e.r.s. groot, the netherlands, session 1, block 1.1: switchgear barcelona 12-15 may 2003 1...

16
1 E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 Successful implemented Condition Based Maintenance for switchgear Presenter: E.R.S. Groot Session No 1, Paper No 14 Edwin R.S. GROOT Nuon InfraCore Edward GULSKI Delft University Abe van DAM Eneco Netbeheer Frank J. WESTER Nuon InfraCore The Netherlands

Upload: branden-davidson

Post on 17-Jan-2016

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

1E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

Successful implemented Condition Based Maintenance for switchgear

Presenter: E.R.S. Groot

Session No 1, Paper No 14

Edwin R.S. GROOTNuon InfraCore

Edward GULSKIDelft University

Abe van DAMEneco Netbeheer

Frank J. WESTER Nuon InfraCore

The Netherlands

Page 2: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

2E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

A guided tour through the implementation process of CBM

(step by step)

based on questions and problems we dealed with

Page 3: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

3E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

Where did we start?? (more then 60 different type of switchgear)

Based on the selection criteria:

• Current maintenance costs

• Current outage time for maintenance

• Risk for maintenance induced failures

• Population size

• Age and expected lifetime

• Current failure behaviour and frequency

…….we started with a minimum oil breaker

Page 4: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

4E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

What are critical components of this switchgear ??

We applied an FMECA approach and weighted each component

• Failure frequency (score 0,1,2)

• Impact of failure on energy supply (score 1,2,3)

• Corrective costs (score 1,2,3)

• Environmental impact (score 1,2)

Page 5: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

5E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

FMECA register (screen dump)

Page 6: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

6E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

The outcome of the FMECA exercise resulted in a new

optimised maintenance program …..

A mixture of maintenance, inspections and measurement activities were focused on critical components only

This optimised maintenance program resulted in the first cost reduction of 29%

Page 7: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

7E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

How do we:- control and update the new maintenance program in the field- support the electrician with actual normsand instructions- guaranty the continuation of feed back of field experience

Page 8: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

8E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

Therefore we developed the Inspector software tool:

Page 9: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

9E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

Field support with actual norms and instructions

Page 10: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

10E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

How do we handle the increased amount of data like:

• Measurement results

• Inspection results

• Maintenance information

• Failure information

Page 11: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

11E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

We developed the I-Core database

typetime

analysis

Page 12: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

12E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

The I-Core database for:

• storage of data (measurement and inspection results, failure information etc)

• optimising norms and criteria

• research of aging mechanisms

• improvement and optimisation of the condition based maintenance program

Page 13: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

13E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

Example: correlation between moisture level in oil and aging of coqolite

0

5

10

15

20

25

30

35

40

0 5 10 15 20 25 30 35

Moisture level (ppm)

Tang

ensD

elta

(%)

Coqolite is good

Coqolite has to be dried

Coqolite is irreparable

Page 14: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

14E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

Example: norm and criteria optimisationSwitch of velocity

1,5 2,0 2,5 3,0 3,5 4,0 4,5

Velocity (m/s)

Ch

anc

e d

en

sit

y

Probability density curve of switching velocity

0,0

0,5

1,0

1,5

2,0

2,5

3,0

3,5

0,0 5,0 10,0 15,0 20,0 25,0

Contactpressure (kg)

Velo

cit

y (

m/s

)

Correlation between contact pressure and velocity

Norm definition for velocity based on large population measured data

Define a maximum norm for contactpressure based on influence on velocity

Page 15: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

15E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

The outcome of the data analyses resulted in a further

optimised maintenance program …..

The optimisation of both the mixture of maintenance and measurement

activities and frequency resulted in a total cost reduction of 35%

Page 16: E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR Barcelona 12-15 May 2003 1 Successful implemented Condition Based Maintenance for switchgear

16E.R.S. Groot, The Netherlands, Session 1, Block 1.1: SWITCHGEAR

Barcelona 12-15 May 2003

Conclusion

• Good experiences with CBM

• Still implemented it succesfully for other type of switchgear

• Growing importance for condition data (not only as a foundation for CBM)