Fernandes & Associates Consulting Engineers - Mechanical & Structural CERTIFICATE OF COMPLIANCE Date: February 22, 2019 Certificate no. FAC-882 Rev. 1 ACE GUTTERS PTY LTD - CORRUGATED ROOF AND WALL CLADDING Specification of items certified: Refer to drawing FA-AG-882 Rev. 1 Aspects of cladding certified: Spans for roofing and walling applications in residential building BASIS OF CERTIFICATION The following documents were referred to in making this certification: a. NCC2016 Volume 2 b. AS 4100:1998 (R2016) Steel structures c. AS/NZS 4600:2018 Cold-formed steel structures d. AS 4055:2012 Wind loads for housing e. AS 1170.1:2002 (R2016) Structural design actions. Permanent, imposed and other actions CERTIFICATION I certify that the spans in drawing FA-AG-882 Rev. 1 comply with the requirements of the Codes and Standards listed above. CONDITIONS OF CERTIFICATION The spans are valid for: a. Residential buildi ngs. (Refer to AS4055 for definition of residential building) b. Maximum roof pitch of 35° (minimum roof pitch is for water drainage purposes) c. Minimum screw size of 12g and GSSO, 1.0mm (BMT) support material (check screw capacity if using smaller screws or thinner/weaker support material) t= Milto Fernandes FIEAus , CPEng, NER, RPEQ 4112 Chartered Professional Engineer Principal Engineer < \. For/and on behalf of Fernandes and Associates Pty. Ltd. [email protected] Mobile: 0411 760 565 e Milto n J. Fernandes .. RPEO, FI EAust CPEng C hartered Profess io na l Engin eer Membership No. 9 2059 5 ENGINEERS Engine ers Aust ralia AUSTRALIA Registered Professional Engineer of Queensland - - .. .. RPEQ 4112 P. 0 . Box 1104 Fort itude Valley QLD 4006 Email: [email protected].au THE MEWS COMMERCIAL. 2/141 Campbell St. Bowen Hills QLD 4006 Fernandes & Associates Pty Ltd (ABN 56 059 624 565) Tel: (07) 3852 13 71 Fax: (07) 3852 1329 www.femandes.net.au

Upload: others

Post on 28-Nov-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Fernandes & Associates Consulting Engineers - Mechanical & Structural

CERTIFICATE OF COMPLIANCE

Date: February 22, 2019 Certificate no. FAC-882 Rev. 1

ACE GUTTERS PTY LTD - CORRUGATED ROOF AND WALL CLADDING

Specification of items certified: Refer to drawing FA-AG-882 Rev. 1

Aspects of cladding certified: Spans for roofing and walling applications in residential building

BASIS OF CERTIFICATION

The following documents were referred to in making this certification:

a. NCC2016 Volume 2 b. AS 4100:1998 (R2016) Steel structures c. AS/NZS 4600:2018 Cold-formed steel structures d. AS 4055:2012 Wind loads for housing e. AS 1170.1:2002 (R2016) Structural design actions. Permanent, imposed and other actions

CERTIFICATION

I certify that the spans in drawing FA-AG-882 Rev. 1 comply with the requirements of the Codes and Standards listed above.

CONDITIONS OF CERTIFICATION

The spans are valid for:

a. Residential buildings. (Refer to AS4055 for definition of residential building)

b. Maximum roof pitch of 35° (minimum roof pitch is 5° for water drainage purposes)

c. Minimum screw size of 12g and GSSO, 1.0mm (BMT) support material (check screw capacity if using smaller screws or thinner/weaker support material)

M~\ t= Milto Fernandes FIEAus , CPEng, NER, RPEQ 4112 Chartered Professional Engineer Principal Engineer

< \.

For/and on behalf of Fernandes and Associates Pty. Ltd. [email protected] Mobile: 0411 760 565

e Milton J. Fernandes .. RPEO, FIEAust CPEng

Chartered Professional Engineer Membership No. 920595

ENGINEERS Engineers Australia AUSTRALIA

Registered Professional Engineer of Queensland

- - .. . . RPEQ 4112

P. 0 . Box 1104 Fortitude Valley QLD 4006 Email: [email protected] THE MEWS COMMERCIAL. 2/141 Campbell St. Bowen Hills QLD 4006 Fernandes & Associates Pty Ltd (ABN 56 059 624 565)

Tel: (07) 3852 1371 Fax: (07) 3852 1329

www.femandes.net.au

ACE GUTTERS - RESIDENTIAL BUILDING SPAN TABLES

CORRUGATED ROOF AND WALL CLADDING- SPAN TABLES FOR NON-CYCLONIC AREAS

ACE CORRUGATED SPECIFICATIONS

Material High tensile steel, GSSO

Base metal thickness (B.M.T.) Available in either 0.42 or 0.48mm

Cover 762 mm (width)

17mm Profile height

Finish Available in ZINCALUMEe or DURAKOTE

Minimum roof pitch s·

SHEET PROFILE

BMT AS4055 Wind Classification (mm) APPLICATION SPAN TYPE 3 Fasteners per support 5 Fasteners per support

NI N2 N3 N4 Nl N2 N3 N4

Single 700 700 600 - 700 700 700 700

Roof End 900 900 750 - 950 900 900 900 Internal 1200 1200 1050 - 1200 1200 1200 1200

0.42 Single 1650 1350 1050 900 1650 1500 1350 1300

Wall End 2100 1550 1100 1000 2100 1900 1500 1450 Internal 2600 2200 1700 1450 2600 2300 2050 1950 Single 800 800 600 - 800 800 800 800

Roof End 1300 1300 1000 - 1300 1300 1300 1300

0.48 Internal 1600 1600 1550 - 1600 1600 1600 1600

Single 1800 1450 1000 950 1800 1750 1450 1400 Wall End 2250 1850 1500 1300 2250 1950 1700 1650

Internal 2700 2200 1950 1800 2700 2300 2100 2000

Notes: 1. All spans are in mm and are valid for 12g screws and G550, l.Omm BMT support material. Check screw capacity if using

smaller screws or thinner support material. 2. Refer to AS4055 for definition of residential building

TABLE 1. ACE CORRUGATED SPANS FOR RESIDENTIAL BUILDING

BMT Maximum (mm) Application Span type recommended

span-(mm)

Single 700

Roof End 900 Internal 1200

0.42 Overhang 200

Single 1650

Wall End 2100 Internal 2600 Overhang 200

Single 800

Roof End 1300 Internal 1600

0.48 Overhang 250 Single 1800

Wall End 2250 Internal 2700 Overhang 250

TABLE 2. MAXIMUM RECOMMENDED SPANS

J), CONSULTING ENGINEERS: CLIENT: Fernandes & Associates Pty Ltd Ace Gutters Pty. Ltd.

Fixed to steel Fixed to timber

~.55to ~1.0 to Hardwood Softwood 1.0mm 3.0mm BMT BMT

Crest Roof Zips 12- 12-llx50, 12-l lx50, fixed M6-llx50 14x35, Type 17, Type 17,

HH Teks HH HH; or Roof Zips MG-llx50

Pan 10-16x16, 10- 10-12x25, 10-12x30, fixed HH Teks; 16x16, Type 17, Type 17,

or Roof HH Teks HH; or 12- HH; or 12-Zips MG- l lx25, 11x25, Type llx25 Type 17 17, HH; or

HH Roof Zips M6-llx25

Notes: 1. HH stands for Hex Head 2. All screws should be used w ith neoprene sealing washers 3. Longer screws may be required if roof insulat ion is used under

the sheets TABLE 3. RECOMMENDED FASTENERS

ACE CORRUGATED ROOFING AND WALL CLADDING

SPAN TABLES FOR RESIDENTIAL BUILDINGS www.fernandes.net. au www.acegutters.com. au DWG: FA·AG-882 Rev. 1