EP.S3100 EP.N5100 EP.S3200 EP.N5200 EP.S3400 EP.N5400
Wiring Guide
Version 1.14 Last Updated: 14-03-2013
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
1
Note: N5100, N5200 and N5400 are network enabled controllers S3100, S3200 and S3400 are serial enabled controllers N5100 and S3100 have 4 inputs and 2 Outputs (2 Relays – Support 2 Doors, 2 Readers) N5200 and S3200 have 8 inputs and 4 outputs (4 Relays - Support 2 Doors, 2 Readers) N5400 and S3400 have 8 inputs and 4 outputs (4 Relays – Support 4 Doors, 4 Readers) N5200, S3200, N5400 and S3400 support unlimited access level Only firmware version 3.00.10.08 and above support features above N5100 and S3100 not support unlimited access level S3100, S3200, S3400, N5100, N5200 and N5400 support HID (AGK00, 09, 10, 11, 14, 19, 20), Wiegand Multi-Bit, Keyed Card + Pin Only firmware version 3.00.10.08 and above support features above N5100, N5200 and N5400 support AES Encryption Only firmware version 3.00.10.08 and above support AES Encryption S3200, S3400, N5200, N5400 support event trigger Only firmware version 3.00.10.08 and above support event trigger See http://www.entrypass.net/ for updates, revisions, and download the latest installation manual Platform1 version 3 support 6 and 10 digits format For existing site, P1 will detect its card database to determine 6 or 10 digits; For new site, user can change the digits as long as the card database is empty Please refer to separate EntryPass Platform1 User Manual for detail operation help. The Official EntryPass Platform1 User Manual can be downloaded from our website under “Download” section
Technical Support If you cannot find the answer to your question in this manual or in the Help files, we recommend you contact your system installer. Your installer is familiar with your system configuration and should be able to answer any of your questions. Should you need additional information, please call our Technical Support Help Desk, Monday to Friday 9:00 AM to 6:00 PM (GMT +8:00) Method Details Phone + 60 (3) - 8068 1929 Fax + 60 (3) - 8068 1922 Internet www.entrypass.net Email [email protected]
Before you begin…
2
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
CAUTION Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire. To prevent a risk of explosion do not pry the battery out with a metal or conductive tool.
Considerations Prior to Installation
Preparing Your EntryPass Controllers EntryPass controller contains numerous delicate electronic circuits and components which can become damaged as a result of electrostatic discharge (ESD). Thus, prior to installation, please follow the instruction below: •Observe precautions while handling the circuit board assembly by using proper grounding straps and handling precautions at all •Visually ensure no onboard parts is broken, damage or contains burn mark •Do not turn on the power supply until you completed all wiring and external add on devices installations
Instances of Non-Warranty •Damage due to natural disaster, accident or human cause. •Damage as a result of violating the conditions recommended in the user manual •Damage due to improper installation •Damage due to use of uncertified components •Damage due to use exceeding the permitted parameters
3
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Component Description
4
Relay 3 Relay 4 Supply Voltage Selector Relay LEDs
Supply Voltage Selector
Relay LEDs
Buzzer Relay 1 Relay 2 Buzzer ON/OFF
MCU Battery
Address Dip Switch
Cold Start Switch
Reset Switch
COM Rx/Tx LEDs
RS232 COMs
Heartbeat LED
RS485 COMs
Network Port
Cold Start, Factory Default and AES Hard reset Selection Jumper
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Legend Description
5
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Lower Connector
Reader 1 Input 1,2 Relay 1 Relay 212V/5V
Voltage
supply
Reader 2 Input 3,4RS485
Com3
RS485
Com2
RS485
Com1
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
O1D0 - Reader 2 Data 0 Input O1D1 - Reader 2 Data 1 Input LED2 - Reader 2 LED BUZ2 - Reader 2 Buzzer IN3 - Input 3 IN4 - Input 4 GND - Inputs Ground C3- - RS485 COM3 (-) Connection C3+ - RS485 COM3 (+) Connection C2- - RS485 COM2 (-) Connection C2+ - RS485 COM2 (+) Connection C1- - RS485 COM1 (-) Connection C1+ - RS485 COM1 (+) Connection
I1D0 - Reader 1 Data 0 Input I1D1 - Reader 1 Data 1 Input LED1 - Reader 1 LED BUZ1 - Reader 1 Buzzer IN1 - Input 1 (Default: Door Sensor) IN2 - Input 2 (Default: Exit Push Button) GND - Inputs Ground NC1 - Relay 1 Normally Close Connection COM1 - Relay 1 Common Input NO1 - Relay 1 Normally On Connection NC2 - Relay 2 Normally Close Connection COM2 - Relay 2 Common Input NO2 - Relay 2 Normally ON Connection VR1+ - Supply Voltage Positive Connection (12V/5V) GND - Supply Voltage Negative/Ground Connection
For VR1+ to supply 12V, please make sure JP6 is at 1-2 pins For VR1+ to supply 5V, please make sure JP6 is at 2-3 pins
Legend Description
6
I2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Upper Connector
Input 5, 6 Relay 3 Relay 4
12V/5V
Voltage
supply Input 7, 8Reader 3 Reader 4
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
I2D0 - Reader 3 Data 0 Input I2D1 - Reader 3 Data 1 Input LED3 - Reader 3 LED BUZ3 - Reader 3 Buzzer IN5 - Input 5 IN6 - Input 6 NC3 - Relay 3 Normally Close Connection COM3 - Relay 3 Common Input NO3 - Relay 3 Normally ON Connection NC4 - Relay 4 Normally Close Connection COM4 - Relay 4 Common Input NO4 - Relay 4 Normally ON Connection
VR2+ - Supply Voltage Positive Connection (12V/5V) GND - Supply Voltage Negative/Ground Connection O2D0 - Reader 4 Data 0 Input O2D1 - Reader 4 Data 1 Input LED4 - Reader 4 LED BUZ4 - Reader 4 Buzzer IN7 - Input 7 IN8 - Input 8 IN9 - Reserved GND - Inputs Ground
Upper connector only applicable to S3200, S3400, N5200 and N5400 Reader 3 and 4 only applicable to S3400 and N5400
For VR2+ to supply 12V, please make sure JP6 is at 1-2 pins For VR2+ to supply 5V, please make sure JP6 is at 2-3 pins
Legend Description
7
+12V - Power Supply Positive 12V DC -12V/GND - Power Supply Ground ETH - Power Supply Earthing ACC - AC Fail Monitoring BAT/BS - Backup Battery Monitoring
+12V-12V/
GND ETH ACCBAT/
BS
Power Supply Connector
BAT/BS (Backup Battery Monitoring) point will monitor the backup battery voltage which will supply power to the board when AC power is cut off.
The minimum voltage for cutoff while using backup battery is 8.4V
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Power Supply Unit Specification
8
Power Supply Unit Specification: • Switching Power Supply • 12V DC • 3 Amp (Minimum)
ENTRYPASS
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Connecting the Lock (Normally Closed - NC), Breakglass and Keyswitch
9
- +
NC1 COM1
Emergency
Breakglass
Emergency
Keyswitch
Electro-Magnetic Lock or Drop Bolt–+
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
12V+
GNDPSU
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF It is advisable to connect EM lock COM to 12V+ of PSU (Power Supply Unit)
Connecting the Striker Lock or Drop Bolt (Normally Open - NO)
10
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF
- +
NO
1
CO
M1
Striker Lock or Drop Bolt–+
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
12V+
GNDPSU
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
CO
M1
-+
NC
2
CO
M2
Emergency
Breakglass 1
Emergency
Keyswitch 1
Electro-Magnetic Lock 1
Electro-Magnetic Lock 2
+-
-+
-+
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
NC
1
12V+
GND
PSU
Emergency
Breakglass 2Emergency
Keyswitch 2
Connecting the Locks (NC), Breakglasses and Keyswitches (2 Doors Mode Only)
11
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
CO
M1
-+
NO
2
CO
M2
Striker Lock or Drop Bolt 1
Striker Lock or Drop Bolt 2
+-
-+
-+
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
NO
1
12V+
GND
PSU
Connecting the Locks (NO) (2 Doors Mode Only)
12
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Connecting the Locks (NC), Breakglasses and Keyswitches (4 Doors Mode Only)
13
CO
M3
-+
NC
4
CO
M4
Emergency
Breakglass 4
Emergency
Keyswitch 4
Electro-Magnetic Lock 4
Emergency
Breakglass 3Emergency
Keyswitch 3
Electro-Magnetic Lock 3
+-
-+
-+
NC
3
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
12V+
GND
PSU
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF NC1 and NC2 connection for 4 Doors Mode please refer to 2 Doors Mode NC connection
4 Doors Mode only applicable for N5400 and S3400
Connecting the Locks (NO) (4 Doors Mode Only)
14
CO
M3
-+
NO
4
CO
M4
Striker Lock or Drop Bolt 4
Striker Lock or Drop Bolt 3
+-
-+
-+
NO
3
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
12V+
GND
PSU
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF NO1 and NO2 connection for 4 Doors Mode please refer to 2 Doors Mode NO connection
4 Doors Mode only applicable for N5400 and S3400
Connecting the Door Sensor and Door Release Button/Push Button
15
Push Button
IN1
IN2
GN
D
Door Sensor
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
16
Connecting the Door Sensors and Door Release Buttons/Push Buttons (2 Doors Mode Only)
Push Button 1
IN1
IN2
GN
D
Door Sensor 1
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
IN3
IN4
GN
D
Push Button 2Door Sensor 2
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
17
Connecting the Door Sensors and Door Release Buttons/Push Buttons (4 Doors Mode Only)
IN5
IN6
GN
D
Push Button 3Door Sensor 3
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
IN7
IN8
GN
D
Push Button 4Door Sensor 4
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
IN1,2,3,4 Connections for 4 Doors Mode please refer to 2 Doors Mode IN1,2,3,4 connections 4 Doors Mode only applicable for N5400 and S3400
Connecting the Readers – MiNi as Reader
18
To configure MINI as a READER Mode, press: •F1 •123456 •01 Enter •01 Enter •05 Enter •1 Enter •ESC x3
Re
ad
er
1
Re
ad
er
2
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Re
ad
er
4
Re
ad
er
3
D0 - Orange D1 - Yellow
12V+ - Red
GND - Black
D0 - Orange D1 - Yellow
GND - Black
12V+ - Red
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Reader 3 and Reader 4 only applicable for N5400 and S3400
Connecting the Readers – 3rd Party Reader
19
Re
d (
VR
1+
)
Bla
ck (
GN
D)
Re
ad
er
1
Re
ad
er
2
I1D
0
I1D
1
LE
D1
BU
Z1
O1
D0
O1
D1
LE
D2
BU
Z2
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Re
ad
er
3
Re
ad
er
4
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Reader 3 and Reader 4 only applicable for N5400 and S3400
Connecting the Readers – Suprema Biometric Devices (BioLite Net)
20
Bio
Lite
Ne
t 2
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Bio
Lite
Ne
t1B
ioL
ite
Ne
t 3
Bio
Lite
Ne
t 4
12V+ (Red)
GND (Black)
Wiegand GND (Black)
C3+ (Blue with White String)
C3- (Yellow with Black String)
12V+ (Red)
GND (Black)
Wiegand GND (Black)
C3+ (Blue with White String)
C3- (Yellow with Black String)
Da
ta1
(Wh
ite
)
Da
ta0
(Gre
en)
Da
ta1
(Wh
ite
)
Da
ta0
(Gre
en)
GND C3- C3+ C2- C2+ C1- C1+
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Reader 3 and Reader 4 only applicable for N5400 and S3400
Connecting the Readers – Suprema Biometric Devices (BioEntry Plus)
21
Bio
En
try P
lus 2
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Bio
En
try P
lus 1
Bio
En
try P
lus 3
Bio
En
try P
lus 4
12V+ (Red)
GND (Black)
C3+ (Blue)
C3- (Yellow)
12V+ (Red)
GND (Black)
Wiegand GND (Black)
C3+ (Blue)
C3- (Yellow)
Da
ta1
(Wh
ite
)
Da
ta0
(Gre
en)
Da
ta1
(Wh
ite
)
Da
ta0
(Gre
en)
GND C3- C3+ C2- C2+ C1- C1+
Wiegand GND (Black)
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Reader 3 and Reader 4 only applicable for N5400 and S3400
Connecting to Another Controller for Cross-Board Interlock Purpose
22
Re
lay O
utp
ut
(NC
)
Re
lay O
utp
ut
(CO
M)
Re
lay O
utp
ut (N
C)
Re
lay O
utp
ut (C
OM
)
Inp
ut
(IN
)
Inp
ut (G
ND
)
Inp
ut (I
N)
Inp
ut (G
ND
)
Controller 1 Controller 2
Maximum 2 controllers can be connected each others for cross-board interlock purpose An interlock input and interlock relay need to be assigned using Platform1 for cross-board interlock on each controller Please configure the interlock input as ‘Open Trigger’ in Platform1 if interlock input is connected with NC relay output
Advisable to use analog input for detecting line open condition The cabling distance for cross-board interlock connection can up to 100 meter
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Connecting to the PC via Serial (RS-485)
23
….C
2-
C2
+
C2-
C2
+
C2-
C2
+
S3100 and S3200 (16)
Unit Address: 16
S3100 or S3200 (1)
Unit Address: 1
S3100 or S3200 (2)
Unit Address: 2
RS-485: 1000 meter (Maximum)
RS-232: 10 meter
EntryPass Platform1
Sserver Access Control System
PCC
(Communicator)
Rx
Tx
Po
we
r
RS
23
2
Serial connection (RS485) only applicable for maximum 16 sets S3100 or S3200 The serial address format in Platform1 is 255.255.255.X where X is unit address
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Connecting to the PC via Serial (RS-232)
24
S3100/S3200/S3400
Unit Address: 1
RS-232: 10 meter
EntryPass Platform1
Sserver Access Control System
1 2 3 4 5
6 7 8 9
JP4
Serial Port
DB9 Female
Connector
JP4
Serial connection (RS232) only applicable for a single S3100 or S3200 or S3400 The serial address format in Platform1 is 255.255.255.1
Connecting to the PC via Serial – Dip Switch Addressing Table
25
Switch 1 (1) Switch 2 (2) Switch 3 (4) Switch 4 (8) Switch 5 (16)
Address 01 ON OFF OFF OFF OFF
Address 02 OFF ON OFF OFF OFF
Address 03 ON ON OFF OFF OFF
Address 04 OFF OFF ON OFF OFF
Address 05 ON OFF ON OFF OFF
Address 06 OFF ON ON OFF OFF
Address 07 ON ON ON OFF OFF
Address 08 OFF OFF OFF ON OFF
Address 09 ON OFF OFF ON OFF
Address 10 OFF ON OFF ON OFF
Address 11 ON ON OFF ON OFF
Address 12 OFF OFF ON ON OFF
Address 13 ON OFF ON ON OFF
Address 14 OFF ON ON ON OFF
Address 15 ON ON ON ON OFF
Address 16 OFF OFF OFF OFF ON
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Each switch is represent by an address, the sum of the switch address will be the controller address The number in ( ) is the address of each individual switch of the dip switch
Example: To obtain Address 11, 1 + 2 + 8 = 11, So just switch on switch 1, 2, 4
Connecting to the PC via Network
26
….
N5100/N5200/N5400 (n)N5100/N5200/N5400 (1) N5100/N5200/N5400 (2)
EntryPass Platform1
Server Access Control System
….
Network Switch
Cat-5
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Network connection only applicable for N5100, N5200 and N5400 Factory default IP address for network controller is 192.168.1.100
Connecting to the Power Supply Unit
27
+12V
-12V
AC Fail (ACC)
Backup Battery Monitoring (BAT/BS)
Switching Mode
Power Supply Unit
(12V DV, 3A Minimum)
+12V
-12V
/
GN
DE
TH
AC
C
BA
T/
BS
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Performing Cold Start
28
Steps of performing cold start: 1. Please ensure that the jumper is inserted on JP1 1-2 2. Press and Hold COLD switch 3. Press RESET Switch and Release RESET switch 4. Release COLD switches when a long beeping sound heard
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
JP1Buzzer Jumper, JP2
Cold Start Initial Button, COLD
Reset Button, RESET
Advisable to perform cold start for the first time you turn on the power The buzzer will only beep if jumper is placed on (JP2) 1-2
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Performing Factory Default
29
Steps of performing Factory Default: 1. Please ensure that the jumper is inserted on JP1 7-8 2. Press and Hold COLD switch 3. Press RESET Switch and Release RESET switch 4. Release COLD switches when a long beeping sound heard
JP1Buzzer Jumper, JP2
Cold Start Initial Button, COLD
Reset Button, RESET
Factory Default will change the IP Address back to 192.168.1.100, Server IP to 192.168.1.254 and Port to 2020 For the network controller support AES Encryption feature, factory default will disable the AES feature
The buzzer will only beep if jumper is placed on (JP2) 1-2
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Performing AES Hard Reset
30
AES setting in the controller will be reset If the controller is connected with AES enabled Platfrom1, Platfrom1 will sync and update AES setting with the controller
Steps of performing AES Hard Reset: 1. Please ensure that the jumper is inserted on JP1 3-4 2. Press RESET Switch and Release RESET switch
JP1
Reset Button, RESET
Input Points Connection
31
Digital Input Connection By manufacturer default setting, IN1 is configured as Door Sensor and IN2 is configures as Push Button.
Analog/Supervised Input Connection A resistor of 3.6kΩ is required when user connect the device to the input connection.
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Input 3,4Input 1,2
IN1/2/3/4
GND
IN1/2/3/4
GND
NC Analog
Device
3600 Ohm
Input default is digital The Inputs are configurable to digital or analog using Platform1
A resistor of 3600 ohm is required when using analog input This system is not support NO Analog device due to the architecture
Upper Connector
I2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Input 5,6 Input 7,8
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Rx
Tx
Power
RS232
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Door SensorExit Button
PCC
Electro-magnetic Lock
Emergency
Breakglass
Emergency
Keyswitch
Entry Reader Exit Reader
Controller
Network Port
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Network
Switch
EntryPass
Platform1
Access Control Sytem
Power Supply Unit
ENTRYPASS
+12V -12V ETH ACC BAT
-+
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Complete Overview (In and Out Door Mode)
32
Serial Controller – S3100, S3200, S3400 Network Controller – N5100, N5200, N5400
Platform1 Profile: In and Out Readers
Complete Overview (2 Doors Mode)
33
Serial Controller – S3100, S3200, S3400 Network Controller – N5100, N5200, N5400
Platform1 Profile: 2 Doors
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Rx
Tx
Power
RS232
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Door Sensor 1Exit Button 1
Door Sensor 2Exit Button 2
PCC
EntryPass
Platform1
Access Control Sytem
Electro-magnetic Lock 2
Electro-magnetic Lock 1
Emergency
Breakglass 1
Emergency
Keyswitch 1
Emergency
Breakglass 2
Power Supply Unit
Reader 1 Reader 2
Controller
Network
Port
Network
Switch
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
ENTRYPASS
+12V -12V ETH ACC BAT
Emergency
Keyswitch 2
-+
-+
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Complete Overview (2x In and Out Doors Mode)
34
Platform1 Profile: 2x In and Out Doors
Serial Controller – S3400 Network Controller – N5400
Rx
Tx
Power
RS232
PCC
Controller
Network Port
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Network
Switch
EntryPass
Platform1
Access Control Sytem
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Power Supply Unit
ENTRYPASS
+12V
-12V
ET
HA
CC
BA
T
Reader 1 Reader 2
Reader 3 Reader 4
Door Sensor 1
&
Exit Button 1
Door Sensor 2
&
Exit Button 2
EM Lock 2
EM Lock 1
- +
-
+
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Complete Overview (4 Doors Mode)
35
Serial Controller – S3400 Network Controller – N5400
Platform1 Profile: 4 Doors
Rx
Tx
Power
RS232
PCC
Controller
Network Port
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Network
Switch
EntryPass
Platform1
Access Control Sytem
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Power Supply Unit
ENTRYPASS
+12V
-12V
ET
HA
CC
BA
T
Reader 1 Reader 2
Reader 3 Reader 4
Door Sensor 1
&
Exit Button 1
Door Sensor 2
&
Exit Button 2
Door Sensor 3
&
Exit Button 3
Door Sensor 4
&
Exit Button 4
EM Lock 3
EM Lock 4
EM Lock 1
EM Lock 2
Complete Overview (In and Out Barriers)
36
Rx
Tx
Power
RS232
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Entry Loop
Detector
Exit Loop
Detector
Entry Reader Exit Reader
PCC
Exit Barrier
Entry Barrier
Controller
Network
Port
Network
Switch
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
lyEntryPass
Platform1
Access Control Sytem
Power Supply Unit
ENTRYPASS
+12V -12V ETH ACC BAT
Serial Controller – S3100, S3200, S3400 Network Controller – N5100, N5200, N5400
Platform1 Profile: In and Out Barriers
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Complete Overview (2x In and Out Barriers)
37
Rx
Tx
Power
RS232
PCC
Controller
Network PortF
or S
eria
l Co
ntro
ller O
nly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Network
Switch
EntryPass
Platform1
Access Control Sytem
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Power Supply Unit
ENTRYPASS
+12V
-12V
ET
HA
CC
BA
T
Entry Reader 1 Exit Reader 1
Entry Reader 2 Exit Reader 2
Entry Barrier 1 Exit Barrier 1
Entry Barrier 2 Exit Barrier 2
Entry Loop Detector 2 Exit Loop Detector 2
Entry Loop Detector 1 Exit Loop Detector 1
Serial Controller – S3400 Network Controller – N5400
Platform1 Profile: 2x In and Out Barriers
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Exit Reader
Rx
Tx
Power
RS232
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Entry Reader
PCC
Bidirectional
Turnstile
EntryPass
Platform1
Access Control Sytem
Controller
Network
Port
Network
Switch
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Power Supply Unit
ENTRYPASS
+12V -12V ETH ACC BAT
IN
OUT
Complete Overview (In and Out Turnstiles Mode) – Bidirectional Turnstile
Serial Controller – S3100, S3200, S3400 Network Controller – N5100, N5200, N5400
Platform1 Profile: In and Out Turnstile
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
38
Complete Overview ( 2 Turnstiles Mode)
39
Serial Controller – S3100, S3200, S3400 Network Controller – N5100, N5200, N5400
Platform1 Profile: 2 Turnstile Mode
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Exit Reader
Rx
Tx
Power
RS232
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Entry Reader
PCC
EntryPass
Platform1
Access Control Sytem
Controller
Network
Port
Network
Switch
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Power Supply Unit
ENTRYPASS
+12V -12V ETH ACC BAT
INOUT
Complete Overview (2x In and Out Turnstiles Mode)
40
Rx
Tx
Power
RS232
PCC
Controller
Network Port
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Network
Switch
EntryPass
Platform1
Access Control Sytem
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Power Supply Unit
ENTRYPASS
+12V
-12V
ET
HA
CC
BA
T
Entry Reader 1 Exit Reader 1
Entry Reader 2 Exit Reader 2
Bidirectional
Turnstile 1
Bi-Directional
Turnstile 2
Serial Controller – S3400 Network Controller – N5400
Platform1 Profile: 2 x In and Out Turnstiles
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Complete Overview (4 Turnstiles Mode)
41
Rx
Tx
Power
RS232
PCC
Controller
Network Port
Fo
r Se
rial C
on
trolle
r On
ly
Fo
r Ne
two
rk C
on
trolle
r On
ly
Network
Switch
EntryPass
Platform1
Access Control Sytem
Upper ConnectionI2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Lower ConnectorI1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Power Supply Unit
ENTRYPASS
+12V
-12V
ET
HA
CC
BA
T
Reader 1 Reader 2
Reader 3 Reader 4
Turnstile 1 Turnstile 2
Turnstile 3 Turnstile 4
Serial Controller – S3400 Network Controller – N5400
Platform1 Profile: 4 Turnstiles
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400
Cabling Information
Communication Data Signal Max Distance Description
PC to PCC RS232 10m
(30 ft) 22 AWG, 2 Pairs, Shielded
PCC to Serial Controller RS485 1000m
(3000 ft) 22 AWG, 2 Pairs, Shielded & Twisted Pair
Network Controller to PC or Network Switch
Network 100m
(300 ft) 24 AWG, 4 Pairs (Cat 5e)
Controller to Reader Wiegand 30m
(100 ft) 22 AWG, 2 Pairs, Shielded & Twisted Pair
Controller to Electro-Magnetic Lock
Power 30m
(100 ft) 18 AWG, 1 Pair
Controller to Push Button Contact 30m
(100 ft) 22 AWG, 1 Pair
Controller to Door Sensor Contact 30m
(100 ft) 22 AWG, 1 Pair
Controller to Controller for Cross-Board Interlock
Contact 100m
(300 ft) 22 AWG, 1 Pair
42
Serial Controller – S3100, S3200, S3400 Network Controller – N5100, N5200, N5400
Model: EP.S3100, S3200, S3400, N5100, N5200, N5400