ethernetethernet digital i/o digital i/o digital i/o...
TRANSCRIPT
Infosystem®
Copyright © 2003~2015
Infosystem Technology Corporation, Ltd.
2F, No. 57, Lane 53, Dongnan St.
Hsinchu, Taiwan 300, R.O.C.
TEL: +886-3-562-7187
FAX: +886-3-561-1435
Service E-mail: [email protected]
Web page URL:http://www.infosystem.com.tw
EEIIOO--DD --221100MMLL
User ManualUser ManualUser ManualUser Manual
Version 1.0Version 1.0Version 1.0Version 1.0
Infosystem Technology Corporation, Ltd.Infosystem Technology Corporation, Ltd.Infosystem Technology Corporation, Ltd.Infosystem Technology Corporation, Ltd.
EthernetEthernetEthernetEthernet Digital I/O Digital I/O Digital I/O Digital I/O
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Index 1. Index ............................ 1.
2. Disclaimers .......................... 3.
A. Warranty ......................... 4.
B. Trademark ........................ 4.
3. Product Information ....................... 5.
A. Introduction ........................ 5.
B. Features ......................... 6.
4. Exterior ........................... 7.
A. Overview ......................... 7.
B. Front Panel ........................ 8.
C. Dimension ........................ 8.
5. Specifications ......................... 9.
A. Basic Specifications ..................... 9.
B. Digital Input Specification ................... 10.
C. Digital Output Specification .................. 11.
D. LED Indicator and Switch Description .............. 12.
E. Wiring ......................... 14.
F. ModBus Holding Register Definition ............... 17.
6. Software Installation ....................... 19.
A. Install ......................... 19.
- Step 1: Insert the CD and click the button ........... 19.
- Step 2: Click the Link of the Page ............. 20.
- Step 3: Press Next to Continue .............. 21.
- Step 4: Decide the Application Directory ........... 22.
- Step 5: Create the Directory if not existent .......... 23.
- Step 6: Create Program’s Shortcut ............. 24.
- Step 7: Decide if Desktop icon needed ............ 25.
- Step 8: Press Install to start installation ........... 26.
- Step 9: Process Installations ............... 27.
- Step 10: Finish Installation ............... 28.
1.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
B. Uninstall ......................... 29.
- Step 1: Execute Uninstall Program ............. 20.
- Step 2: Click “Yes” to process ............... 30.
- Step 3: Finished .................... 30.
7. Configuration.......................... 31.
A. By Browser ........................ 31.
- Step 1: Ready to login ................. 31.
- Step 2: Configure your parameters ............. 32.
- Step 3: Finish and reboot ................ 33.
B. By Setup Tools ...................... 34.
- Step 1: Searching the devices ............... 34.
- Step 2: Double click the selected item ............ 34.
- Step 3: Configure and update your parameters ......... 35.
C. By Direct Broadcast Commands ................ 36.
- Command List A .................... 36.
- Command List B ................... 37.
- Command List C ................... 38.
8. Application Notes ........................ 39.
A. Description ....................... 39.
B. Disable Firewall of Windows XP SP2 .............. 39.
- Step 1: Execute "Windows Firewall" ............. 39.
- Step 2: Close the Firewall ................ 40.
C. Make Program exception for Firewall ............... 41.
- Step 1: Choose "Exception" ............... 41.
- Step 2: Add on New Program ............... 42.
- Step 3: Allow "Accept Any Computer" ............ 43.
- Step 3: Finished .................... 44.
2.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Disclaimers
The information in this manual has been carefully checked
and is believed to be accurate. Infosystem Technology
Corporation, Ltd. assumes no responsibility for any
infringements of patents or other rights of third parties,
which may result from its use.
Infosystem assumes no responsibility for any inaccuracies
that may be contained in this document. Infosystem makes
no commitment to update or to keep current the
information contained in this manual.
Infosystem reserves the right to make improvements to this
document and/or product at any time without notice.
No part of this publication may be reproduced, stored in a
retrieval system, or transmitted in any form of or by any
means, electronic, mechanical, photocopying, recording, or
otherwise, without the prior written permission of
Infosystem Technology Corporation, Ltd.
Copyright © 2003 - 2005
Infosystem Technology Corporation, Ltd.
All rights reserved. Printed in Taiwan.
3.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Warranty
All products manufactured by Infosystem are warranted
against defective materials for a period of one year from the
date of delivery to the original purchaser.
Trademark
The names used for identification only maybe registered
trademark of their respective companies.
4.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Product Information
A. Introduction
EIO is an I/O controller product with Ethernet on its
data communication and makes data acquisition easier
through ModBus/TCP protocol on an existing Ethernet
network. For different conditions, EIO basically has
been design into four models. EIO-R is Relay I/O
Controller. EIO-A is Analog I/O. EIO-D is Digital I/O.
And EIO-T is Thermo Coupler I/O Controller. By using
these products, the controlling and monitoring of
distributed control system can easily be accomplished.
EIO-D-210ML uses 8051’s family microprocessor for
implementing Ethernet functions. It uses the state
machine to handle TCP/IP stack with most but limited
functions because of the limited resources.
EIO-D-210ML supports ARP, ICMP, TCP, UDP, IP,
DHCP-Client and even HTTP protocols. You can use
any browsers to set the parameters, or just use the
commands in console mode. With no doubt,
EIO-D-210ML will bring you the best integration in
your applications.
5.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Product Information
B. Features � Easy Configuration Setting
� Use Setup Tools to Configure the Settings
� Use HTTP, IE/Netscape Browser for Setting
� Good Security Concerned � Setup Login in Password Protect
� Access Password Protect
� High Reliability � Stable and Robust
� Working 24Hours per day
� Support Necessary Network Protocols � ARP, ICMP, TCP, UDP, IP, DHCP Client, HTTP
� Support ModBus Protocol � ModBus/TCP, ModBus/RTU, ModBus/ASCII
� Easy integration with HMI/SCADA or OPC Server
� High Reliability � Stable and Robust
� Working 24Hours per day
� Isolation � Photo Coupler Isolated Inputs
� Photo Coupler Isolated Outputs
� Input / Output � DC 24V Input x 12
� DC 24V Output x 6
6.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Exterior
A. Overview
Serial
PortDigital
Input
LED
Indicator
Digital Output DC 24V
Power InputDip Switch
Serial
PortDigital
Input
LED
Indicator
Digital Output DC 24V
Power InputDip Switch
7.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Exterior B. Front Panel
a. Connector 1 (CONN1)
b. Ethernet 10/100MBaseT RJ45 Connector
c. LED Indication
d. Connector 2 (CONN2)
C. Dimension
(UNIT: mm)4 xψ3.0
50.0
102.0
80.094.0
9.0
33.0
(UNIT: mm)4 xψ3.0
50.0
102.0
80.094.0
9.0
33.0
8.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Specifications
A. Basic Specifications
Entry Description
Communication Interface Ethernet 10/100M BaseT, RJ-45
Protocol
ARP, ICMP, TCP, UDP, IP, DHCP Client,
HTTP, Modbus/TCP Slave, Modbus/RTU,
Modbus/ASCII
Reset Built-in reset key to restore the defaults
Watch Dog Timer Built-in hardware auto reset function
Discrete I/O 10 points, DC 24V Input
8 points, DC 0.5A Output
Led Indication SYS x1 (Red), LINK x1 (Green)
Power Requirement 24V DC
Power consumption < 1W
Operation: 0ºC~+55º C (32ºF~+131ºF) Temperature
Storage: -20ºC~+70ºC (-4ºF~+158ºF)
Humidity 15% to 95% (non-condensing)
Dimension 100mm x 68mm x 25mm
Configuration Web Browser, Windows Utility via Ethernet
9.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Specifications
B. Digital Input Specifications
Entry Description
Number of Input Points 10 points
Isolated Method Photo Coupler
Rated Input Voltage 24V DC
Rated Input Current 7 mA
Operation Voltage Range 21.6V DC ~ 26.4V DC
Turn ON State 12V DC / 2 mA or higher
Turn OFF State 4V DC / 1 mA or lower
Input Impedance Approx. 3.9 KΩ
OFF � ON 8 msec or less (24 VDC) Response Time
ON � OFF 8 msec or less (24 VDC)
Common Terminal Arrangement 12 points / common
Internal Current Consumption MAX. 100 mA (type, all points ON)
10.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Specifications
C. Digital Output Specifications
Entry Description
Number of Input Points 8 points
Isolated Method Photo Coupler
Rated Load Voltage 24V DC
Operation Voltage Range 21.6V DC ~ 26.4V DC
Type NPN / Sink
Max. Load Current 0.5 A/pt
Leakage Current at OFF Circuit 0.1 mA or less
Max. Voltage Drop at ON Circuit 1.5V or less
OFF � ON 8 msec or less Response Time
ON � OFF 8 msec or less
Common Terminal Arrangement 6 points / common
Voltage 24V DC (21.6V DC ~ 26.4V DC) External Power Supply
Current 100 mA
International Current Consumption 100 mA (type, all points on)
11.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Specifications
D. LED Indicator and Switch Description – Box View –
12.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Specifications
D. LED Indicator and Switch Description – Description – LED Indicator:
LED Description SYS The SYS LED blinks at a rate of 1.5Hz and indicating normal work.
LINK If ON, the Ethernet connection is activated.
13.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Specifications
E. Wiring
Users may refer to the following diagram to connect the
external wiring for the EIO-D-210ML module.
Front Panel PIN Definition –
14.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Specifications
E. Wiring – Equivalent Input Circuit –
15.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Specifications
E. Wiring – Equivalent Output Circuit –
16.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Specifications
F. ModBus Holding Register Definition
The discrete I/O points of the EIO-D-210ML can easily be controlled and
monitored through Modbus protocol. The Modbus address mapping with
discrete I/O is described as the followings.
– Output Address – The 8-points digital output of EIO-D-210ML is mapped with the Modbus
Coil Status “00001 ~ 00008”..
Output Status (Coil Status, ON=1, OFF=0)
Address Output
00001 DO1, OUT1
00002 DO2, OUT2
00003 DO3, OUT3
00004 DO4, OUT4
00005 DO5, OUT5
00006 DO6, OUT6
00007 DO7, OUT7
00008 DO8, OUT8
17.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Specifications
F. ModBus Holding Register Definition
– Input Address – The 10-points digital input of EIO-D-210ML is mapped with the Modbus
Input Status “10001 ~ 10010”..
Input Status (Input Status, High=1, Low=0)
Address Input
10001 DI1, IN1
10002 DI2, IN2
10003 DI3, IN3
10004 DI4, IN4
10005 DI5, IN5
10006 DI6, IN6
10007 DI7, IN7
10008 DI8, IN8
10009 DI9, IN9
10010 DI10, IN10
18.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Software Installation
A. Installation
Step 1: Insert the CD and click the button
The Software Installation CD that came with EIO-A-200 will
automatically be run after inserting it into the CD-ROM drive. Click
the “Ethernet converter Setup Utilities” button will bring the
installation page out,
Figure1. Software Install CD Auto-Run Screen Shot
19.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Software Installation
A. Installation
Step 2: Click the Link of the Page
Click the Link of the Page to run the Ethernet Converter Setup Tools
Installation Software.
Figure2. Ethernet Converter Setup Tools Page
20.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Software Installation
A. Installation
Step 3: Press Next to Continue
Figure3. Installation Welcome Message
– 3. Connect to Configuration Mode –
21.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Software Installation
A. Installation
Step 4: Decide the Application Directory
Figure4. Decide the Application Directory
22.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Software Installation
A. Installation
Step 5: Create the Directory if not existent
Figure5. Create Application Directory
23.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Software Installation
A. Installation
Step 6: Create Program’s Shortcut
Figure6. Shortcut Creation
24.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Software Installation
A. Installation
Step 7: Decide if Desktop icon needed
Figure7. Desktop Icon Creation
25.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Software Installation
A. Installation
Step 8: Press Install to start installation
Figure8. Review the Installation Settings
26.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Software Installation
A. Installation
Step 9: Process Installations
Figure9. Installing
27.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Software Installation
A. Installation
Step 10: Finish Installation
Figure10. Installation Finished
28.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Software Installation
B. Uninstall
Step 1: Execute Uninstall Program
Uninstall Program is located at the application directory named
“Uninstall Ethernet Converter Setup”. Execution of it could let the
Ethernet Converter Setup Tools clearly be removed.
Figure11. Decide the Application Directory
29.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Software Installation
B. Uninstall
Step 2: Click “Yes” to process
Figure12. Process Uninstall
Step 3: Finished
Figure12. Process Uninstall
30.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Configuration
A. By Browser
Step 1: Ready to login.
31.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Configuration
A. By Browser
Step 2: Configure your parameters.
32.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Configuration
A. By Browser
Step 3: Finish and reboot.
33.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Configuration
B. By Setup Tools
Step 1: Searching the devices. Step 2: Double click the selected item.
34.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Configuration
B. By Setup Tools
Step 3: Configure and update your parameters.
35.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Configuration
C. By Direct Broadcast Commands
It needs broadcasting to handle all the configurations and it allows users to code their own application software.
– Command List A – User Level – – Command Description Notes
Purpose For Broadcast search
Syntax X <magic code>
Magic code 99.130.83.99
Return AX <MAC>/<IP>/<Device ID>
Send X 99.130.83.99
X or x
Example Back AX 0.128.200.255.251.242/192.168.1.1/1
Purpose Get all the parameters of the WM-110
Syntax G <MAC>/<IP>/<Setup Password>
Return All the parameters of the WM-110
Send G 0.128.200.255.251.242/192.168.1.1/123
CG for cancel
G or g
Example Back
AG<All Messages>
36.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Configuration
C. By Direct Broadcast Commands
User Level: For General Users Admin Level: For Factory Default Setting
– Command List B – User Level –
Command Description Notes
Purpose Set the parameters of WM-110
Syntax S <MAC>/<IP>/<Password>/<Parameter>/<Value>
A for accept Return
C for cancel
Send S 0.128.200.255.251.242/192.168.1.1/123/IP/192.168.1.2
S
Example Back A or C
Purpose Reboot WM-110
Syntax R <MAC>/<IP>/<Setup Password>
AR for accept Return
CR for cancel
Send R 0.128.200.255.251.242/192.168.1.1/123
R
Example Back AR or CR
37.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Configuration
C. By Direct Broadcast Commands
User Level: For General Users Admin Level: For Factory Default Setting
– Command List C – Admin Level –
Command Description Notes
Purpose Set MAC address of WM-110 then reboot automatically
Syntax M <Old MAC>/<New MAC>/<Factory Password>
AM for accept Return
CM for cancel
Send S 0.128.200.255.251.242/0.128.200.255.251.243/123
M
Example Back ‘A’ or ‘C’
Purpose Set IP for Factory settings
Syntax I <MAC>/<New IP>/<Factory Password>
AI for accept Return
CI for cancel
Send I 0.128.200.255.251.242/192.168.1.1/123’
I
Example Back AR or CR
38.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Application Notes
A. Description:
Firewall will make the program off normal, so one might choose the following solutions to Firewall program, “Disable” or “Exception”.
B. Disable Firewall of Windows XP SP2.
Step 1: Execute "Windows Firewall" Execute “Windows Firewall” in Control Panel.
39.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Application Notes
B. Disable Firewall of Windows XP SP2.
Step 2: Close the Firewall Choose “Close” to close firewall.
40.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Application Notes
C. Make Program exception for Firewall
Step 1: Choose "Exception" Choose “Exception” in Firewall Program. And add on new program of Setup Tools.
41.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Application Notes
C. Make Program exception for Firewall
Step 2: Add on New Program and Selection Choose “Setup Tools” to make it as an exception.
42.
Infosystem®
Digital Ethernet I/O Module EIO-D-210ML
(Preliminary Version)
Application Notes
C. Make Program exception for Firewall
Step 3: Allow "Accept Any Computer" Allow “Accept Any Computer” to finish exception.
43.
Infosystem®
Digital Ethernet I/O Module EIO-D_210ML
(Preliminary Version)
Application Notes
C. Make Program exception for Firewall
Step 4: Finished Finish Exception.
44.