fats, oil and grease (fog) control james baginski, p.e. james baginski enterprises 731 kokomo place...
TRANSCRIPT
![Page 1: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/1.jpg)
Fats, Oil and Grease (FOG) Control
James Baginski, P.E.
James Baginski Enterprises
731 Kokomo Place
Honolulu, Hawaii 96825 (808) 358-9453email: [email protected]
AlohaAloha
![Page 2: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/2.jpg)
2
•Maintain a Pristine EnvironmentMaintain a Pristine Environment
•Comply with Federal Clean Water ActComply with Federal Clean Water Act
MISSION:
![Page 3: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/3.jpg)
3
One of the Major Problems - Sanitary Sewer Overflows
(SSOs)
![Page 4: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/4.jpg)
4
One of the Major Causes - Grease Blockages in Sewer Pipes
Inside view of sewer pipes
![Page 5: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/5.jpg)
5
Grease Blockage SourcesRestaurants & Food Processing Facilities
![Page 6: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/6.jpg)
6
Regulatory ControlPretreatment Program
![Page 7: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/7.jpg)
7
Method of Control Typical Grease Interceptor Design
![Page 8: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/8.jpg)
8
Honolulu Wastewater System
Number of Treatment Plants
Number of Pump Stations
Total Design Flow (mgd)
8 72 120
Collection System - approximately 2,000 miles of sewer lines
Honolulu population is about 800,000.
![Page 9: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/9.jpg)
9
Compliance Background
• 1982 Honolulu’s Pretreatment Program Approved by EPA
• 1990 EPA issues Findings of Violations to Honolulu (related to SSO’s)
• 1995 Honolulu enters into Consent Agreement with EPA
• 1999 GI retrofit program begins; 90 grease related SSO’s = 36% of total annual SSO’s.
• 2002 20% of facilities retrofitted; 46 grease related SSO’s = 23% of total annual SSO’s.
![Page 10: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/10.jpg)
10
Collection System Maintenance & Historical Data
![Page 11: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/11.jpg)
11
Collection System Maintenance
• Repair collection system conditions which promote grease blockages (e.g. line sag, surcharge conditions, pipe cracks/breaks, root intrusion).
• Modify collection system standards to accommodate grease (e.g. seamless pipe, increased slope, larger pipe).
• Conduct effective preventive maintenance program (i.e. identify and target “hot spots”).
• Report chronic FOG problem areas or dischargers to the Pretreatment Program for enforcement.
• Maintain detailed and accurate records of system condition.
Infrastructure Efforts to control FOG
![Page 12: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/12.jpg)
12
Collection System Historical Data
LOCATION
1999 2000 2001 2002% of GIs upgraded
% of records indicating heavy grease in line
KALAKAUA0% 12% 12% 12%67% 100% 100% 67%
KAPIOLANI4% 4% 4% 9%
92% 82% 100% 100%
AUAHI0% 0% 5% 11%
100% 100% 100% 100%
ALA MOANA0% 6% 6% 6%
100% 100% 100% 100%
Areas with Low Percentage of Retrofitted GIs
Approximately 20% of businesses requiring a GI have been retrofitted.
![Page 13: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/13.jpg)
13
Collection System Historical Data
LOCATION
1999 2000 2001 2002
% of GIs upgraded% of records indicating heavy grease in line
BERETANIA0% 0% 12% 21%
96% 100% 23% 22%
KAM HWY0% 10% 15% 20%
75% 50% 50% 0%
KALAKAUA0% 5% 10% 25%
100% 100% 75% 0%
KALAKAUA0% 8% 33% 33%
84% 80% 35% 14%
Areas with Higher Percentage of Retrofitted GIs
Approximately 20% of businesses requiring a GI have been retrofitted.
![Page 14: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/14.jpg)
14
Collection System Historical Data
Year Miles of Pipes
Cleaned
Number of Wastewater
Spills
Number of Grease Related
Spills *
Grease Spills as a Percentage of
Total Spills
1995 343 268 73 27%
1996 406 332 95 29%
1997 401 310 88 28%
1998 558 231 63 27 %
1999 ** 891 252 90 36 %
2000 658 263 86 33 %
2001 675 240 73 30%
2002 707 199 46 23%
* Grease was primary cause of spill
** Began GI retrofits in June 1999 (20% Complete)
Pipe Cleaning and Spill Records:
![Page 15: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/15.jpg)
15
Collection System Historical Data
Year Flow (mgd)
Influent O&G (mg/l)
Grease Spills
1995 75.935 44.2 73
1996 75.623 37.2 95
1997 77.047 27.7 88
1998 73.462 28.5 * 63
1999 73.917 22.5 90
2000 72.654 25.3 86
2001 70.664 24.5 73
2002 69.559 24.2 46
Reduction % 10% 45% 48%
Sand Island WWTP Data:
* O&G analytical method changed
from 413.1 to 1664A (freon to
hexane) in November 1998, as well as, new NPDES permit
required increased monitoring
frequency from 1/week to 3/week.
![Page 16: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/16.jpg)
16
Pretreatment Program
![Page 17: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/17.jpg)
17
Pretreatment Program
Many Fats, Oil and Grease (FOG) Sources are Not Connected to a GI (Pre-rinse garbage disposals).
Existing Grease Interceptors (GI) are “Inadequate”.
How do you determine what is adequate?
Research Findings:
![Page 18: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/18.jpg)
18
Pretreatment Program
Consider…Stokes’ Law:
Vr = g/18ν [S.G.w – S.G.o] x D²
Where:Vr – rising velocity of the oil particle (cm/sec)
g – gravity constant (980 cm/sec²)
ν – viscosity of water in poises (0.01)
S.G.w – specific gravity or density of water (gm/cm³)
S.G.o – specific gravity or density of oil (gm/cm³)
D - diameter of the oil droplet (cm)
![Page 19: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/19.jpg)
19
Pretreatment Program
Factors Affecting FOG Separation:
1. Temperature – the less viscous the fluid (higher temp.), the faster the particle rise rate. However, too high temp. promotes emulsification.
2. Specific Gravity - The greater the differential specific gravity or density between the fluid and the particle, the faster the rise rate.
3. Diameter – The larger the particle diameter the faster the particle rise rate.
![Page 20: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/20.jpg)
20
Pretreatment ProgramOil Globule Rise Times for 3 inches @ 68 F:
Diameter
[microns]
Rise Time (S.G.=0.9) [hr:min:sec]
300 0:00:15
125 0:01:27
60 0:06:36
40 0:14:24
20 0:58:08
10 (colloidal) 3:52:33
1 387:35:49
Table info from American Petroleum Institute Publication 421. FOG S.G. range = 0.92-0.95
![Page 21: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/21.jpg)
21
Pretreatment Program
YEAH BABY, YEAH!!
Grease Interceptors must be sized to promote the adequate separation of FOG from wastewater. An important factor to consider is………..
Retention Time
Does Size Matter??
www.ace-movie-posters.com/a/austin-powers.php
![Page 22: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/22.jpg)
22
Pretreatment ProgramGI Sizing Criteria
Minimum Grease Interceptor Volume (Vmin) isdetermined using Retention Time (R), StorageFactor (S) and Flow Rate (F).
or, V(min) = R x S x F
R = 30 Minutes
S = 1.25 (25% Allowance)
F = Maximum Flow Rate Entering the GI (gpm)
where,
©
![Page 23: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/23.jpg)
23
Pretreatment Program
GI Sizing Criteria
V (min) = 30 x 1.25 x F
F - Flow rate is determined based on Drainage Fixture Units (DFU)
![Page 24: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/24.jpg)
24
Pretreatment ProgramGI Sizing Criteria
DFU’s based on the Uniform Plumbing Code, 1997 edition, Table 7-3: Drainage Fixture Unit Values, Section 702.0 Maximum Trap Loading, or Table 7-4: Discharge Capacity (gpm) for Intermittent Flow Only.
* “Piping Handbook, 7th Edition”, Muhinder L. Nayyar, McGraw-Hill; Tables C13.3 & C13.4 on pages C.690 & C.691.
Flow Rate
No. of Drainage Fixture Units 40
* F = (0.7 x DFU)
No. of Drainage Fixture Units 40
* F = (0.2 x DFU) + 20
©
![Page 25: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/25.jpg)
25
Pretreatment ProgramPretreatment ProgramComparison of Grease Interceptor Sizing Criteria
UPC Appendix H
1999 Honolulu Criteria
(Denver Based) 2001 Honolulu Criteria
Type of FacilityCalculated
SizeTank
RequirementCalculated
SizeTank
RequirementCalculated
SizeTank
Requirement
Chinese Restaurant 6,000 2 x 3,000 1,125 1,500 885 1,000
Seafood Restaurant 6,000 2 x 3,000 2,088 3,000 1,080 1,500
Fine Dining 16,500 3 x 5,000 + 3,275 4,000 1,390 1,500
Hotel with Kitchen and Restaurant 3,500 4,000 1,688 2,000 1,050 1,500
Dinner Theatre (Luau) 7,500 2 x 4,000 2,500 3,000 919 1,000
Large Restaurant 10,320 2 x 5,000 + 3,225 4,000 2,520 3,000
Medium Restaurant 2,100 3,000 1,531 2,000 1,208 1,500
Small Restaurant 375 500 750 1,000 456 500
![Page 26: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/26.jpg)
26
Pretreatment ProgramHONOLULU SIZED GREASE INTERCEPTOR
SAMPLING RESULTS
Number of GIs sampled - 45
Number of samples taken - 90
Average Oil & Grease
Effluent Concentration (Avg) - 79 mg/l
pH - (min) 5 (avg) 5.8 (max) 7
Temp. (degrees F) - (min) 69º (avg) 86.6º (max) 105º
(Melting Point of Tallow (i.e. animal fat) - 108 degees F)
![Page 27: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/27.jpg)
27
Pretreatment ProgramGI Maintenance Requirements
• 25% RULE Storage factor used to
determine GI maintenance frequency consisting of surface FOG material and settled solids.
• PUMP-IN-FULL – Insure all solids are
removed.– Inspect the GI for corrosion
damage or cracks.– Enables “cradle-to-grave”
tracking of FOG waste.
![Page 28: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/28.jpg)
28
FOG Control Success Factors
www.simplyawesome.com/products/miracleonice.html
![Page 29: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/29.jpg)
29
FOG Control Success Factors
Consistent Facility Compliance Evaluations Persistent/Consistent Enforcement Actions Plan Reviews to verify Compliance with GI Program Database Tracking and Follow-upProgram Implementation Strategy Economic ConsiderationsPublic Outreach and Education
![Page 30: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/30.jpg)
30
FOG Control Success Factors
Program Implementation Strategy!
1. Understand the Political Environment – Votes.
2. Understand the Media – Stay 2 steps ahead. Create a “No Story” situation.
3. Involve the Industry – Raise awareness by meeting with Stakeholders (Property Owners, Restaurant Owners, Area Organizations/ Committees, Trade and Business Associations, City and Elected Officials).
4. Think “Money” - Businesses focus is on $. Find a way to merge environment and regulations. Build partnerships with the “Big Dogs”.
![Page 31: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/31.jpg)
31
FOG Control Success Factors
• Project coordination & funding by property owners:– Property owners and tenants equally liable under most
Ordinances.– Owners finance improvements and renegotiate tenant leases.– Tenants pay only their fair share while they are there.
• Shared Grease Interceptors
• Mixed Waste (kitchen/domestic) Grease Interceptors. [Currently 2 operating in Hawaii with more proposed]
• Grant easements where space is limited.
• ADDITIVES - Biologicals Only…No Enzymes or Surfactants.
Economic Considerations:
![Page 32: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/32.jpg)
32
FOG Control Success FactorsPublic Outreach and Education
• Public Info Meetings, Community/Industry Events
• Brochures, Bus Posters
• Educational Videos/Public Service Anouncements (Show Video)
![Page 33: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/33.jpg)
33
Contact Information
James Baginski, P.E.
President
James Baginski Enterprises
731 Kokomo Place
Honolulu, Hawaii 96825
Tel: (808) 358-9453
Email: [email protected]
![Page 34: Fats, Oil and Grease (FOG) Control James Baginski, P.E. James Baginski Enterprises 731 Kokomo Place Honolulu, Hawaii 96825(808) 358-9453 email:jbe@hawaii.rr.com](https://reader036.vdocuments.us/reader036/viewer/2022062423/56649c9d5503460f9495c3dc/html5/thumbnails/34.jpg)
34
Questions?
Aloha Aloha and and
MahalMahaloo