evaluation of energy-efficient design strategies comparison of the … of... · 2018. 6. 20. ·...
TRANSCRIPT
-
Contents lists available at ScienceDirect
Solar Energy
journal homepage: www.elsevier.com/locate/solener
Review
Evaluation of energy-efficient design strategies: Comparison of the thermalperformance of energy-efficient office buildings in composite climate, India
Farheen Bano⁎, Vandana SehgalFaculty of Architecture, Dr. A.P.J. Abdul Kalam Technical University, Tagore Marg, Lucknow 226007, India
A R T I C L E I N F O
Keywords:Energy efficiencyOffice buildingEnergy consumptionEnergy performance indexComposite climate
A B S T R A C T
The aim of this paper is to examine the energy consumption of and determine energy-efficient design strategiesfor mid-rise and high-rise office buildings in composite climate. For this purpose, a comparative study is per-formed of six energy-efficient office buildings in composite climate in India. The selected energy-efficient officebuildings are situated in the major cities (Delhi, Gurgaon, and Hyderabad) of India with a composite climate.This study investigates the effectiveness of different design strategies for reducing the heating, ventilation, andair-conditioning (HVAC) and lighting loads of the six buildings. The effect of factors such as the building form,envelope configuration, placement of the service core, window-to-wall ratio (WWR), and percentage of air-conditioned space on the HVAC load are analyzed. Similarly, the effect of the plan depth and WWR on thelighting load is also determined. Finally, the findings of the study are used to recommend effective designstrategies for high-rise office buildings in composite climate. Moreover, the energy performance data arecompared with the national energy consumption benchmarks for composite climate. The comparison indicatesthe design strategies performed well, that lead to a decrease in the energy consumption of high-rise officebuildings in composite climate.
1. Introduction
To make Indian cities sustainable and smart, the energy consump-tion of buildings must be reduced (Ministry of Urban Development,Government of India, 2015). Energy-conscious design requires the in-tegration of climate-responsive design with the functionality of thebuilding. Several studies have investigated the effect of design strate-gies on the energy consumption of high-rise office buildings. Ismail(2007) conducted a comparative study of six Malaysian high-rise officebuildings (three bioclimatic and three typical) and found that biocli-matic high-rise office buildings provide a superior working environ-ment for their users. These buildings also provide a high level ofcomfort with low energy usage. Zhang and Zhu (2013) analyzed fourenergy-efficient office buildings in four climate zones of China anddetermined the breakdown of the energy consumption patterns of thesebuildings. They reported that lighting and cooling account for the lar-gest proportions of energy consumption in office buildings. Moreover,Raji et al. (2016) stated that additional considerations must be made inthe design of high-rise buildings in tropical climate because the energyconsumption of sustainable buildings is relatively higher than the en-ergy benchmarks for a good-practice building.
The literature indicates that air conditioning and lighting are the
main components of energy consumption in high-rise office buildings.The air-conditioning and lighting consumption can be reduced by in-corporating climate-responsive features in the design. Moreover, therecurrently exists a lack of in-depth research on the influence of designstrategies on the energy consumption of high-rise buildings in tropicalclimate (Raji et al., 2016). Therefore, in this study, appropriate designstrategies for reducing the energy consumption of high-rise officebuildings in composite climate (a type of tropical climate) are describedby analyzing case studies of energy-efficient office buildings.
2. Methodology
India has various types of tropical climates due to its large land area,which spans a wide range of latitudes (Bureau of Energy Efficiency,Ministry of Power, 2016). According to the Energy conservationbuilding code (ECBC) (2011) and National Building Code (NBC, 2016),India can be divided into five climate zones, namely hot and dry, warmand humid, composite, temperate, and cold, in terms of the thermaldesign of buildings. The composite zone covers the largest area in India(Fig. 1). Consequently, in this study, six sustainable high-rise officebuildings located in different cities (New Delhi, Gurgaon, and Hyder-abad) of India in the composite climate zone are considered as case
https://doi.org/10.1016/j.solener.2018.10.057Received 20 June 2018; Received in revised form 15 October 2018; Accepted 18 October 2018
⁎ Corresponding author.E-mail addresses: [email protected] (F. Bano), [email protected] (V. Sehgal).
Solar Energy 176 (2018) 506–519
0038-092X/ © 2018 Published by Elsevier Ltd.
T
http://www.sciencedirect.com/science/journal/0038092Xhttps://www.elsevier.com/locate/solenerhttps://doi.org/10.1016/j.solener.2018.10.057https://doi.org/10.1016/j.solener.2018.10.057mailto:[email protected]:[email protected]://doi.org/10.1016/j.solener.2018.10.057http://crossmark.crossref.org/dialog/?doi=10.1016/j.solener.2018.10.057&domain=pdf
-
studies for analyzing the energy consumption patterns and designstrategies used for energy efficiency in buildings. The energy data anddesign strategies of the selected high-performance buildings are col-lected through a literature review. The performance of the buildings iscompared to analyze the effectiveness of the various design strategiesused in the buildings. Finally, the inferences obtained from the casestudies are used to define appropriate design measures for reducing theenergy consumption of buildings situated in composite climate.
The energy performance index (EPI), which is expressed in kWh/m2/year, is commonly used to compare the energy use of buildings. TheEPI is obtained by dividing the annual total energy consumed by abuilding in kilowatt hours by the gross floor area of the building insquare meters (Eq. (1); Tahir et al., 2015). The EPI is expressed asfollows:
=EPITotal Energy Consumed in a year kWh
Total Floor Area of the building m( )( )2 (1)
The methodology adopted for the review of design strategies com-prises the following steps (Fig. 2):
1. Case studies are selected according to the selection criteria de-scribed in Section 3.
2. The case studies are summarized to obtain insight regarding theselected projects. The summary includes the year of completion,significance of the project, energy rating, and sustainable designstrategies employed in the building. (Table 1).
3. The heating, ventilation, and air-conditioning (HVAC) and lightingloads of the buildings are compared. The influence of the designvariables, such as the building plan configuration, building envelopematerials, window-to-wall ratio (WWR), shading devices, and per-centage of air-conditioned space (mix-mode ventilation), on theHVAC performance index is analyzed. The effect of the WWR andplan depth on the lighting performance index is assessed. The effectof the equipment and daylight sensor efficiency on the energyconsumption is also noted.
4. The overall EPI of the selected buildings is analyzed in light of theaforementioned parameters and conclusions are drawn to frameeffective passive design strategies for high-rise office buildings incomposite climate.
3. Selection criteria for the case studies
The selected buildings were already evaluated using one of the
rating systems or standards for high-performance buildings, and theirenergy performance data (metered or simulated) was available. Theselected buildings were occupied for at least 2 years and have at leastfive floors. To expand the analysis, six buildings with different planprofiles (square, rectangular, L-shape, and I-shape), energy-savingstrategies, and building envelope materials are selected.
The buildings selected for the case study are as follows (Fig. 3):
1. ITC Green Centre, Gurgaon2. Wipro Technologies, Gurgaon3. Infosys, Hyderabad4. Volvo-Eicher Corporate Headquarters, Gurgaon5. Indra Paryavaran Bhawan, New Delhi6. Skyview Corporate Park, Gurgaon
From the selected case studies except for Indra Paryavaran Bhawan(IPB), energy consumption data have been obtained through simulationwhile IPB building energy performance data has been acquired throughenergy audit of metered consumption.
4. Case studies
Table 1 lists the details of the energy consumption and designstrategies used in the selected buildings. However, to have the overviewof the case studies, they have been discussed in brief below.
4.1. ITC Green Centre, Gurgaon
ITC Green Centre, located in Sector 3, Gurgaon, was one of the firstbuildings in India to adopt green building practices and is still con-sidered a benchmark for green buildings (Fig. 4). ITC Green Centre,constructed in 2004, was the first platinum-rated building (scored 52out of 69 points) in India. ITC Green Centre achieved the twin aims ofallowing abundant natural light and reducing heat gain in the interiorsby using advanced high-performance glazing solutions (HPCB, 2010;ITC Green Centre, 2017).
With a built-in area of 15,799m2 (of which 9294m2 is air-condi-tioned and 6505m2 is non-air-conditioned), the ITC building includesfeatures such as solar thermal technology, reflective high-albedo roofpaint, minimal exterior lighting, separate smoking rooms with an ex-haust system, and zero water discharge (Fig. 5). More than 10% of thebuilding materials were refurbished from other sites, and 40% of thematerials were obtained from within 500 miles of the project site
Fig. 1. Climate zones in India.Source: Appendix E, ECBC, 2011.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
507
-
(HPCB, 2010; ITC Green Centre, 2017).
4.2. Wipro Technologies, Gurgaon
Wipro Technologies, Gurgaon, was honored by the US GreenBuilding Council in 2005 with a Leadership in Energy andEnvironmental Design (LEED) platinum award (57 points), whichmakes it the second-highest platinum-rated green building in the worldand the highest platinum-rated green building in India. The main focusof the design is the inverted cone strategically located at the crossjunction of two roads, which provides visibility to the building (Fig. 6).The open-to-sky landscape courtyard is the most striking feature of thebuilding, which keeps it cool during summers because the courtyardwalls receive mutual shade and remain cooler than the outside walls(Fig. 7). Moreover, all the open office spaces overlook the courtyard,which consequently allows appropriate access to daylight and max-imizes the outside view. The courtyard acts as a multifunction device,light well, microclimate generator, and social space (The 3C company,2017).
A reduced overall heat conductance from the envelopes and features
such as terrace gardens, high-performance glazing with optimum visuallight transmittance, exterior light shelves, overhangs on all the win-dows, efficient chillers, efficient lighting, and sufficiently daylit interiorspaces with photo sensor controls make Wipro Technologies an ex-emplary energy-efficient building (51% savings over the ASHRAE basecase; ASHRAE, 2013). Moreover, the wood used for the construction ofthe building was sourced from shipwrecks at Jamnagar port (Designand Development, 2016).
4.3. Infosys, Hyderabad
Software Development Block 1 (SDB-1) in the Infosys campus,Hyderabad, has two cooling systems, namely a variable air volume(VAV) system and a radiant cooling system with a dedicated outdoor airsystem (Fig. 8), in the two halves of the building. Thus, the Infosyscampus was the first radiantly cooled building in India, which resultedin the world’s largest HVAC side-by-side comparison. Therefore, thebuilding is highly instrumented to measure the influence of these twosystems. After two years of operation, the radiant system, which ismarginally cheaper than the VAV system, used 34% less energy and
Selection of case studies
Analysis
HVAC load Equipment load i n load
• Building plan con gu a on
• Building envelope- mate ials s ading devices and
• Mixed mode ven la on- of ai condi ons space.
ve vie of case studies
• • plan depth
ea of comple on signi cance ene gy a ng sustaina le design st ategies applied in the uilding.
• C of HVAC system • E ciency of ligh ng
xtu es and equipment
• igh ng senso s
ve all ene gy pe fo manceindex
Conclusions
• Evaluated using one of the a ng systems o standa ds fo high-pe fo mance uildings • Availa ility of uilding- elated ene gy pe fo mance data mete ed o simulated • if it as ne ly const ucted o ce uilding then it must have een occupied fo yea s
and it should have at least ve oo s • i e ent plan p o les squa e ectangula -shape and -shape ene gy-saving
st ategies and uilding envelope mate ials. EEC
CE
A A
A C
EA
VEV
E
CE
A
E ec ve design st ategies fo high- ise o ce uildingsin composite climate.
Fig. 2. Flowchart of the methodology used in the study.Source: Author.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
508
-
Table1
Details
oftheselected
energy
-efficien
toffi
cebu
ildings.
ITC
Gre
en C
entr
e, G
urga
on
Wip
ro T
echn
olog
ies,
Gur
gaon
In
fosy
s,
Hyd
erab
ad
IPB
, N
ew D
elhi
V
EC
H,
Gur
gaon
Sk
yvie
w C
orpo
rate
Par
k,
Gur
gaon
ITC
WIPRO
INFO
SYS
IPB
VEC
HSK
YVIEW
Yearof
completion
2004
2005
2011
2014
2012
2015
Sign
ificanc
ePlatinum
-rated
byLE
ED52
/69
Platinum
-rated
byLE
ED57
/69
Platinum
-rated
byLE
EDPlatinum
-rated
byLE
EDFive
-star-rated
byGRIH
APlatinum
-rated
byLE
EDWorld
Architecture
Award
Platinum
-rated
byLE
ED
Ope
nplan
/Cellularoffi
ce60
%Cellularoffi
ce+
40%
Ope
nplan
Ope
nplan
Ope
n+
Cellular
Ope
n+
Cellular
Ope
nOpe
n
%of
air-co
nditione
dspace
5965
7038
100
100
Build
ingco
nfigu
ration
Orien
tation
Long
axis
ofthebu
ildingoriented
NE–
NW
Squa
replan
facade
sin
the
NE,
SE,N
W,a
ndSW
directions
N–S
orientation
N–S
orientation
NE–
SWorientation
NE–
SWorientation
Placem
entof
core
Cen
tral,E
ast,an
dWest
Cen
tral,Ea
st,a
ndWest
Cen
tral
Cen
tral
andWest
Cen
tral
Cen
tral
Typicalfloo
rarea
(m2)
2047
1726
4073
3150
1246
2730
Totalfloo
rarea
(m2)
15,799
16,258
24,730
31,400
9972
23,500
No.
offloo
rsab
ove
grou
nd6(2B+
G+
5)6(2B+
G+
5)6(G
+5)
8(G
+7)
6(2B+
G+
5)9(G
+8)
Floo
r-to-floo
rhe
ight
(m)
3.6
3.6
3.6
3.9
3.6
3.6
Aspectratio
1:1
1:1
1:2.4
1:1.3
1:2.6
1:1.6
Com
pactne
ssratio
(perim
eter/area)
9.9
9.5
9.7
1617
.510
Plan
depth(m
)ov
erall
2413
1815
1734
(13m
from
core)
Windo
wpa
rameters
Ove
rallWWR
(%)
3335
2520
8055
Shad
ingde
vice
Few
windo
wsshad
edwith
horizo
ntal
louv
ers
Horizon
tallouv
ers
Recessedwindo
wBo
xRecycledrailw
ays
sleepe
rsused
tomak
ethedo
uble-curve
dlouv
ers
Noshad
ing
Sillleve
l(m
)0.3
0.8
0.8
0.8
00
Windo
whe
ight
(m)
2.1
1.6
1.8
1.8
Fullleng
thFu
llleng
th
(con
tinuedon
next
page)
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
509
-
Table1(con
tinued)
ITC
Gre
en C
entr
e, G
urga
on
Wip
ro T
echn
olog
ies,
Gur
gaon
In
fosy
s,
Hyd
erab
ad
IPB
, N
ew D
elhi
V
EC
H,
Gur
gaon
Sk
yvie
w C
orpo
rate
Par
k,
Gur
gaon
ITC
WIPRO
INFO
SYS
IPB
VEC
HSK
YVIEW
Build
ingen
velope
materials
Walla
ssem
blyU-value
inW/m
2K
250-mm
AACbloc
kwith70
-mm
ston
eclad
ding
and12
.5-m
mplasterinside
U-value
:0.607
Fly-ash-ba
sedAACbloc
kbloc
ksU-value
:0.63
Wallinsulation
andcavity
wallwithinsulation
U-value
:0.36
AACbloc
kmason
rywallan
dfly-ash-ba
sedplasteran
dmortar
U-value
:0.34
Ston
ean
dferroc
emen
tjaalis
used
inthecirculationarea
Cav
itywallclad
with
tiles
U-value
:1.1
Cav
itywall
U-value
:1.166
Roo
fassemblyU-value
inW/m
2K
120-mm
RCCroof
witha76
-mm
ISO
boardin
theinterior
U-value
:0.335
75-m
mextrud
edpo
lystyren
eredu
ceshe
attran
smission
by50
%.
Roo
ffinish
withhigh
-Refl
ection
material
Solarreflective
inde
x(SRI)
>78
U-value
:0.31
Roo
fwithinsulation
U-value
:0.33
Coo
lroof:
2.6millionft2area
cove
red
withawhite
roof
Red
uction
ofap
prox
imately5%
inthe
HVACen
ergy
150-mm
RCCslab
with
insulation
andlocalston
esU-value
:0.5
Roo
fga
rden
U-value
:0.25
Refl
ective
insulated
roof
U-value
:0.3
Glazing
type
U-value
inW/m
2K
Dou
ble-glazingwindo
w(6-12-6),S
C=
0.26
,an
dU-value
=1.81
W/m
2K
6-mm
glass+
12-m
mairga
p+
6-mm
high
-perform
ance
glass(ST1
50,light
blue
gray
,U
factor
of1.81
W/m
2K)
21%
reflectanc
ean
d39
%tran
smittanc
eRed
uction
inthehe
atga
inby
15–2
0%
Dou
ble-glazingwithargo
nga
sU-value
less
than
1.2W/m
2K
Low
SHGCwithlow-e
glass
SHGC:1
.8
Dou
ble-glasswindo
wswitha
high
efficien
cy,v
isible
light
tran
smission
(VLT
=0.6),a
ndU-value
(1.8)
Ligh
tshelve
sforallowingthe
entryof
diffused
sunlight
Dou
ble-glasswindo
ws
U-value
:2.1
SHGC=
0.69
7
Dua
l-pan
elow-e
glass
U-value
:1.8
SHGC=
0.62
9
(con
tinuedon
next
page)
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
510
-
Table1(con
tinued)
ITC
Gre
en C
entr
e, G
urga
on
Wip
ro T
echn
olog
ies,
Gur
gaon
In
fosy
s,
Hyd
erab
ad
IPB
, N
ew D
elhi
V
EC
H,
Gur
gaon
Sk
yvie
w C
orpo
rate
Par
k,
Gur
gaon
ITC
WIPRO
INFO
SYS
IPB
VEC
HSK
YVIEW
Occup
ancy
&en
ergy
consum
ption
Wor
king
hour
s10
h(5
days
perweek)
10h
(5da
yspe
rweek)
8.5h
(5da
yspe
rweek)
10am
–5pm
(5da
yspe
rweek)
10am
–5pm
(5da
yspe
rweek)
10am
–5pm
(6da
yspe
rweek)
Occ
upan
cyno
tav
ailable(N
A)
1305
peop
le26
00pe
ople
1000
peop
leNA
NA
HVACtype
andca
pacity
ECBC
reco
mmen
dsCOP:
5.4
Cen
tral,2
850kW
capa
city,
18m
2/T
RCOP:
6.1
Cen
tral,22
85kW
capa
city,
25m
2/T
RCOP:
6.5
Cen
tral,14
00kW
capa
city,
75m
2/T
RCOP:
7
Chille
dbe
amsystem
ofHVAC,
geothe
rmal
tech
nology
for
heat
rejection,
563kW
capa
city,4
5m
2/T
RCOP:
6.7
HVACun
derthefloo
rredu
cesen
ergy
consum
ptionby
30%
2335
kWcapa
city,
15m
2/T
RCOP:
6
High-effi
cien
cyfilters
intheHVACsystem
6357
kWcapa
city,
13m
2/T
RCOP:5
.4
Ligh
ting
fixtur
esT5
andCFL
lamps
(day
light
sensors)
Ligh
tshelve
s,T-5,
andCFL
Ligh
tshelve
s,T-5,
andLE
Dfixtures
(day
light
sensors)
Ligh
tshelve
s,T-5,
andLE
Dfixtures
(day
light
sensors)
Ligh
tsworkon
motion
sensorsan
d95
%are
LEDs
T-5an
dLE
Dfixtures
(day
light
sensors)
LPD
ECBC
reco
mmen
ds10
.8W/m
2
7.2W/m
25.4W/m
24.8W/m
25W/m
24W/m
29.5W/m
2
Metho
dof
acqu
iring
energy
cons
umption
data
(inav
ailable
literature)
simulated
simulated
simulated
metered
(ene
rgyau
ditrepo
rt)
simulated
simulated
Ligh
ting
perfor
man
ceinde
x(kWh/
m2/y
ear)
1310
8.8
9.2
716
.9
HVACpe
rfor
man
ceinde
x(kWh/
m2/y
ear)
6458
32.25
2771
79
EPI(kWh/
m2/y
ear)
ECBC
energy
benc
hmark:
179kW
h/m
2/y
ear
93(48%
redu
ction)
85(53%
redu
ction)
51.85(71%
redu
ction)
45.25(75%
redu
ction)
96(46%
redu
ction)
112(37%
redu
ction)
Ren
ewab
leen
ergy
(kWp)
Photov
oltaic
cells
forem
erge
ncy
lighting
NA
44kW
pSP
Vpa
nels
930kW
pSP
Vpa
nels
NA
NA
Sources:
HPC
B(201
0)forITCGreen
Cen
tre,
Gurga
on.
The3C
compa
ny(201
7)an
dDesignan
dDev
elop
men
t(201
6)forWipro
Tech
nologies,G
urga
on.
GRIH
A(201
8),Sa
gar(201
3),a
ndSa
stry
(201
4)forInfosys,
Hyd
erab
ad.
Prasha
dan
dChe
tia(201
4)an
dGRIH
A(201
7)forIPB,
New
Delhi.
Kho
sla(201
7)an
dSing
hal(201
4)forVEC
H,G
urga
on.
Skyv
iew
Corpo
rate
Park
(201
7)forSk
yview
Corpo
rate
Park,G
urga
on.
NBC
(201
6)fortheU-value
ofthewall,roof,a
ndglazingassembly.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
511
-
improved thermal satisfaction (Sagar, 2013).Other strategies adopted to reduce energy consumption include
suitably orienting the building (north–south orientation) and opti-mizing the WWR (
-
glass in fenestration to reduce heat transfer, use of recycled and locallyavailable materials, and a user-friendly built environment (Fig. 13;GRIHA, 2017).
4.6. Skyview Corporate Park, Gurgaon
Skyview Corporate Park is a multiphase project developed on a 21-acre site that faces National Highway 8 (NH-8). Phase I of the corporatepark was completed in 2015. The project achieved platinum certifica-tion under the Indian Green Building Council’s LEED India program in2015. The dual-pane, low-e, high-performance glass in the facade of thebuilding decreases heat transfer, and the air-conditioning system, whichincludes a microfilter, increases the comfort of the office space (Fig. 14;Skyview Corporate Park, 2017).
5. Comparison of the design strategies used in the selected officebuildings for energy efficiency
Table 1 presents the design strategies and energy consumption datafor the selected buildings in composite climate. Areas with compositeclimate experience a constant high temperature and intense radiationthroughout the year (excluding two or three months). Hence, designstrategies that restrict heat gains and maximize daylight into the in-teriors reduce the total energy consumption in office buildings (Banoand Tahseen, 2017). Minimizing the surface-to-volume ratio (com-pactness ratio), placing service areas as thermal buffers on the hot sides,constructing a low U-value and shaded building envelope, and opti-mizing the WWR and plan depth are some of the strategies that reducethe HVAC and lighting loads of an office building in composite climate(Raji et al., 2016). The case studies are analyzed to investigate the ef-fectiveness of the aforementioned strategies for reducing the HVAC andlighting loads of a building. Moreover, the ITC and Wipro; Infosys andIPB; and VECH and Skyview buildings were compared with each otherbecause they had similar shapes, plan configurations, and energy con-sumption (Table 1).
5.1. HVAC load
In composite climate, approximately 50–60% of the operationalenergy of an office building is used for cooling. A decrease in thecooling load reduces the electricity bill. The design strategies used inthe selected buildings for reducing the HVAC load are analyzed anddiscussed in the following text. The HVAC load is represented by theHVAC performance index (expressed in kWh/m2/year) in the Table 1.The HVAC performance is the total energy used by an HVAC system in1 year divided by total floor area of the building.
5.1.1. Building plan configurationThe ITC and Wipro buildings have a similar aspect ratio (nearly 1),
compactness ratio of the building plan (9.9 for ITC and 9.5 for Wipro),and orientation (plan rotated by 45°). Therefore, their design strategiesand energy consumption are compared. The solar radiation from theeast and west is reduced by mutual shading because of the L-shapedplan of ITC Green Centre, whose longer facades are in the northeast andnorthwest directions. By contrast, the Wipro building does not have anyspecific orientation. However, its compact square form reduces heatgains and losses from the building envelope (Raji et al., 2017). Thecourtyard of Wipro has multifaceted advantages. It acts as a light well,microclimate generator, and landscape element (Fig. 7). Moreover, itprovides mutual shading to the courtyard walls, which keeps themcooler than the outside walls (The 3C company, 2017). The placementof the service core at an appropriate location in both buildings furtherminimizes heat transfer and reduces unpleasant glare from the east andwest directions (Table 1). Moreover, the L-shaped plan of ITC GreenCentre and square plan of Wipro Technologies (with a courtyard in thecenter) reduces the width of the floor plate (24m for ITC Green Centreand 13m for Wipro Technologies), allows daylight to penetrate deepinto interior spaces, and provides an external view of almost every openoffice space (Figs. 4–7). The octagonal atrium has a side light at the top,which allows glare-free light to be directed into the interiors.
The Infosys and IPB buildings comprise twin blocks connected by avertical atrium and horizontal courtyard and have aspect ratios of 1:2.4
Fig. 5. Shading devices and central atrium of ITC Green Centre.Source: HPCB, 2010.
Fig. 6. West-side view, east-side view, and site plan of Wipro Technologies, Gurgaon.Source: Design and Development, 2016.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
513
-
and 1:1.3, respectively (Figs. 8 and 13). Both buildings are orientedaccording to the path of the sun’s rays, with the long axis oriented alongthe east–west direction to reduce solar heat gain. Moreover, they alsoprovide mutual shading because of their plan configurations. The ser-vice core of the IPB building is placed in the west direction. Thus, thecore acts as a buffer between the sun and the interior working area. Bycontrast, the service core of the Infosys building is placed centrally onthe east and west facades. The slender shape (plan depth of 18m for theInfosys building and 15m for the IPB building) of both the buildingsallows increased daylight penetration and a view of the scenic sur-roundings from most locations on the office floor plate (Prashad andChetia, 2014).
VECH and Skyview Corporate Park are rectangular in shape, withaspect ratios of 1:2.6 and 1:1.6, respectively (Figs. 10 and 14). Bothbuildings are oriented in the northeast–southwest direction. Thebuilding orientation and plan configuration of both the buildings ap-pear to be derived from the urban grid for maximizing the view. En-vironmental concerns were not taken into account in the design. Theservice core could have been used as a solar buffer on the hot east andwest sides; however, the core is placed centrally. This could be thereason for the high HVAC performance index of these two buildings.
5.1.2. Shaded energy-efficient building envelopeThe ITC and Wipro buildings have thermal-resistive building en-
velopes, which comprise 250mm aerated concrete (AAC) block wallswith a 70-mm-thick stone cladding, 12-mm-thick internal plaster (U-value of approx. 0.6W/m2/K), 75-mm thick extruded polystyrene slab(XPS) roof insulated on a 120-mm reinforced cement concrete (RCC)slab (U-value of approx. 0.3W/m2/K), and double-glazed window (U-value of 1.81W/m2/K) having a shading coefficient of 0.26.Consequently, the heat gain or loss and HVAC load of both the buildingsdecreases (HPCB, 2010). However, the HVAC performance index of ITCGreen Centre is higher than that of Wipro Technologies possibly be-cause only 20% of the windows are shaded and horizontal louvers areused in ITC Green Centre.
Similar to the ITC and Wipro buildings, the Infosys and IPB build-ings also include an energy-efficient building envelope that decreases
the HVAC load. A reflective roof, AAC block walls, a un-plasticized polyvinyl chloride (uPVC) window with composite sections, and a high-performance glazing (double-glazed with low-e coating) are used inIPB, which lowers the thermal transfer through the envelope (Prashadand Chetia, 2014). Similarly, the building envelope of the Infosysbuilding allows a heat transfer of less than 0.75W/ft2 (Sastry, 2014).Moreover, a low WWR (28% for the Infosys building and 20% for IPB)and shaded (recessed) windows reduce the heat gain and requirementfor high-efficiency glass.
The VECH and Skyview office buildings are completely air-condi-tioned, with their facades almost completely covered with full-heighthigh-performance glass. The VECH and Skyview buildings have a WWRof 80% and 55%, respectively. Thus, the cooling load of the buildingsincreases because even a very-high-performance glazing allows ap-proximately one-third of the solar radiation (solar heat gain coefficient(SHGC)= 0.3) to enter the building. However, the service core, whichhas a thick concrete wall along the center of the southwest facade, actsas a thermal buffer on the hot side and reduces the cooling load ofVECH. Moreover, correctly angled doubly curved louvers restrict directradiation and allow evenly distributed indirect radiation in thebuilding. HVAC diffusers with a heat recovery system are installedunder the floor, which results in a 30% reduction in the energy con-sumption for cooling. Therefore, the cooling load of VECH (66 kWh/m2/year) is less than that of Skyview Corporate Park (74 kWh/m2/year).
5.1.3. Mixed-mode ventilation systemA mixed-mode (natural and mechanical) ventilation system can ef-
fectively reduce the HVAC load. Circulation areas with tolerable mar-ginal discomfort, such as lobbies and passages, can be naturally venti-lated to reduce the load on the HVAC system. A large number of spaces,such as corridors and lobbies, in the ITC, Wipro, Infosys, and IPBbuildings are non-air-conditioned spaces (Fig. 15a) with adequatenatural ventilation (through jaalis in IPB). IPB has the lowest HVACperformance index (27 kWh/m2/year) among the selected buildingsbecause of its non-dependency on the mechanical system (62% of itsarea is naturally ventilated; Fig. 15b). The ITC, Wipro, and Infosys
Fig. 7. View of the open-to-sky courtyard and terrace garden at Wipro Technologies, Gurgaon.Source: Design and Development, 2016.
Fig. 8. North-side view and plan of Infosys, Hyderabad.Source: Sagar, 2013; GRIHA, 2018.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
514
-
buildings have an air-conditioned area ranging from 60% to 70%(Fig. 15a). Thus, the HVAC loads in these buildings may vary because ofother reasons. However, the HVAC loads of the VECH and Skyviewbuildings are comparatively high possibly because the total area of thebuildings is mechanically ventilated.
5.2. Lighting load
The lighting load is represented in terms of the lighting performanceindex (expressed in kWh/m2/year). The lighting performance index isthe total energy used by the artificial lighting system in 1 year dividedby the total floor area of the building.
The VECH building has the highest transparency (WWR of 85%)among the six studied buildings, with a depth of 8.5m from the facadeto the center (Fig. 16a). The slender shape of the building and its highWWR results in approximately 95% daylit office space. Moreover, thecolumn-less building structure allows superior natural light penetrationthrough the building and flexibility in workstation layout. Doublycurved louvers inclined at a specific angle are installed for the deeppenetration and even distribution of daylight throughout the officespace. All the lights work on motion sensors, and 95% of the lights areLEDs. Consequently, the VECH building has the lowest electricity con-sumption for lighting (7 kWh/m2/year) among the selected buildings(Fig. 16b).
The Infosys and IPB buildings rank second and third, respectively,with regard to energy consumption for lighting (approximately 8.8 and9.2 kWh/m2/year, respectively). The Infosys and IPB buildings com-prise two environmentally oriented (N–S) parallel blocks with a centralvoid. The Infosys and IPB buildings have a plan depth (from the facadeto the center) of 9 and 7.5m, respectively. Thus, the offices in thesebuildings receive daylight from two sides. The WWR of the Infosys andIPB buildings are similar. However, the optimum plan depth of the IPBbuilding causes a higher reduction in its lighting load compared withthat of the Infosys building.
Similar to the Infosys and IPB buildings, the Wipro building has a
central courtyard, which reduces the plan depth and WWR to 6.5 m andless than 40%, respectively. However, the unsuitable orientation andlow central void width of the Wipro building may be cause of lowdistribution of natural light in the interior, which marginally increasesthe lighting performance index (10 kWh/m2/year).
In contrast to the other four buildings, the ITC and Skyview build-ings have deep plan offices, with plan depths of 12m from the centerand 13m from the service core, respectively. Although the Skyviewbuilding has a high WWR (55%), its broad plan with a central servicecore has the highest artificial lighting demand (16.9 kWh/m2/year).However, the placement of the service core on the external facade andnear the central atrium with clearstory vertical windows reduces thelighting load of the ITC building.
5.3. Fixtures and equipment
Efficient HVAC systems having a coefficient of performance (COP)higher than 6 and energy-efficient lighting fixtures with motion sensorsare installed in all the selected buildings. An energy-efficient chilledbeam system is used in the Wipro and IPB buildings for air con-ditioning, which reduces the cooling load by 40% (Prashad and Chetia,2014). In this air-conditioning system, the air flows around beamsthrough which chilled water is circulated. Furthermore, geothermaltechnology is used in the IPB building for heat rejection from the waterused for the cooling condenser. The radiant cooling system in the In-fosys building and the installation of diffusers with a heat recoverysystem under the floor in the VECH building reduces the energy con-sumption by 30% (Sagar, 2013). Cooled surfaces are used to remove thesensible heat by radiation and convection through the radiant coolingsystem.
5.4. Comparison of the EPI of the selected buildings
The EPI of IPB is the lowest (45.25 kWh/m2/year) among the se-lected buildings (Fig. 17) because of the passive features adopted in the
Fig. 9. External shading and light shelves used in SBD-1, Infosys, Hyderabad.Source: Sagar, 2013.
Fig. 10. Northeast-side view and typical floor plan of VECH, Gurgaon.Source: Romi Khosla Design Studio, 2017; Singhal, 2014.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
515
-
building design, namely the climate-responsive form and orientation,optimum plan depth and WWR, high percentage of naturally ventilatedspaces, service core acting as a buffer space, highly insulated andshaded building envelope and HVAC system, chiller beams, and geo-thermal heat rejection system. Moreover, solar photovoltaic cells with acapacity of 930 kWp are installed on the terraces and projections. Thesolar cells produce an energy of 14,91,000 kWh/year, which exceedsthe building’s consumption (14,21,000 kWh/year). Thus, IPB is an en-ergy-positive building.
Despite possessing all the passive design features of IPB, the Infosysbuilding ranks second with regard to total energy consumption, whichmay be due to its high dependency on the air-conditioning system (70%
air-conditioned space; Fig. 17).The Wipro and ITC buildings have the same orientation, the same
plan aspect ratio, an optimum WWR, and a mixed-mode ventilationsystem. However, the EPI of Wipro Technologies (85 kWh/m2/year) islower than that of ITC Green Centre (90 kWh/m2/year) possibly be-cause Wipro Technologies has a compact square plan; a reduced plandepth (6.5 m from the center to the outer facade) due to the presence ofa central landscaped courtyard, a shaded external facade, and courtyardwalls; and an environmentally placed service core.
The VECH and Skyview buildings are completely air-conditionedand have a high WWR. Although the facade of VECH is almost com-pletely covered with full-height dual-pane glass (WWR 80%), its EPI
Fig. 11. Recycled wood used to clad columns and recycled railway sleepers used for making the louvers.Source: Singhal, 2014.
Fig. 12. North-side elevation and view of the central atrium of IPB.Source: Ministry of Environment and Forests, 2011.
Fig. 13. Site plan and section indicating cross ventilation in IPB.Source: Prashad and Chetia, 2014.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
516
-
(96 kWh/m2/year) is less than that of the Skyview building (112 kWh/m2/year) because the location of the service core, presence of an angleddoubly curved series of louvers shading the envelope, and location ofthe HVAC system under the floor reduce the HVAC load of VECH.Moreover, the slender plan and high transparency of the facade reducesthe lighting load of the VECH building. The working hours of theSkyview building (6 days per week) are higher than those of VECH(5 days per week), which may be one of the reasons for the higherenergy consumption in the Skyview building (Skyview Corporate Park,2017; Khosla, 2017).
6. Conclusions
Effective design strategies for high-rise office buildings in composite
climate are investigated through a comparative study of six sustainableoffice buildings. Although some design strategies reduce the lightingload, they increase the HVAC load of the building. Therefore, a linearbuilding may sometimes exhibit better energy performance than acompact building. This research aims to determine the most-effectivedesign strategies for reducing the HVAC and lighting energy con-sumption in energy-efficient mid- and high-rise office buildings incomposite climate. The effective design strategies for buildings incomposite climate are as follows:
1. Building envelope: The use of insulated (low U-value) walls, an in-sulated roof, high-performance dual-pane glass in fenestrations, andshaded windows can effectively reduce the HVAC load of buildingsin composite climate.
Fig. 14. Northeast-side view and typical floor plan of Skyview Corporate Park.Source: Skyview Corporate Park, 2017.
(a) (b)
59 6570
38
100 100
0102030405060708090
100
ITC WIPRO INFOSYS IPB VOLVO SKYVIEW
Comparison of percentage of air condi oned area in selected buildings.
% of condi oned area % of non condi oned area
Fig. 15. Influence of the air-conditioned area on the HVAC performance of the selected buildings.
(a) (b)
33 35 25 20
80
55
12
6.5
97.5
8.5
13
0
2
4
6
8
10
12
14
0102030405060708090
ITC WIPRO INFOSYS IPB VOLVO SKYVIEW
Plan
dep
th in
m
WW
R %
WWR and plan depth of selected buildings
WWR% Plan depth from centre
13
108.8 9.2
7
16.9
0
2
4
6
8
10
12
14
16
18
ITC WIPRO INFOSYS IPB VOLVO SKYVIEW
Kwh/
m²/
year
Ligh ng performace index
Fig. 16. Influence of the air-conditioned area on the energy performance of the selected buildings.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
517
-
2. Building plan configuration: Placing service areas with limitedopenings as thermal buffers on the west side and minimizing thesurface-area-to-volume ratio are some of the strategies for control-ling the heat gain and consequently reducing the cooling load.Moreover, placing the service core along the facade allows naturalventilation and lighting.
3. Mixed-mode ventilation system: The mixed-mode ventilation systemcan effectively reduce the energy consumption for cooling. The ef-fectiveness of ventilation can be improved using special designelements, such as atriums and landscaped courtyards, which canincrease the penetration of daylight into the plan.
4. WWR: A very low WWR reduces the cooling load. However, it alsoreduces the availability of natural light inside the building, whichincreases the lighting and heating load. The case studies indicatethat the cooling and lighting loads of a building are reduced if theWWR is less than 40% and the maximum plan depth (between ex-ternal facades) is 15m.
The EPI of the six selected energy-efficient office buildings rangesfrom 45 to 112 kWh/m2/year. The EPI benchmark for conventionaloffice buildings in composite climate is 177 kWh/m2/year (Bassi,2015). Therefore, the energy savings of the selected buildings rangefrom 37% to 75%.
A comprehensive analysis of the energy consumption for heating,cooling, and lighting can be performed by determining the monthlyvolatility in the total energy consumption of the selected buildings.Moreover, the influence of occupancy on the EPI of the buildings can beexamined in future studies.
Conflict of interest
The authors declared that there is no conflict of interest.
References
ASHRAE, 2013. ANSI/ASHRAE/IES Standard 90.1. Energy Standard for Buildings exceptlow rise residential Building, Atlanta.
Bano, F., Tahseen, M., 2017. Bioclimatic building design guidelines for Lucknow city: useof various climate analysis methods. Int. J. Res. Appl. Sci. Eng. Technol. (IJRASET) 5(XI), 330–341. https://doi.org/10.22214/ijraset.2017.11049.
Bassi, S., 2015. Benchmarking of commercial buildings in India. 17 – 18 December 2015In: Srinivas, S.N., Gadde, B., Seth, S., Dhage, V. (Eds.), Implementing EnergyEfficiency in Buildings, A compendium of experiences from across the world, ICEEB.United Nations Development Programme., New Delhi, pp. 99–106 (RetrievedNovember 12, 2016, from http://www.undp.org/content/dam/india/docs/ICEEB%202015_Compendium.pdf).
Bureau of Energy Efficiency, Ministry of Power, 2016. Energy Conservation Building Code2016. Government of India. (Retrieved from https://beeindia.gov.in/sites/default/files/ECBC%202016_Draft_V8.pdf).
Design and Development, 2016. Wipro Technologies. (Retrieved December 15, 2016,from http://www.des-dev.co.in: http://www.des-dev.co.in/project_detail.php?subcat=1&pid=57).
ECBC, 2011, Aril 01. ECBC User Guide v 2.0. (Retrieved 6 2015, 16, from EnergyConservation Building Code: http://www.eco3.org/wp-content/plugins/. ECBC UserGuide v 2.0).
GRIHA, 2017. Case study: Indira Paryavaran Bhawan (IPB). (Retrieved November 24,2017, from Green Rating for Integrated Habitat Assessment, India: http://www.grihaindia.org/images/casestudies/pdf/Indira-Paryavaran-Bhawani.pdf).
GRIHA, 2018. Case study of SBD1, Infosys Limited, Hyderabad. (Retrieved February 12,2018, from Green Rating for Integrated Habitat Assessment, India: http://grihaindia.org/images/casestudies/pdf/Infosys-hyderabad.pdf).
HPCB, 2010. Case Study: ECBC Complaint Building, ITC Green Centre, Gurgaon.(Retrieved February 11, 2018, from High performance commercial buildings in India:http://high-performancebuildings.org/case_study_ECBC_comp_gurgaon.php).
Ismail, L.H., 2007. An Evaluation of Bioclimatic High Rise Office Buildings in a TropicalClimate: Energy Consumption and Users' Satisfaction in Selected Office Buildings inMalaysia. School of Architecture, University of Liverpool, Malaysia(Ph.D ThesisRetrieved November 1, 2017, from http://eprints.uthm.edu.my/1274/1/24_Pages_from_AN_EVALUATION_OF_BIOCLIMATIC_HIGH_RISE_OFFICE_BUILDINGS_IN_A_TROPICAL_CLIMATE_ENERGY.pdf).
ITC Green Centre, 2017. Retrieved March 23, 2017, from glazette.com: http://www.glazette.com/upload/resources/tb_90520091157467157.PDF.
Khosla, R. 2017. Volvo - Eicher headquarter, Gurgaon. (Retrieved from Zingyhomes:https://www.zingyhomes.com/project-detail/romi-khosla_8736/volvo-eicher-headquarter-gurgaon/).
Ministry of Environment and Forests, 2011. Indira Paryavaran Bhawan. (RetrievedOctober 23, 2017, from moef.nic.in: http://www.moef.nic.in/ipb/home1.htm).
Ministry of Urban Development, Government of India, 2015. Smart Cities: MissionStatement & Guidelines. New Delhi: Ministry of Urban Development, Government ofindia. (Retrieved November 12, 2017, from http://smartcities.gov.in/upload/uploadfiles/files/SmartCityGuidelines(1).pdf).
NBC, 2016. National Building Code. Bureau of Indian Standards, New Delhi.Prashad, D., Chetia, S., 2014. A Paradigm of Self-Sufficiency- Indira Paryavaran Bhawan.
Akshay Urja, December 2014, 26–31. (Retrieved February 13, 2018, from http://mnre.gov.in/file-manager/akshay-urja/november-december-2014/EN/26-31.pdf).
Raji, B., Tenpierik, M.J., Dobbelsteen, A.V., 2016. A comparative study: design strategiesfor energy-efficiency of high-rise office buildings. J. Green Building 11 (1), 134–158.https://doi.org/10.3992/jgb.11.1.134.1.
Raji, B., Tenpierik, M., Dobbeslsteen, A., 2017. Early-stage design considerations for theenergy-efficiency of high-rise office buildings. Sustainability 9 (623), 1–28. https://doi.org/10.3390/su9040623.
Romi Khosla Design Studio, 2017. Projects- Volvo-Eicher Headquarter. (RetrievedSeptember 12, 2017, from ebuild.in: https://ebuild.in/volvo-eicher-headquarters-gurgaon-romi-khosla-design-studio).
Sagar, N., 2013. Case study of buildings with radiant cooling, Infosys Limited, Bangalore,India. (Retrieved October 16, 2016, from beepindia.org: http://www.beepindia.org/sites/default/files/L5%20-%20Case%20study%20on%20radiant%20buildings%20-%20Infosys.pdf).
Sastry, G., 2014, September 17. (Retrieved October 26, 2016, from Green BuildingCongress: www.greenbuildingcongress.com/site/.../Mr_Guruprakash_Sastry_Infosys.pdf).
Singhal, S., 2014, April 30. Volvo Eicher Corporate Headquarter in Gurgaon, Indi by RomiKhosla Design Studios. [Web log post]. (Retrieved December 07, 2017, from aecafe.com: https://www10.aeccafe.com/blogs/arch-showcase/2014/04/30/volvo-eicher-corporate-headquarter-in-gurgaon-india-by-romi-khosla-design-studios/).
Skyview corporate park, 2017. Image gallery. (Retrieved October 23, 2017, from sky-viewcorporatepark.com: http://www.skyviewcorporatepark.com).
Srinivas, S., 2005. Green Building Congress 2005. IGBC Green Habitate, A newsletter onGreen Building, October. (Retrieved November 22, 2017, from https://igbc.in/igbc/
9385
51.8545.25
96
112
13 10 8.8 9.2 7
16.9
6458
32.2527
7179
0
20
40
60
80
100
120
ITC WIPRO INFOSYS IPB VOLVO SKYVIEW
Kwh/
m²/
year
Energy Performance of Selected energy e cient o ce buildings
Energy Performance Index
Ligh ng performace index
HVAC performace index
Fig. 17. Energy performance of the selected green-rated buildings.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
518
http://refhub.elsevier.com/S0038-092X(18)31036-3/h0005http://refhub.elsevier.com/S0038-092X(18)31036-3/h0005https://doi.org/10.22214/ijraset.2017.11049http://refhub.elsevier.com/S0038-092X(18)31036-3/h0015http://refhub.elsevier.com/S0038-092X(18)31036-3/h0015http://refhub.elsevier.com/S0038-092X(18)31036-3/h0015http://refhub.elsevier.com/S0038-092X(18)31036-3/h0015http://refhub.elsevier.com/S0038-092X(18)31036-3/h0015http://refhub.elsevier.com/S0038-092X(18)31036-3/h0015https://beeindia.gov.in/sites/default/files/ECBC%202016_Draft_V8.pdfhttps://beeindia.gov.in/sites/default/files/ECBC%202016_Draft_V8.pdfhttp://www.des-dev.co.in:%20http://www.des-dev.co.in/project_detail.php?subcat=1%26pid=57http://www.des-dev.co.in:%20http://www.des-dev.co.in/project_detail.php?subcat=1%26pid=57http://www.eco3.org/wp-content/plugins/http://www.grihaindia.org/images/casestudies/pdf/Indira-Paryavaran-Bhawani.pdfhttp://www.grihaindia.org/images/casestudies/pdf/Indira-Paryavaran-Bhawani.pdfhttp://grihaindia.org/images/casestudies/pdf/Infosys-hyderabad.pdfhttp://grihaindia.org/images/casestudies/pdf/Infosys-hyderabad.pdfhttp://high-performancebuildings.org/case_study_ECBC_comp_gurgaon.phphttp://eprints.uthm.edu.my/1274/1/24_Pages_from_AN_EVALUATION_OF_BIOCLIMATIC_HIGH_RISE_OFFICE_BUILDINGS_IN_A_TROPICAL_CLIMATE_ENERGY.pdfhttp://eprints.uthm.edu.my/1274/1/24_Pages_from_AN_EVALUATION_OF_BIOCLIMATIC_HIGH_RISE_OFFICE_BUILDINGS_IN_A_TROPICAL_CLIMATE_ENERGY.pdfhttp://eprints.uthm.edu.my/1274/1/24_Pages_from_AN_EVALUATION_OF_BIOCLIMATIC_HIGH_RISE_OFFICE_BUILDINGS_IN_A_TROPICAL_CLIMATE_ENERGY.pdfhttp://www.glazette.com/upload/resources/tb_90520091157467157.PDFhttp://www.glazette.com/upload/resources/tb_90520091157467157.PDFhttps://www.zingyhomes.com/project-detail/romi-khosla_8736/volvo-eicher-headquarter-gurgaon/https://www.zingyhomes.com/project-detail/romi-khosla_8736/volvo-eicher-headquarter-gurgaon/http://www.moef.nic.in/ipb/home1.htmhttp://smartcities.gov.in/upload/uploadfiles/files/SmartCityGuidelines(1).pdfhttp://smartcities.gov.in/upload/uploadfiles/files/SmartCityGuidelines(1).pdfhttp://refhub.elsevier.com/S0038-092X(18)31036-3/h0075http://mnre.gov.in/file-manager/akshay-urja/november-december-2014/EN/26-31.pdfhttp://mnre.gov.in/file-manager/akshay-urja/november-december-2014/EN/26-31.pdfhttps://doi.org/10.3992/jgb.11.1.134.1https://doi.org/10.3390/su9040623https://doi.org/10.3390/su9040623https://ebuild.in/volvo-eicher-headquarters-gurgaon-romi-khosla-design-studiohttps://ebuild.in/volvo-eicher-headquarters-gurgaon-romi-khosla-design-studiohttp://www.beepindia.org/sites/default/files/L5%20-%20Case%20study%20on%20radiant%20buildings%20-%20Infosys.pdfhttp://www.beepindia.org/sites/default/files/L5%20-%20Case%20study%20on%20radiant%20buildings%20-%20Infosys.pdfhttp://www.beepindia.org/sites/default/files/L5%20-%20Case%20study%20on%20radiant%20buildings%20-%20Infosys.pdfhttp://www.greenbuildingcongress.com/site/.../Mr_Guruprakash_Sastry_Infosys.pdfhttp://www.greenbuildingcongress.com/site/.../Mr_Guruprakash_Sastry_Infosys.pdfhttps://www10.aeccafe.com/blogs/arch-showcase/2014/04/30/volvo-eicher-corporate-headquarter-in-gurgaon-india-by-romi-khosla-design-studios/https://www10.aeccafe.com/blogs/arch-showcase/2014/04/30/volvo-eicher-corporate-headquarter-in-gurgaon-india-by-romi-khosla-design-studios/http://www.skyviewcorporatepark.comhttps://igbc.in/igbc/html_pdfs/newsletter/Green%20Habitat%20October%202005.pdf
-
html_pdfs/newsletter/Green%20Habitat%20October%202005.pdf).Tahir, M.Z., Nawi, N.M., Rajemi, M.F., 2015. Building energy index: a case study of three
government office buildings in Malaysia. Adv. Sci. Lett. 21 (6), 1799–1802. https://doi.org/10.1166/asl.2015.6239.
The 3C company, 2017. Executed Projects: Wipro Technologies, Gurgaon. (Retrieved
April 9, 2017, from The 3C company: http://www.the3c.in/wipro-technologies.htm).Zhang, K., Zhu, N., 2013. Comparison and analysis of energy consumption of energy
effiecient office buildings in different climate regions in China: case studies. Front.Energy 7 (30), 399–405. https://doi.org/10.1007/s11708-013-0260-z.
F. Bano, V. Sehgal Solar Energy 176 (2018) 506–519
519
https://igbc.in/igbc/html_pdfs/newsletter/Green%20Habitat%20October%202005.pdfhttps://doi.org/10.1166/asl.2015.6239https://doi.org/10.1166/asl.2015.6239http://www.the3c.in/wipro-technologies.htmhttps://doi.org/10.1007/s11708-013-0260-z
Evaluation of energy-efficient design strategies: Comparison of the thermal performance of energy-efficient office buildings in composite climate, IndiaIntroductionMethodologySelection criteria for the case studiesCase studiesITC Green Centre, GurgaonWipro Technologies, GurgaonInfosys, HyderabadVolvo-Eicher Corporate Headquarters (VECH), GurgaonIndira Paryavaran Bhawan (IPB), New DelhiSkyview Corporate Park, Gurgaon
Comparison of the design strategies used in the selected office buildings for energy efficiencyHVAC loadBuilding plan configurationShaded energy-efficient building envelopeMixed-mode ventilation system
Lighting loadFixtures and equipmentComparison of the EPI of the selected buildings
ConclusionsConflict of interestReferences