Environmental Statement Appendix 4.B (6.3.4.2)
Indicative Lighting Drawings
April 2016
Page 1 of 6
THIS PAGE HAS INTENTIONALLY BEEN LEFT BLANK
SAFETY, HEALTH AND ENVIRONMENTAL
INFORMATION
In addition to the hazards/risks normally associated with the types of work
detailed on this drawing, note the following significant residual risks
(Reference shall also be made to the design hazard log).
Construction
National Grid electricity and gas utilities present
High risk of encountering unexploded ordnance (UXO) during the civil works.
Royal Victoria sewer affected
Maintenance / Cleaning
No significant risks
Use
No significant risks
Decommissioning / Demolition
No significant risks
Date
Designed / Drawn
Revision
Scale
Drawing Number
Drawing Title
Project TitleDrawing Status
DO
N
OT
S
CA
LE
Date Date Date
Checked ApprovedClient
Original Size
Suitability
Millim
etres
100
10
0
A1
Plo
tte
d: A
pr 1
3, 2
01
6 - 2
:1
0p
m b
y: B
RO
W3
18
4
Drawn / Des DateCheckedRev Approved
Description
Authorised
Copyright C Atkins Limited (2014)
Woodcote Grove
Ashley Road
Epsom
Surrey
KT18 5BW
www.atkinsglobal.com
Tel:
Fax:
+44 (0)1372 726140
+44 (0)1372 740055
SILVERTOWN TUNNEL
REFERENCE DESIGN
SILVERTOWN END (NORTH)
ISOLUX CONTOUR LAYOUT
STWTN-ATK-HLG-ANXX-DR-E-0001 P06.1
S3FOR REVIEW AND COMMENT
1:1000 ---
---
---
---
---
---
---
---
P06.1 --- --- --- ---
Post Consultation Update
P05 DB MJC MF 23/04/15
Reference Design Submission
P04 AC MJC MF 16/01/15
For TFL Review
P03 AC BH MF 05/12/14
First Issue
P02 AC BH KS 17/11/14
First Issue
P01 AC BH KS 05/11/14
First Issue
NOTES
1. THIS DRAWING IS NOT FOR CONSTRUCTION
2. ALL DIMENSIONS ARE IN METRES UNLESS
OTHERWISE STATED
3. LIGHTING SYMBOLS ARE INDICATIVE AND NOT TO
SCALE
4. DESIGNED IN ACCORDANCE WITH BS 5489-1:2013
AND BS EN 13201-2:2003
5. THIS DRAWING SHOULD BE PRINTED IN COLOUR
6. ILLUMINANCE CONTOURS ARE CALCULATED ON
A TWO-DIMENSIONAL PLANE AND DO NOT TAKE
ACCOUNT OF SOLID OBJECTS OR CHANGES IN
TOPOGRAPHY. THEY SHOW THE LIGHTING
LEVELS AT THE START OF THE SCHEME'S 6 YEAR
MAINTENANCE CYCLE AND OPERATING AT 100%
OUTPUT, THEREFORE SHOWING THE MAXIMUM
EXTENT OF LIGHT SPILL AT THE CONTOUR
VALUES SHOWN
7. THE IMPACT OF LIGHTING UNITS THAT DO NOT
FORM PART OF THIS SCHEME HAS NOT BEEN
FACTORED IN THE ILLUMINANCE CONTOUR PLAN
REFERENCE DESIGN
LIGHTING COLUMN
POSITION
KEYISOLUX KEY
20 LUX
10 LUX
5 LUX
3 LUX
1 LUX
Scale 1:1000
10m 10m0m 20m 60m40m30m 50m 70m
Crown copyright and database rights 2014 Ordnance Survey 100035971c
SAFETY, HEALTH AND ENVIRONMENTAL
INFORMATION
In addition to the hazards/risks normally associated with the types of work
detailed on this drawing, note the following significant residual risks
(Reference shall also be made to the design hazard log).
Construction
National Grid electricity and gas utilities present
High risk of encountering unexploded ordnance (UXO) during the civil works.
Ground contamination from former gas works
Maintenance / Cleaning
No significant risks
Use
No significant risks
Decommissioning / Demolition
No significant risks
Date
Designed / Drawn
Revision
Scale
Drawing Number
Drawing Title
Project TitleDrawing Status
DO
N
OT
S
CA
LE
Date Date Date
Checked ApprovedClient
Original Size
Suitability
Millim
etres
100
10
0
A1
Plo
tte
d: A
pr 1
3, 2
01
6 - 2
:1
3p
m b
y: B
RO
W3
18
4
Drawn / Des DateCheckedRev Approved
Description
Authorised
Copyright C Atkins Limited (2014)
Woodcote Grove
Ashley Road
Epsom
Surrey
KT18 5BW
www.atkinsglobal.com
Tel:
Fax:
+44 (0)1372 726140
+44 (0)1372 740055
SILVERTOWN TUNNEL
REFERENCE DESIGN
GREENWICH END (SOUTH)
ISOLUX CONTOUR PLAN
STWTN-ATK-HLG-ASXX-DR-E-0001 P06.1
S3FOR REVIEW AND COMMENT
1:1000 ---
---
---
---
---
---
---
---
P06.1 --- --- --- ---
Post Consultation Update
P05 DB MJC MF 23/04/15
Reference Design Submission
P04 AC MJC MF 16/01/15
For TFL Review
P03 AC BH MF 05/12/14
First Issue
P02 AC BH KS 17/11/14
First Issue
P01 AC BH KS 05/11/14
First Issue
Crown copyright and database rights 2014 Ordnance Survey 100035971c
NOTES
1. THIS DRAWING IS NOT FOR CONSTRUCTION
2. ALL DIMENSIONS ARE IN METRES UNLESS
OTHERWISE STATED
3. LIGHTING SYMBOLS ARE INDICATIVE AND NOT TO
SCALE
4. DESIGNED IN ACCORDANCE WITH BS 5489-1:2013
AND BS EN 13201-2:2003
5. THIS DRAWING SHOULD BE PRINTED IN COLOUR
6. ILLUMINANCE CONTOURS ARE CALCULATED ON
A TWO-DIMENSIONAL PLANE AND DO NOT TAKE
ACCOUNT OF SOLID OBJECTS OR CHANGES IN
TOPOGRAPHY. THEY SHOW THE LIGHTING
LEVELS AT THE START OF THE SCHEME'S 6 YEAR
MAINTENANCE CYCLE AND OPERATING AT 100%
OUTPUT, THEREFORE SHOWING THE MAXIMUM
EXTENT OF LIGHT SPILL AT THE CONTOUR
VALUES SHOWN
7. THE IMPACT OF LIGHTING UNITS THAT DO NOT
FORM PART OF THIS SCHEME HAS NOT BEEN
FACTORED IN THE ILLUMINANCE CONTOUR PLAN
REFERENCE DESIGN
LIGHTING COLUMN
POSITION
KEYISOLUX KEY
20 LUX
10 LUX
5 LUX
3 LUX
1 LUX
Scale 1:1000
10m 10m0m 20m 60m40m30m 50m 70m
SAFETY, HEALTH AND ENVIRONMENTAL
INFORMATION
In addition to the hazards/risks normally associated with the types of work
detailed on this drawing, note the following significant residual risks
(Reference shall also be made to the design hazard log).
Construction
National Grid electricity and gas utilities present
High risk of encountering unexploded ordnance (UXO) during the civil works.
Royal Victoria sewer affected
Maintenance / Cleaning
No significant risks
Use
No significant risks
Decommissioning / Demolition
No significant risks
Date
Designed / Drawn
Revision
Scale
Drawing Number
Drawing Title
Project TitleDrawing Status
DO
N
OT
S
CA
LE
Date Date Date
Checked ApprovedClient
Original Size
Suitability
Millim
etres
100
10
0
A1
Plo
tte
d: M
ar 1
0, 2
01
6 - 3
:1
3p
m b
y: W
IL
D2
37
7
Drawn / Des DateCheckedRev Approved
Description
Authorised
Copyright C Atkins Limited (2014)
Woodcote Grove
Ashley Road
Epsom
Surrey
KT18 5BW
www.atkinsglobal.com
Tel:
Fax:
+44 (0)1372 726140
+44 (0)1372 740055
SILVERTOWN TUNNEL
REFERENCE DESIGN
NORTH SCHEME
CONCEPTUAL LIGHTING
ARRANGEMENT
STWTN-ATK-HEL-ANXX-DR-E-0001 P04.1
S3FOR REVIEW AND COMMENT
1:500 ---
---
---
---
---
---
---
---
P04.1 --- --- --- ---
Post Consultation Update
P03 DB MJC MF 23/04/15
Reference Design Submission
P02 AC MJC MF 16/01/15
For TFL Review
P01 AC BH MF 12/01/15
First Issue
Crown copyright and database rights 2014 Ordnance Survey 100035971c
STEEL ROAD LIGHTING COLUMN OF 10m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 3 LUMINAIRE OF TYPE R5 DS-NW TO
PROVIDE 27klm WITH 200 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 187W NOMINAL WATTAGE
STEEL ROAD LIGHTING COLUMN OF 6m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 1 LUMINAIRE OF TYPE R6 DS-NW TO
PROVIDE 10klm WITH 80 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 67W NOMINAL WATTAGE
KEY
STEEL ROAD LIGHTING COLUMN OF 10m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 3 LUMINAIRE OF TYPE R5 DS-NW TO
PROVIDE 25klm WITH 200 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 171W NOMINAL WATTAGE
STEEL ROAD LIGHTING COLUMN OF 10m
NOMINAL HEIGHT WITH PLANTED BASE
WITH WRTL LUMA 3 LUMINAIRE OF TYPE R5
DS-NW TO PROVIDE 25klm WITH 200
NEUTRAL WHITE LEDS OF 4000K COLOUR
TEMPERATURE AND 171W NOMINAL
WATTAGE AT 10m MOUNTING HEIGHT AND
PIGGYBACK MOUNTED WRTL LUMA 1 OF
TYPE R5 DS-NW TO PROVIDE 3klm WITH 60
NEUTRAL WHITE LEDS OF 4000K COLOUR
TEMPERATURE AND 44W NOMINAL
WATTAGE AT 6m MOUNTING HEIGHT
STEEL ROAD LIGHTING COLUMN OF 10m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 3 LUMINAIRE OF TYPE R1 DS-NW TO
PROVIDE 17klm WITH 140 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 114W NOMINAL WATTAGE
STEEL ROAD LIGHTING COLUMN OF 5m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 1 LUMINAIRE OF TYPE R6 DS-NW TO
PROVIDE 7klm WITH 68 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 47W NOMINAL WATTAGE
NOTES
1. THIS DRAWING IS NOT FOR CONSTRUCTION
2. ALL DIMENSIONS ARE IN METRES UNLESS OTHERWISE
STATED
3. LIGHTING SYMBOLS ARE INDICATIVE AND NOT TO
SCALE
4. DESIGNED IN ACCORDANCE WITH BS 5489-1:2013 AND
BS EN 13201-2:2003
5. COLUMN NUMBERS SHOWN ARE FOR DRAWING
REFERENCE ONLY. COLUMNS SHALL BE NUMBERED
FOLLOWING COMPLETION OF ALL OTHER WORKS. THE
NUMBERING SYSTEM SHALL BE IN ACCORDANCE WITH
TfL'S NUMBERING SYSTEM
6. MOUNTING HEIGHT REFERS TO THE NOMINAL HEIGHT
BETWEEN THE PHOTOMETRIC CENTRE OF A ROAD
LIGHTING LUMINAIRE AND THE SURFACE OF THE ROAD
AS DEFINED IN BS 5489-1:2003
7. LIGHTING DESIGN BASED ON A MAINTENANCE FACTOR
OF 0.74 FOR LUMINAIRES OVER 6m MOUTNING HEIGHT
AND 0.67 FOR LUMINAIRES UP TO 6m MOUNTING
HEIGHT IN ACCORDANCE WITH BS 5489-1:2013
ENVIRONMENT ZONE E3/E4 AND AN LED LUMEN
DEPRECIATION - INCORPORATING FAILURE FRACTION
- OF 0.8
Scale 1:1000
10m 10m0m 20m 60m40m30m 50m 70m
RETAINING WALL
SECANT WALL WITH VERTICAL
UPSTAND
SAFETY, HEALTH AND ENVIRONMENTAL
INFORMATION
In addition to the hazards/risks normally associated with the types of work
detailed on this drawing, note the following significant residual risks
(Reference shall also be made to the design hazard log).
Construction
National Grid electricity and gas utilities present
High risk of encountering unexploded ordnance (UXO) during the civil works.
Ground contamination from former gas works
Maintenance / Cleaning
No significant risks
Use
No significant risks
Decommissioning / Demolition
No significant risks
Date
Designed / Drawn
Revision
Scale
Drawing Number
Drawing Title
Project TitleDrawing Status
DO
N
OT
S
CA
LE
Date Date Date
Checked ApprovedClient
Original Size
Suitability
Millim
etres
100
10
0
A1
Plo
tte
d: M
ar 1
0, 2
01
6 - 3
:1
6p
m b
y: W
IL
D2
37
7
Drawn / Des DateCheckedRev Approved
Description
Authorised
Copyright C Atkins Limited (2014)
Woodcote Grove
Ashley Road
Epsom
Surrey
KT18 5BW
www.atkinsglobal.com
Tel:
Fax:
+44 (0)1372 726140
+44 (0)1372 740055
SILVERTOWN TUNNEL
REFERENCE DESIGN
GREENWICH END (SOUTH)
LIGHTING ARRANGEMENT
STWTN-ATK-HEL-ASXX-DR-E-0001 P04.1
S3FOR REVIEW AND COMMENT
1:1000 ---
---
---
---
---
---
---
---
P04.1 --- --- --- ---
Post Consultation Update
P03 DB MJC MF 23/04/15
Reference Design Submission
P02 AC MJC MF 16/01/15
For TFL Review
P01 AC BH MF 05/12/14
First Issue
Crown copyright and database rights 2014 Ordnance Survey 100035971c
STEEL ROAD LIGHTING COLUMN OF 10m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 3 LUMINAIRE OF TYPE R5 DS-NW TO
PROVIDE 27klm WITH 200 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 187W NOMINAL WATTAGE
STEEL ROAD LIGHTING COLUMN OF 6m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 1 LUMINAIRE OF TYPE R6 DS-NW TO
PROVIDE 10klm WITH 80 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 67W NOMINAL WATTAGE
KEY
STEEL ROAD LIGHTING COLUMN OF 10m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 3 LUMINAIRE OF TYPE R5 DS-NW TO
PROVIDE 25klm WITH 200 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 171W NOMINAL WATTAGE
STEEL ROAD LIGHTING COLUMN OF 10m
NOMINAL HEIGHT WITH PLANTED BASE
WITH WRTL LUMA 3 LUMINAIRE OF TYPE R5
DS-NW TO PROVIDE 25klm WITH 200
NEUTRAL WHITE LEDS OF 4000K COLOUR
TEMPERATURE AND 171W NOMINAL
WATTAGE AT 10m MOUNTING HEIGHT AND
PIGGYBACK MOUNTED WRTL LUMA 1 OF
TYPE R5 DS-NW TO PROVIDE 7klm WITH 60
NEUTRAL WHITE LEDS OF 4000K COLOUR
TEMPERATURE AND 44W NOMINAL
WATTAGE AT 6m MOUNTING HEIGHT
STEEL ROAD LIGHTING COLUMN OF 10m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 3 LUMINAIRE OF TYPE R1 DS-NW TO
PROVIDE 17klm WITH 140 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 114W NOMINAL WATTAGE
STEEL ROAD LIGHTING COLUMN OF 5m
MOUNTING HEIGHT WITH PLANTED BASE
AND POST-TOP MOUNTED PHILIPS WRTL
LUMA 1 LUMINAIRE OF TYPE R6 DS-NW TO
PROVIDE 7klm WITH 68 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 47W NOMINAL WATTAGE
NOTES
1. THIS DRAWING IS NOT FOR CONSTRUCTION
2. ALL DIMENSIONS ARE IN METRES UNLESS
OTHERWISE STATED
3. LIGHTING SYMBOLS ARE INDICATIVE AND NOT TO
SCALE
4. DESIGNED IN ACCORDANCE WITH BS 5489-1:2013
AND BS EN 13201-2:2003
5. COLUMN NUMBERS SHOWN ARE FOR DRAWING
REFERENCE ONLY. COLUMNS SHALL BE NUMBERED
FOLLOWING COMPLETION OF ALL OTHER WORKS.
THE NUMBERING SYSTEM SHALL BE IN
ACCORDANCE WITH TfL'S NUMBERING SYSTEM
6. MOUNTING HEIGHT REFERS TO THE NOMINAL
HEIGHT BETWEEN THE PHOTOMETRIC CENTRE OF
A ROAD LIGHTING LUMINAIRE AND THE SURFACE
OF THE ROAD AS DEFINED IN BS 5489-1:2003
7. LIGHTING DESIGN BASED ON A MAINTENANCE
FACTOR OF 0.74 FOR LUMINAIRES OVER 6m
MOUTNING HEIGHT AND 0.67 FOR LUMINAIRES UP
TO 6m MOUNTING HEIGHT IN ACCORDANCE WITH
BS 5489-1:2013 ENVIRONMENT ZONE E3/E4 AND AN
LED LUMEN DEPRECIATION INCORPORATING
FAILURE FRACTION OF 0.8
8. LIGHTING COLUMNS P97 AND P110 RELOCATED TO
AVOID CLASH WITH SUPER SPAN PORTAL GANTRY.
LIGHTING COLUMN RELOCATION IS NOT
SUPPORTED BY CALCULATION AND LIGHTING
LEVELS IN THIS AREA REQUIRE VERIFICATION AT
DETAILED DESIGN STAGE.
9. LIGHTING COLUMN P85 RELOCATED TO AVOID
CLASH WITH EMERGENCY CROSSOVER. LIGHTING
COLUMN RELOCATION IS NOT SUPPORTED BY
CALCULATION AND LIGHTING LEVELS IN THIS AREA
REQUIRE VERIFICATION AT DETAILED DESIGN
STAGE. NO SPECIFIC LIGHTING PROVISION HAS
BEEN MADE FOR THE EMERGENCY CROSSOVER AT
THIS STAGE.
Scale 1:1000
10m 10m0m 20m 60m40m30m 50m 70m
WRTL LUMA 1 OF TYPE R5 DS-NW TO
PROVIDE 3klm WITH 60 NEUTRAL WHITE
LEDS OF 4000K COLOUR TEMPERATURE
AND 44W NOMINAL WATTAGE AT 6m
MOUNTING HEIGHT
PROPOSED FOOT & CYCLE BRIDGE
THAMES PATH NATIONAL TRAIL
FOOTWAY/CYCLE WAY