SEEE DIGIBOOK ON ENGINEERING & TECHNOLOGY, VOL. 01, MAY 2018 ALTERNATE ENERGY TECHNOLOGIES 978-81-933187-0-6 © 2018 SEEEPEDIA.ORG Society for Engineering Education Enrichment N. Dhanusri, [email protected] ; Dr.S.Chitra, [email protected] ; Fault Detection and Isolation in DC Microgrid using Least Square Method N. Dhanusri 1 , Dr.S.Chitra 1 , Dr.N.Devarajan 2 1 Government College of Technology, Coimbatore, India 2 Sri Ramakrishna Institute of Technology, Coimbatore, India [email protected] , [email protected] Abstract-DC Microgrid protection is essential for continuous power supply to the customers. The objective of this proposed work is to detect and locate the fault for fast restoration of the system to normal operation. The proposed protection scheme for DC Microgrid uses Intelligent Electronic Device for detecting and locating the fault. For accurate fault location, the Least Square based estimation technique is used to estimate the inductance of the fault path, from which the direction of fault will be identified. Using the direction of the fault information, internal and external faults are discriminated. The proposed system is tested with various fault conditions and locations in DC Ring Microgrid. The DC Microgrid with ring configuration and its protection schemes are simulated using MATLAB/Simulink environment. Index TermsDC Ring Microgrid, Least Square Estimation Method, IED’s. I. INTRODUCTION The electrical power system is significantly changing in order to cope with the increasing participation of various distributed energy resources. The arising concerns on environmental and sustainable energy issues like greenhouse gas emission, depletion on energy sources, ageing of current transmission and distribution infrastructure and ever-growing demand of electrical energy due to conventional energy sources have promoted the development of distributed renewable power generation [1]. These changes are required to ensure reliable and clean energy sources and to improve the quality of life. Since renewable power sources are naturally dispersed, it is very difficult for the power system to manage the growing and intermittent distributed power generation in a traditional way. In order to effectively manage distributed generation sources, load and energy storages, all the distributed units are integrated together to form a micro power system at the distribution side, the Microgrid. Microgrid is a low or medium voltage electrical network consisting of especially renewable sources of energy, energy storage devices and loads. The electrical network can be AC, DC or combination of both. It is operated either in a grid- connected mode or an islanded mode [2]. Microgrids are normally interconnected to the distribution networks via a direct connection or an interfacing power converter, which gives an opportunity to get power from the utility grid and also feeds power back to utility grid during surplus power generation. In the event of a fault, the microgrid disconnects from the utility network as fast as possible and controls its load using different control methods [3]. In this condition, the microgrid operates in an islanding mode. The concept of microgrid is an advancement towards present unidirectional (i.e. generation →transmission →distribution) electrical distributed networks to futuristic bidirectional active networks (i.e. generation →transmission →distribution ↔distributed generations), aimed to meet the growing energy demand. The possibility of securing power from renewable energy based Distributed Generation (DG) is the key ingredient to the Microgrid. II. DC MICROGRID RING CONFIGURATION A protection scheme for smart DC microgrid with ring configuration is proposed. Using local intelligent electronic device(IED), voltage and current data during fault, a LS based technique estimates the inductance of the fault path which is able to discriminate forward and reverse faults with respect to the IED [4]. This fault direction information is communicated to the other end IED of a line segment. Using the local and other end fault direction information, each IED identifies any internal fault of the line segment correctly. Signals generally being contaminated by noise in a system, as proposed method uses least square filtering, it is able to estimate the scene inductance in IEDs accurately. A smart DC microgrid with ring configuration is considered as shown in Fig. 1. 93

Upload: others

Post on 30-Mar-2021

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fault Detection and Isolation in DC Microgrid using Least ...seeepedia.org/wp-content/uploads/2018/06/S18_05_22.pdfFault detection is an important part ofDC Microgrid protection. Rapidfault

SEEE DIGIBOOK ON ENGINEERING & TECHNOLOGY, VOL. 01, MAY 2018 ALTERNATE ENERGY TECHNOLOGIES

978-81-933187-0-6 © 2018 SEEEPEDIA.ORG Society for Engineering Education Enrichment

N. Dhanusri, [email protected]; Dr.S.Chitra, [email protected];

Fault Detection and Isolation in DC Microgrid using Least

Square Method

N. Dhanusri1, Dr.S.Chitra1, Dr.N.Devarajan2 1Government College of Technology, Coimbatore, India

2Sri Ramakrishna Institute of Technology, Coimbatore, India [email protected], [email protected]

Abstract-DC Microgrid protection is essential for continuous power supply to the customers. The objective of this proposed work is to detect and locate the fault for fast restoration of the system to normal operation. The proposed protection scheme for DC Microgrid uses Intelligent Electronic Device for detecting and locating the fault. For accurate fault location, the Least Square based estimation technique is used to estimate the inductance of the fault path, from which the direction of fault will be identified. Using the direction of the fault information, internal and external faults are discriminated. The proposed system is tested with various fault conditions and locations in DC Ring Microgrid. The DC Microgrid with ring configuration and its protection schemes are simulated using MATLAB/Simulink environment. Index Terms—DC Ring Microgrid, Least Square Estimation Method, IED’s.

I. INTRODUCTION The electrical power system is significantly changing in order to cope with the increasing participation of various distributed energy resources. The arising concerns on environmental and sustainable energy issues like greenhouse gas emission, depletion on energy sources, ageing of current transmission and distribution infrastructure and ever-growing demand of electrical energy due to conventional energy sources have promoted the development of distributed renewable power generation [1]. These changes are required to ensure reliable and clean energy sources and to improve the quality of life. Since renewable power sources are naturally dispersed, it is very difficult for the power system to manage the growing and intermittent distributed power generation in a traditional way. In order to effectively manage distributed generation sources, load and energy storages, all the distributed units are integrated together to form a micro power system at the distribution side, the Microgrid. Microgrid is a low or medium voltage electrical network consisting of especially renewable sources of energy, energy storage devices and loads. The electrical network can be AC, DC or combination of both. It is operated either in a grid-connected mode or an islanded mode [2]. Microgrids are normally interconnected to the distribution networks via a direct connection or an interfacing power converter, which gives an opportunity to get power from the utility grid and also feeds power back to utility grid during surplus power generation. In the event of a fault, the microgrid disconnects from the utility network as fast as possible and controls its

load using different control methods [3]. In this condition, the microgrid operates in an islanding mode. The concept of microgrid is an advancement towards present unidirectional (i.e. generation →transmission →distribution) electrical distributed networks to futuristic bidirectional active networks (i.e. generation →transmission →distribution ↔distributed generations), aimed to meet the growing energy demand. The possibility of securing power from renewable energy based Distributed Generation (DG) is the key ingredient to the Microgrid.

II. DC MICROGRID RING CONFIGURATION A protection scheme for smart DC microgrid with ring configuration is proposed. Using local intelligent electronic device(IED), voltage and current data during fault, a LS based technique estimates the inductance of the fault path which is able to discriminate forward and reverse faults with respect to the IED [4]. This fault direction information is communicated to the other end IED of a line segment. Using the local and other end fault direction information, each IED identifies any internal fault of the line segment correctly. Signals generally being contaminated by noise in a system, as proposed method uses least square filtering, it is able to estimate the scene inductance in IEDs accurately. A smart DC microgrid with ring configuration is considered as shown in Fig. 1.

93

Page 2: Fault Detection and Isolation in DC Microgrid using Least ...seeepedia.org/wp-content/uploads/2018/06/S18_05_22.pdfFault detection is an important part ofDC Microgrid protection. Rapidfault

SEEE DIGIBOOK ON ENGINEERING & TECHNOLOGY, VOL. 01, MAY 2018

978-81-933187-0-6 © 2018 SEEEPEDIA.ORG Society for Engineering Education Enrichment

Fig 2.1 350V Monopolar DC Microgrid with Ring Configuration To the microgrid PV array is connected which supply power to different DC and AC loads. For efficient and reliable energy management and as a backup, battery is connected to the microgrid [28]. Using bidirectional AC-DC front-end converter and DC-DC converters, integration of sources, loads and storage is done. Grid forming DGs regulate voltage and behave as a slack terminal in the islanded DC microgrid. PV array operate as grid following sources that injects power under maximum power point tracking(MPPT) mode. Hierarchical droop control strategy [5] for grid forming DGs is considered. Inner current and outer voltage controllers including MPPT in the DC-DC converters for grid following sources are modelled [6]. Line segments in the DC ring consist of cables of different lengths [7]. One of the main limitations of present day converters is that their fault current withstand is much lower than that of thyristor-based converters, typically twice the nominal current rating of the converter [8]. The proposed protection scheme for the DC Microgrid uses the measured voltage and current data’s from the system. During the fault, the disturbance index h is checked, if it exceeds the threshold, the fault is detected and the location of fault is carried out. The voltage, current and its derivatives are sampled and using least square method estimation of seen inductance at IED is obtained. If the inductance seen by the IED is negative at one end of the line segment and if the other end IED also sees negative inductance, then the fault is consisted to be the forward fault and tripping command is given to the corresponding circuit breaker [9]. If any one of the IED shows seen inductance positive, then it is a reverse fault and the tripping is not derived. A. Fault Detection Fault detection is an important part of DC Microgrid protection. Rapid fault detecting strategy is a prerequisite for the DC protection scheme. It aims to detect if there is a fault, discriminate which is the faulty part, determine which breakers to trip and send them such signals. This is realized by the protection relays. The fault detection function is designed to overcome the problem of limited fault current magnitude. To detect the disturbance such as fault, the disturbance index (h) is calculated by

III. PROPOSED PROTECTION SCHEME

Fig 3.1 Flow Chart for the proposed system

h = .......(3.1) where

- Sample value of current - Sampling interval

N - Change in current over a period is the current value that is sampled and is the sampling

interval. The change in current over a period of time N is 5A. For 4kHz sampling, the threshold value is fixed as 4000A/s. When the disturbance index h exceeds the threshold ξ, the fault is detected and the algorithm triggers the main algorithm to accurately identify the fault location to derive the protection decision to restore to normal operation. For small disturbance or change in light load where rate of rise of current is slow, the numerator of h is not high enough and h does not exceed ξ and there no fault is detected. B. Fault Location Fault locating is to estimate the exact fault location in the faulty line. Although this is not compulsory in the protecting

VOLTAGE & CURRRENT DATA

FAULT DETECTION USING h INDEX h -

h>ξ

CONSIDER VOLTAGE &CURRT SAMPLES

ESTIMATE PARAMETER USING LEAST SQUARE METHOD

𝐿 𝑠𝑒𝑒𝑛 < 0

CHECK IF BOTH IEDs SEES

FORWARD FAULT

START

yes

yes

No

No

Trip No Trip

yes

No

94

Page 3: Fault Detection and Isolation in DC Microgrid using Least ...seeepedia.org/wp-content/uploads/2018/06/S18_05_22.pdfFault detection is an important part ofDC Microgrid protection. Rapidfault

SEEE DIGIBOOK ON ENGINEERING & TECHNOLOGY, VOL. 01, MAY 2018

978-81-933187-0-6 © 2018 SEEEPEDIA.ORG Society for Engineering Education Enrichment

scheme, fault locating is still significant and essential in DC cable short circuit since these faults are almost always permanent and require repairs later on [10-12]. In this circumstance, it is usually assumed that the faulty line has already been determined and isolated from the system. As a result, speed is no longer the highest priority in this condition, and that the data is usually processed offline. However, it is always desirable that the fault location can be estimated only with the data which have already been obtained during the fault. C. Least square based estimation technique Under normal condition, there is no inductance in the DC system. During transient condition in DC system, the inductance occurs and the drop in the line increases due to effect of inductance at that period. From the figure 5.2, the voltage, 𝑣𝐶 at any time t will be

…. (3.2) where 𝑣𝐶, 𝑖𝐶.1 are the voltage and current seen by 𝐼𝐸𝐷𝐶.1 during transient and 𝑅𝐶𝐷, 𝐿𝐶𝐷 are the resistance and inductance of cable section CD. During steady state voltage at bus C, 𝑉𝐶 will be 𝑉𝐶 = 𝑉𝐷 + 𝐼𝐶.1𝑅𝐶𝐷 …. (3.3) where 𝑉𝐶, 𝐼𝐶.1 are the RMS voltage and current seen by 𝐼𝐸𝐷𝐶.1. The prefault voltage and current values are constant for an event. i) Forward fault In the DC ring microgrid, line sections BC and CD and a ground fault is created at instant t1 in the line section CD and the voltage and current at 𝐼𝐸𝐷𝐶.1 is analyzed. Voltage at bus C will be

…. (3.4) where 𝑣𝐶𝑓(𝑡1) and 𝑖𝐶.1𝑓(𝑡1) are the sample voltage and current seen 𝐼𝐸𝐷𝐶.1 by during fault. 𝑣𝑓(𝑡1) is the voltages at fault point and 𝑅𝐶𝑓, 𝐿𝐶𝑓 are the resistance and inductance from 𝐼𝐸𝐷𝐶.1 to fault point. Subtracting (3.4) which is the prefault voltage, from (3.3),

(3.5)

Fig 3.2 Model for forward fault analysis ii) Reverse fault A fault in the section BC is treated as a reverse fault for 𝐼𝐸𝐷𝐶.1. Considering such a fault at time t2, voltage seen by 𝐼𝐸𝐷𝐶.1 is

….. (3.6) Subtracting (3.3) from (3.6),

.... (3.7)

Fig 3.3 Model for Reverse Fault Analysis For the two sides of fault situations in the system, 𝐼𝐸𝐷𝐶.1measures the current 𝐼𝐶.1and voltage 𝑣𝐶. From equation (3.5) and (3.7), it is to be observed that for forward and reverse fault 𝑖𝐶.1 is 𝑖𝐶.1𝑓(𝑡1) and 𝑖𝐶.1𝑓(𝑡1) respectively. Similarly, the rate of change of current seen by 𝐼𝐸𝐷𝐶.1 during fault situation is

in case of forward and reverse direction respectively. Using Least Square technique, equations (3.5) and (3.7) can be written as [A][x] = [m] …….(5.8) where [A]+ = ([A]T [A])-1 which is the left pseudo-inverse of [A] The parameters seen by the IEDs are obtained from the computation of (3.8). For forward fault the voltage and current relation in (3.5) and corresponding relation forreverse

fault in (3.7) reveals that the coefficient of are 𝐿𝐶𝑓 and 𝐿𝐶𝐷 respectively. Therefore, when this coefficient which is termed as seen inductance is estimated for any case using (3.8), a negative value for forward fault and a positive value for reverse fault are obtained. This principle using estimated inductance is successfully applied for identifying direction of fault in DC Microgrid.

IV. RESULT AND DISCUSSION The DC Microgrid with ring configuration is simulated in the MATLAB R2014a /Simulink environment. The DC Microgrid is

constructed with 6 buses connected through DC cables. Fig 4.1 Simulation model for the proposed DC Microgrid with IED’s There are 6-line segments connecting the buses, each containing 2 IEDs at both the ends of the line. There are totally 12 IEDs associated with corresponding solid-state circuit breaker.

95

Page 4: Fault Detection and Isolation in DC Microgrid using Least ...seeepedia.org/wp-content/uploads/2018/06/S18_05_22.pdfFault detection is an important part ofDC Microgrid protection. Rapidfault

SEEE DIGIBOOK ON ENGINEERING & TECHNOLOGY, VOL. 01, MAY 2018

978-81-933187-0-6 © 2018 SEEEPEDIA.ORG Society for Engineering Education Enrichment

There are 2 solar panels having 500kW and 125kW capacity with temperature and irradiance at standard test condition. Maximum Power Point Tracker(MPPT) controller is used to maximize the amount of power produced from the array. Lead acid battery is used as a backup storage. DC to DC boost converter are used increase the input voltage. DC loads of 200kW, 200kW, 100kW are used. Solar, battery and loads are incorporated into the DC microgrid by specifying the DC output at 350V DC.

Fig 4.2 Simulation model of solar with DC-DC Converter Fig 4.2 shows the solar source of 500kW capacity with standard temperature of 250 C and irradiance of 1000W/m2 is used in the DC Microgrid. Fig 4.3 output voltage waveform of 500KW solar panel Fig 4.4 output current waveform of 500KW solar panel

Fig 4.5 Simulation model of battery with DC-DC Converter Fig 4.5 shows the simulation model of DC-DC converter. Battery regulates DC voltage by maintaining the microgrid power balance through their ability to supply the power deficit or absorb extra power. Lead-acid batteries are commonly used for PV-based renewable systems. The lead-acid type battery with 90V and 400 Ah rated capacity. Fig 4.6 output voltage waveform of battery Fig 4.7 current voltage waveform of battery

Fig 4.8 Simulation model of the proposed IED associated with solid – state circuit breaker IED is simulated in the MATLAB function-coding block to detect and locate the fault. The IED acquire voltage and current data after sampling. The voltage and current values are sampled at 4kHz sampling rate.

96

Page 5: Fault Detection and Isolation in DC Microgrid using Least ...seeepedia.org/wp-content/uploads/2018/06/S18_05_22.pdfFault detection is an important part ofDC Microgrid protection. Rapidfault

SEEE DIGIBOOK ON ENGINEERING & TECHNOLOGY, VOL. 01, MAY 2018

978-81-933187-0-6 © 2018 SEEEPEDIA.ORG Society for Engineering Education Enrichment

Fig 4.9 Simulation model of proposed solid-state circuit breaker The solid-state circuit breaker is designed using two thyristors in anti-parallel because the switch requires a continuous current carrying and a short time overcurrent rating equal to the feeder faults level. It has low conduction losses. The thyristors in the feeder are normally energized by continuous and synchronized firing control signal. On detection of fault, these firing pulses are stopped to break the current. The SSCB block is controlled by signals from firing controller.

Fig 4.10 Simulation of firing controller for SSCB Fig 4.10 shows the firing controller for SSCB is designed to generate firing signals to turn on the thyristors, a saw-tooth signal with a DC reference signal are compared. The resultant pulse signal is used in the SSCB block. The controlling signal strongly depends on the level of a sensed quantity that is usually either current or voltage. The firing command decides the SSCB status whether to turn-on or turn-off for interrupting the fault current. Table 4.1 System data for the proposed DC Microgrid

System Voltage 350V DC

Base Power 500 kW

Solar Panel 𝑉𝑚𝑝 = 54.7𝑉, 𝐼𝑚𝑝=5.58A at STC

PV Array 1 Rating 125 kW

PV Array 2 Rating 500kW

Battery 96 V, 0.4 kAh

Load 500kW

V CONCLUSION The fault detection and location for the DC Microgrid system is simulated using MATLAB/Simulink platform. The proposed protection scheme estimates the fault inductance at each IED during the fault and discriminates the forward and reverse faults. The results show the credibility for achieving fault detection and location with line to ground fault in different fault locations with a good level of selectivity. The performance of the proposed method is better for high resistance fault compared to current based directional protection. ACKNOWLEDGMENT The authors are thankful to the authorities of Government College of Technology, Coimbatore and Sri Ramakrishna Institute of Technology, Coimbatore for the facilities rendered to carry out this research work. REFERENCES [1] R. C. Dugan and T. E. McDermott, “Distributed

generation,” IEEE Industry Applications Magazine, vol. 8, pp. 19–25, Mar 2002.

[2] S. Mishra, D. Ramasubramanian, and P. C. Sekhar, “A seamless control methodology for a grid connected and isolated pv-diesel microgrid,” IEEE Trans. Power Syst., vol. 28, pp. 4393–4404, Nov 2013.

[3] J. Wu and X. Guan, “Coordinated multi-microgrids optimal control algorithm for smart distribution management system,” IEEE Trans.Smart Grid, vol. 4, pp. 2174–2181, Dec 2013.

[4] J. Dong, F. Gao, X. Guan, Q. Zhai, and J. Wu, “Storage-reserve sizing with qualified reliability for connected high renewable penetration micro-grid,” IEEE Trans. Sustainable Energy, vol. 7, pp. 732–743, April 2016.

[5] R. H. Lasseter and P. Paigi, “Microgrid: a conceptual solution,” in 35th Annual IEEE Power Electronics Specialists Conference, vol. 6, pp. 4285–4290, June 2004.

[6] H. Nikkhajoei and R. H. Lasseter, “Distributed generation interface to the certs microgrid,” IEEE Trans. Power Del., vol. 24, pp. 1598–1608, July 2009.

[7] R. Cuzner, “Does DC distribution make sense?,” IEEE Electrification Magazine, vol. 4, pp. 2–3, June 2016.

[8] M. Starke, L. M. Tolbert, and B. Ozpineci, “AC vs. DC distribution: A loss comparison,” in Proc. IEEE/PES Transmission and Distribution Conference and Exposition, pp. 1–7, April 2008.

[9] D. Salomonsson, L. Soder, and A. Sannino, “Protection of low-voltage DC microgrids,” IEEE Trans. Power Del., vol. 24, pp. 1045–1053, July 2009.

[10] J. D. Park and J. Candelaria, “Fault detection and isolation in low-voltage DC-bus microgrid,” IEEE Trans. Power Del., vol. 28, pp. 779–787, Jan. 2013.

[11] M. Starke, F. Li, L. M. Tolbert, and B. Ozpineci, “AC vs. DC distribution: Maximum transfer capability,” in Proc. IEEE

97

Page 6: Fault Detection and Isolation in DC Microgrid using Least ...seeepedia.org/wp-content/uploads/2018/06/S18_05_22.pdfFault detection is an important part ofDC Microgrid protection. Rapidfault

SEEE DIGIBOOK ON ENGINEERING & TECHNOLOGY, VOL. 01, MAY 2018

978-81-933187-0-6 © 2018 SEEEPEDIA.ORG Society for Engineering Education Enrichment

Power and Energy Society General Meeting – Conversion and Delivery of Electrical Energy in the 21st Century, pp. 1–6, July 2008.

[12] D. Salomonsson and A. Sannino, “Low–voltage DC distribution system for commercial power systems with sensitive electronic loads,” IEEE Trans. Power Del., vol. 22, pp. 1620–1627, July 2007.

[13] M. Saeedifard, M. Graovac, R. F. Dias, and R. Iravani, “DC power systems: challenges and opportunities,” in IEEE PES General Meeting, pp. 1–7, July 2010.

[14] R. M. Cuzner and G. Venkataramanan, “The status of DC micro-grid protection,” in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, pp. 1–8, Oct 2008.

[15] B. Lu and S. K. Sharma, “A literature review of IGBT fault diagnostic and protection methods for power inverters,” IEEE Trans. Ind. Appl., vol. 45, pp. 1770–1777, Sept 2009.

[16] A. Meghwani, S. Srivastava, and S. Chakrabarti, “A non-unit protection scheme for DC microgrid based on local measurements,” IEEE Trans. Power Del., available on early access, no. 99, DOI. 10.1109/TPWRD.2016.2555844, 2016.

[17] M. J. Mousavi and K. L. Butler-Purry, “A novel condition assessment system for underground distribution applications,” IEEE Trans. Power Syst., vol. 24, pp. 1115–1125, Aug 2009.

[18] S. D. A. Fletcher, P. J. Norman, K. Fong, S. J. Galloway, and G. M. Burt, “High-speed differential protection for smart DC distribution systems,” IEEE Trans. Smart Grid, vol. 5, pp. 2610–2617, Sept 2014.

[19] J. D. Park, J. Candelaria, L. Ma, and K. Dunn, “DC ring-bus microgrid fault protection and identification of fault location,” IEEE Trans. Power Del., vol. 28, pp. 2574–2584, May 2013.

[20] S. D. A. Fletcher, P. J. Norman, S. J. Galloway, P. Crolla, and G. M. Burt, “Optimizing the roles of unit and non-unit protection methods within DC microgrids,” IEEE Trans. Smart Grid, vol. 3, pp. 2079–2087, Dec 2012.

[21] B. Wang, M. Sechilariu, and F. Locment, “Intelligent DC microgrid with smart grid communications: Control strategy consideration and design,” IEEE Trans. Smart Grid, vol. 3, pp. 2148–2156, Dec 2012.