1
SX.EX.01 O 2 ATEX gasdetector TECHNICAL SPECIFICATIONS Model number SX.EX.01 Available gases Measuring range Span repeatability Long term zero drift Measuring method Response time (T90) Sensor lifecycle Operating temperature range Humidity range Oxygen 0..25% O 2 +/- 2% of the output signal <2% full scale per annum electrochemical <15s +/- 24 months -20...+45 o C 15...90 % R.V., noncondensing Pressure range +/- 10% versus atmosferic pressure Operating voltage range 15 to 30 VDC, nominal 24 VDC Output signal 2-wire, 4...20 mA, lineair Dimensions 100x160x65 mm Weight 850 g IP class 54 IP Certificates EN 50270 - Electromagnetic compatabilty ATEX EEx d IIC T4 Gb II 2 G SIRA10ATEX1358X EEx d IIC T4 Ex II 2 GD INERIS01ATEX0023 Gasdetector in a flame proof enclosure for detection of Oxygen. The Steuma SX.IR.EX serie gasdetectortransmitters have a 24VDC 3wire, 4…20mA outputsignal, allowing them to easily connect to standard types of control units such as the Steuma M500 Series, Series M600 and M2000 series gas monitors. The enclosure of the SX.IR.EX Serie gasdetectortransmitter is made of aluminium, splashproof, HFshielded and explosion proof.

Upload: others

Post on 17-Feb-2021

11 views

Category:

Documents


0 download

TRANSCRIPT

  • SX.EX.01 O2 ATEX gasdetector

    TECHNICAL SPECIFICATIONS Model number SX.EX.01Available gases Measuring range Span repeatability Long term zero drift Measuring method Response time (T90) Sensor lifecycle Operating temperature range Humidity range

    Oxygen0..25% O2+/- 2% of the output signal