energy 408-859-5415€¦ · this document contains proprietary information of "free hot...

8
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF "FREE HOT WATER", AND ITS POSSESSION DOES NOT CONSTITUTE ANY RIGHTS TO REPRODUCE, DISCLOSE ITS CONTENTS, OR TO MANUFACTURE, UTILIZE, OR SELL ANYTHING IT MAY DESCRIBE. REPRODUCTION, DISCLOSURE OR USE WITHOUT EXPRESSED WRITTEN PERMISSION OF "FREE HOT WATER" IS FORBIDDEN. ENERGY 408-859-5415 AREA OF WORK

Upload: others

Post on 24-Apr-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS

POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS

CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.

REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION

OF "FREE HOT WATER" IS FORBIDDEN.

ENER

GY

408-

859-

5415

AREA OFWORK

Page 2: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS

POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS

CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.

REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION

OF "FREE HOT WATER" IS FORBIDDEN.

ENER

GY

408-

859-

5415

Salt Controller &Sensor

Chlorking & CO-2 controlled bychemical controller

Chlorking Chlor-25SM Controllers

3 x Chlorking Cells,25 lb per day each

pH 7.4 On 7.4

ORP 750 Off 752

Flow Switch On

Temperaure: 81

ControllerSample Stream

CO-2Supply

Page 3: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS

POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS

CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.

REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION

OF "FREE HOT WATER" IS FORBIDDEN.

ENER

GY

408-

859-

5415

pH 7.4 On 7.4

ORP 750 Off 752

Flow Switch On

Temperaure: 81

ControllerSample StreamSalt Controller &

Sensor

Chlorking & CO-2 controlled bychemical controller

CO-2Supply

Chlorking Chlor-25 Controller

Chlorking Cell,25 lb per day

Page 4: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS

POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS

CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.

REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION

OF "FREE HOT WATER" IS FORBIDDEN.

ENER

GY

408-

859-

5415

Page 5: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

THIS DOCUMENT CONTAINS PROPRIETARYINFORMATION OF "FREE HOT WATER", AND ITS

POSSESSION DOES NOT CONSTITUTE ANYRIGHTS TO REPRODUCE, DISCLOSE ITS

CONTENTS, OR TO MANUFACTURE, UTILIZE, ORSELL ANYTHING IT MAY DESCRIBE.

REPRODUCTION, DISCLOSURE OR USEWITHOUT EXPRESSED WRITTEN PERMISSION

OF "FREE HOT WATER" IS FORBIDDEN.

ENER

GY

408-

859-

5415

Page 6: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

1/16" = 1'-0"GRAPHIC SCALES:

5'0 50' 0 5'

1/8" = 1'-0" 1/4" = 1'-0"

25' 0 1' 12'

1/2" = 1'-0"

0 1' 6' 0

1" = 1'-0"3/4" = 1'-0"

4' 0 1' 3'

A REDUCED PRINT SCALE ACCORDINGLY

IF THIS SHEET IS NOT 24"x36" , IT IS

Facility

Project

Sheet Title

Permit No.:

Sheet

Drawn By:

Checked By:

Issue Date:

Scale: AS NOTED

07/15/2016

NWB

NWB

LANEY COLLEGE900 FALLON STREETOAKLAND, CA 94607

Whittington

Electric, Inc.Engineering / Commercial / Industrial

1940 Industrial Drive • Auburn, CA 95603

Office (530) 823-3055 • Fax (530) 823-3066

WEI Project#: 215-095

LANEY COLLEGE POOLBOILER REPLACEMENT

REVIEW SET - NOT FOR CONSTRUCTION

E0

ELECTRICAL SHEET INDEX,

SYMBOL LIST, ABBREVIATIONS,

PANEL SCHEDULES, LOAD

CALCULATION, ONE-LINE DIAGRAM,

AND CONNECTION SCHEDULE

Panel: Panel "EPH"Location: Lower Mechanical Area Volts: 277/480V Wye Mains: 100A Main Breaker

Supply From: 0 Phases: 3 Bus Rating: 100A

Mounting: Surface Wires: 4 AIC Rating: -

Load DescriptionLoad (VA) Circuit Breaker Ckt

#Ckt#

Circuit Breaker Load (VA)Load Description

A B C Amp Pole Amps Poles A B C

(R) ChlorTec 0 20 3 1 2 15 3 0 (E) Spare

- 0 - - 3 4 - - 0 -

- 0 - - 5 6 - - 0 -

(E) Spare 0 15 3 7 8 15 3 0 (E) Spare

- 0 - - 9 10 - - 0 -

- 0 - - 11 12 - - 0 -

(E) 5HP Dive Pool Pump 2100 15 3 13 14 70 3 9350 (E) 20HP Lap Pool Pump

- 2100 - - 15 16 - - 9350 -

- 2100 - - 17 18 - - 9350 -

Space - 1 19 20 - 1 Space

Space - 1 21 22 - 1 Space

Space - 1 23 24 - 1 Space

Space - 1 25 26 - 1 Space

Space - 1 27 28 - 1 Space

Space - 1 29 30 - 1 Space

Notes:1.

Totals

kVA Amps

Phase A 11.5 31.79

Phase B 11.5 31.79

Phase C 11.5 31.79

Total 34.4 41.32

EXISTING ELECTRICAL BRANCH CIRCUIT PANEL - SURFACE MOUNTED

NON-FUSED SAFETY SWITCH DISCONNECT. SIZE AS NOTED.

NEW CONDUIT WITH WIRING AS NOTED ON PLANS.

EXISTING CONDUIT WITH WIRING TO BE REMOVED.

NUMBERED SHEET NOTE TAG. REFER TO MATCHING NUMBERED

SHEET NOTE ON SAME SHEET.

ELECTRICAL MOTOR - SIZED IN AS NOTED (EXAMPLE 5HP).

SYMBOL LIST

E0 ELECTRICAL SHEET INDEX, SYMBOL LIST, ABBREVIATIONS, PANEL

SCHEDULES, LOAD CALCULATIONS, ONE-LINE DIAGRAM AND CONNECTION

SCHEDULE

E1 MECHANICAL AREA - UPPER LEVEL - ELECTRICAL

E2 MECHANICAL AREA - LOWER LEVEL - ELECTRICAL

E3 ELECTRICAL SPECIFICATIONS

SHEET INDEX

ABBREVIATIONS

A AMPERE

AFF ABOVE FINISHED FLOOR

C CONDUIT

CKT CIRCUIT

CB CIRCUIT BREAKER

DIA DIAMETER

(E) EXISTING

FLA FULL LOAD AMPERES

(F) FUTURE

GALV GALVANIZED

GFCI GROUND-FAULT CIRCUIT

INTERRUPTER

HZ HERTZ

JB JUNCTION BOX

KVA KILOVOLT AMPERE

KW KILOWATT

LT LIGHT

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.S. NURSE STATION

NTS NOT TO SCALE

OC ON CENTER

PNL PANEL

PH PHASE

(R) REMOVE

RCPT RECEPTACLE

SM SHEET METAL

SMS SHEET METAL SCREW

SWBD SWITCHBOARD

TYP. TYPICAL

V VOLT

VA VOLT AMPERE

W WATT

WP WEATHERPROOF

1

5

1PARTIAL ONE-LINE POWER DIAGRAMSCALE: NONE

(E)

70/3

(E) PANEL "EPH"

100A, 480Y/277V, 3ɸ, 4W

(E)

100/3

(E) FEEDER

(E)

15/3

(N)

70/3

(N) 1" C.,

(3) #4, AND

(1) #8 GND.

(N) PANEL "EPL2"

100A, 208Y/120V, 3ɸ, 4W

(N) XFMR "TEPL2"

30 KVA, 480-208Y/120V, 3ɸ, 4W

(N) 1-1/4" C.,

(4) #2, AND

(1) #8 GND.

(N)

100/3

(N)

60/2

(N)

60/2

(N)

30/2

(N)

45/2

(N)

20/2

(N)

20/2

(N)

20/2

(N)

20/1

20 5

(E) FEEDER

(E) FEEDER (E) FEEDER

(E) VFD (E) VFD

(E) LAP POOL PUMP (E) DIVE POOL PUMP

TO BE REPLACED

IN KIND

1 1 13

P

3

P

1

P

2

P

4

JJJJ

SEE MECHANICAL

EQUIPMENT CONNECTION

SCHEDULE FOR CONDUIT

AND CONDUCTOR SIZING

DISCONNECT PER

MECHANICAL EQUIPMENT

CONNECTION SCHEDULE,

TYPICAL OF (7)

SM

-1

CH

LO

R 4

0 #

1

CH

LO

R 4

0 #

2

CH

LO

R 2

5S

M

(E)

(E) FEEDER

Panel: Panel "EPL2"Location: Lower Mechanical Area Volts: 120/208V Wye Mains: 100A Main Breaker

Supply From: Panel "EPH" via Xfmr"TEPL2"

Phases: 3 Bus Rating: 100A

Mounting: Surface Wires: 4 AIC Rating: Match existing AIC

Load DescriptionLoad (VA) Circuit Breaker Ckt

#Ckt#

Circuit Breaker Load (VA)Load Description

A B C Amp Pole Amps Poles A B C

CHLOR 40 #1 [1] 3328 60 2 1 2 916 Pump P-1

- 3328 - - 3 4 916 -

CHLOR 40 #2[1] 3328 60 2 5 6 916 Pump P-2

- 3328 - - 7 8 916 -

CHLOR 25SM [1] 1560 30 2 9 10 1945 Pump P-3

- 1560 - - 11 12 1945 -

Space - 1 13 14 - 1 916 Pump P-4

Space - 1 15 16 - 1 916 -

Space - 1 17 18 - 1 1320 SM-1

Space - 1 19 20 - 1

Space - 1 21 22 -

Notes:1. Provide new GFCI circuit breaker with rating indicated matching existingbreaker type and AIC ratings.

Totals

kVA Amps

Phase A 9.4 26.11

Phase B 8.7 24.06

Phase C 9.1 25.18

Total 27.1 75.34

ELECTRICAL LOAD CALCULATION FOR PANEL EPH

Phase

A B C A+B+C

20 HP Lap Pool Pump 9.35 kVA 9.35 kVA 9.35 kVA 28.05 kVA

+25% Largest Motor Load 2.34 kVA 2.34 kVA 2.34 kVA 7.01 kVA

5 HP Dive Pool Pump 2.10 kVA 2.10 kVA 2.10 kVA 6.30 kVA

(N) CHLOR 25SM 0.00 kVA 1.56 kVA 1.56 kVA 3.12 kVA

(N) CHLOR 40 3.30 kVA 3.30 kVA 0.00 kVA 6.60 kVA

(N) CHLOR 40 3.30 kVA 0.00 kVA 3.30 kVA 6.60 kVA

(N) P-1 0.90 kVA 0.90 kVA 0.00 kVA 1.80 kVA

(N) P-2 0.90 kVA 0.00 kVA 0.90 kVA 1.80 kVA

(N) P-3 0.00 kVA 1.95 kVA 1.95 kVA 3.90 kVA

(N) P-4 0.90 kVA 0.90 kVA 0.00 kVA 1.80 kVA

(N) SM-1 0.00 kVA 0.00 kVA 1.32 kVA 1.32 kVA

Total Load kVA ( Existing and New) 23.09 kVA 22.40 kVA 22.82 kVA 68.30 kVA

Total Load Amps ( Existing and New) 192.40 A 186.65 A 190.15 A 82.16 A

Therefore 100A Panel, Breaker, and Feeder have capacity for the added load.

Notes:1. Existing loads calculated per 2013 CEC 430.2.

MECHANICAL EQUIPMENT CONNECTION SCHEDULE

EQUIPMENT DATA POWER SUPPLY CONDUIT & WIRE DISCONNECT SWITCH

NO

TE

S

DESIGNATION LOCATION

HP

OR

KW

FLA

MC

A

MO

CP

PH

AS

E

VO

LT

S

BR

EA

KE

R

PO

LE

S

PANELBOARD

OR MCCCKT # QUANTITIES AND SIZE

TYPE LOCATION SIZE

FU

SE

D (

F)

OR

NO

N-F

US

ED

(NF

)

AT

UN

IT

INT

EG

RA

L

FU

SE

SIZ

E

NE

MA

EN

CL.

RA

TIN

G

SM-1 LOWER LEVEL - 1.0 A - - 1 120 V 20 A 1 EPL2 18 (N) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 1

P1 UPPER LEVEL 1 HP 8.8 A 11.0 A 20.0 A 1 208 V 20 A 2 EPL2 2,4 (N) 1/2"C, (2) #12 & (1) #12 GND F X - 20 A 3R 30A/2P 3

P2 UPPER LEVEL 1 HP 8.8 A 11.0 A 20.0 A 1 208 V 20 A 2 EPL2 6,8 (N) 1/2"C, (2) #12 & (1) #12 GND F X - 20 A 3R 30A/2P 3

P3 UPPER LEVEL 3 HP 18.7 A 24.0 A 45.0 A 1 208 V 45 A 2 EPL2 10,12 (N) 1/2"C, (2) #8 & (1) #10 GND F X - 45 A 3R 60A/2P 3

P4 UPPER LEVEL 1 HP 8.8 A 11.0 A 20.0 A 1 208 V 20 A 2 EPL2 14,16 (N) 1/2"C, (2) #12 & (1) #12 GND F X - 20 A 3R 30A/2P 3

CHLOR 25 UPPER LEVEL - 15.0 A - - 1 208 V 30 A 2 EPL2 9,11 (N) 1/2"C, (2) #10 & (1) #10 GND NF X - - 3R 30A/2P 3

CHLOR 40-1 UPPER LEVEL - 32.0 A - - 1 208 V 60 A 2 EPL2 1,3 (N) 3/4"C, (2) #6 & (1) #10 GND NF X - - 3R 60A/2P 3

CHLOR 40-2 UPPER LEVEL - 32.0 A - - 1 208 V 60 A 2 EPL2 5,7 (N) 3/4"C, (2) #6 & (1) #10 GND NF X - - 3R 60A/2P 3

BLR-1 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2

BLR-2 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2

BLR-3 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2

BLR-4 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2

BLR-5 LOWER LEVEL - 5.0 A - - 1 120 V 20 A 1 - - (E) 1/2"C, (2) #12 & (1) #12 GND - - - - - - 2

Notes:

1. Mechanical to provide (1) SM-1 per sensor. See mechanical drawings.

2. Re-use existing circuits. Replacement in kind. No load chance.

3. Coordinate location with mechanical. See mechanical drawings.

Page 7: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

LOCATION OF NEW CHLORINATOR EQUIPMENT, COORDINATE WITH MECHANICAL

(R) CHLORINATION EQUIPMENT(R) DISCONNECT, EPH-1,3,5 1 1

1/16" = 1'-0"GRAPHIC SCALES:

5'0 50' 0 5'

1/8" = 1'-0" 1/4" = 1'-0"

25' 0 1' 12'

1/2" = 1'-0"

0 1' 6' 0

1" = 1'-0"3/4" = 1'-0"

4' 0 1' 3'

A REDUCED PRINT SCALE ACCORDINGLY

IF THIS SHEET IS NOT 24"x36" , IT IS

Facility

Project

Sheet Title

Permit No.:

Sheet

Drawn By:

Checked By:

Issue Date:

Scale: AS NOTED

07/15/2016

NWB

NWB

LANEY COLLEGE900 FALLON STREETOAKLAND, CA 94607

Whittington

Electric, Inc.Engineering / Commercial / Industrial

1940 Industrial Drive • Auburn, CA 95603

Office (530) 823-3055 • Fax (530) 823-3066

WEI Project#: 215-095

LANEY COLLEGE POOLBOILER REPLACEMENT

REVIEW SET - NOT FOR CONSTRUCTION

1MECHANICAL AREA - UPPER LEVEL - NEW ELECTRICALSCALE: 3/4" = 1'-0"

E1

MECHANICAL AREA FLOOR

PLAN - UPPER LEVEL -

ELECTRICAL

REMOVE EXISTING DISCONNECT, CONDUIT AND CONDUCTORS TO EXISTING

CHLORINATION EQUIPMENT.

NUMBERED SHEET NOTES1

2PARTIAL MECHANICAL AREA - UPPER LEVEL - DEMO ELECTRICALSCALE: 3/4" = 1'-0"

Page 8: ENERGY 408-859-5415€¦ · this document contains proprietary information of "free hot water", and its possession does not constitute any rights to reproduce, disclose its

(5) BOILERS TO BE REPLACED IN KIND

5 20

(E) VFD, DIVE POOL PUMP

(E) VFD, LAP POOL PUMP

(N) 5HP DIVE POOL PUMP (E) 20HP LAP POOL PUMP

(E) PANEL "EPL"

(E) PANEL "EPH"

(E) ELECTRICAL GUTTER

(R) ABANDONED FUSED DISCONNECTS

8

7

6

54

2

3

1

(E) PANEL "EPL2" (E) XFMR "TEPL2"109

1/16" = 1'-0"GRAPHIC SCALES:

5'0 50' 0 5'

1/8" = 1'-0" 1/4" = 1'-0"

25' 0 1' 12'

1/2" = 1'-0"

0 1' 6' 0

1" = 1'-0"3/4" = 1'-0"

4' 0 1' 3'

A REDUCED PRINT SCALE ACCORDINGLY

IF THIS SHEET IS NOT 24"x36" , IT IS

Facility

Project

Sheet Title

Permit No.:

Sheet

Drawn By:

Checked By:

Issue Date:

Scale: AS NOTED

07/15/2016

NWB

NWB

LANEY COLLEGE900 FALLON STREETOAKLAND, CA 94607

Whittington

Electric, Inc.Engineering / Commercial / Industrial

1940 Industrial Drive • Auburn, CA 95603

Office (530) 823-3055 • Fax (530) 823-3066

WEI Project#: 215-095

LANEY COLLEGE POOLBOILER REPLACEMENT

REVIEW SET - NOT FOR CONSTRUCTION

1MECHANICAL AREA - LOWER LEVEL - ELECTRICALSCALE: 3/4" = 1'-0"

E2

MECHANICAL AREA FLOOR

PLAN - LOWER LEVEL -

ELECTRICAL

(R) ABANDONED CONDUIT

EXISTING BOILERS TO BE REPLACED IN KIND. NO CHANGE IN PANEL/CIRCUIT

LOADS.

EXISTING 480/277V, 3 PHASE, 4 WIRE PANEL. SEE PANEL SCHEDULE, SHEET

"E0".

EXISTING 208/120V, 3 PHASE, 4 WIRE PANEL.

EXISTING 5 HP DIVE POOL PUMP MOTOR TO BE REPLACE IN KIND. NO LOAD

CHANGE. PROVIDE MEGGER TEST ON PHASE CONDUCTORS TO VERIFY

CONDUCTOR INSULATION CONDITION. REPLACE CONDUCTORS IN KIND IF

NECESSARY.

EXISTING 20 HP LAP POOL PUMP MOTOR TO REMAIN. PROVIDE MEGGER TEST

ON PHASE CONDUCTORS TO VERIFY CONDUCTOR INSULATION CONDITION.

REPLACE CONDUCTORS IN KIND IF NECESSARY.

REMOVE EXISTING FUSED DISCONNECTS. CIRCUIT BREAKERS ARE WITHIN

LINE OF SITE AND OF SUITABLE RATING FOR SHORT-CIRCUIT AND GROUND

FAULT PROTECTION OF CONDUCTORS. RELOCATE CONDUCTOR SPLICES INTO

ELECTRICAL GUTTER ABOVE.

IDENTIFY AND PROVIDE LABELS FOR ALL CIRCUIT CONDUCTORS IN GUTTER.

REMOVE ABANDONED CONDUITS AND PROVIDE KNOCKOUT SEALS.

REMOVE ABANDONED CONDUIT. EXISTING CAT CABLE TO REMAIN, PROVIDE

NEW CABLE SUPPORTS ALONG CONCRETE WALL.

PROVIDE NEW BRANCH CIRCUIT PANEL. SEE ONE-LINE DIAGRAM AND PANEL

SCHEDULE, SHEET "E0".

PROVIDE NEW TRANSFORMER. SEE ONE-LINE DIAGRAM, SHEET "E0". EXTEND

HOUSE KEEPING PAD AS NECESSARY.

NUMBERED SHEET NOTES1

2

3

4

5

6

7

8

9

10