Draft 25 March 2004 Forthcoming in the Association of Facility Engineers Newsletter Energy Management in Cleanrooms: From The Lab to the Marketplace Evan Mills Lawrence Berkeley National Laboratory Lawrence Berkeley Laboratory is working to improve energy efficiency in high-tech facilities i.e. laboratories, data centers, and cleanrooms. With their high ventilation requirements and correspondingly high process loads, 7x24 operation, and importance to the overall economy, these types of facilities offer important (and often under-exploited) potential for energy savings. In California alone, two large electric power plants could be avoided with the widespread adoption of measures to improve energy efficiency in this arena, saving half a billion dollars per year for facility owners. To help identify specific promising opportunities, the California Energy Commission sponsored the development of technology research “Roadmaps” for cleanrooms and laboratories (in 2002) and data centers (in 2003). These were developed with industry participation and provided dozens of specific recommendations. The balance of this article focuses on the case of cleanrooms. What’s Your Cleanroom’s Energy IQ?: Benchmarking and Identifying Best Practices Energy benchmarking can help identify “Best Practices” and establish performance targets for utility incentive programs or in-house energy management goal-setting. LBNL has benchmarked fourteen cleanrooms thus far, with a new series underway. Our results show that indicators of energy efficiency vary widely [Figure 1]. In addition to characterizing the energy use profiles, careful examination often reveals other operational issues such as unintended cooling tower cycling [Figure 2], or chiller part-load efficiency variation (by a factor of two) [Figure 3]. Efficient Air Movement: Evaluating Fan Filter Units (FFUs) The benchmarking results have also revealed a wide variation in recirculation air systems performance. Examination of the results revealed a tendency for cleanrooms with FFUs to have poorer efficiency (expressed as cfm/kW) than other air-distribution strategies. In addition, huge variations in FFUs performance were observed in test results performed by ITRI in Taiwan [Figure 4]. LBNL is helping to address designer and end-user needs for better information on FFU performance. Currently there is no way to compare one unit’s energy performance to another’s because they are not tested and rated in a standard fashion. LBNL is working with IEST to develop such a standardized procedure. Standard reporting of performance will also help utilities and others develop incentive programs or other initiatives.

Upload: others

Post on 08-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Energy Management in Cleanrooms: From The Lab ... - High Tech · What’s Your Cleanroom’s Energy IQ?: Benchmarking and Identifying Best Practices Energy benchmarking can help identify

Draft 25 March 2004

Forthcoming in the Association of Facility Engineers Newsletter

Energy Management in Cleanrooms: From The Lab to the Marketplace

Evan MillsLawrence Berkeley National Laboratory

Lawrence Berkeley Laboratory is working to improve energy efficiency in high-techfacilities i.e. laboratories, data centers, and cleanrooms. With their high ventilationrequirements and correspondingly high process loads, 7x24 operation, and importance tothe overall economy, these types of facilities offer important (and often under-exploited)potential for energy savings. In California alone, two large electric power plants could beavoided with the widespread adoption of measures to improve energy efficiency in thisarena, saving half a billion dollars per year for facility owners.

To help identify specific promising opportunities, the California Energy Commissionsponsored the development of technology research “Roadmaps” for cleanrooms andlaboratories (in 2002) and data centers (in 2003). These were developed with industryparticipation and provided dozens of specific recommendations.

The balance of this article focuses on the case of cleanrooms.

What’s Your Cleanroom’s Energy IQ?: Benchmarking and Identifying BestPractices

Energy benchmarking can help identify “Best Practices” and establish performancetargets for utility incentive programs or in-house energy management goal-setting.LBNL has benchmarked fourteen cleanrooms thus far, with a new series underway. Ourresults show that indicators of energy efficiency vary widely [Figure 1]. In addition tocharacterizing the energy use profiles, careful examination often reveals other operationalissues such as unintended cooling tower cycling [Figure 2], or chiller part-load efficiencyvariation (by a factor of two) [Figure 3].

Efficient Air Movement: Evaluating Fan Filter Units (FFUs)

The benchmarking results have also revealed a wide variation in recirculation air systemsperformance. Examination of the results revealed a tendency for cleanrooms with FFUsto have poorer efficiency (expressed as cfm/kW) than other air-distribution strategies. Inaddition, huge variations in FFUs performance were observed in test results performed byITRI in Taiwan [Figure 4]. LBNL is helping to address designer and end-user needs forbetter information on FFU performance. Currently there is no way to compare one unit’senergy performance to another’s because they are not tested and rated in a standardfashion. LBNL is working with IEST to develop such a standardized procedure.Standard reporting of performance will also help utilities and others develop incentiveprograms or other initiatives.

Page 2: Energy Management in Cleanrooms: From The Lab ... - High Tech · What’s Your Cleanroom’s Energy IQ?: Benchmarking and Identifying Best Practices Energy benchmarking can help identify

Draft 25 March 2004

The Potential for Mini Environments

The use of mini cleanroom environments is on the rise. If mini-environments can be usedin place of large cleanrooms, energy savings (and quality control) can be improvedconsiderably. However, it is common for mini-environments to be placed inside ofstandard large cleanrooms. If the cleanliness standards are relaxed in the larger room,then significant energy savings can be attained, but this is not necessarily done today.LBNL is investigating the energy efficiency opportunity, in collaboration withSEMATECH.

From Rules of Thumb to Performance-Based Controls: Demand-ControlledFiltration

Cleanrooms typically maintain a constant airflow, irrespective of the actual level ofcleanliness. The concept of demand-controlled filtration allows airflow to be variedbased on real-time particle counts. This shift towards a performance-based controlstrategy promises to garner considerable energy savings, with better real-time feedbackon cleanroom environmental conditions. LBNL is performing a proof-of-conceptdemonstration in a small cleanroom, and will subsequently conduct a workshop todiscuss the results with practitioners.

Improved Tools for Design and Planning

LBNL has developed a suite of tools to help cleanroom and laboratory designers andplanners make better use of energy efficiency, while fostering increased communicationand shared goals among owners and design team members. The Laboratory DesignGuide inventories a wide range of technologies and design strategies, with extensive linksto in-depth documentation. The Cleanroom Programming Guide gives owners anddesigners an awareness of efficiency related issues to consider early in the project toavoid inadvertently “locking in” inefficiencies. Lastly, the Design Intent Tool provides aconvenient method for documenting design objectives and associated performance goalsand targets.

Demonstration Projects: From Concept to Application

An essential complement to the LBNL research program is conducting full-scaledemonstrations in industrial settings. LBNL and the California Energy Commission areseeking ideas for novel technologies and practices, and industry sites willing toparticipate in controlled demonstrations. Interested parties can contact William Tschudiat [email protected].

* * *Sponsors of the research described here include the California Energy Commission(Public Interest Energy Research), the California Institute for Energy Efficiency, the U.S.Department of Energy, the U.S. Environmental Protection Agency (via Labs21), PacificGas and Electric Company, and San Diego Gas and Electric Company. For Moreinformation, see http://ateam.lbl.gov

Page 3: Energy Management in Cleanrooms: From The Lab ... - High Tech · What’s Your Cleanroom’s Energy IQ?: Benchmarking and Identifying Best Practices Energy benchmarking can help identify

Draft 25 March 2004

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

11000

Fac. A

Class 10 Press.Plen.

Fac. A

Class 100Press.Plen.

Fac. B.1

Class 100 Ducted

Fac. B.1

Class 100 FFU

Fac. B.2

Class 100 Ducted

Fac. B.2

Class 100 FFU

Fac. C

Class 100 Press.Plen.

Fac. D

Class 10Ducted

Fac. E

Class 100FFU

Fac. E

Class 100Press.Plen.

Fac. F

Class 10Press.Plen.

Fac. F

Class 10Press.Plen.

Fac. F

Class 10Press.Plen.

Fac. F

Class 10k

CF

M / k

W (

hig

her

is b

ett

er)

Averages (cfm / kW)FFU: 1664

Ducted: 1733Pressurized Plenum: 5152

Overall Average 3440

Figure 1. Cleanroom benchmarking results (Chiller CFM/kW)Figure 1. Cleanroom benchmarking results (recirculation air, CFM/kW)

Tower #2 Cell B Power

05101520253035

0:00 0:10 0:20 0:30 0:40 0:50 1:00

Time: Hour; June 16, 2000

Po

we

r (k

W)

Figure 2. Unintended cooling tower cycling. Figure 3. Chiller efficiency variation.

Chillers Efficiency

0

0.2

0.4

0.6

0.8

1

0 200 400 600 800 1000 1200 1400

Ton

kW/T

on