exterior wall cladding - huber engineered woods · exterior wall cladding window header stud wall...
TRANSCRIPT
EXTERIOR WALL CLADDING
AIR / DRAINAGE CAVITY PER
CLADDING MANUF.
RECOMMENDATIONS.
MECH. FASTENED EXTERIOR
RIGID FOAM INSULATION.
ZIP SYSTEM SHEATHING
"INNIE" FLANGED
WINDOW
JACK AND KING STUD
FRAMING AT WINDOW
ROUGH OPENING
STUD WALL FRAMING
TYPICAL WALL CAVITY
INSULATION
WINDOW EXTENSION
BOX BEYOND PER
ARCH. DETAILS
LOW-EXPANDING FOAM SEALANT OR
100% SILICONE, POLYURETHANE, OR
BUTYL SEALANT. USE BACKING ROD
AS NEEDED.
WINDOW SEALANT BEHIND
WINDOW JAMB FLANGE
6-INCH ZIP SYSTEM FLASHING
TAPE. 3.75-INCH ZIP SYSTEM
SEAM TAPE OR LIQUID FLASH
MAY ALSO BE USED.
EXTERIOR WINDOW TRIM PER
ARCHITECTURAL OR WINDOW
MANUF. DETAILS.
TYPICAL WALL CAVITY INSULATION (NOT CLOSED-CELL
FOAM). DO NOT USE POLYETHYLENE SHEETING, FOIL FACED
BATTS OR OTHER CLASS I VAPOR RETARDER ON THE INSIDE
FACE OF WALL FRAMING WHEN USING THIS DETAIL.
TYPICAL WALL CAVITY INSULATION
CLOSED-CELL FOAM, FOIL-FACED BATTS,
POLY SHEETING OR OTHER CLASS 1
VAPOR RETARDER
"INNIE" MOUNTED FLANGED WINDOW
"OUTIE" MOUNTED FLANGED WINDOW
07-09-2012
Telephone: 800.933.9220 - Facsimile: 704.547.9228 - www.zipsystem.comSales Office: 10925 David Taylor Drive - Suite 300 - Charlotte, NC 28262
DRAWING NOT TO SCALE
These construction details are provided to assist in the installation of ZIP System product(s) and may not apply to
every stituation. Manufacturer accepts no responsibility or liability for the use of these or other construction details.
ZIP SYSTEM® TYPICAL "INNIE" WINDOWJAMB DETAIL K-2
ZIP SYSTEM SHEATHING
WINDOW EXTENSION
BOX BEYOND PER ARCH.
DETAILS
EXTERIOR WALL CLADDING
WINDOW HEADER
STUD WALL FRAMING
TYPICAL WALL CAVITY
INSULATION
AIR / DRAINAGE CAVITY PER
CLADDING MANUF.
RECOMMENDATIONS.
MECH. FASTENED EXTERIOR
RIGID FOAM INSULATION.
WINDOW SEALANT BEHIND
WINDOW HEAD FLANGE (ONLY
USE POLYURETHANE, BUTYL OR
100% SILICONE SEALANTS)
WINDOW TRIM PER
ARCHITECTURAL DETAILS
LOW-EXPANDING FOAM
SEALANT OR 100% SILICONE,
POLYURETHANE, OR BUTYL
SEALANT. USE BACKER ROD
AS NEEDED.
EXTERIOR WINDOW TRIM PER
ARCHITECTURAL OR WINDOW
MANUF. DETAILS.
"INNIE" FLANGED WINDOW
TYPICAL WALL CAVITY INSULATION (NOT CLOSED-CELL
FOAM). DO NOT USE POLYETHYLENE SHEETING, FOIL FACED
BATTS OR OTHER CLASS I VAPOR RETARDER ON THE INSIDE
FACE OF WALL FRAMING WHEN USING THIS DETAIL.
TYPICAL WALL CAVITY INSULATION
CLOSED-CELL FOAM, FOIL-FACED BATTS,
POLY SHEETING OR OTHER CLASS 1
VAPOR RETARDER
"INNIE" MOUNTED FLANGED WINDOW
"OUTIE" MOUNTED FLANGED WINDOW
6-INCH ZIP SYSTEM FLASHING
TAPE. 3.75-INCH ZIP SYSTEM
SEAM TAPE OR LIQUID FLASH
MAY ALSO BE USED.
07-09-2012
Telephone: 800.933.9220 - Facsimile: 704.547.9228 - www.zipsystem.comSales Office: 10925 David Taylor Drive - Suite 300 - Charlotte, NC 28262
DRAWING NOT TO SCALE
These construction details are provided to assist in the installation of ZIP System product(s) and may not apply to
every stituation. Manufacturer accepts no responsibility or liability for the use of these or other construction details.
ZIP SYSTEM® TYPICAL "INNIE"WINDOW HEAD DETAIL K-3
EXTERIOR WALL CLADDING
AIR / DRAINAGE CAVITY PER
CLADDING MANUF.
RECOMMENDATIONS.
ZIP SYSTEM SHEATHING
"OUTIE" FLANGED WINDOW
JACK AND KING STUD
FRAMING AT WINDOW
ROUGH OPENING
STUD WALL FRAMING
TYPICAL WALL CAVITY INSULATION
LOW-EXPANDING FOAM SEALANT OR
100% SILICONE, POLYURETHANE, OR
BUTYL SEALANT. USE BACKING ROD
AS NEEDED.
WOOD BLOCKING PERIMETER
OF WINDOW ROUGH OPENING
TO MATCH FACE OF EXTERIOR
FOAM INSULATION
WINDOW SEALANT BEHIND
WINDOW JAMB FLANGE
CONTINUOUS BEAD OF
SEALANT (ONLY USE
POLYURETHANE, BUTYL OR
100% SILICONE SEALANTS)
MECH. FASTENED EXTERIOR
RIGID FOAM INSULATION
INSTALLED DIRECTLY TO ZIP
SYSTEM SHEATHING.
TYPICAL WALL CAVITY INSULATION (NOT CLOSED-CELL
FOAM). DO NOT USE POLYETHYLENE SHEETING, FOIL FACED
BATTS OR OTHER CLASS I VAPOR RETARDER ON THE INSIDE
FACE OF WALL FRAMING WHEN USING THIS DETAIL.
ZIP SYSTEM TAPE, ZIP SYSTEM
LIQUID FLASH OR OTHER
CODE-RECOGNIZED PAN FLASHING
TYPICAL WALL CAVITY INSULATION
CLOSED-CELL FOAM, FOIL-FACED BATTS,
POLY SHEETING OR OTHER CLASS 1
VAPOR RETARDER
"INNIE" MOUNTED FLANGED WINDOW
"OUTIE" MOUNTED FLANGED WINDOW
07-09-2012
Telephone: 800.933.9220 - Facsimile: 704.547.9228 - www.zipsystem.comSales Office: 10925 David Taylor Drive - Suite 300 - Charlotte, NC 28262
DRAWING NOT TO SCALE
These construction details are provided to assist in the installation of ZIP System product(s) and may not apply to
every stituation. Manufacturer accepts no responsibility or liability for the use of these or other construction details.
ZIP SYSTEM® TYPICAL "OUTIE"WINDOW JAMB DETAIL K-6
ZIP SYSTEM SHEATHING
"OUTIE" FLANGED WINDOW
EXTERIOR WALL CLADDING
WINDOW HEADER
STUD WALL FRAMING
AIR / DRAINAGE CAVITY PER
CLADDING MANUF.
RECOMMENDATIONS.
MECH. FASTENED EXTERIOR
RIGID FOAM INSULATION.
CONTINUOUS BEAD OF SEALANT
(ONLY USE POLYURETHANE, BUTYL
OR 100% SILICONE SEALANTS)
LOW-EXPANDING FOAM SEALANT OR
100% SILICONE, POLYURETHANE, OR
BUTYL SEALANT. USE BACKER ROD
AS NEEDED.
WOOD BLOCKING PERIMETER OF
WINDOW ROUGH OPENING TO
MATCH FACE OF EXTERIOR FOAM
INSULATION
WINDOW SEALANT BEHIND
WINDOW HEAD FLANGE
DRAINAGE MAT OR FUR STRIPS
(1/8-INCH RECOMMENDED)
DRAINAGE MAT OR FUR STRIPS
(1/8-INCH RECOMMENDED)
CLOSED-CELL WALL CAVITY
INSULATION, FOIL-FACED BATTS
OR CLASS I VAPOR RETARDER
DRYING / DRAINAGE (1/8-INCH RECOMMENDED) MUST BE PROVIDED
BETWEEN FOAM INSULATION AND ZIP SYSTEM SHEATHING FOR
CLOSED-CELL WALL CAVITY INSULATION OR WHEN USING
FOIL-FACED BATTS, POLYETHYLENE SHEETING OR OTHER CLASS I
VAPOR RETARDER ON THE INSIDE FACE OF WALL FRAMING.
TYPICAL WALL CAVITY INSULATION
CLOSED-CELL FOAM, FOIL-FACED BATTS,
POLY SHEETING OR OTHER CLASS 1
VAPOR RETARDER
"INNIE" MOUNTED FLANGED WINDOW
"OUTIE" MOUNTED FLANGED WINDOW
6-INCH ZIP SYSTEM FLASHING TAPE.
3.75-INCH ZIP SYSTEM SEAM TAPE
OR LIQUID FLASH MAY ALSO BE
USED.
07-09-2012
Telephone: 800.933.9220 - Facsimile: 704.547.9228 - www.zipsystem.comSales Office: 10925 David Taylor Drive - Suite 300 - Charlotte, NC 28262
DRAWING NOT TO SCALE
These construction details are provided to assist in the installation of ZIP System product(s) and may not apply to
every stituation. Manufacturer accepts no responsibility or liability for the use of these or other construction details.
ZIP SYSTEM® OUTIE WINDOW HEAD W/CLOSED-CELL INSULATION & EXTERIOR FOAM K-7
EXTERIOR WALL CLADDING
AIR / DRAINAGE CAVITY PER
CLADDING MANUF.
RECOMMENDATIONS.
MECH. FASTENED EXTERIOR
RIGID FOAM INSULATION.
ZIP SYSTEM SHEATHING
"OUTIE" FLANGED WINDOW
JACK AND KING STUD
FRAMING AT WINDOW
ROUGH OPENING
STUD WALL FRAMING
CLOSED-CELL WALL CAVITY
INSULATION, FOIL-FACED BATTS OR
CLASS I VAPOR RETARDER
DRAINAGE MAT OR FUR STRIPS
(1/8-INCH RECOMMENDED)
LOW-EXPANDING FOAM SEALANT OR
100% SILICONE, POLYURETHANE, OR
BUTYL SEALANT. USE BACKER ROD
AS NEEDED.
WOOD BLOCKING PERIMETER
OF WINDOW ROUGH OPENING
TO MATCH FACE OF EXTERIOR
FOAM INSULATION
WINDOW SEALANT BEHIND
WINDOW JAMB FLANGE
CONTINUOUS BEAD OF
SEALANT (ONLY USE
POLYURETHANE, BUTYL OR
100% SILICONE SEALANTS)
DRAINAGE MAT OR FUR STRIPS
(1/8-INCH RECOMMENDED)
DRYING / DRAINAGE (1/8-INCH RECOMMENDED) MUST BE PROVIDED
BETWEEN FOAM INSULATION AND ZIP SYSTEM SHEATHING FOR
CLOSED-CELL WALL CAVITY INSULATION OR WHEN USING
FOIL-FACED BATTS, POLYETHYLENE SHEETING OR OTHER CLASS I
VAPOR RETARDER ON THE INSIDE FACE OF WALL FRAMING.
6-INCH ZIP SYSTEM FLASHING
TAPE. 3.75-INCH ZIP SYSTEM
SEAM TAPE OR LIQUID FLASH
MAY ALSO BE USED.
TYPICAL WALL CAVITY INSULATION
CLOSED-CELL FOAM, FOIL-FACED BATTS,
POLY SHEETING OR OTHER CLASS 1
VAPOR RETARDER
"INNIE" MOUNTED FLANGED WINDOW
"OUTIE" MOUNTED FLANGED WINDOW
07-09-2012
Telephone: 800.933.9220 - Facsimile: 704.547.9228 - www.zipsystem.comSales Office: 10925 David Taylor Drive - Suite 300 - Charlotte, NC 28262
DRAWING NOT TO SCALE
These construction details are provided to assist in the installation of ZIP System product(s) and may not apply to
every stituation. Manufacturer accepts no responsibility or liability for the use of these or other construction details.
ZIP SYSTEM® OUTIE WINDOW JAMB W/CLOSED-CELL INSULATION & EXTERIOR FOAM K-8
STUD WALL FRAMING
MECH. FASTENED EXTERIOR
RIGID FOAM INSULATION
BRICK VENEER CLADDING
MIN. 1-INCH AIR SPACE
PER LOCAL CODE
SLAB-ON-GRADE
ZIP SYSTEM SHEATHING
TYPICAL WALL CAVITY INSULATION (NOT CLOSED-CELL
FOAM). DO NOT USE POLYETHYLENE SHEETING, FOIL FACED
BATTS OR OTHER CLASS I VAPOR RETARDER ON THE INSIDE
FACE OF WALL FRAMING WHEN USING THIS DETAIL.
BRICK TIES MUST ATTACH THROUGH
FOAM INTO WALL STUD FRAMING
TOP EDGE OF FLASHING TAPED
WITH ZIP SYSTEM TAPE OR LIQUID
FLASH
CODE APPROVED BASE
FLASHING
WEEP HOLES (AS PRESCRIBED
BY LOCAL BUILDING CODE)
TYPICAL WALL CAVITY
INSULATION
TYPICAL WALL CAVITY INSULATION
CLOSED-CELL FOAM, FOIL-FACED BATTS,
POLY SHEETING OR OTHER CLASS 1
VAPOR RETARDER
"INNIE" MOUNTED FLANGED WINDOW
"OUTIE" MOUNTED FLANGED WINDOW
07-09-2012
Telephone: 800.933.9220 - Facsimile: 704.547.9228 - www.zipsystem.comSales Office: 10925 David Taylor Drive - Suite 300 - Charlotte, NC 28262
DRAWING NOT TO SCALE
These construction details are provided to assist in the installation of ZIP System product(s) and may not apply to
every stituation. Manufacturer accepts no responsibility or liability for the use of these or other construction details.
ZIP SYSTEM® TYPICAL BRICK BASEFLASHING DETAIL K-11
STUD WALL FRAMING
TOP EDGE OF FLASHING TAPED
WITH ZIP SYSTEM TAPE OR LIQUID
FLASH
CODE APPROVED BASE
FLASHING
WEEP HOLES (AS PRESCRIBED
BY LOCAL BUILDING CODE)
MECH. FASTENED EXTERIOR
RIGID FOAM INSULATION.
BRICK VENEER CLADDING
MIN. 1-INCH AIR SPACE
PER LOCAL CODE
SLAB-ON-GRADE
DRAINAGE MAT OR FUR
STRIPS (1/8-INCH
RECOMMENDED)
CLOSED-CELL WALL CAVITY
INSULATION, FOIL-FACED BATTS
OR CLASS I VAPOR RETARDER
ZIP SYSTEM SHEATHING
BRICK TIES MUST ATTACH THROUGH
FOAM INTO WALL STUD FRAMING
DRYING / DRAINAGE (1/8-INCH RECOMMENDED) MUST BE PROVIDED
BETWEEN FOAM INSULATION AND ZIP SYSTEM SHEATHING FOR
CLOSED-CELL WALL CAVITY INSULATION OR WHEN USING
FOIL-FACED BATTS, POLYETHYLENE SHEETING OR OTHER CLASS I
VAPOR RETARDER ON THE INSIDE FACE OF WALL FRAMING.
TYPICAL WALL CAVITY INSULATION
CLOSED-CELL FOAM, FOIL-FACED BATTS,
POLY SHEETING OR OTHER CLASS 1
VAPOR RETARDER
"INNIE" MOUNTED FLANGED WINDOW
"OUTIE" MOUNTED FLANGED WINDOW
07-09-2012
Telephone: 800.933.9220 - Facsimile: 704.547.9228 - www.zipsystem.comSales Office: 10925 David Taylor Drive - Suite 300 - Charlotte, NC 28262
DRAWING NOT TO SCALE
These construction details are provided to assist in the installation of ZIP System product(s) and may not apply to
every stituation. Manufacturer accepts no responsibility or liability for the use of these or other construction details.
ZIP SYSTEM® BRICK FLASHING W/CLOSED-CELL INSULATION & EXTERIOR FOAM K-13