enhancement of power quality using dstatcom

Upload: keerthi-ambati

Post on 06-Apr-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    1/51

    CHAPTER-1

    INTRODUCTIONINTRODUCTION

    OVERVIEW:

    The electric power system is considered to be composed of three

    functional blocks - generation, transmission and distribution. For a reliable

    power system, the generation unit must produce adequate power to meet

    customers demand, transmission systems must transport bulk produce adequate

    power to meet power over long distances without overloading system stability

    and distribution systems must deliver electric power to each customers

    premises from bulk power systems

    Distribution system locates the end of power system and is connected to

    the customer directly, so the power quality mainly depends on distribution

    system. The reason behind this is that the electrical distribution network failures

    account for about 90% of the average customer interruptions. In the earlier days,

    the major focus for power system reliability was on generation and transmissiononly as these more capital cost is involved in these. In addition their

    insufficiency can cause widespread catastrophic consequences for both society

    and its environment.

    But now a days distribution systems have begun to receive more

    attention for reliability assessment. Initially for the improvement of power

    quality or reliability of the system FACTS devices like static synchronous

    compensator (STATCOM), static synchronous series compensator SSSC),

    interline power flow controller (IPFC), and unified power flow controller

    (UPFC) etc are introduced.

    These FACTS devices are designed for the transmission system. But

    now a days more attention is on the distribution system for the improvement of

    power quality, these devices are modified and known as custom power devices.

    The main custom power devices which are used in distribution system for

    1

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    2/51

    power quality improvement are distribution static synchronous compensator

    (DSTATCOM), dynamic voltage Restorer (DVR), active filter (AF), unified

    power quality conditioner (UPQC) etc.

    In this from the above custom power devices, D-Statcom and

    D-statcom with LCL passive filter is used to reduce voltage sag and total

    harmonic distortions.

    2.1..LITERATURE SURVEY:

    Power Quality in electric networks is one of today's most concerned

    areas of electric power system. The power quality has serious economic

    implications for consumers, utilities and electrical equipment manufacturers.

    The impact of power quality problems is increasingly felt by customers -

    industrial, commercial and even residential. Some of the main power quality

    problems are sag, swell, transients, harmonic, and flickers etc

    By custom power devices, we refer to power electronic static controllers

    used for power quality improvement on distribution systems rated from 1 to 38

    kV . This interest in the practice of power quality devices (PQDs) arises from

    the need of growing power quality levels to meet the everyday growing

    sensitivity of customer needs and expectations. One of those devices is the

    Distribution Static Compensator (DSTATCOM), which is the most efficient and

    effective modern custom power device used in power distribution networks. Its

    application includes lower cost, smaller size, and its fast dynamic response to

    the disturbance.

    Several research papers and reports addressed the subject of improving

    power quality in distribution system by the use of custom power devices. The

    followings present a brief review of the work undertaken so far

    N.G. Hingorani, [1] presents the concept of custom power is now becoming

    familiar. The term describes the value-added power that electric utilities and

    other service providers will offer their customers in the future. The enhanced

    2

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    3/51

    level of reliability of this power, in terms of reduced interruptions and less

    variation, will stem from an integrated solution to present problems, of which a

    prominent feature will be the application of power electronic controllers to

    utility distribution systems and/or at the supply end of many industrial and

    commercial customers and industrial parks.

    Yash Pal, A. Swarup, et al. [2] presents a comprehensive review of

    compensating custom power devices mainly DSTATCOM (distribution static

    compensator), DVR (dynamic voltage restorer) and UPQC (unified power

    quality compensator). It is aimed at providing a broad viewpoint on the status of

    compensating devices in electric power distribution system to researchers and

    application engineers dealing with power quality problems. is highly required to

    increase the reliability of the distribution system

    2.2. SCOPE OF WORK :

    From the literature review, it is observed that the work on the

    investigation on power with compensating devices is very much diversified.

    However it is observed that there is a scope to investigate the effectiveness of

    compensating devices for different loads and with different depends on

    distribution system. As the customers demand for the reliability of power

    supply is increasing day by day, so the reliability of the distribution system has

    to be increased. Electrical distribution network failures account for about 90%

    of the average customer interruptions. So it is highly required to increase the

    reliability of the distribution system.

    The objective of the proposed work is to improve the power quality or

    reliability in the distribution system with the use of custom power device.

    Different conditions are considered to analyze the operation of D-Statcom for

    the improvement the power quality in distribution system.

    3

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    4/51

    CHAPTER-2

    POWER QUALITY

    3.1.INTRODUCTION

    Power quality is The provision of voltages and system design so that

    the user of electric power can utilize electric energy from the distribution

    system successfully without interference or interruption. A broad definition of

    power quality borders on system reliability, dielectric selection on equipment

    and conductors, long-term outages, voltage unbalance in three-phase systems,power electronics and their interface with the electric power supply and many

    other areas.

    3.2 POWER QUALITY- A BIG ISSUE

    Power quality in electric networks is one of today's most concerned

    areas of electric power system. The power quality has serious economic

    implications for consumers, utilities and electrical equipment manufacturers.

    Modernization and automation of industry involves increasing use of

    computers, microprocessors and power electronic systems such as adjustable

    speed drives. Integration of non-conventional generation technologies such as

    fuel cells, wind turbines and photo-voltaic with utility grids often requires

    power electronic interfaces.

    The power electronic systems also contribute to power quality problems

    (generating harmonics). Under the deregulated environment, in which electric

    utilities are expected to compete with each other, the customer satisfaction

    becomes very important. The impact of power quality problems is increasingly

    felt by customers - industrial, commercial and even residential.

    4

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    5/51

    3.3 PROBLEMS ASSOCIATED WITH POWER QUALITY

    3.3.1 MOMENTARY PHENOMENA

    3.3.1.1 Transients:

    Transients are unwanted decay with time and hence not a steady state

    problem. A broad definition is that a transient is that part of the change in a

    variable that disappears during transition from one steady state operating

    situation to the other". Another synonymous term which can be used is surge.

    3.3.1.2 Long Duration Voltage Variations:

    When rms (root mean square) deviations at power frequency last longer

    than one minute, then we say they are long duration voltage variations. They

    can be either over voltages which is greater than 1.1p.u or under voltages which

    is less than 0.9p.u.

    Over voltage is due to switching off a load or energizing a capacitor

    bank. Also incorrect tap settings on transformers can result in over voltages.

    Under voltage are the results of actions which are the reverse of events that

    cause over voltages i.e. switching in a load or switching off a capacitor bank.

    3.3.1.3 Sustained Interruptions:

    If the supply voltage becomes zero for a period of time which is greater

    than one minute, then we can say that it is a sustained interruption. Normally,

    voltage interruption lasting for more than one minute is often unending and

    requires human intervention to restore the supply. The term outage is also

    used for long interruption. However it does not bring out the true impact of the

    power interruption. Even an interruption of half a cycle can be disastrous for a

    customer with a sensitive load.

    3.3.1.4 SHORT DURATION VOLTAGE VARIATIONS:

    The short duration voltage variations are generally caused by fault

    conditions like single line to ground or double line to ground and starting of

    large loads such as induction motors. The voltage variations can be temporary

    5

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    6/51

    voltage dips i.e. sag or temporary voltage rise i.e. swells or a absolute loss of

    voltage which is known as interruptions .

    Voltage Sags:

    Voltage sag is defined as the reduction of rms voltage to a value

    between 0.1 and 0.9p.u and lasting for duration between 0.5 cycle to 1 minute.

    Voltage sags are mostly caused by system faults and last for durations ranging

    from 3 cycles to 30 cycles depending on the fault clearing time. It is to be noted

    that under-voltages (lasting over a minute) can be handled by voltage

    regulation equipment. Starting of large induction motors can result in voltage

    dip as the motor draws a current up to 10 times the full load current during the

    starting. Also, the power factor of the starting current is generally poor.

    VOLTAGE SWELLS:

    A voltage swell is defined as a raise in rms voltage which is between 1.1

    and 1.8p.u for time duration between 0.5 cycles to 1 minute. A voltage swell is

    characterized by its magnitude (rms) and duration. As with sag, swell is

    associated with system faults. A SLG (single line to ground) fault can result in a

    voltage swell in the healthy phases. Swell can also result from energizing a

    large capacitor bank. On an ungrounded system, the line to ground voltages on

    the ungrounded phases is 1.73p.u during a SLG fault. However in a grounded

    system, there will be negligible voltage rise on the un faulted phases close to a

    substation where the delta connected windings of the transformer provide low

    impedance paths for the zero sequence current during the SLG fault.

    INTERRUPTION:

    If the supply voltage or load current decreases to less than 0.1 p.u for a

    period of time not more than one minute is known as interruption. Interruption

    can be caused either by system faults, equipment failures or control

    malfunctions.

    The interruptions are measured by their duration alone. The duration

    due to a fault is determined by the operating time of the protective devices.

    Duration of an interruption due to equipment malfunction can be irregular.

    6

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    7/51

    Some interruptions may also be caused by voltage sag conditions when there are

    faults on the source side.

    3.3.2 STEADY STATE PHENOMENA

    3.3.2.1 Waveform Distortion

    This is defined as a steady-state deviation from an ideal sine wave of

    power frequency.

    There are five types of waveform distortion:

    (a) DC offset

    (b) Harmonics

    (c) Inter harmonics

    (d) Notching

    (e) Noise

    3.3.2.2 Voltage Imbalance:

    Voltage imbalance can be defined using symmetrical components. The

    ratio of the negative sequence or zero sequence component to the positive

    sequence component is a measure of unbalance. The main cause of voltage

    unbalance is single phase loads on a three phase circuit which resulting in load

    imbalance. Severe imbalance can be caused by single-phasing conditions in the

    system.

    3.3.3 VOLTAGE FLUCTUATIONS AND FLICKER:

    Voltage fluctuations are systematic variations of the voltage or a series

    of random changes in the voltage magnitude which lies in the range of 0.9 to

    1.1p.u. High power loads that draw fluctuating current, such as large motor

    drives and arc furnaces, cause low frequency cyclic voltage variations that result

    in flickering of light sources like incandescent and fluorescent lamps which can

    cause significant physiological discomfort or irritation in human beings.

    The voltage flicker can also affect stable operation of electrical and

    electronic devices such as motors and CRT devices. The typical frequency

    spectrum of voltage flicker lies in the range from 1 Hz to 30 Hz.

    7

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    8/51

    3.3.4 POWER FREQUENCY VARIATIONS:

    Power frequency variations are defined as the deviations of the system

    frequency from its particular value of 50 or 60 Hz. The variations in the

    frequency begin from the changes in the load and the response of the generators

    to meet the load. Thus the load characteristics which dependence on the

    frequency and the control characteristics of the generators change the shift in

    the frequency.

    In current interconnected power systems, frequency variations are

    insignificant most of the time unless governor and load frequency controls are

    disabled under a system of power shortages and a lack of grid discipline.

    Profitable incentives or disincentives that ensure balance between existing

    generation and load may help control over frequency variations under normal

    operating conditions.

    3.4 SOLUTION OF POWER QUALITY PROBLEMS:

    For the improvement of power quality there are two approaches.

    According to first approach the solution to the power quality problems can be

    done from the utility side. The first approach is called load conditioning, which

    ensures that the equipment is less sensitive to power disturbances, allowing the

    operation even under significant voltage distortion. The other solution is to

    install line conditioning systems that suppress the power system disturbances.

    In this approach the compensating device is connect to low and medium

    voltage distribution system in shunt or in series. Shunt active power filters

    operate as a controllable current source and series active power filters operates

    as a controllable voltage source. Both schemes are implemented preferable with

    voltage source PWM inverters, with a dc source having a reactive element such

    as a capacitor.

    However, with the restructuring of power sector and with shifting trend

    towards distributed and dispersed generation, the line conditioning systems or

    utility side solutions will play a major role in improving the inherent supply

    quality; some of the effective and economic measures can be identified as

    following:

    8

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    9/51

    3.4.1 THYRISTOR BASED STATIC SWITCHES:

    The static switch is a versatile device for switching a novel element into

    the circuit when the voltage support is desired. It has a dynamic response time

    of about one cycle. To correct rapidly for voltage spikes, sags or interruptions,

    such static switch can used to switch one or more of devices such as capacitor,

    filter, alternate power line, energy storage systems etc. The static switch can be

    used in the alternate power line applications.

    3.4.2 ENERGY STORAGE SYSTEMS:

    Storage systems can be used to protect sensitive production equipments

    from shutdown which is caused by voltage sag or temporary interruptions.

    These are generally DC storage systems such as UPS, batteries,

    superconducting magnet energy storage (SMES), storage capacitors or even fly

    wheels driving DC generators are used. The output of these devices can be

    supplied to the system through an inverter on a momentary basis by a fast

    performing electronic switch like GTO or IGBT etc. Sufficient energy is fed to

    the system to compensate for the energy that would be lost by the fault

    conditions like voltage sag or interruption.

    However there are many different methods to mitigate voltage sags and

    swells, but the use of a custom Power device is considered to be the most

    efficient method. Flexible AC Transmission Systems (FACTS) for transmission

    systems, the term custom power pertains to the use of power electronics

    controllers in a distribution system, particularly, to deal with a variety of power

    quality problems. Just as FACTS improves the power transfer capabilities and

    stability limits, custom power makes sure customers get pre-specified quality

    and reliability of supply.

    There are many types of Custom Power devices like Active Power

    Filters (APF), Battery Energy Storage Systems (BESS), Distribution static

    synchronous compensators (DSTATCOM), Dynamic Voltage Restorer (DVR),

    Surge Arresters (SA), Super conducting Magnetic Energy Systems (SMES),

    Static Electronic Tap Changers (SETC), Solid-State Transfer Switches (SSTS),

    9

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    10/51

    Solid State Fault Current Limiter (SSFCL), and unified power quality

    conditioner (UPQC).

    CHAPTER-4CHAPTER-4

    FACTS

    4.1 INTRODUCTION:

    10

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    11/51

    4.2 NEED OF CUSTOM POWER DEVICES:

    Power quality is one of major concerns in the present era. Distribution

    system locates the end of power system and is connected to the customer

    directly, so the reliability of power supply mainly depends on distribution

    system. It has become important, especially, with the introduction of

    sophisticated devices, whose performance is very sensitive to the quality of

    power supply.

    Power quality problem is an occurrence manifested as a nonstandard

    voltage, current or frequency that results in a failure of end use equipments. The

    electrical distribution network failures account for about 90% of the average

    customer interruptions. As the customers demand for the reliability of power

    supply is increasing day by day, so the reliability of the distribution system has

    to be increased. One of the major problems dealt here is the power sag.

    Power distribution systems, ideally, should provide their customers with

    an uninterrupted flow of energy at smooth sinusoidal voltage at the contracted

    magnitude level and frequency. However, in practice, power systems, especially

    the distribution system, have numerous nonlinear loads,which significantly

    affect the quality of power supplies.

    As a result of the nonlinear loads, the purity of the waveform of supplies

    is lost. This ends up producing many power quality problems. While power

    disturbances occur on all electrical systems, the sensitivity of todays

    sophisticated electronic devices makes them more disposed to the quality of

    power supply.

    For some sensitive devices, a temporary disturbance can cause

    scrambled data, interrupted communications, a frozen mouse, system crashes

    and equipment failure etc. A power voltage spike can damage valuable

    components.

    11

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    12/51

    To solve this problem, custom power devices are used. One of those

    devices is the Distribution Static Compensator (DSTATCOM), which is the

    most efficient and effective modern custom power device used in power

    distribution networks. Its appeal includes lower cost, smaller size, and its fast

    dynamic response to the disturbance.

    4.3 CONFIGURATIONS:

    The compensating type custom power devices can be classified on the

    basis of different topologies and the number of phases. For power quality

    improvement the voltage source inverter (VSI) bridge structure is generally

    used for the development of custom power devices, while the use of current

    source inverter (CSI) is less reported. The topology can be shunt

    (DSTATCOM), series (DVR), or a combination of both (UPQC).

    CHAPTER-5

    D-STATCOM

    5.1 INTRODUCTION:

    12

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    13/51

    Among the power quality problems like sag, swell, harmonic etc,

    voltage sag is the most severe disturbances in the distribution system. To

    overcome these problems the concept of custom power devices is introduced

    lately. One of those devices is the DSATCOM, which is the most efficient and

    effective modern custom power device used in power distribution networks.

    DSTATCOM is a recently proposed shunt connected solid state device

    that injects voltage into the system in order to regulate the load side voltage. It

    is generally installed in a distribution system between the supply and the critical

    load feeder at the point of common coupling (PCC).Other than voltage sags and

    swells compensation, DSTATCOM is used to reduce the Total harmonic

    distortions.

    5.2 PRINCIPLE OF D-STATCOM:

    FIG: DSTATCOM

    A DSATCOM is a solid state power electronics switching device

    consisting of either GTO or IGBT, a capacitor bank as an energy storage device.

    It is linked in shunt between a distribution system and a load that shown in

    Figure.

    13

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    14/51

    However, when voltage sag occurs in the distribution system, the

    DSTATCOM control system calculates and synthesizes the voltage required to

    preserve output voltage to the load by injecting a controlled voltage with a

    certain magnitude and phase angle into the distribution system to the load. Here

    a LCL passive filter is used in order to reduce the total harmonic distortions and

    PWM , PI controller are being used.

    5.3 BASIC ARRANGEMENT OF DSTATCOM:

    Voltage Source Converter

    Controller

    Energy Storage Device

    LCL Passive Filter

    FIG: Schematic diagram of a D-STATCOM

    EQUATIONS OF D-STATCOM:

    14

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    15/51

    Where,

    5.3.1 VOLTAGE SOURCE CONVERTER:

    A voltage-source converter is a power electronic device that connected

    in shunt or parallel to the system. It can generate a sinusoidal voltage with any

    required magnitude, frequency and phase angle. The VSC used to either

    completely replace the voltage or to inject the missing voltage. The missing

    voltage is the difference between the nominal voltage and the actual.

    It also converts the DC voltage across storage devices into a set of three

    phase AC output voltages. It could be a 3 phase - 3 wire VSC or 3 phase - 4

    wire VSC. Either a conventional two level converter or a three level converter is

    used. For DSTATCOM application, the VSC is used to momentarily replace the

    supply voltage or to generate the part of the supply voltage which is absent. The

    VSC here is a two level i.e two phase.

    5.3.2 ENERGY STORAGE DEVICE:

    15

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    16/51

    The function of storage devices is to supply the required energy to the

    VSC via a dc link for the generation of injected voltages. DC source is

    connected in parallel with the DC capacitor. It carries the input ripple current of

    the converter and it is the main reactive energy storage element. This DC

    capacitor could be charged by a battery source or could be recharged by the

    converter itself.

    FIG: ENERGY STORAGE DEVICE

    5.3.3 LCL PASSIVE FILTER:

    LCL Passive filter is more effective on reducing harmonic distortion.

    The line-filter between the converter and the grid can be reduced by using an

    LCL-filter instead of an L-filter. The main drawback with this is that the LCL-

    filter will introduce a resonance frequency into the system. Harmonic

    components in the output voltage can lead to resonance oscillations and

    instability problems unless they are properly handled.

    One way of reducing the resonance current is by adding a passive

    damping circuit to the filter. This damping circuit can be purely resistive,

    causing relatively high losses, or a more complex solutions consisting of a

    combination of capacitors and inductors.

    16

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    17/51

    A typical LCL-filter is shown in Figure where V1 is the grid side

    voltage, Vc is the voltage across the filter capacitor and V2 is the converter

    output voltage.

    FIG: LCL PASSIVE FILTER

    EQUATIONS:

    To design an efficient LCL Passive filters make sure that,

    5.3.4 CONTROLLER :

    In this project we use a Proportional plus integral controller.

    Proportional- integral controller (PI Controller) is a feedback controller which

    drives the system to be controlled with a weighted sum of the error signal

    17

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    18/51

    (difference between the output and desired set point) and the integral of that

    value.

    FIG: PI CONTROLLER

    In this case, PI controller will process the error signal to zero. The load

    r.m.s voltage is brought back to the reference voltage by comparing the

    reference voltage with the r.m.s voltages that had been measured at the load

    point. It also is used to control the flow of reactive power from the DC capacitorstorage circuit.

    PWM generator is the device that generates the Sinusoidal PWM

    waveform or signal. To operate PWM generator, the angle is summed with the

    phase angle of the balance supply voltages equally at 120 degrees. Therefore, it

    can produce the desired synchronizing signal that required.

    PWM generator also received the error signal angle from PI controller.

    The modulated signal is compared against a triangle signal in order to generate

    the switching signals for VSC valves.

    18

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    19/51

    CHAPTER-6

    POWER QUALITY PROBLEMS IN DSTATCOM

    The major power quality problems here are voltage sag and harmonic

    distortion.

    6.1 VOLTAGE SAG

    Voltage sags and momentary power interruptions are probably the

    most important PQ problem affecting industrial and large commercial

    customers. These events are usually associated with a fault at some location in

    the supplying power system. Interruptions occur when the fault is on thecircuit supplying the customer. But voltage sags occur even if the faults

    happen to be far away from the customer's site.

    Voltage sags lasting only 4-5 cycles can cause a wide range of sensitive

    customer equipment to drop out. To industrial customers, voltage sag and a

    momentary interruption are equivalent if both shut their process down. A

    typical example of voltage sag is shown in fig . The susceptibility of utilization

    equipment to voltage sag is dependent upon duration and magnitude of voltage

    sags and can be defined.

    FIG : VOLTAGE SAG

    19

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    20/51

    6.1.1 Characteristics of Voltage Sags:

    Voltage sags which can cause equipment impacts are caused by faults on

    the power system.Motor starting also results in voltage sags but the magnitudes

    are usually not severe enough to cause equipment mis operation

    How a fault results in voltage sag at a customer facility?

    The one line diagram given below in fig. 3 can be used to explain this

    phenomenon.

    Consider a customer on the feeder controlled by breaker 1. In the case

    of a fault on this feeder, the customer will experience voltage sag during the

    fault and an interruption when the breaker opens to clear the fault. For

    temporary fault, enclosure may be successful.

    Anyway, sensitive equipment will almost surely trip during this

    interruption. Another kind of likely event would be a fault on one of the

    feeders from the substation or a fault somewhere on the transmission

    system, In either of these cases, the customer will experience a voltage sag

    during the actual period of fault. As soon as breakers open to clear the fault,

    normal voltage will be restarted at the customer's end. Fig is a plot of rms

    voltage versus time and the waveform characteristics at the customer's location

    for one of these fault conditions.

    20

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    21/51

    This waveform is typical of the customer voltage during a fault on a

    parallel feeder circuit that is cleared quickly by the substation breaker. The total

    duration of fault is 150m sec. The voltage during a fault on a parallel feeder

    will depend on the distance from the substation to fault point. A fault close to

    substation will result in much more significant sag than a fault near the end of

    feeder. Fig 5 shows the voltage sag magnitude at the plant bus as a function of

    fault location for an example system.

    FIG: VOLTAGE SAG CHARACTERISTIC DURING FAULT

    A single line to ground fault condition results in a much less severe

    voltage sag than 3-phase fault Condition due to a delta--star transformer

    connection at the plant. Transmission related voltage sags are normally much

    more consistent than those related to distribution. Because of large amounts of

    energy associated with transmission faults, they are cleared as soon as possible.

    This normally corresponds to 3-6 cycles, which is the total time for fault

    detection and breaker operation Normally customers do not experience an

    interruption for transmission fault. Transmission systems are looped or

    networked, as distinct from radial distribution systems. If a fault occurs

    as shown on the 115KV system, the protective relaying will sense the fault

    and breakers A and B will open to clear the fault.

    21

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    22/51

    FIG: MAGNITUDE OF VOLTAGE SAG

    While the fault is on the transmission system, the entire power system,

    including the distribution system will experience Voltage sag. Fig shown the

    magnitude of measured voltage sags at an industrial plant supplied from a 115

    kV system .

    FIG: VOLTAGE SAG OF MAGNITUDE AND DURATION

    22

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    23/51

    Most of the voltages were 10-30% below nominal voltage, and no

    momentary interrupts were measured at the plant during the monitoring period

    (about a year). Fig given a three-dimensional plot illustrating the number of

    sags experienced as a function of both the voltage sag magnitude and the

    duration.

    This is a convenient way to completely characterize the actual or

    expected voltage sag conditions at a site. Evaluating the impact of voltage sags

    at a customer plant involves estimating the member of voltage sags that can be

    expected as a function of the voltage sag magnitude and then comparing

    this with equipment sensitivity.

    The estimate of voltage sag performance are developed by performing

    short-circuit simulations to determine the plant voltage as a function of fault

    location throughout the power system. Total circuit miles of line exposure that

    can affect the plant (area of vulnerability) are determined for a particular sag

    level.

    Historical fault performance (fault per year per 100 miles) can, then

    be used to estimate the number of sags per year that can be expected below the

    magnitude. A chart such as the one in fig 8. Can be drawn in splitting the

    expected number of voltage sags by magnitude. This information can be used

    directly by the customers to determine the need for power conditioning

    equipment at sensitive loads in the plant.

    6.1.2Voltage-Sag Analysis- Methodology

    The methodology is outlined is (proposed) of IEEE Gold book (IEEE

    standard 493, Recommended practice for the design of reliable industrial and

    commercial power system) The methodology basically consists of the following

    four steps:

    23

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    24/51

    6.1.2.1Voltage Sag Calculation

    Sliding faults which include line-line, line to ground, line to line- to

    ground and three phase are applied to all the lines in the load flow. Each line is

    divided into equal sections and each section is faulted as shown in fig 9.

    6.1.2.2 Sag Occurrence Calculation:

    Based upon the utilities reliability data (the number of times each line

    section will experience a fault) and the results of load flow and voltage sag

    calculations, the number of voltage sags at the customer site due to remote

    faults can be calculated.

    Depending upon the equipment connection, the voltage sag occurrence

    rate may be calculated in terms of either phase or line voltages dependent upon

    the load connection. For some facilities, both line and phase voltages may be

    required. The data thus obtained from load flow, Voltage sag calculation,

    and voltage sag occurrence calculation can be sorted and tabulated by sag

    magnitude, fault type, location of fault and nominal system voltage at the fault

    location

    6.2 Study of Results of Sag- Analysis:

    The results can be tabulated and displayed in many different ways to

    recognize difficult aspects. Area of vulnerability can be plotted on a

    geographical map or one - line diagram (fig above). These plots can be used to

    target transmission and distribution lines for enhancements in reliability.

    Further bar charts, and pie-charts showing the total number of voltage sags

    with reference to voltage level at fault point, area/zone of fault, or the fault

    type can be developed to help utilities focus on their system improvements

    (figs.) To examining the existing system, system modifications aimed at

    mitigating or reducing voltage sags can also be identified, thus enabling cost

    benefits analysis. Possible such system structural changes that can be identified

    include.

    24

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    25/51

    Reconnection of a customer from one voltage level to another,

    Installation of Ferro-resonant transformers or time delayed under voltage, drop

    out relay to facilitate easy ride - through the sag Application of static transfer

    switch and energy storage system., Application of fast acting synchronous

    condensers, Neighborhood generation capacity addition , Increase service

    voltage addition through transformer tap changing, By enhancement of system

    reliability.

    6.3 Solutions to Voltage Sag Problems:

    Efforts by utilities and customers can reduce the number and severity of

    sags.

    A. Utility solutions:

    Utilities can take two main steps to reduce the detrimental effects of

    sags

    (1) Prevent fault

    (2) Improve fault clearing methods

    Fault prevention methods include activities like tree trimming, adding

    line arrests, washing insulators and installing animal guards. Improved fault

    clearing practices include activities like adding line recloses, eliminating fast

    tripping, adding loop schemes and modifying feeder design. These may reduce

    the number and /or duration of momentary interruptions and voltage sags but

    faults cannot be eliminated completely.

    B. Customer solutions:

    Power conditioning is the general concept behind these methods. Fig 12

    is a schematic f the general approach used.

    Power conditioning helps to

    1. Isolate equipment from high frequency noise and transients.

    2. Provide voltage sag ride through capability

    25

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    26/51

    6.4 TOTAL HARMONIC DISTORTION:

    Harmonics

    Introduction:

    The typical definition for a harmonic is a sinusoidal component of a

    periodic wave or\quantity having a frequency that is an integral multiple of the

    fundamental frequency. Some references refer to clean or pure power as

    those without any harmonics. But such clean waveforms typically only exist in a

    laboratory. Harmonics have been around for a long time and will continue to do

    so. In fact, musicians have been aware of such since the invention of the first

    string or wood wind instrument. Harmonics (called overtones in music) are

    responsible for what makes a trumpet sound like a trumpet, and a clarinet like a

    clarinet.

    Electrical generators try to produce electric power where

    voltageone frequency associated with it, the fundamental frequency. In the

    North America, this frequency is 60 Hz, or cycles per second. In European

    countries and other parts of the world, this frequency is usually 50 Hz. Aircraft

    often uses 400 Hz as the fundamental frequency. At 60 Hz, this means that sixty

    times a second, the voltage waveform increases to a maximum positive value,

    then decreases to zero, further decreasing to a maximum negative value, and

    then back to zero. The rate at which these changes occur is the trigometric

    function called a sine wave, as shown in figure . This function occurs in many

    natural phenomena, such as the speed of a pendulum as it swings back

    and forth, or the way a string on a voilin vibrates when plucked. Fig . Sine wave

    The frequency of the harmonics is different, depending on the fundamentalfrequency. For example, the 2nd harmonic on a 60 Hz system is 2*60 or 120

    Hz. At 50Hz, the second harmonic is 2* 50 or 100Hz.300Hz is the 5th harmonic

    in a 60 Hz system, or the 6th harmonic in a 50 Hz system. Figure shows how a

    signal with two harmonics would appear on an oscilloscope-type display, which

    some power quality analyzers provide.

    In order to be able to analyze complex signals that have many different

    frequencies present, a number of mathematical methods were developed. One of

    the more popular is called the Fourier Transform. However, duplicating the

    26

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    27/51

    mathematical steps required in a microprocessor or computer-based

    instrument is quite difficult. So more compatible processes, called the FFT for

    Fast Fourier transform, or DFT for Discrete Fourier Transform, are used. These

    methods only work properly if the signal is composed of only the fundamental

    and harmonic frequencies in a certain frequency range.

    The frequency values must not change during the measurement period.

    Failure of these rules to be maintained can result in mis-information. For

    example, if a voltage waveform is comprised of 60 Hz and 200 Hz signals, the

    FFT cannot directly see the 200Hz. It only knows 60, 120, 180, 240,..., which

    are often called bins. The result would be that the energy of the 200 Hz signal

    would appear partially in the 180Hz bin, and partially in the 240Hz bin.

    An FFT-based processer could show a voltage value of 115V at 60 Hz,

    18 V at the 3rdharmonic, and 12 V at the 4th harmonic, when it really should

    havebeen30Vat200Hz.

    These in between frequencies are called inter harmonics. There is

    also a special category of inter harmonics, which are frequency values less than

    the fundamental frequency value, called sub-harmonics.

    For example, the process of melting metal in an electric arc furnace can

    result large currents that are comprised of the

    fundamental , inter harmonic, and sub harmonic frequencies being drawn from

    the electric power grid. These levels can be quite high during the melt-down

    phase, and usually effect the voltage waveform.

    Effects of harmonics:

    The presence of harmonics does not mean that the factory or office

    cannot run properly .Like other power quality phenomena, it depends on the

    stiffness of the power distribution system and the susceptibility of the

    equipment. As shown below, there are a number of different types of equipment

    that can have mis-operations or failures due to high harmonic voltage

    and/or current levels. In addition, one factory may be the source of high

    harmonics but able to run properly. This harmonic pollution is often carried

    back onto the electric utility distribution system, and may effect facilities on the

    same system which are more susceptible.

    27

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    28/51

    Some typical types of equipment susceptible to harmonic pollution

    include: - Excessive neutral current, resulting in overheated neutrals. The odd

    triple n harmonics in three phase wave circuits are actually additive in the

    neutral. This is because the harmonic number multiplied by the 120 degree

    phase shift between phases is a integer multiple of 360 degrees. This puts the

    harmonics from each of the three phase legs in-phase with each other in the

    neutral, as shown in figure

    Harmonic problems are almost always introduced by the consumers

    equipment and installation practices. Harmonic distortion is caused by the high

    use of non-linear load equipment such as computer power supplies, electronic

    ballasts, compact fluorescent lamps and variable speed drives etc, which create

    high current flow with harmonic frequency components.

    The limiting rating for most electrical circuit elements is determined by

    the amount of heat that can be dissipated to avoid overheating of bus bars,

    circuit breakers, neutral conductors, transformer windings or generatoralternators.

    28

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    29/51

    TOTAL HARMONIC DISTORTION:

    THD is defined as the RMS value of the waveform remaining when the

    fundamental is removed. A perfect sine wave is 100%, the fundamental is the

    system frequency of 50 or 60Hz.

    Harmonic distortion is caused by the introduction of waveforms at

    frequencies in multiplies of the fundamental ie: 3rd harmonic is 3x the

    fundamental frequency / 150Hz. Total harmonic distortion is a measurement of

    the sum value of the waveform that is distorted.

    FIG: HARMONIC DISTORTION

    Power Measurement:

    Despite the use of good quality test meter instrumentation, high current

    flow can often remain undetected or under estimated by as much 40%. Thissevere underestimation causes overly high running temperatures of equipment

    and nuisance tripping. This is simply because the average reading test meters

    commonly used by maintenance technicians, is not designed to accurately

    measure distorted currents, and can only provide indication of the condition of

    the supply at the time of checking.

    Power quality conditions change continuously, and only instruments

    offering true RMS measurement of distorted waveforms and neutral currents

    29

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    30/51

    can provide the correct measurements to accurately determine the ratings of

    cables, bus bars and circuit breakers.

    Neutral Currents

    High harmonic environments can produce unexpected and dangerous

    neutral currents. In a balanced system, the fundamental currents will cancel out,

    but, triple- Ns will add, so harmonic currents at the 3rd, 9th, 15th etc. will flow

    in the neutral. Traditional 3 phase system meters are only able to calculate the

    vector of line to neutral current measurements, which may not register the true

    reading. Integral 1530, 1560 and 1580 offer a 3 phase 4 wire versions with a

    neutral 4th CT allowing true neutral current measurement and protection in high

    harmonic environments.

    Harmonic Profiles

    There is much discussion over the practical harmonic range of a

    measurement instrument; however study of the harmonic profiles of typically

    installed equipment can guide the system designer to the practical solution. A

    typical harmonic profile graph will show a logarithmic decay as the harmonic

    frequency increases. It is necessary to establish the upper level at which the

    harmonic content is negligible.

    For Example:

    A laptop switch mode power supply causes approximately 25% of 3rd

    harmonic, 19% of 5th harmonic, 10% of 7th harmonic and 5% of 9th harmonic

    etc. Therefore it can be seen that almost all the harmonic content in an IT

    dominated load will be below the 15th harmonic. In a 3 phase load

    incorporating 6 pulse bridge technology as is common in many variable speed

    drives, UPS systems and DC converters, similar profiles will be observed but

    extending to the 25th and 27th harmonic. It can therefore be deduced that in the

    majority of industrial and commercial applications an instrument measuring up

    to the 31st harmonic is ideal.

    30

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    31/51

    6.5 MINIMIZATION OF HARMONICS:

    Care should be undertaken to make sure that the corrective action taken

    to minimize the harmonic problems dont actually make the system worse. This

    can be the result of resonance between harmonic filters, PF correcting

    capacitors and the system impedance. Isolating harmonic pollution devices on

    separate circuits with or without the use of harmonic filters are typical ways of

    mitigating the effects of such. Loads can be relocated to try to balance the

    system better. according to the latest NEC-1996 requirements covering such.

    Whereas the neutral may have been undersized in the past, it may now be

    necessary to run a second neutral wire that is the same size as the phase

    conductors. This is particularly important with some modular office partition-

    type walls, which can exhibit high impedance values. Use of higher pulse

    converters, such as 24-pulse rectifiers, can eliminate lower harmonic values.

    CHAPTER-7

    D-STATCOM TEST MODELS

    DSTATCOM is a device, which is used to

    31

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    32/51

    Improve the Voltage Sag

    Reduce the Total Harmonic Distortion

    7.1 D-STATCOM TEST SYSTEM:

    FIG: SINGLE LINE DIAGRAM OF THE TEST SYSTEM

    The above figure comprises of a 230kV, 50Hz transmission system,

    which is represented by a Thevenin equivalent, feeding into the primary side of

    a 3-winding transformer connected in Y/Y/Y, 230/11/11 kV. A varying load is

    connected to the 11 kV, secondary side of the transformer. A two-level D-

    STATCOM is connected to the 11kV tertiary winding to provide instantaneous

    voltage support at the load point.

    A 750 F capacitor on the dc side provides the D-STATCOM energy

    storage capabilities. Breaker 1 is used to control the period of operation of theD-STATCOM and breaker 2 is used to control the connection of load 1 to the

    system.

    7.2 METHODOLOGY:

    STEP-1:

    Start the program.

    Design a distribution system using Matlab version R2009A.

    32

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    33/51

    Create distortions by inserting different types of faults such as

    Three phase to ground Fault(TPG)

    Single Line to ground Fault (SLG)

    Double Line to ground Fault (DLG)Line to Line (LL) into the distribution system.

    STEP-2:

    Run the simulation.

    Vary the values of the fault resistances for different types of faults.

    If voltage sag >0.9p.u , it means the condition satisfies go to STEP-3

    Otherwise i.e., if voltage sag

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    34/51

    (breaker-2) to the load. Another winding is connected to the breaker (breaker-

    1) to DSTATCOM with LCL Filter.

    FIG: SIMULINK TEST MODELOF DSTATCOM WITH

    LCL PASSIVE FILTER

    7.4 RESULTS WITHOUT DSTATCOM:

    The scope-2 gives the output wave forms of simulink model without

    DSTATCOM. For different types of fault resistances we get different

    wave forms.

    6.4.1 OUTPUT WAVEFORMS:

    34

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    35/51

    FIG : VOLTAGE SAG AT 0.2 *10^-6 for SLG FAULT

    35

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    36/51

    FIG: VOLTAGE SAG AT 6.2*10^-7 FOR DLG FAULT

    FIG: VOLTAGE SAG AT 4.99*10^-7 FOR TPG FAULT

    36

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    37/51

    FIG: VOLTAGE SAG AT 8.1*10 -7 FOR LL FAULT

    From the figure we can see the voltage sag i.e., the reduction in voltage.

    For different values of fault resistances we get different types of waveforms.

    Here we can see the waveforms for different types of faults. The wave forms are

    not greater than 0.9 p.u which shows that there is a voltage reduction or voltage

    sag.

    37

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    38/51

    7.5 OUTPUT WAVEFORMS WITH DSTATCOM:

    The scope 1 gives the output waveforms of simulink model with

    DSTATCOM . The following are the figures of voltage sags

    FIG: VOLTAGE SAG AT 1.3p.u FOR SLG FAULT

    38

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    39/51

    FIG: VOLTAGE SAG AT 1.3p.u FOR DLG FAULT

    FIG: VOLTAGE SAG AT 1.4p.u FOR TPG FAULT

    39

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    40/51

    FIG: VOLTAGE SAG AT 1.41p.u FOR LL FAULT

    From the figure we can see the voltage sag i.e., the reduction in voltage.

    For different values of fault resistances we get different types of waveforms.

    Here we can see the waveforms for different types of faults. The wave forms are

    greater than 0.9 p.u which shows that there is a improvement in voltage sag.

    40

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    41/51

    7.6 OUTPUT WAVE FORMS OF DSTATCOM WITH LCL PASSIVE

    FILTER:

    The power gui opens an FFT analysis which gives the output wave

    forms

    0 0 . 0 5 0 . 1 0 . 1 5 0 . 2 0 . 2 5 0 . 3

    - 0 . 5

    0

    0 . 5

    S e l e c t e d s i g n a l : 1 5 c y c l e s . F F T w i

    T i m e ( s )

    0 5 1 0 1 5 2 00

    0 . 2

    0 . 4

    0 . 6

    0 . 8

    H a r m o n i c o r d e r

    F u n d a m e n t a l ( 5 0 H z ) = 1 , T H D .

    M

    ag

    (%

    ofFundam

    ental)

    FIG: OUTPUT WAVEFORMS OF DSTATCOM WITH

    LCL PASSIVE FILTER

    41

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    42/51

    7.7 SIMULINK MODEL OF DSTATCOM WITHOUT LCL PASSIVE

    FILTER:

    42

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    43/51

    FIG: SIMULINK TEST MODEL FOR DSTATCOM WITHOUT

    LCL PASSIVE FILTER

    RESULTS:

    7.7.1 OUTPUT WAVEFORMS OF DSTATCOM WITHOUT LCL PASSIVE

    FILTER:

    0 0 . 0 5 0 . 1 0 . 1 5 0 . 2 0 . 2 5 0 . 3

    - 0 . 0 5

    0

    0 . 0 5

    S e l e c t e d s i g n a l : 1 5 c y c l e s . F :

    T i m e ( s )

    0 5 1 0 1 5 2 00

    1

    2

    3

    4

    5

    6

    H a r m o n i c o r d e r

    F u n d a m e n t a l ( 5 0 H z ) = 8 . 8 2

    M

    ag

    (%

    ofFundam

    ental)

    FIG: OUTPUT WAVEFORM OF DSTATCOM WITHOUT

    LCL PASSIVE FILTER:

    43

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    44/51

    CHAPTER-8

    CONCLUSION

    Power quality in electric networks is one of today's most concerned

    areas of electric power system. The power quality has serious economic

    implications for consumers, utilities and electrical equipment manufacturers.

    Most occurring power quality problems are voltage sag and total

    harmonic distortion. These are due to faults such as increase in load while

    starting a motor, transformer energizing etc., The impact of power qualityproblems is increasingly felt by customers - industrial, commercial and even

    residential.

    In this project we discuss about the improvement of voltage sag in

    distribution system using DSTATCOM and reduction of total harmonic

    distortion by using LCL passive filter with DSTATCOM in Distribution system.

    Atlast we have seen the output waveforms regarding them using

    Matlab/simulink.

    44

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    45/51

    45

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    46/51

    ENHANCEMENT OF POWER QUALITY

    DISTRIBUTION SYSTEM USING D-STATCOM

    INDEX

    Abstract

    List of Figures:

    List of Tables:

    CHAPTER-1: MATLAB INTRODUCTION 1-30

    CHAPTER-2: INTRODUCTION 31-33

    2.1LITERATURE SURVEY

    2.2SCOPE OF WORK

    CHAPTER-3: POWER QUALITY 34-40

    3.1 INTRODUCTION

    3.2 POWER QUALITY-A BIG ISSUE

    3.3 PROBLEMS ASSOCIATED WITH POWER QUALITY

    3.3.1 MOMENTARY PHENAMINA

    3.3.1.1 TRANSIENTS

    3.3.1.2 LONG DURATION VOLTAGE VARIATIONS

    3.3.1.3 SUSTAINED INTURRUPTION

    3.3.1.4 SHORT DURATION VOLTAGE VARIATIONS

    3.3.2 STEADY STATE PHENMINA

    3.3.2.1 WAVE FORM DISTORTION

    3.3.2.2 VOLTAGE IMBALANCE

    3.3.3 VOLTAGE FLUCTUVATIONS AND FLICKERS

    3.3.4 POWER FREQUANCY VARIATIONS

    46

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    47/51

    3.4 SOLUTIONS OF POWER PROBLEMS

    3.4.1 THYRISTER BASED STATIC SWITCHES

    3.4.2 ENERGY STORAGE SYSTEM

    CHAPTER-4: CUSTOM POWER DEVICES 41-47

    4.1 INTRODUCTION

    4.2 NEED OF CUSTOM POWER DEVICES

    4.3 CONFIGURATIONS

    4.3.1 CONVERTER BASED CLASIFICATION

    4.3.2 TOPOLOGY BASED CLASIFICATION

    4.4 BENEFITS WITH THE APPLICATION OF CUSTOM

    POWER DEVICES

    CHAPTER-5: D-STATCOM 48-53

    5.1 INTRODUCTION

    5.2 PRINCIPLE OF D-STATCOM

    5.3 BASIC ARRANGEMENTS OF D-STATCOM

    5.3.1 VOLTAGE SOURCE CONVERTER

    5.3.2 ENERGY STORAGE DEVICE

    5.3.3 LCL PASSIVE FILTER

    5.3.4 CONTROLLER

    CHAPTER-6: POWER PROBLEMS IN D-STATCOM 54-66

    6.1 VOLTAGE SAG

    6.1.1 CHARACTERSTICS OF VOLTAGE SAG

    47

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    48/51

    6.1.2 VOLTAGE GENERATING ANALYSIS-

    METHODOLOGY

    6.1.2.1 VOLTAGE SAG CALCULATIONS

    6.2. STEADY OF RESULT SAG CALCULATIONS

    6.3 SOLUTION OF VOLTAGE SAG PROBLEMS

    6.4 TOTAL HORMONIC DISTORTION

    6.5 MINIMISATION OF HORMONICS

    CHAPTER-7: D-STATCOM TEST MODELS 67-79

    7.1 D-STATCOM TEST SYSTEM

    7.2 METHODOLOGY

    7.2.1 PROCEDURE

    7.3 SIMULINK MODEL FOR THE TEST SYSTEM

    7.4 RESULTS WITHOUT D-STATCOM

    7.5 RESULTS WITH D-STATCOM

    7.6 OUTPUT WAVE FORM OF D-STATCOM WITH LCL

    PASSIVE FILTER

    7.7 SIMULINK MODEL OF D-STATCOM WITH OUT LCL

    PASSIVE FILTER

    7.7.1 OUTPUT WAVE FORM OF D-STATCOM WITHOUT

    LCL PASSIVE FILTER

    CHAPTER-8: CONCLUSION 80

    48

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    49/51

    LIST OF FIGURES:

    FIGURE NUMBER NAME OF THE

    FIGURE

    PAGENO

    5.2.2 45

    5.2.3(a) 48

    5.2.3(b) 49

    50

    LIST OF TABLES:

    TABLE NUMBER NAME OF THE

    TABLE

    PAGE NO

    2.2 Types of HT Motors 23

    ABSTRACT

    49

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    50/51

    This project presents the enhancement of voltage sags, harmonic

    distortion using Distribution Static Compensator (D-STATCOM) with LCL

    Passive Filter in distribution system. The model is based on the Voltage Source

    Converter (VSC) principle. The D-STATCOM injects a current into the system

    to mitigate the voltage sags. LCL Passive Filter was then added to D-

    STATCOM to improve harmonic distortion and low power factor.

    A new PWM-based control scheme has been implemented to control the

    electronic valves in the D-STATCOM. The D-STATCOM has an additional

    capability to sustain reactive current at low voltage, and can be developed as a

    voltage and frequency support by replacing capacitors. Voltage sag is a short

    time event during which a reduction in r.m.s voltage magnitude occurs. Voltage

    sags are improved with insertion of D-STATCOM. When the value of fault

    resistance is increased, the voltage sags will also increase for different types of

    fault.

    Suitable adjustment of the phase and magnitude of the D-STATCOM

    output voltages allows effective control of active and reactive power exchanges

    between D-STATCOM and AC system. The PI controller will process the

    error signal to zero. The load r.m.s voltage is brought back to the reference

    voltage by comparing the reference voltage with the r.m.s voltages that had

    been measured at the load point. It also is used to control the flow of reactive

    power from the DC capacitor storage circuit. The PWM generator can produce

    the desired synchronizing signal that is required. PWM generator also receives

    the error signal angle from PI controller.

    The modulated signal is compared against a signal in order to generate

    the switching signals for VSC valves. To enhance the performance of

    distribution system, D-STATCOM was connected to the distribution system.

    50

  • 8/2/2019 Enhancement of Power Quality Using Dstatcom

    51/51