ex wall chart

1
For more information, visit the sira website: www.siracertification.com email: [email protected] tel: +44 (0) 1244 670 900 August 2009 PROTECTION CONCEPTS } FIRST NUMERAL Protection against solid objects 0 - No special protection 1 - Objects > 50 mm diameter (e.g. part of a hand) 2 - Objects > 12.5 mm diameter (e.g. finger) 3 - Objects > 2.5 mm diameter (e.g. tool) 4 - Objects > 1.00 mm diameter (e.g. wire) 5 - Dust protected 6 - Dust tight SECOND NUMERAL Protection against water 0 - No special protection 1 - Vertically dripping water 2 - Vertically dripping water, when enclosure tilted by 15° 3 - Sprayed water up to 60° from the vertical 4 - Sprayed water from all directions 5 - Water jets 6 - Powerful water jets 7 - Temporary submersion to a depth of 1m 8 - Extended submersion to a depth > 1m Zone Equipment Relevant ATEX Annexes Gas Dust Category for Compliance Group 0 20 1 III and IV or V 1 21 2* III and VII or VI II 1 21 2** VIII# 2 22 3 VIII M1 III and IV or V Mining M2* III and VII or VI I M2** VIII# Any Any IXAny INGRESS PROTECTION (IP) CODE BS EN 60529 (IEC 60529) NEMA TYPE NEMA 1 NEMA 2 NEMA 3 NEMA 3R NEMA 3S NEMA 4 and 4X NEMA 5 NEMA 6 and 6P NEMA 12 and 12K NEMA 13 NEMA TESTING APPROXIMATE EQUIVALENT TO IPXX Hazardous Area Characteristics Explosive atmosphere present continuously or long periods or frequently (>1000 hours/year) Explosive atmosphere is likely to occur in normal operation occasionally (>10 <1000 hours/year) Explosive atmosphere is not likely to occur in normal operation or infrequently and for short periods (<10 hours/year) If explosive atmosphere present, equipment remains energised If explosive atmosphere present, equipment de-energised If explosive atmosphere present, equipment de-energised 011 0327 Accredited certification and EU Notified Body activities are undertaken by Sira Certification Service. Sira has provided the technical information for this publication to DronDickson. The IP and copyright remains with Sira. Sira's association with this publication does not extend to endorsement of DronDickson’s products with respect to performance or fitness for purpose. Gas/Vapour Acetic acid Acetone Acetylene Ammonia Butane Cyclohexane Di-ethyl ether Ethanol (ethyl alcohol) Ethylene Gasoline (petrol) Hydrogen Kerosene Methane (natural gas) (non-mining) Methanol (methyl alcohol) Methyl ethyl ketone (MEK) Propane Propan-1-ol (n-propyl alcohol) Propan-2-ol (iso-propyl alcohol) Toluene Xylene Dust Apparatus Groups IIIA IIIB IIIC Temperature class T1 T1 T2 T1 T2 T3 T4 T2 T2 T3 T1 T3 T1 T2 T2 T1 T2 T2 T1 T1 Apparatus group llA llA llC llA llA llA llB llA llB IIA llC llA llA llA llB llA llB llA llA llA APPARATUS GROUPS & TEMPERATURE CLASSES FOR COMMON FLAMMABLE MATERIALS Dusts Typical Ignition T emperature (˚C) Aluminium Coal dust (lignite) Flour Grain dust Methyl cellulose Phenolic resin Polythene PVC Soot Starch Sugar Layer >450 225 340 300 320 >450 (melts) >450 570 435 460 T Class T1 T2 T3 T4 T5 T6 450˚C 300˚C 200˚C 135˚C 100˚C 85˚C N.B. For Group I applications, apparatus has rigid 150˚C (coal dust) and 450˚C (methane) limits rather than T classes. Maximum surface temperature TEMPERATURE CLASS (GROUP II) S I R A 0 9 A T E X 1 2 3 4 Serial number Reference to ATEX 95 directive Year of certification Name of notified body performing EC-type examination Suffixes: U – component certification X – special conditions for safe use apply SIRA ATEX CERTIFICATE NUMBER SIRA TRAINING Cloud 590 380 490 510 420 530 420 700 810 460 490 TYPICAL EQUIPMENT MARKING (NON-ELECTRICAL EQUIPMENT) Ref: Annex VIII (Internal Control of Production) General description of product Design/manufacturing drawings List of standards applied Applicable test reports Ignition hazard assessment CONTENTS OF AN ATEX TECHNICAL FILE (FOR CATEGORY 2/3 NON-ELECTRICAL EQUIPMENT) Protection Concept(s) T Class * Electrical equipment and internal combustion engines only ** Non-electrical equipment only # and communicate the technical file to a notified body Alternative route for any product P I IP10 IP11 IP54 IP14 IP54 IP55 IP52 IP67 IP52 IP54 COMPETENCE CERTIFICATE (Scope) Registration Training Personal log KNOWLEDGE EXPERIENCE Application to Sira Qualifications Job details Experience Scope Knowledge Certificate If sufficient and relevant Assessment Periodic Review THE ROUTE TO COMPETENCE Combustive flyings Non-conductive dust Conductive dust Da Db Dc Ex Supplies Ltd, Chester CH4 9JN Scirocco Mk II Pump 30/600 r.p.m IP65 File ref. no. 108112 Serial number: 1234 Manufactured: 2009 The Competence Professional Scheme The only UKAS Accredited and nationally recognised personnel certification scheme for individuals working in hazardous areas. Log on to www.competencepro.com for more details. Technical file reference Equipment group/category & type of explosive atmosphere NORTH AMERICAN / EUROPEAN AREA CLASSIFICATION EQUIVALENTS - GAS IEC / EU US NEC 505 US NEC 500 CA CEC Section 18 CEC Annex 0 1 - 9 7 0 0 6 N E r e p n o i t a c i f i s s a l c C E I 0 1 - 9 7 0 0 6 C E I r e p n o i t a c i f i s s a l c C E I US classification per ANSI / NFPA 70 National Electrical Code ® (NEC ® ) Article 505 CA classification per CSA C22.1 Canadian Electrical Code (CEC) Section 18 or Annex J Flammable Material Present Intermittently Zone 1 Zone 1 Zone 1 Flammable Material Present Continuously Zone 0 Zone 0 Zone 0 Flammable Material Present Abnormally Zone 2 Zone 2 Division 2 Zone 2 Division 2 Division 1 Division 1 NORTH AMERICAN / EUROPEAN EQUIPMENT GROUPING EQUIVALENTS - DUST Typical material Metal dusts Carbonaceous dusts Non-conductive dusts Fibres and flyings EU (60079-0) IEC (60079-0) IIIC IIIB IIIB IIIA US (NEC 506) N/A D D D IEC (61241-0) EU (61241-0) D D D D US (NEC 500) CA (CEC Section 18) Class II, Group E Class II, Group F Class II, Group G Class III NORTH AMERICAN / EUROPEAN AREA CLASSIFICATION EQUIVALENTS - DUST IEC / EU US NEC 506 US NEC 500 CA CEC Section 18 US area classification per ANSI / NFPA 70 National Electrical Code ® (NEC ® ) Article 500 or 506 CA area classification per CSA C22.1 Canadian Electrical Code (CEC) Section 18 0 1 - 1 4 2 1 6 C E I r e p n o i t a c i f i s s a l c a e r a C E I 0 1 - 1 4 2 1 6 N E r e p n o i t a c i f i s s a l c a e r a U E Combustible Dust Present Intermittently Zone 21 Zone 21 Combustible Dust Present Continuously Zone 20 Zone 20 Combustible Dust Present Abnormally Zone 22 Zone 22 Division 2 Division 2 Division 1 Division 1 NORTH AMERICAN / EUROPEAN EQUIPMENT GROUPING EQUIVALENTS - GAS Typical gas Acetylene Hydrogen Ethylene Propane Methane * Not within scope of NEC ® . Under jurisdiction of MSHA. Not within scope of CEC. US (NEC ® 500) CA (CEC Annex J) Class I / Group A Class I / Group B Class I / Group C Class I / Group D Mining* US (NEC ® 505) CA (CEC Section 18) EU IEC Group IIC (Group IIB + H 2 ) Group IIB Group IIA Group I* NORTH AMERICAN APPROVAL MARKING COMPLIANCE ROUTES AND EQUIPMENT SELECTION Need training on Ex disciplines? Sira offers courses covering all aspects of 'hazardous area' requirements. For more details, log on to www.siracertification.com This table cannot be used to convert IP codes to NEMA ratings }{ Electrical Optical Radiation Increased safety Type ‘n’ (non-sparking) Flameproof Type ‘n’ (enclosed break) Quartz/sand filled Intrinsic safety Intrinsic safety Intrinsic safety Type ‘n’ (energy limitation) Pressurised (up to 2007) Pressurised Pressurised Pressurised Type ‘n’ (sealing & hermetic sealing) Type ‘n’ (restricted breathing) Type ‘n’ (simple pressurised) Encapsulation Encapsulation Oil immersion Dust Protection (Electrical) Enclosure Intrinsic safety Encapsulation Pressurised Non-electrical General Flow restricted enclosure Flameproof enclosure Constructional safety Control of ignition sources Pressurisation Liquid immersion Typical IEC EPL Ga Gb Gc Gb Gc Gb Gc Gb Ga Gb Gc Gc Gb Gb Gb Gc Gc Gc Gc Ga Gb Gb Typical IEC EPL Db Dc Typical IEC EPL - - - - - - - Symbol Op pr Op sh Op is e nA d nC q ia ib ic nL p px py pz nC nR nZ ma mb o Symbol t i m p Symbol - fr d c b p k Typical Zone(s) 0,1,2 0,1,2 0,1,2 1,2 2 1,2 2 1,2 0,1,2 1,2 2 2 1,2 1,2 1,2 2 2 2 2 0,1,2 1,2 1,2 Typical Zone(s) 20, 21, 22 21, 22 22 21, 22 22 Possible Zone(s) 0,1,2 2 1,2 0,1,2 0,1,2 1,2 0,1,2 IEC Standard (status at August 2009) IEC 60079-28 IEC 60079-28 IEC 60079-28 IEC 60079-7 IEC 60079-15 IEC 60079-1 IEC 60079-15 IEC 60079-5 IEC 60079-11 IEC 60079-11 IEC 60079-11 IEC 60079-15 IEC 60079-2 IEC 60079-2 IEC 60079-2 IEC 60079-2 IEC 60079-15 IEC 60079-15 IEC 60079-15 IEC 60079-18 IEC 60079-18 IEC 60079-6 IEC Standard (status at August 2009) IEC 61241-1 IEC 61241-11 IEC 61241-18 IEC 61241-2 EN Standard (status at August 2009) 1 - 3 6 4 3 1 N E EN 13463-2 EN 13463-3 EN 13463-5 EN 13463-6 EN 13463-7 EN 13463-8 n o i t c e t o r p f o t p e c n o c c i s a B Inherently safe protected. Protected by shutdown No arcs, sparks or hot surfaces. Enclosure IP54 or better Contain the explosion, quench the flame Quench the flame Limit the energy of sparks and surface temperatures Keep the flammable gas out Basic concept of protection Standard protection for dusts, rugged tight enclosure Similar to t, but with some relaxations if circuit inside is intrinsically safe Protection by encapsulation of incendive parts Protection by pressurisation of enclosure Basic concept of protection Low potential energy Relies on tight seals, closely matched joints and tough enclosures to restrict the breathing of the enclosure Ignition hazards eliminated by good engineering methods Control equipment fitted to detect malfunctions Enclosure is purged and pressurised to prevent ignition sources from arising Enclosure uses liquid to prevent contact with explosive atmosphere TYPICAL EQUIPMENT MARKING (ELECTRICAL EQUIPMENT) Protection Concept(s) Equipment Protection Level (EPL) s s a l C T d n a p u o r G s u t a r a p p A Ambient Temperature (-20˚C to +40˚C if not marked) Certificate number (ATEX only) Certificate number (IECEx only) Series or type designation IECEx licenced mark (IECEx only) CE mark and number of notified body responsible for quality audit (ATEX only - CAT 1 & 2 electrical, CAT 1 non-electrical) Specific marking of explosion protection (ATEX only) Equipment Group and Category 2009 Sn 0001 Type of explosive atmosphere G - gases, vapours or mists, D - dust Year of manufacture and serial number Name and address of manufacturer Ex Supplies Ltd Chester CH4 9JN United Kingdom Floodlight P7 0518 II 2 G D Ex de IIB T4 Gb Ex tb IIIC T135 o C Db IP66 Ta = -20 o C to +60 o C SIRA 09ATEX1234 IECEx SIR 09.0788 a CSA International company SIRA TEST & CERTIFICATION LTD Rake Lane, Eccleston, Chester, CH4 9JN, England Tel: +44 (0) 1244 670 900 Fax: +44 (0) 1244 681 330 Email: info@siracertification.com www.siracertification.com www.drondickson.com Specialists in design, supply and maintenance of industrial and hazardous area electrical equipment UK Offices Stirling +44 (0)1786 449444 Aberdeen +44 (0)1224 874554 Hull +44 (0)1482 213626 Lowestoft +44 (0)1502 539991 www.drondickson.com

Upload: nvinodn06

Post on 26-Oct-2015

27 views

Category:

Documents


0 download

DESCRIPTION

hazardous chart

TRANSCRIPT

Page 1: Ex Wall Chart

For more information, visit the sira website: www.siracertification.com email: [email protected] tel: +44 (0) 1244 670 900 August 2009

PROTECTION CONCEPTS

}

FIRST NUMERALProtection against solid objects

0 - No special protection

1 - Objects > 50 mm diameter (e.g. part of a hand)

2 - Objects > 12.5 mm diameter (e.g. finger)

3 - Objects > 2.5 mm diameter (e.g. tool)

4 - Objects > 1.00 mm diameter (e.g. wire)

5 - Dust protected

6 - Dust tight

SECOND NUMERALProtection against water

0 - No special protection1 - Vertically dripping water2 - Vertically dripping water,

when enclosure tilted by 15°3 - Sprayed water up to 60°

from the vertical4 - Sprayed water from all directions5 - Water jets6 - Powerful water jets7 - Temporary submersion to

a depth of 1m8 - Extended submersion to

a depth > 1m

Zone Equipment Relevant ATEX AnnexesGas Dust Category for Compliance Group

0 20 1 III and IV or V

1 21 2* III and VII or VIII1 21 2** VIII#

2 22 3 VIII

M1 III and IV or V

Mining M2* III and VII or VI I

M2** VIII#

Any Any IX≠ Any

INGRESS PROTECTION (IP) CODE BS EN 60529 (IEC 60529)

NEMA TYPENEMA 1

NEMA 2

NEMA 3

NEMA 3R

NEMA 3S

NEMA 4 and 4X

NEMA 5

NEMA 6 and 6P

NEMA 12 and 12K

NEMA 13

NEMA TESTING APPROXIMATE EQUIVALENT

TO IPXX

Hazardous Area Characteristics

Explosive atmosphere present continuously or long periods or frequently (>1000 hours/year)

Explosive atmosphere is likely to occur in normal operation occasionally (>10 <1000 hours/year)

Explosive atmosphere is not likely to occur in normal operation or infrequentlyand for short periods (<10 hours/year)

If explosive atmosphere present, equipment remains energised

If explosive atmosphere present, equipment de-energised

If explosive atmosphere present, equipment de-energised

0110327

Accredited certification and EU Notified Body activities are undertaken by Sira Certification Service. Sira has provided the technical information for this publication to DronDickson. The IP and copyright remains with Sira. Sira's association with this publication does not extend to endorsement of DronDickson’s products with respect to performance or fitness for purpose.

Gas/Vapour

Acetic acidAcetoneAcetyleneAmmoniaButaneCyclohexaneDi-ethyl etherEthanol (ethyl alcohol)EthyleneGasoline (petrol)HydrogenKeroseneMethane (natural gas) (non-mining)Methanol (methyl alcohol)Methyl ethyl ketone (MEK)PropanePropan-1-ol (n-propyl alcohol)Propan-2-ol (iso-propyl alcohol)TolueneXylene

Dust Apparatus Groups

IIIAIIIBIIIC

Temperatureclass

T1T1T2T1T2T3T4T2T2T3T1T3T1T2T2T1T2T2T1T1

Apparatusgroup

llAllAllCllAllAllAllBllAllBIIAllCllAllAllAllBllAllBllAllAllA

APPARATUS GROUPS & TEMPERATURE CLASSES FOR COMMON FLAMMABLE MATERIALS

Dusts Typical Ignition Temperature (˚C)

AluminiumCoal dust (lignite)FlourGrain dustMethyl cellulosePhenolic resinPolythenePVCSootStarchSugar

Layer>450225340300320

>450(melts)>450570435460

T Class

T1T2T3T4T5T6

450˚C300˚C200˚C135˚C100˚C85˚C

N.B. For Group I applications, apparatus has rigid 150˚C (coal dust) and 450˚C (methane) limits rather than T classes.

Maximum surface temperature

TEMPERATURE CLASS (GROUP II)SIRA 09 ATEX 1234

Serial numberReference to ATEX 95 directive

Year of certificationName of notified body performing EC-type examination

Suffixes:U – component certification X – special conditions for safe use apply

SIRA ATEX CERTIFICATE NUMBER

SIRA TRAINING

Cloud590380490510420530420700810460490

TYPICAL EQUIPMENT MARKING(NON-ELECTRICAL EQUIPMENT)

Ref: Annex VIII (Internal Control of Production)

• General description of product

• Design/manufacturing drawings

• List of standards applied

• Applicable test reports

• Ignition hazard assessment

CONTENTS OF AN ATEX TECHNICAL FILE(FOR CATEGORY 2/3 NON-ELECTRICAL EQUIPMENT)

ProtectionConcept(s)

T Class

* Electrical equipment andinternal combustion

engines only

** Non-electricalequipment only

# and communicate thetechnical file to a

notified body

≠ Alternative route forany product

PIIP10

IP11

IP54

IP14

IP54

IP55

IP52

IP67

IP52

IP54

COMPETENCE CERTIFICATE(Scope)

Registration

Training Personal log

KNOWLEDGE EXPERIENCE

Application to SiraQualifications

Job detailsExperience

Scope

Knowledge Certificate If sufficient and relevant

Assessment

Periodic Review

THE ROUTE TO COMPETENCE

Combustive flyingsNon-conductive dustConductive dust

DaDbDc

Ex Supplies Ltd, Chester CH4 9JNScirocco Mk II Pump30/600 r.p.m IP65File ref. no. 108112

Serial number: 1234Manufactured: 2009

The Competence Professional Scheme The only UKAS Accredited and nationally recognised personnel certification scheme for individuals working in hazardous areas. Log on to www.competencepro.comfor more details.

Technical filereference

Equipment group/category &type of explosive atmosphere

NORTH AMERICAN / EUROPEAN AREA CLASSIFICATION EQUIVALENTS - GAS

IEC / EUUS NEC 505US NEC 500CA CEC Section 18CEC Annex

01-97006NErepnoitacifissalcCEI01-97006CEIrepnoitacifissalcCEIUS classification per ANSI / NFPA 70 National Electrical Code® (NEC®) Article 505CA classification per CSA C22.1 Canadian Electrical Code (CEC) Section 18 or Annex J

FlammableMaterial Present

Intermittently

Zone 1Zone 1

Zone 1

FlammableMaterial Present

Continuously

Zone 0Zone 0

Zone 0

FlammableMaterial Present

Abnormally

Zone 2Zone 2

Division 2Zone 2

Division 2

Division 1

Division 1

NORTH AMERICAN / EUROPEANEQUIPMENT GROUPING EQUIVALENTS - DUST

Typical material

Metal dusts

Carbonaceous dusts

Non-conductive dusts

Fibres and flyings

EU (60079-0)IEC (60079-0)

IIIC

IIIB

IIIB

IIIA

US (NEC 506)

N/A

D

D

D

IEC (61241-0)EU (61241-0)

D

D

D

D

US (NEC 500)CA (CEC Section 18)

Class II,Group EClass II,Group FClass II,Group GClass III

NORTH AMERICAN / EUROPEAN AREA CLASSIFICATION EQUIVALENTS - DUST

IEC / EU

US NEC 506

US NEC 500

CA CEC Section 18US area classification per ANSI / NFPA 70 National Electrical Code® (NEC®) Article 500 or 506CA area classification per CSA C22.1 Canadian Electrical Code (CEC) Section 18

01-14216CEIrepnoitacifissalcaeraCEI01-14216NErepnoitacifissalcaeraUE

CombustibleDust PresentIntermittently

Zone 21

Zone 21

CombustibleDust PresentContinuously

Zone 20

Zone 20

CombustibleDust PresentAbnormally

Zone 22

Zone 22

Division 2

Division 2

Division 1

Division 1

NORTH AMERICAN / EUROPEANEQUIPMENT GROUPING EQUIVALENTS - GAS

Typical gas

AcetyleneHydrogenEthylenePropaneMethane* Not within scope of NEC®. Under jurisdiction of MSHA. Not within scope of CEC.

US (NEC® 500)CA (CEC Annex J)

Class I / Group AClass I / Group BClass I / Group CClass I / Group DMining*

US (NEC® 505)CA (CEC Section 18)EUIEC

Group IIC(Group IIB + H2)Group IIBGroup IIAGroup I*

NORTH AMERICAN APPROVAL MARKING

COMPLIANCE ROUTES AND EQUIPMENT SELECTION

Need training on Ex disciplines?

Sira offers courses covering all aspects of 'hazardous area' requirements. For more details, log on to www.siracerti�cation.com

This table cannot be used to convert IP codes to NEMA ratings

} {

ElectricalOptical Radiation

Increased safetyType ‘n’ (non-sparking)

FlameproofType ‘n’ (enclosed break)

Quartz/sand filled

Intrinsic safetyIntrinsic safetyIntrinsic safetyType ‘n’ (energy limitation)

Pressurised (up to 2007)PressurisedPressurisedPressurisedType ‘n’ (sealing & hermetic sealing)Type ‘n’ (restricted breathing)Type ‘n’ (simple pressurised)EncapsulationEncapsulationOil immersion

Dust Protection (Electrical)

Enclosure

Intrinsic safety

Encapsulation

Pressurised

Non-electricalGeneral

Flow restricted enclosureFlameproof enclosure

Constructional safety

Control of ignition sources

Pressurisation

Liquid immersion

TypicalIEC EPL

GaGbGc

GbGc

GbGc

Gb

GaGbGcGc

GbGbGbGcGcGcGcGaGbGb

TypicalIEC EPL

DbDc

TypicalIEC EPL

-

--

-

-

-

-

Symbol

Op prOp shOp is

enA

dnC

q

iaibicnL

ppxpypznCnRnZmambo

Symbol

t

i

m

p

Symbol

-

frd

c

b

p

k

TypicalZone(s)

0,1,20,1,20,1,2

1,22

1,22

1,2

0,1,21,222

1,21,21,22222

0,1,21,21,2

TypicalZone(s)

20, 21, 22

21, 22

22

21, 2222

PossibleZone(s)

0,1,2

21,2

0,1,2

0,1,2

1,2

0,1,2

IEC Standard(status at August 2009)

IEC 60079-28IEC 60079-28IEC 60079-28

IEC 60079-7IEC 60079-15

IEC 60079-1IEC 60079-15

IEC 60079-5

IEC 60079-11IEC 60079-11IEC 60079-11IEC 60079-15

IEC 60079-2IEC 60079-2IEC 60079-2IEC 60079-2

IEC 60079-15IEC 60079-15IEC 60079-15IEC 60079-18IEC 60079-18IEC 60079-6

IEC Standard(status at August 2009)

IEC 61241-1

IEC 61241-11

IEC 61241-18

IEC 61241-2

EN Standard(status at August 2009)

1-36431NE

EN 13463-2EN 13463-3

EN 13463-5

EN 13463-6

EN 13463-7

EN 13463-8

noitcetorpfotpecnoccisaB

Inherently safe protected. Protected by shutdown

No arcs, sparks or hot surfaces. Enclosure IP54 or better

Contain the explosion, quench the flame

Quench the flame

Limit the energy of sparks and surface temperatures

Keep the flammable gas out

Basic concept of protection

Standard protection for dusts, rugged tight enclosure

Similar to t, but with some relaxations if circuit insideis intrinsically safe

Protection by encapsulation of incendive parts

Protection by pressurisation of enclosure

Basic concept of protection

Low potential energy

Relies on tight seals, closely matched joints and toughenclosures to restrict the breathing of the enclosure

Ignition hazards eliminated by good engineering methods

Control equipment fitted to detect malfunctions

Enclosure is purged and pressurised to prevent ignitionsources from arising

Enclosure uses liquid to prevent contact withexplosive atmosphere

TYPICAL EQUIPMENT MARKING(ELECTRICAL EQUIPMENT)

Protection Concept(s)

Equipment Protection Level (EPL)

ssalCTdnapuorGsutarappA

Ambient Temperature(-20˚C to +40˚C if not marked)

Certificate number (ATEX only)

Certificate number (IECEx only)Series or type designation

IECEx licenced mark (IECEx only)

CE mark and number of notifiedbody responsible for quality audit (ATEX only - CAT 1 & 2 electrical,

CAT 1 non-electrical)

Specific marking of explosion protection (ATEX only) Equipment Group

and Category

2009 Sn 0001

Type of explosive atmosphere G - gases, vapours or mists, D - dust

Year of manufacture and serial number

Name and address of manufacturer

Ex Supplies LtdChester CH4 9JNUnited Kingdom

Floodlight P7

0518

II 2 G D

Ex de IIB T4 Gb

Ex tb IIIC T135 oC Db IP66

Ta = -20 oC to +60 oC

SIRA 09ATEX1234

IECEx SIR 09.0788

a CSA International company

SIRA TEST & CERTIFICATION LTDRake Lane, Eccleston, Chester, CH4 9JN, England

Tel: +44 (0) 1244 670 900 Fax: +44 (0) 1244 681 330 Email: [email protected]

www.siracertification.com

www.drondickson.com

Specialists in design, supply and maintenance of industrial and

hazardous area electrical equipmentUK Offices

Stirling +44 (0)1786 449444Aberdeen +44 (0)1224 874554

Hull +44 (0)1482 213626Lowestoft +44 (0)1502 539991

www.drondickson.com