multi-core, single mode fibre optic cable. The fibre optic cable operates as a
distributed sensor and is directly mounted on the fence along the perimeter or around an area
to be protected.
FFT Aura works equally well on chainmesh, weldmesh and palisade style fences. With an
FFT Aura fence-mounted system, intrusions on approved fences can be detected and located
to within 6 metres.
There is no power required along the fence-line, and no electronics installed in the field. The
sensors installed in the field are intrinsically safe and immune to lightning strikes, EMI and RFIevents.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
16/90
12 FFT Aura Fence Operations Manual
Figure 4-2 System logic fence
4.5.2 Resilience
FFT Aura has the ability to continue operating up to the point of fibre damage or a cable cut.
Figure 4-3 Cut survivability
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
17/90
FFT Aura system overview 13
Optionally, a fully redundant, cut-immune system will ensure that the fibre optic sensor cable,
either side of the cut would continue to operate. Two controllers are required to perform this
function.
Figure 4-4 Redundancy with two controllers
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
18/90
14 FFT Aura Fence Operations Manual
5.0 FFT Aura Fence sensing controller
FFT Aura Fence is an integrated system made up of three main modules: the FFT Aura sensing
controller, the FOSS 3 alarming module and FFT CAMS. The three modules work together to
provide event disturbance detection, analysis and alarm reporting.
The configuration of the FFT Aura controller occurs in three parts. Firstly, the controller will
need to be tuned to the connected fibre path; secondly, the sensing configuration will be set
within the Helios Web Interface (HWI) utility, and thirdly, the alarm configuration and
reporting will be configured in FOSS 3.
5.1 Connect cables
With the controller turned off, ensure that all cables are connected before proceeding.
Before starting the controller, perform the following steps:
Ensure the controller is sitting on a shelf within the cabinet and fixed to the front rails
with four screws.
Ensure that there is 1RU of space available above the controller for ventilation.
Clean and connect the supplied E2000 to SC/APC patch lead to the optical fibre port
and the patch panel at the other end.
Connect keyboard, video and mouse cables.
Connect an Ethernet cable from the controller to a network switch.
Connect coax cables from the two BNC ports to a BNC T-piece. This T-piece will beconnected to channel 1 on an oscilloscope.
Connect any external HDDs that may be required for data logging.
Switch the power switch on the rear of the controller to the off position.
Connect the power cable to a suitable UPS. A UPS should always be used to protect
the equipment from an unreliable power supply.
Switch the laser lockout key to the locked position (see Figure 5-1).
At no time should the laser be turned on while there is no fibre connected to the
controllers output port. Doing so may cause serious damage to the optical
transmission circuit. If this type of damage occurs, the controller must be
returned to FFT for repair.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
19/90
FFT Aura Fence sensing controller 15
Figure 5-1 Laser in locked position
With the initial steps complete, switch the power supply to the on position and press the Power
button on the front of the controller (see Figure 5-1).
5.2 Front panel information
The LCD display on the front of the controller displays the systems status and offers a number
of hardware configurations. Note that detailed configurations will be performed via the webbased interface.
While in status mode, the display will cycle through a number of screens that will indicate
items such as:
Systems IP address
System status
Systems name
Systems software version.
Below the display, there are a number of LEDs that quickly indicate the systems status:
Laser operating LED on when the laser is on
Laser locked out LED on when the lockout key is in the locked position
System error LED on when there is a hardware error
Power LED on when the controller is switched on.
When the controller is powered on and not in use, ensure that the laser light LED is off and the
laser lockout LED is on.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
20/90
16 FFT Aura Fence Operations Manual
Figure 5-2 Laser locked out indicator
The LCD display is bordered by four soft buttons. Pressing any of the buttons will access
configuration mode. If a change is made here or the menu is to be escaped from, wait 5 seconds
and the display will reset itself to the status mode.
5.3 Ventilation
As the controller requires ventilation, ensure that the front mounted fans are not obscured and
that there are no objects left on the top lid of the controller.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
21/90
Configuring the hardware 17
6.0 Configuring the hardware
6.1 Datasheet
Each controller will be supplied with a datasheet that contains a number of default values
specific to that controller. Many of these values will need to be entered via the front panel
before the laser is started.
Figure 6-1 Datasheet information
Importantly, the following values will need to be set or confirmed before proceeding:
TEC set point
Trigger level
Back box delay
Pulse width
Pulse repetition frequency
Bias current
EDFA 1, 2 and 3.
These settings will be found within the configuration menus:
System Conf
- TEC Ctrl to set the value of TEC 1
- EDFA Ctrl to choose one of three EDFA gain stages.
Laser Conf
- Pulse Width
- Pulse Rep
- Bias Current.
Once set, the laser can be turned on and the system activated.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
22/90
18 FFT Aura Fence Operations Manual
6.2 Start the laser and detection system
To start the detection and laser systems, start by selecting Unlocked with the lockout key onthe front panel. Note that the Laser Locked Out light will extinguish and the Laser Operating
light will be lit.
Figure 6-2 Unlock the laser
To start the detection system, press any of the buttons next to the LCD display and select
Detect On. Listen for a click as the data acquisition card enables.
6.3 System shutdown
In order to correctly shutdown the controller, enter the configuration menu on the front panel
and select Detect Off. This will shut down the Event Detection System, and also turn off the
source laser. Ensure that the laser lockout key is then set to the locked position.
To power down the controller, press and the power button on the front panel once. The LCD
screen will display the message CNCD exiting. Note that it may take 90 seconds for the
controller to completely shut down.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
23/90
Configuring the hardware 19
6.4 Tuning FFT Aura to the sensing fibre
An oscilloscope is required to correctly tune FFT Aura to the sensing fibre. It will be used tocorrectly set the pulse width and repetition frequency, as well as determine the correct gain
required for the sensor length. Connect and power on the oscilloscope and adjust until the pulse
signal is visible.
Figure 6-3 Connect the oscilloscope
Pulse width: determines the systems spatial resolution and is the period of time that the
pulse is energised. It also determines how much light is in the fibre at any one time. The
pulse width used will be determined by the length of the total optical path and the
controller supports pulse widths ranging from 10 ns up to 1 s. As light travels at
approximately 2 x 108 m/s in an optical fibre, a 10 ns pulse width equates to
approximately 1m in fibre length.
To adjust the pulse width:
1 Press any button to access the configuration menus and select Laser Conf.
2 Select pulse width to view the current pulse width.
3 To reduce the pulse width press the lower left button, to increase the pulse width press
the lower right button.
4 The pulse width will immediately change to the value indicated next to the button
pressed and the top line of the LCD display will indicate the new pulse width.
5 When the correct value is set, allow 8 seconds to elapse and the display will revert to
status mode.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
24/90
20 FFT Aura Fence Operations Manual
Pulse Repetition Frequency (PRF): defines the systems temporal resolution and therefore
the maximum detectable frequency of the disturbance. The maximum PRF is limited by
the length of time it takes for a laser pulse to travel to the end of the fibre sensor and back(twice the length of the fibre sensor).
As light travels at approximately 2 108 m/s in an optical fibre, it takes approximately
10 seconds for light to travel to the far end of a 1 km length of fibre and back. Therefore,
the fastest allowable PRF in this example would be 100 kHz or a period of 10 seconds or
the maximum PRF for a 10 kilometre length of fibre is 10 kHz. As the length of the fibre
increases, the length of time for the pulse to get to the end of the fibre and back also
increases. As the sampling rate is reduced, the maximum frequency of vibration that can
be detected by the system is also reduced. The maximum frequency that a digital system
can detect is half the sampling frequency. Table 6-1 shows a number of examples.
Adjustment of the PRF should be done while viewing the oscilloscope. The scope show
display noticeable individual pulses. If there is only one pulse, the PRF is too frequent,
where large gaps between pulses indicates an insufficient PRF.
Figure 6-4 Pulses seen on the oscilloscope display
Table 6-1 PRF, maximum fibre length and detected frequency
PRF
(kHz)
Max. fibre length
(m)
Max. detected freq.
(kHz)
100 1000 50
50 2000 25
40 2500 20
20 5000 10
10 10,000 5
5 20,000 2.5
2.5 40,000 1.25
2 50,000 1
1 100,000 0.5
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
25/90
Configuring the hardware 21
To adjust the PRF:
1 Press any button to access the configuration menus and select Laser Conf.
2 Select PRFto view the current setting.
3 To reduce the PRF, press the lower left button, to increase the PRF press the lower right
button.
4 The PRF will immediately change to the value indicated next to the button pressed and
the top line of the LCD display will indicate the new PRF value.
Drive Current: determines intensity of the pulse being launched into the optical fibre.
There are situations where adjusting the light intensity can improve the system's ability todetect event disturbances however, too much drive current will result in a saturated signal.
To adjust the drive current:
1 Select Bias Crntfrom the Laser Confmenu.
2 The bias current setting is displayed on the top row together with the maximum setting
value. The setting is in normalised units.
3 To reduce the bias current press the lower left button. To increase the bias current press
the lower right button. The bias setting will immediately change to the value indicated
next to the button pressed.
4 The top line of the LCD display will indicate the new bias current setting.
5 The available range of bias current settings is 1 to 255.
6 If no buttons are pressed for 8 seconds, the display will automatically revert back to the
main idle screen.
Ideal signal: The ideal pulse should look similar in form to Figure 6-5. The length of the
pulse will determine the length of the optical path. The height of the signal will bedetermined by the amount of gain added with the drive current and the EDFAs. Record the
maximum height for use later in the configuration process.
Figure 6-5 Ideal pulse shape
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
26/90
22 FFT Aura Fence Operations Manual
If there is no gap between the pulses, decrease the PRF. If the bottom of the pulse begins to
lift, there is too much gain.
Figure 6-6 Too much gain
If there are any reflections in the optical path, it may greatly affect the pulse. If any are
detected, they must be found and repaired before continuing the setup process.
Figure 6-7 Pulses with reflections
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
27/90
Web Configuration Utility 23
7.0 Web Configuration Utility
Once the sensing controller is configured, the Helios Web Interface (HWI), will be used to
monitor the sensing signals and health of the system, configure the controller parameters and
sensor configuration, and perform other functions such as recording and playing back signals.
Access to HWI can be achieved by using a web browser such as GoogleRChromeTMor
FirefoxTM. For versions older than v4.4.0, only Google Chrome that has had Java installed
should be used.
7.1 Logging into the FFT Aura HWI
To access the FFT Aura HWI, type the IP address of the controller into the address bar of
Google Chrome. Each controller has a built-in web server that allows easy remote access for
configuration and reporting purposes. Communication is via the default HTTP port number 80.
If this port number needs to be changed, ensure the new port number is entered into FFT
CAMS to maintain communications.
To access the different configuration and parameter menus, you will be required to log
into theAccess secure pages(see Figure 7-1). The login details will be specified on
the datasheet accompanying the sensing controller and can also be supplied by FFT.
Figure 7-1 Accessing configurations and parameter menus
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
28/90
24 FFT Aura Fence Operations Manual
7.2 Main screen
The main screen consists of six main areas:
Colour map displays real time sensor disturbance
Waterfall display historical display of the sensor disturbance
Configuration menus access configurations
Data logging enable logging of the live signal
System control start and stop the detection and the laser
System Health panel monitor system health and processing loads
Figure 7-2 HWI main screen
Configuration
menus
Data logging
System control
Waterfall
display
Colour map
System Health
panel
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
29/90
Web Configuration Utility 25
7.3 Main Configuration menu
The Mainconfiguration menu can be accessed by clicking on the red button as shown inFigure 7-3, and contains information about the controller.
Figure 7-3 Main menu options
About this controller: displays SW version and serial numbers.
Report a problem: email link used to report system errors if required.
View alarm list: lists the alarms currently active on the controller.
Colour map: configure and change the colour map as described in the colour map
section called Adjusting the scale.
Clear sound field: clear the current display.
Clear alarms from sound field:
Preferences: adjust the system time zone and distance units.
Print: prints a copy of the current sound field.
Toggle oscilloscope mode: puts the screen into oscilloscope mode.
Logout factory: log out of secure access mode.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
30/90
26 FFT Aura Fence Operations Manual
7.3.1 Colour map
The colour map displays a real-time representation of the disturbances being detected by thesensor cable. The intensity of the disturbance is visually displayed by scaling it against a colour
scale. The colour map also displays the location of the disturbance along the sensor path.
Figure 7-4 Colour map showing two disturbances
In Figure 7-4, the intensity is measured along the vertical axis and distance is determined along
the horizontal axis.
Adjusting the scale
If the received signal displayed is too tall for the colour map, enter a new number into
the scale box displayed at the top left of the window. Enter a new value then press
ENTERto apply the change.
Figure 7-5 Colour map scale adjustment
To adjust the actual colour scale, click on the menu icon and select Colour Map
(Figure 7-6). The settings menu (Figure 7-7) allows the colour fades to be adjusted in
stages or for new colours to be added.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
31/90
Web Configuration Utility 27
Figure 7-6
Figure 7-7 Adjust colour scale
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
32/90
28 FFT Aura Fence Operations Manual
7.3.2 Preferences
ThePreferences
menu contains parameters for setting the time zone, distance units andwaterfall configuration parameters.
Figure 7-8 Preferences
7.3.3 Print
To print the main screen, click on Print.
Figure 7-9 Print
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
33/90
Web Configuration Utility 29
Figure 7-10 Print the sound field
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
34/90
30 FFT Aura Fence Operations Manual
7.4 Waterfall display / Sound field
The waterfall displays a historical representation of the disturbances being detected by thesensor cable. Once displayed on the colour map, the disturbance is recorded to the waterfall,
which allows the disturbances duration and direction of travel to be determined.
Figure 7-11 Real-time and historic display of the disturbance
Optionally, the waterfall can be configured to display other diagnostic features such as the raw
disturbance signal. For FFT Aura fence-mounted systems, the setting should be set to
Stream Detection Value ST-Level Crossings.
Figure 7-12 Waterfall views
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
35/90
Web Configuration Utility 31
Pause and zoom the display
The waterfall display can be paused by clicking the Pauseicon shown in the colour map. The
display will freeze; however, the background processing will continue. Pressing the Playicon
will recommence the real-time display.
To view a specific section of the sensor, zoom in to the waterfall display. Click the
Magnifying glassicon then place the cursor to the left of the location of interest, drag
the cursor to the right of the point of interest and then release the mouse button.
Return to the full or previous view by selecting the Zoom out icon.
Figure 7-13 Viewing a section of the waterfall
Figure 7-14 Pause and zoom controls
Pause or Play
Move around the
display
Zoom in
Zoom out
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
36/90
32 FFT Aura Fence Operations Manual
7.5 Configuration menus
System control
The system control panel contains the following settings:
Replay mode change controller to signal replay mode.
Control start/stop Start or stop the data acquisition process. Will display either
Runningor Not Running.
Laser control Turns the laser on or off. Will display Laser Onor Laser Off.
Figure 7-15 System control
Start data acquisition
To start the data acquisition process, click the green icon on the right-hand side of the
display. The system will begin to display data in the waterfall display, and the systemstatus will change from Not Runningto Running. The laser will also change to Laser
On.
Figure 7-16 Not running, running
If the laser lockout key is in the locked position, it will not be possible to start the FFT Aura
system. Unlock then attempt to restart.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
37/90
Web Configuration Utility 33
Replay mode
Replay mode allows the system to replay previously acquired signals.
To enable replay mode, click on the icon with the green arrow in the system control
box. A warning message will be displayed requesting confirmation of the change.
Figure 7-17 Replay mode setting
Click the disk icon to select the data file. A file selection dialog is displayed showing a
list of available raw FDS formatted data files. Navigate to the file and choose Select.
Figure 7-18 Select a file
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
38/90
34 FFT Aura Fence Operations Manual
Choose a replay start and end time then select the Playicon.
Figure 7-19 Press Play
The signal can be replayed at a faster rate using the fast forward button. Each time it is
clicked the playback speed increases by a factor of 2, i.e. 1 2 4 8 16 32
MAX. The progress bar will show the files progress as it is replayed.
7.6 System health
The system health panel shows a real-time view of important system functions for the
following modules:
System Health
Processing maintain below 80%
Logging
Display
Figure 7-20 System health display
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
39/90
Web Configuration Utility 35
7.7 Data Logging
Displays controls used to determine which data is to be logged, where it will be stored and thestorage status. Data acquisition will need to be stopped before the mount option is available.
Figure 7-21 Data logging
To log a file, select the Mount Deviceicon. If an external drive connected via the USB
or eSata port has been detected, it will be available in the drive options window.
Otherwise data can be logged to the internal HDD.
Figure 7-22 Drive mounting utility
Data Logging properties
Click on the Gearicon (see Figure 7-21) to determine the logging details such as the default
directory, the part of the sensor to be logged and the ability to enable the logging.
By default, the system will log the entire monitored sensor. To reduce the effects of
logging on the controller, enter a start and end distance to limit the processing required
to capture the data. Alternatively, choose a predefined zone that may be specifically
logged.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
40/90
36 FFT Aura Fence Operations Manual
Figure 7-23 Global logging properties
Once enabled, the status in the data logging window will change from Not Loggingto
Logging.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
41/90
Web Configuration Utility 37
7.8 Admin Configuration menu
TheAdminconfiguration menu contains settings used to configure the hardware as well asdefining the system signal processing and alarming performance.
Figure 7-24 Admin menu options
7.8.1 Hardware propertiesThis option contains settings that setup the initial system properties. Any setting inputted into
the front panel that differed from those supplied on the technical datasheet will need to be
updated here.
Figure 7-25 Identity options
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
42/90
38 FFT Aura Fence Operations Manual
Identity
Contains factory assigned name and ID fields.
Optics Module
Importantly, this module contains three factory settings that must match the supplied datasheet.
Figure 7-26 Optics module
Note that if the serial numbers are incorrect, the controller may fail to function. The trigger
level and box delay are factory set and should not be changed.
Laser bias current
The Laser Bias Current sets the amplitude of the light pulse being launched by the source laser.
This value is not typically changed from the factor defaults, and for most deployments it should
be left at the factor default.
MUX
This module describes the MUX parameters if a MUX option has been selected for the sensing
controller. In most cases this will be blank.
Figure 7-27 Local Comms settings
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
43/90
Web Configuration Utility 39
Reporting
Contains settings that send alarms and sound field data to FFT CAMS. Once set at
commissioning, these settings should not be changed.
Figure 7-28 Reporting options
Watchdog
These settings configure the behaviour of FDEL under different failure type scenarios.
Figure 7-29 Watchdog settings
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
44/90
40 FFT Aura Fence Operations Manual
7.8.2 Fibre processing properties
Settings used to acquire, analyse, process and log raw data from the optics module are definedhere. The Opticsand Data Capturemenu options form the foundation of the processing flow.
They are designed to optimise the raw data being acquired, as well as ensure that the correct
portion of the fibre sensor is being monitored.
Optics
Optics properties will initially be set with values supplied in the controllers datasheet then
adjusted after the controller has been connected to the sensor.
Figure 7-30 Optics properties
Laser properties
The laser properties are used to control the operational characteristics of the laser, which pulses
the fibre in order to produce the fibre response.
PRF (Pulse Repetition Frequency)
The PRF determines how frequently the controller sends a pulse of light into the fibre sensor.
It is equivalent to the sampling frequency, which dictates the maximum frequency that can be
detected by the HWI interface. The fibre sensor length determines the maximum PRF that can
be set as a new pulse cannot be sent until the previous pulse has been received.
Increasing the PRF will increase the response bandwidth, but will increase the compute load,
as there are more fibre shots to be processed in a given time interval.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
45/90
Web Configuration Utility 41
Pulse Width
The larger the pulse width, the more light is launched into the fibre sensor, and the more
sensitive the system is. Reducing the pulse width improves location accuracy and the ability to
distinguish two nearby event disturbances (increased spatial resolution). The nominal pulse
width is 50 ns, as this is a good compromise between maximizing spatial resolution and system
sensitivity to event disturbances on reasonably short fibres (< 10 km). As fibre sensor lengths
increase toward our maximum of 40 km, the pulse width needs to be increased to 200 ns in
order to alarm on event disturbances at these longer distances.
EDFA properties
EDFA (Erbium Doped Fibre Amplifier) are optical amplifiers are used to set the optimal pulse
amplitude, as well as to optimally amplify the very low level backscattered light. These are
rarely changed from the factory defaults and should only be modified by a trained technician.
There are three EDFAs with the controller.
TEC 1 controller set point
The TEC (Thermal Electric Cooler) controller is used to stabilise the centre wavelength of the
laser. As the lasers temperature drifts, so does its centre wavelength. To obtain optimal fibresensor response, the centre wavelength of the laser must stay in alignment with the receive
chains FBG (Fibre Bragg Grating). This property will very rarely require field adjustment and
requires an OSA (Optical Spectrum Analyser).
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
46/90
42 FFT Aura Fence Operations Manual
Data Capture properties
Determines how much of the sensor path is to be analysed and how the data is to be buffered.
Figure 7-31 Data capture
Physical Fibre Length
Defines the maximum length of fibre that is to be monitored. The fibre length will also restrictthe maximum PRF that can be used to ensure that the pulse has time to exit the fibre prior to
the next one entering.
Zero Point
Determines the actual sensor start point and is typically set to zero.
Refractive Index
The Refractive Index (RI) is used to properly calibrate the speed of light (SOL) in the fibre.
The typical value will be around 1.468 to 1.48 depending on the glass in the fibre sensor.
Monitor Start
Determines the optical distance where analysis will occur. This distance will be set to the same
length as the lead-in and defines the start of the sensitive section.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
47/90
Web Configuration Utility 43
Monitor End
Determines the optical distance where analysis will stop. This distance will be set to the same
length as the lead-in plus the sensor and defines the length of the sensitive section.
Sample Rate
The Acquisition Sample Rate is the rate that the controller samples the incoming data. Default
setting is 150 megasamples per second.
Number of Samples
Displays the number of data samples required to analyse the sensor.
Input Voltage
The input voltage is used to maximise the amplitude of the raw fibre shot without clipping data.
Depending on the sensitivity of the optics module, the maximum amplitude of the analog
voltage can vary between 100 and 500 mV at the beginning of the fibre sensor. This value can
be determined via the oscilloscope or in the raw mode of the sound field.
Spectral Processing properties
These settings set the spectral processing parameters.
Figure 7-32 Spectral Processing module
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
48/90
44 FFT Aura Fence Operations Manual
FFT size
Sets the size of the FFTs used when performing the spectral analysis and is a fundamental
component of the controller. Shorter FFT sizes, in the order of 128 samples, will provide better
time domain resolution, at the expense of smearing out spectral resolution. Larger FFT sizes
in the order of 1024 samples, will provide much better spectral resolution at the expense of
reducing the temporal (time) resolution.
Analysis DC cutoff
Used to remove the very low frequency DC component from the signal prior to computing the
output signal. A typical value for this property is on the order of 10-20 Hz.
Data Logging properties
The data logging tab contains all the properties used to log data. Allows the user to log raw or
sound field data from the entire sensor or from a selected distance range. Files are self-
contained, and contain all the property information required to allow them to be used with the
Playbackmodule.
Figure 7-33 Data Logging
Data Logging directory
Determines where logged data will be written to.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
49/90
Web Configuration Utility 45
Logging Filename
Tags the file name with relevant information.
Raw Logging properties
Enable or disable global raw signal logging.
Logging Start / End
Determine the starting and finishing distances used for global raw data logging.
Sound Field Logging properties
The processed Sound Field data can also be logged to disk. The size of a Sound Field data file
is significantly smaller than that of a raw data file, so there is no need (or ability) to define a
distance subset of the currently monitored section. To enable Sound Field data logging, ensure
that the Sound Field logging checkbox is selected. If the check mark is visible, Sound Field
logging is enabled.
Sound Field Logging Data Type
When logging Sound Field data, there is a choice to log either the currently displayed display
type, all of the available display types, or a specific display type.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
50/90
46 FFT Aura Fence Operations Manual
Fibre Break
The Fibre Break parameters activate the fibre break functionality as well as the fibre break
monitoring period, which is typically 5 seconds. Make sure the checkbox is enabled for Fibre
Break functionality to operate.
Figure 7-34 Fibre Break
Suppression
In the situation where sections of the sensor need to have their signals suppressed, a start and
end distance can be defined to isolate individual areas or zones along the sensor. This can also
be done visually by using the Select Visuallybutton.
Figure 7-35 Suppression parameters
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
51/90
Web Configuration Utility 47
Alarm Report
The alarm report section determines which predefined signal stream is used and also allows its
output to be reported to the sound field and FOSS 3 (for FFT Aura Fence) or FFT CAMS. For
fence-mounted FFT Aura systems,AR-level crossingsshould be selected.
Figure 7-36 Alarm Report parameters
7.8.3 Zones
A zone is a defined section of the sensor path that may have unique processing requirements.
For example, a fence line may have two different fence types, or a system may have a sensor
cable run above and below ground within the same run. In these cases, unique filter ranges and
detection parameters can be employed as a result of differing levels of sensitivity.
New zone
To create a new zone, select the Zoneoption from the menu then click the green plus
symbol near the right edge of the dialog box.
A popup is displayed allowing a name to be entered for the newly created zone.
From here, the Sound Fielddisplay updates showing two drag handles, the left for the
start distance and the right for the end distance of the new zone. If the exact distances
are known, they can be entered in the two text fields accompanying the drag handles.
This will allow the zone limits to be defined graphically on the waterfall plot.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
52/90
48 FFT Aura Fence Operations Manual
Once the start and end distances have been entered, click the Submitbutton. Once
confirmed, the zone is added to the Zonedialog, and the zone is displayed on the
Sound Fielddisplay at the top of the waterfall section.
Repeat this procedure for each zone to be defined on the fibre sensor.
Figure 7-37 Configuring zones
Figure 7-38 Naming a new zone
Figure 7-39 Add a zone
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
53/90
Web Configuration Utility 49
Figure 7-40 Define the zone size
Editing the start and end distance of a zone
To change the zones start and end distance click on the Zone Resizeicon (the icon
containing two small green squares third from the left). This displays the start and end
drag handles showing the zones current extents, which can thereafter be graphically or
manually altered (using the same procedure as creating the zone).
Once edited, click the Submitbutton to register the change.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
54/90
50 FFT Aura Fence Operations Manual
Editing zone properties
By default, when a zone is first created, it inherits the global fibre properties such as
the filters and the threshold counts. Click on the Zone Propertyicon, immediately to
the left of the red X icon, to display the zone properties dialog.
Figure 7-41 Resize zone
Figure 7-42 Zone properties set to defaults
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
55/90
Web Configuration Utility 51
To customise any of the parameters, deselect the Defaultto allow editing.
Figure 7-43 Editable parameters
7.8.4 View FDEL properties
Select to view the current configuration file.
Figure 7-44 Configuration file
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
56/90
52 FFT Aura Fence Operations Manual
Download diagnostic logs
In the event of an error, the system diagnostics log can be downloaded and forwarded to FFT
for analysis.
Reset to factory defaults
Reset the controller to its factory defaults.
Restart
Selecting this option will initiate a system reboot.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
57/90
Web Configuration Utility 53
7.9 Level Crossings in HWI
The FFT Aura Fence system uses FFTs level crossings (LC) algorithm to process the rawsignals. This algorithm is effective for discriminating between intrusion and nuisance events,
and to minimise nuisance alarms. logic. When using FFT Aura as a fence-mounted perimeter
sensor, the LC algorithm must be used. For level crossings-based alarm logic, the HWI
software performs the following tasks:
filtering the sensor signal
calculating level crossing counts for each sensing channel and generating a LC sound
field
applying dynamic threshold to the level crossings sound field.
7.9.1 Signal Filtering and Level Crossings Counts
The filter and level crossings parameters can be accessed via the HWI configuration menu
(AdminDetection statisticsDS-Level Crossingdialog).
Figure 7-45 Admin menu option with Detection statistics
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
58/90
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
59/90
Web Configuration Utility 55
Figure 7-47 Filter parameters
Level crossings parameters
The level crossings counts have the following parameters:
Block size: the number of samples in a block. The configurable block sizes in HWI
software are 16, 32, 64, 128, 256 and 512 samples.
Threshold: the threshold used to detect level crossings. A signal must go from below
this threshold to equal to or above it for a level crossing to occur. Threshold location: location at which Threshold is accurate. All other locations have
the Degradation Factor applied to work out the threshold at that location.
Degradation factor: number of units the Threshold goes down over one kilometre of
sensor. For example, if the Threshold = 900; the Threshold location = 1000 m and the
Degradation factor = 48, the new Threshold at 2000 m will be 852.
Threshold minimum: the minimum threshold used to detect level crossings. If the
degradation factor would cause the Threshold to go below this value for a given bin
then this minimum threshold is used instead.
Always choose the largest stable number of tap within the band to get sharper
cut off frequency.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
60/90
56 FFT Aura Fence Operations Manual
To set the correct value for the level crossings parameters (Threshold, Degradation
factorand Threshold minimum), the Level Crossings Soundfield can be used for
visualisation. A number of test points along the sensor can be set to calibrate the levelcrossings parameters by tapping at each point to visualise the response on the LCs
sound field.
Figure 7-48 Level crossings parameters
Figure 7-49 LCs sound field with three test points for calibration
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
61/90
Web Configuration Utility 57
Setting the LC parameters (Degradation Factor)
An example of how to set the correct value for the important level crossings parameters
(Threshold, Degradation factorand Threshold minimum) is shown in the Figures 7-50 to 7-52.
Four test points along the 5 km sensor are chosen (at 1280 m, 1424 m, 1590 m and 4796 m).
Strong event data, such as fence kicking or fence tapping, are collected. Figure 7-50 shows a
strong event at 1280 m, 1424 m and 1590 m with two different thresholds (1200 and 2000). If
the Degradation factor is set to zero, the threshold along the entire sensor is fixed and can lead
to a loss of sensitivity over distance. Figure 7-50 shows a drop in the level crossings generated
at the far end of the sensor if a zero Degradation factor is used, even if the Threshold is
adjusted. The Degradation factor should have a value greater than zero to compensate for the
attenuation in the signal over distance.
Figure 7-50 Strong events at 1280 m, 1424 m and 1590 m with two different
fixed thresholds (1200 and 2000)
Figure 7-53 shows the effect of the Degradation factor on the detected level crossings sound
field for a strong event. When the Degradation factor is increased to 50, it effectively lowers
the Threshold with distance (per km), and the level crossings counts of the test events at4796 m are now higher. This can be seen by looking at the LC waterfall in Figure 7-53, where
a Degradation factor of 50 has increased the LC counts at the far end of the sensor.
It is important that the Degradation factor is not too high, as an excessive value will reduce the
Threshold too low and below the background noise, resulting in too many unwanted nuisance
alarms. An example of this is shown in Figure 7-52 where the LC counts increase significantly
with a degradation factor of 300. A factor of 50 is suitable for this example.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
62/90
58 FFT Aura Fence Operations Manual
Figure 7-51 Effect of the degradation factor on the detected level crossings
sound field for kicks event
Figure 7-52 Higher degradation factor triggers noise
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
63/90
Web Configuration Utility 59
7.9.2 Dynamic Threshold
The LC algorithm used by FFT Aura allows for a dynamic event threshold that automaticallyadjusts itself as the background nuisance event increases or decreases in strength (as is the case
with wind or rainfall). The dynamic threshold parameters can be accessed via the HWI
configuration menu (Admin StreamsST-Level Crossingsdialog).
Figure 7-53 Admin menu option with streams
The HWI streams include parameters that monitor background noise to update the dynamic
threshold and parameters for event detection when the level crossing goes above the dynamicthreshold.
Figure 7-54 Streams parameters
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
64/90
60 FFT Aura Fence Operations Manual
Background noise monitoring
The background noise monitoring is used to update the dynamic threshold. It has the following
parameters:
Monitor duration: the number of blocks (along shots axis) that are monitored to
determine whether activity on the sensor is background noise or genuine activity.
Indicates the duration of the Monitor Window.
Monitor width: the number of bins (along bins axis) that are monitored to determine
whether activity on the sensor is background noise or genuine activity. Indicates the
width of the Monitor Window.
Monitor overlap: the number of bins of Monitor Window overlap used when sliding the
Monitor Window across the sensor to determine the dynamic threshold for each bin. Max variation: the maximum amount of variation in level crossings within the region
of interest before activity is considered genuine. If the variation within the Monitor
Window is less than this value then the region inside the Monitor Window is
considered background noise. This parameter has direct impact on the sensitivity.
Increasing the Max variation decreases the sensitivity and vice versa.
Figure 7-55 Background noise monitoring parameters
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
65/90
Web Configuration Utility 61
Event detection
In HWI software, any level crossings counts above the dynamic threshold will be sent to
FOSS 3 for further event grouping and processing. The parameters that control these level
crossings counts are:
Start disturbance threshold: the number of level crossings above the background noise
required for an event to be generated. Increasing this number reduces detection
sensitivity.
End disturbance threshold: the number of level crossings above the background noise
required for activity to be below before an event is determined to have finished.
End disturbance duration: the number of consecutive blocks below the End
disturbance thresholdrequired before an event is determined to have finished. Max disturbance duration: the maximum length of an event.
Event region margin: the number of bins either side of an event to be included in the
area or interest.
Figure 7-56 Event detection parameters in FFT Aura
All level crossings values above the dynamic threshold in FFT Aura machines will be sent to
FOSS 3, including their bins locations along the sensor for classification and alarming. The
following section discusses the event detection, event classification and alarm reporting within
FOSS 3.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
66/90
62 FFT Aura Fence Operations Manual
8.0 FFT Aura Fence Alarming Module:
FOSS 3 Configuration
FOSS 3 is FFT Aura Fences alarming module. It receives level crossing information from
HWI, classifies the detected events, and processes them to generate intrusion alarms. FOSS 3
runs on a separate computer, typically on the same computer that also runs FFT CAMS. While
HWI can interface directly to FFT CAMS, for fence-mounted FFT Aura systems, FOSS 3
replaces this interface.
8.1 Level Crossings in FOSS 3
The HWI software communicates all level crossings values above the dynamic threshold to
FOSS 3 for further analysis and alarm generation. FFT Aura Fence uses all FOSS 3 utilities:
FOSS 3 Manager
FOSS 3 Classification Utility
FOSS 3 Diagnostic Utility
8.1.1 FOSS 3 Manager
FOSS 3 can be connected to one or more FFT Aura sensing controllers. The FOSS 3 Managerhas a number of configuration panels that are used for communicating with the FFT Aura
sensing controller, event accumulation, event classification and event location methods.
Figure 8-1 FFT Aura configuration views and modules
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
67/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 63
The configuration of FOSS 3 to work with HWI can be performed by importing a preset default
foss3.xmlfile that can be supplied by FFT. Alternatively, the configuration can also be done
manually, but it is recommended that a default configuration file is obtained from FFT.
The following sections describe each configuration panel in FOSS 3 Manager.
FFT Aura Configuration view
The FFT Aura parameters in FOSS 3 include event types/classes that are configured within the
FOSS 3 Classification Utility and also include FFT Aura timeouts parameters that are used to
check the status of the FFT Aura sensing controller.
Event types include the list of events that can be used within the accumulator to trigger alarms.
Some of the events can be used with level crossings detection method and others can be usedwith the FFT Aura standard detection method.
Figure 8-2 FFT Aura Configuration view
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
68/90
64 FFT Aura Fence Operations Manual
Figure 8-3 Events used with LCs detection method
Figure 8-4 Events used with FFT Aura standard detection method
The following list the FFT Aura timeouts parameters that are used to check the status of the
FFT Aura system:
Connection retry interval: the time interval spend by FOSS 3 to reconnect to the FFTAura system.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
69/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 65
Fibre break reset interval: the system sends fibre break messages at regular intervals. If
a fibre break alarm is active and a fibre break message is not received in the required
interval, the fibre break alarm will be reset. Laser temperature reset interval: the system sends laser temperature warning
messages at 60-second intervals. If a temperature warning is active and a temperature
warning message is not received within the required interval, the warning will be reset.
Maximum heartbeat interval: the system sends heartbeat messages at regular intervals
(apparently 15 seconds for binary connection). If a heartbeat message is not received
in the required interval, an alarm will be generated.
System shutdown interval: the system may occasionally be restarted. The system may
be restarted due to a configuration change or because an error has occurred. Do not
generate a system alarm until the system has been down for at least the specifiedperiod of time.
Suppress duplicate events: the system may occasionally report the same event more
than once with updated location information. This setting tells FOSS 3 application
whether to ignore these updated events or report them as new ones.
Maximum event history age: how long events are stored to determine if a new event is
a duplicate of an old one.
Fibre break location tolerance: the system send fibre break associated with its location.
If another fibre break alarm is received from the system within the location tolerance,
FOSS 3 will keep fibre break alarm active.
Figure 8-5 FFT Aura timeouts parameters
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
70/90
66 FFT Aura Fence Operations Manual
System Configuration view
The Systemview includes parameters that automatically acknowledge an alarm within a
specified time duration.
Figure 8-6 System configuration view
Accumulation Configuration View
The Accumulation view has two types of accumulators; standard and clustering. This manual
discusses only the standard accumulator. These accumulators work in a similar way to the
accumulators as described in the FOSS 3 Locator manual.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
71/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 67
Figure 8-7 Standard accumulator
TheAccumulationview is used to configure the accumulation Instances such as events due to
classification accumulators (for example, Aura Accumulator and Aura Fence Accumulator).
Figure 8-8 illustrates how to create the Accumulator instances. Two accumulator instances
created. A number of instances can be created, depending on the site requirements.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
72/90
68 FFT Aura Fence Operations Manual
Figure 8-8 Accumulator Instances creation
Figure 8-9 shows how to suppress an event within a range of location. In Figure 8-10, an
example is illustrated in which any AuraStrongActivity event will be suppressed occurring
between the location range specified. This event will be suppressed from all the accumulator
instances. It has to be noted that any other instances or events taking place during this Aura
StrongActivity event duration will be suppressed completely and will not be reported.
Accumulators have different rules and conditions that can be used for configuration.
Accumulator reports alarm when it satisfies All the rules and conditions. The following section
provides simple example of how to configure an accumulator.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
73/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 69
Figure 8-9 Event Suppression within a range of location
Figure 8-10 Example of Event Suppression
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
74/90
70 FFT Aura Fence Operations Manual
Example of Accumulator configuration (FFT Aura Accumulator)
Each accumulator triggers an alarm when it satisfies specific weighting criteria within an
Accumulation Duration. For example, this accumulator will trigger an alarm when the weight
of the classified events is equal to or exceeds the Trigger Threshold AND the same
accumulator includes at least one AuraStrongActivity event (one AuraStrongActivity event
will have a weight of 2). The logic for this accumulator to trigger an alarm is as follows:
(Meet the Events Accumulated rules)
AND
(The Required Events rules)
Figure 8-11 Example of reporting Alarm using multiple conditions
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
75/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 71
Connection with Sensor 1
FOSS 3 can be connected to single or multiple FFT Aura systems. Each machine in FOSS 3
has four configuration views. These views are FFT Aura Sensor, Accumulation, Locator and
Event Classification.
FFT Aura Sensor view
The FFT Aura Sensor view for each FFT Aura system includes parameters that are used to
group level crossings counts above dynamic threshold as an event for classification and also
includes communication parameters (IP Address and Ports) to connect with FFT Aura system
and FFT CAMS.
Figure 8-12 Event detection parameters within FOSS 3
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
76/90
72 FFT Aura Fence Operations Manual
Figure 8-13 Communication with Aura System and FFT CAMS
The status of the communication link between the FFT Aura system and FOSS 3 can be
verified via the FOSS 3 Diagnostic Utility.
Figure 8-14 FOSS 3 - FFT Aura system communication status
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
77/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 73
The FFT Aura event detection parameters are described below:
Bin proximity threshold: the number of bins with zero LCs value allowed between two
active (non-zero LCs value) bins to be included in the same event.
Block proximity threshold: the number of blocks with zero LCs value allowed between
two active (non-zero LCs value) blocks to be included in the same event.
Minimum event duration: the minimum length of an event.
Maximum event duration: the maximum length of an event.
Minimum width: the minimum distance of an event.
Accumulation View
This view allows a user to enable certain accumulators to be used with each FFT Aura sensor
(i.e Sensor 1).
Figure 8-15 Enabling accumulators
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
78/90
74 FFT Aura Fence Operations Manual
Locator view
The Locator view has binning and clustering methods. These location methods are used to
determine the alarm that is generated by the accumulator.
Figure 8-16 Location methods
Event Classification view
This view allows the user to enable the event classification method and to specify the
classification method to be used from the Classification Utility.
Figure 8-17 Event classification view
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
79/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 75
8.1.2 FOSS 3 Classification Utility
In the FOSS 3 Classification Utility, the event classification consists of classification methodsand each method has the followings stages:
1 Event Detection
2 Features
3 Event Types (Classifiers).
Figure 8-18 shows three classification methods (Default, Aura Method 1, Aura Method 2).
Each classification method can be configured independently and enabled within FOSS 3
Manager.
Figure 8-18 Classification methods in FOSS 3 Classification Utility.
For training and tuning parameters, one method can be selected at a time
from a drop-down list.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
80/90
76 FFT Aura Fence Operations Manual
Note:While Training the Events Configuration, the Selected Classification Method has to be
Default, for the First Method Parameters settings to be applicable and the selected
Classification Method has to be Aura Method 1 for the Second Method and so forth as shownin Figure 8-19.
Figure 8-19 Method selection for tuning and training purposes
Event Detection
Event detection in FFT Aura software is based on level crossings and configured in the FOSS 3Manager. The Event detection parameters in the FOSS 3 Classification Utility are not
applicable to FFT Aura software.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
81/90
FFT Aura Fence Alarming Module: FOSS 3 Configuration 77
Figure 8-20 Event detection parameters within FOSS 3 configured in
FOSS 3 Manager (same as Figure 8-12)
Features
After the event is detected, a number of features will be extracted. The FOSS 3 Classification
Utility includes features used with the FFT Locator (not used here) and features used with FFT
Aura system. The followings are the features that are used with FFT Aura system:
Duration: duration of event in blocks (similar to Height [Aura] feature).
Area Density Windows [Aura]: number of windows where the density of the window is
greater than or equal to the Required Density.
Area [Aura]: number of bin/block cells covered by event.
LC Density Windows [Aura]: the number of shots in an event that have a bin/block
value greater than the Required Level Crossingsthreshold.
Value - Maximum [Aura]: maximum level crossings count for a bin/block cell included
in the Aura event. Value - Total [Aura]: total number of level crossings in Aura event.
Width [Aura]: width in bins of the Aura event.
Height [Aura]: height (or duration) of event in blocks.
Perimeter [Aura]: number of bin/block cells required to form a perimeter around the
event.
Area Density [Aura]: number of bin/block cells above/below (depending on 'Threshold
Rule') the specified threshold divided by the total number of event bin/block cells
multiplied by 100. Value - Minimum [Aura]: minimum level crossing count for a bin/block cell included in
the FFT Aura event.
-
8/12/2019 FFT Aura Fence Operations Manual v2.0
82/90
78 FFT Aura F