Hilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423-234 2965 I www.hilti.com/seismic Hilti. Outperform. Outlast. Hilti = registered trademark of Hilti Corp., Schaan | © 2015 | Right of technical and programme changes reserved S. E. & O. Everything you require for easy and reliable seismic specifications. Post-installed anchoring Fastening structural and non-struc- tural elements according to new Eu- ropean regulations. Ventilated facade Aluminum sub construction for light ventilated façade systems, system tested for seismic applications. Firestop Solutions for pipe and cable penetra- tions through floors or walls, and for fire rated joint seals to reduce post earthquake impacts. Post-installed rebar Injectable mortar and everything re- quired for the safe installation of con- crete-to-concrete connections. Installation systems Maximum safety assured by expert design and the use of Hilti standard pre-design solutions. Structure detection PS 250 and PS 1000 - Compact, cordless and complete system quickly operational and simple to operate to detect rebar in order not to hit them during drilling. Siding and decking Nails and screws tested in accordance with the new AC 70 american standard. Hilti engineering services A team of qualified and experienced engineers is available to provide you with more detailed information and to help you determine and design the best solution for your particular project. Contact them by phone at 01 30 12 65 01 (from 8h30 to 12h30 and from 13h30 to 17h00), by fax at 01 30 12 52 40 or by e-mail at [email protected]

Upload: doanmien

Post on 06-Feb-2018

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Hilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423-234 2965 I www.hilti.com/seismic

Hilti. Outperform. Outlast.

Hilt

i = re

gist

ered

trad

emar

k of

Hilt

i Cor

p., S

chaa

n |

© 2

015

| R

ight

of t

echn

ical

and

pro

gram

me

chan

ges

rese

rved

S. E

. & O

.

Everything you require for easy and reliable seismic specifications.

Post-installed anchoring

Fastening structural and non-struc-tural elements according to new Eu-ropean regulations.

Ventilated facade

Aluminum sub construction for light ventilated façade systems, system tested for seismic applications.

Firestop

Solutions for pipe and cable penetra-tions through floors or walls, and for fire rated joint seals to reduce post earthquake impacts.

Post-installed rebar

Injectable mortar and everything re-quired for the safe installation of con-crete-to-concrete connections.

Installation systems

Maximum safety assured by expert design and the use of Hilti standard pre-design solutions.

Structure detection

PS 250 and PS 1000 - Compact, cordless and complete system quickly operational and simple to operate to detect rebar in order not to hit them during drilling.

Siding and decking

Nails and screws tested in accordance with the new AC 70 american standard.

Hilti engineering services

A team of qualified and experienced engineers is available to provide you with more detailed information and to help you determine and design the best solution for your particular project. Contact them by phone at 01 30 12 65 01 (from 8h30 to 12h30 and from 13h30 to 17h00), by fax at 01 30 12 52 40 or by e-mail at [email protected]

Page 2: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Hilti. Outperform. Outlast.

IN SEISMIC DESIGN.

HILTI PARTNER OF SPECIFYERS

Page 3: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Page 2 I Edition march 2015 www.hilti.fr/le-risque-sismique

Seismic design and specification of seismic products is crucial in both structural and non-structural applications.

Seismic-relevant structural applicationsStructural connections are vital to ensure that the structure responds to a seismic event in a proper, predictable manner. Connections should therefore be clearly detailed in the design phase to make certain that both contractors and building inspectors comprehend project specifications.Firm, well thought out specifications are the best way to ensure that the designed product is the one that is actually used.

Seismic retrofitting (e.g. bracings, shear reinforcement)

Structural steel element connections to concrete

Post-installed rebar connections

Shear wall fastenings

Siding and decking and roofing on metallic structure

Seismic-relevant non-structural applicationsAnchors are often used to fasten non-structural components. Their design and selection is therefore crucial in terms of minimi-zing both injuries to building occupants and the costs associated with seismic events.As fire is a common byproduct of earthquakes, firestop systems should be specified in accordance with their ability to withstand extreme deformation.

Secondary steel connections and fastenings for utilities

Equipments

Mechanical and electrical supports

Ventilated façade systems and curtain walls

Firestop cable and pipe penetrations and joints

6

7

7

2

8

9

10

Page 4: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Hilti solution for earthquake applications

www.hilti.fr/le-risque-sismique Edition march 2015 I Page 3

Seismic design and specification of seismic products is crucial in both structural and non-structural applications.

Source: Taghavi S. and Miranda E.: “Seismic Performance and Loss Assessment of Nonstructural Building Components,” Proceedings of 7th National Conference on Earthquake Engineering, Boston, 2002.

Average Concrete Building

Repair costs resulting from a seismic event

Nonstructural

Contents

Office Hotel Hospital

18%20%

62%

13%17%

70%

8%

44% 48%

20%40%

40%

1

3

7

4

10

8

7

7

Structural

5

Page 5: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Page 4 I Edition march 2015 www.hilti.fr/le-risque-sismique

New European testing procedure for determining the seismic suitability of fasteningsThe seismic pre-qualification of anchors has been regulated since early 2013 in Europe following the release of ETAG 001 Annex E. Anchors subject to this new test procedure must now incorporate in the ETA all the required seismic design technical data . The suitability for seismic loading is classified as:

ETA seismic category C1 – similar to U.S. pre-qualification procedure; only suitable for non-structural applications according to the EOTA TR045 recommendations

ETA seismic category C2 – arduous seismic crack movement tests qualify an anchor as suitable for more demanding structural and non-structural applications

New rating classifications for anchor perfor-mance under seismic load: C1 and C2

Structural applications

Acceleration (ag.S) Building importance II, III, IV

< 0.05g non-seismic

0.05g to 0.1gETA C2

> 0.1g

Non-structural applications

Acceleration (ag.S) Building importanceII, III

Building importanceIV

< 0.05g non-seismic

0.05g to 0.1g ETA C1ETA C2

> 0.1g ETA C2

The map above is based on national earthquake data (for ordinary buildings and ground type A) and provides perspective on the relevance of the new ETA guidelines in various countries. For more precise information see national regulations.

Page 6: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Hilti solution for earthquake applications

www.hilti.fr/le-risque-sismique Edition march 2015 I Page 5

a1) Capacity designThe anchorage is designed for the force corresponding to the yield of a ductile component or, if lower, the maximum force that can be transferred by the fixture or the attached element.

a2) Elastic designThe fastening is designed for the maximum load assuming an elastic behavior of the fastening and of the structure.

b) Design with requirements on the ductility of the anchorsThis design for ductile steel failure requires an anchor classified as ductile. Additionally, this approach is applicable only for the tension component and some provisions require to be observed in order to ensure that the cause of failure is steel failure.

Post-installed anchor seismic design

EOTA TR045 sets the fastening seismic design standardEOTA TR045 sets the standard for the seismic design of steel-to-concrete connections until the new EN 1992-4 is released (release date pending confirmation). This code is in full compliance with the standards in the new ETAG 001 Annex E.

Three design optionsThe design code incorporates three design approaches which are described below. Note that all three of these approaches are acceptable within their application conditions.

Hilti seismic qualified anchors

M8 M10 M12 M16 M20 M24 M30ETA seismic category C1 and C2

HIT-HY 200-A mortar + HIT-Z rod (galvanised and stainless)

ETA 12/0006 15/03/2013C1 C1 C1 C1 C1

C2 C2

HST stud anchor (galvanised and stainless) ETA 98/0001 08/05/2013

C1 C1 C1

C2 C2 C2

HDA undercut anchor (galvanised and stainless) ETA 99/0009 06/01/2015

C1 C1 C1 C1

C2 C2 C2 C2

ETA seismic category C1HIT-HY 200-A mortar + HIT-V rod (galvanised and stainless)

ETA 11/0493 20/06/2013 C1 C1 C1 C1 C1 C1 C1

HIT-RE 500-SD mortar + HIT-V rod and HIS-N sleeve (galvanised and stainless)

ETA 07/0260 16/05/2013 C1 C1 C1 C1 C1 C1 C1

HUS3-H, HUS3-C screw anchor (galvanised)HUS-HR screw anchor (stainless)

ETA 13/1038

ETA 08/0307

13/01/2015 29/04/2014

C1 * C1 * C1 *

Post installed anchor accessoryHilti dynamic set Filling washer, conical washer, nut and lock-nut.

Doubles shear resistance and prevents loosening.

* HUS3-H, HUS3-C, HUS-HR screw anchors are available in size 8, 10 and 14.

Page 7: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Page 6 I Edition march 2015 www.hilti.fr/le-risque-sismique

Design tools

Design is further simplified by Hilti’s own PROFIS software, which allows users to design fastening systems and rebar connections easily and in accordance with the state-of-the art seismic code framework.

Additionally, the printed version of the Fastening Technical Manual (FTM) provides all technical data for both anchoring and rebar connections.

PROFIS Anchor

Structural rebar applicationsApproved per CSTB seismic pre-qualification

Post-installed structural rebarReinforced concrete design assumes that concrete has negligible tensile strength while allowing for the design of rebar development length and avoiding brittle concrete failure, in the following two situations:• Transferring tensile loads from one bar to another (overlap splice)• Development length of the tensile force in a bar beyond a node in equilibrium

Seismic structural rebar approvalFrench DTA approvals delivered by CSTB, a member of EOTA, recognizes Hilti HIT-RE 500-SD and HIT-HY 200-A injectable mortars as products qualified for structural rebar applications in seismic zones. By applying engineering judgment, engineers can use this French approval when designing seismic structural post-installed rebar connections.

Included in the DTAs• The design bond strength fbd,seism of Hilti mortar considered for use in seismic zones• Formatted data for design with Eurocode 2 and Eurocode 8• Application limit information (e.g. transverse reinforcement, settings instructions)

DTA seismic approval

Hilti HIT-RE 500-SD Slow-curing anchor mortar.CSTB approval DTA 3/13-746 for seismic rebar applications.

FTM

Hilti HIT-HY 200-A fast-curing anchor mortar.CSTB approval DTA 3/13-749 for seismic rebar applications.

Page 8: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Hilti solution for earthquake applications

www.hilti.fr/le-risque-sismique Edition march 2015 I Page 7

PROFIS Rebar FTMDedicated web page for specifyers

Siding, decking and roofing applicationsTested according to AC 70 acceptance criteria

The screws and nails are not covered by any regulation in Europe as far as seis-mic behaviour is covered. Nevertheless, on seismic jobsite, the specifyer is quite often ask to justify also these fastenings.

Reason why Hilti has decided to test some nails and screw according to the quite new AC 70 american acceptance criteria which contains seismic test for nails on metallic base material.

If the resistances after the test are not more than 20% below the initial values, the fastening may be qualified for siesmic application without any loss of perfor-mance. This is similar to the C1 criteria for anchors.

Nails and screw seismic tested

Hilti X-ENP 19 Holds the most approvals worldwide for siding and decking

Hilti X-BT designed to create a weld to the base material for an extremely strong hold and high loading capacity

Hilti S-MD 31 PS, S-MD 33 PS For fastening of venitlated facade panels on aluminium structure

Page 9: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Page 8 I Edition march 2015 www.hilti.fr/le-risque-sismique

Recommanded firestop products in seismic

Fires following earthquakes represent a major risk, both for the safety of human lives and for the protection of facilities and assets.

After an earthquake, fire, smoke and water damage can cause severe problems including:

■ Damage to mechanical and electrical equipment■ Breaking/leaks in pipe systems■ Damage to electrical lines, including emergency equipment, lighting■ Damaged communication networks■ Gas leaks, creating an explosion risk■ Blocked, unusable escape routes

Once these problems have been managed there will also be a need for repair, maintenance and reinspection.Hilti seismic testsHilti has conducted extensive tests to determine the behavior of firestop products in a seismic event while taking fire integrity and smoke tightness issues in a post-earthquake environment into consideration. Test setup The quasi-static cyclic loads according to FEMA 461* protocol were applied directly on the penetrants, whereas the wall was fixed. Tests were carried out in x-direction (load in same direction as the penetrant), in y-direction (load perpendicular to the penetrant) and in z-direction (rotation with the center in the wall layer). Air/gas tightness was measured during the test with a pressure testing device to reach measurable conclusions about damages of the penetration seal. After the seismic test an additional firestop test was conducted to evaluate permeability of smoke and fire integrity of the relevant firestop system. ResultsSignificant factors that were measured: displacement (mm), movement force, pressure drop (Pa/min), start of pressure drop (mm), % pressure drop, plastic deformation of penetrant (kN), absolute pressure at start (Pa).Determining factors: flexibility-elasticity, adhesion, tightness, damage to penetrants, installation reliability.Outcome: recommendations for suitable and non-suitable firestop products, installation and design recommendations. * Federal Emergency Management Agency: Code for interim testing protocol for determining the seismic performance characteristics of structural and non-structural components.

Cable penetration

Firestop foam Hilti CFS-F FX Firestop acrylic sealant CFS-S ACR

Firestop block Hilti CFS-BL Firestop plug Hilti CFS-PL

Pipe penetration

Firestop collar Hilti CFS-C P

Joints

Firestop acrylic sealant CFS-S ACRFirestop silicone sealant CFS-S SIL

Firestop spray CFS-SP ACRFor joints applications and curtain walls

Firestop sleeve Hilti CFS-SL Firestop endless collar Hilti CFS-C EL

Page 10: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Hilti solution for earthquake applications

www.hilti.fr/le-risque-sismique Edition march 2015 I Page 9

Sub-structures for ventilated facade has been tested in seismic

Brackets

Bracket MFT-MFI MFor sliding point

L Profile In Aluminium, thickness 2,0 mm and 2,5 mm

Bracket MFT-MFI LFor fixed point

Profiles

T Profile In Aluminium, thickness 2,0 mm and 2,5 mm

Ventilated facade present a risk of falling down in case of earthquake. The French state of the art defines a

seismic test method for the entire system.

A design method based on EN 1998-1-1 (Eurocode 8) for non structural elements is also defined

(document CSTB 3725 dated January 2013).

For more information, please contact our technical back office.

Required displacement

Gliders

Required displacement

Test setup Three tests are defined:

■ Parallelogram test: This test is performed to observe the behaviour of the system to follow the movement of the building on which it is fixed. The ventilated facade is installed on a rigid frame (3 000 x 3 000 mm) fixed on the bottom. The support is gradually deformed in its plane (parallelogram) by a static displacement applied at the head according to the cycles predefined. The maximum displacement is ± 60 mm. A visual control is done on fall elements, breakage or deformation of a component system.

■ Dynamic test: This test is to observe the behavior of the system when the support on which it is mounted is moving in its plane under the action a cyclic reciprocating motion imposed. The ventilated facade is installed on a rigid frame (3 000 x 3 000 mm) on gliders. Cycles of movements are applied around the frequency of the system. The maximum displacement is ± 60 mm. A visual control is done on fall elements, breakage or deformation of a component system.

■ Dynamic perpendicular test: This test is the same as the dynamci test with movement perpendilar to its plane

Parallelogram test

Dynamic test

Page 11: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Page 10 I Edition march 2015 www.hilti.fr/le-risque-sismique

Installation systems need to be designed specifically to resist of seismic loads

PipesFor pipes installation, the basic principle is that the fastenings have to be designed so that the horizontal seismic loads can be taken in addition to the gravity forces.To take horizontal forces, the pipe fastenings must either be designed to be sufficiently flexurally stiff, or have bracing that can transfer the horizontal forces (Fh). It must be ensured that horizontal loads can be taken transversely and longitudinally in relation to the pipe axis.

Horizontal seismic forces Fh,x transverse in relation to pipe axisHorizontal seismic forces Fh,y in direction of pipe axis

Threaded rods

Hinge MQS-AB For bracing of threated rod to base material

Channels

Hinge MQS-AC For bracing of channel to base material or to angleExist in renforced version MQS-ACD

Angle MQS-W For connecting two channelsCan be installed on MQ 41, MQ 72, MQ 41 D

Hinge MQS-H For connecting two threaded rods

Page 12: Everything you require for easy and ... - Hilti België · PDF fileHilti Corporation I 9494 Schaan I Liechtenstein I P +423-234 2111 I F +423 ... The seismic pre-qualification of anchors

Hilti solution for earthquake applications

www.hilti.fr/le-risque-sismique Edition march 2015 I Page 11

Seismic bracing

Braces for a earthquake-resistant installation need to be arranged at a distance (b) from each other that must be assessed in relation to seismic acceleration, the mass of the pipes or (system in general) and the type of braces itself - i.e. the situation of the seismic brace respect to the main axis of the pipe. For this reason, we can distinguish three basic types of seismic-resistant media:■ Longitudinal bracing: seismic brace arranged longitudinally to the main direction of the plant - resistance to horizontal actions acting

along the main axis of the pipe■ Transversal bracing: seismic brace perpendicular to the main direction of the plant - resistance to horizontal actions acting transversely

of the pipe■ 4-way bracing: structure composed of both longitudinal and transversal braces, therefore able to withstand all of the forces acting on

the horizontal plane.

It is advantageous for the bracing to be at a spacing that is a multiple of the normal pipe fastening spacing of (s), so that, for example, every third or fourth pipe fastening is braced.

Design tools Manuel techniqueSystème de supportage

M

an

ue

l te

ch

niq

ue

Systè

me

s d

e s

up

po

rta

ge

I

vri

er

20

14

édition Février 2014

Hilti France I 1 rue Jean Mermoz I 78778 Magny les Hameaux I T +33 1 30 12 50 00 I F + 33 1 30 12 50 12 I www.hilti.fr© 02/2014 I Hilti = marque déposée du Groupe Hilti. Photos et textes non contractuels, sous réserve d’erreur typographique I MK homologation I Ref 2038 I 4 000 ex.

Hilti. Performance. Fiabilité. Service client 0 825 01 05 05

Design is further simplified by Hilti PROFIS Installation, which helps users to design installation systems easily and in accordance with the state-of-the art code.

Additionally, the Installation systems catalogue provides all technical data for all products MM, MQ and MI.Download the latest version of Hilti PROFIS Installation and the technical data sheets from www.hilti.com.

Catalogue

Single pipe applicationTransversal bracing

Single pipe applicationLongitudinal bracing

Trapeze with threated rodsTransversal bracing

Trapeze with threated rodsLongitudinal bracing

Trapeze with threated rods4 ways bracing

PROFIS Installation