Enclosure heat exchanger
Lower the temperature of an enclosure interior
without allowing entry of heat, dust and moisture
https://www.ohm.jp/
Features
1) Versatile lineup
2) Keep air cleanBOXFAN brings interior temperature close to outside air effectively while keeping dust and mist away.
To meet customers’ demand for global usage,BOXFAN Standard series and OC-153H-A** are UL-listed and CE series is CE-marked.
3) Worldwide use
Avaialble from Standard, Compact and CE-marked series
Operating principle
Heat exchange in the Radiation fin
1) Heated air inside an enclosure circulates as pictured right to transfer heat to the radiation fin.2) Cool air outside an enclosure circulates to take away heat from the fin to the outside.The above cycle is repeated and the internal air temperaturefalls to near the external air temperature.
BOXFAN’s radiation fin is specially designed so as hot internal air and cold external air flows in the opposite direction in adjacentfins. Thus, efficient heat exchange takes place.
Internal airExternal air
Radiation fin
Heated air
Outer air
ex. internal mounting
– 1 –
Application examples
Site of use
Electrical connection of terminal block
Mounting
For control panels of NC machines, robots, measuring instrument and distribution panels
NC machine toolsWelding robotsElectric discharge machines Power electronics
Machining plant Welding shop Spinnery Foundry Sheet-metal plant Paper mill
Do not expose to direct sunshine or rain.
Internal lateral mounting External lateral mounting
Note : Mounting cutouts differ by type of mounting.
Terminal block (with terminal cover)
Notes: 1. Supply voltage should be as specified on the rating plate.
2. Use crimp terminals with insulation cap for power connection.
3. OC-201L, OC-0810HIL and OC-0820HIL are equipped with a power code. 4. Average tightening torque is 1.4N・m(14kgf・cm). 5. M4 screws are used in the terminal block.
OC-15-A※※ OC-15S-A※※
Power Earth
UL-listed standard models for wide application■ How to see model
1 :Working voltage 100V AC
2 :Working voltage 200V AC
OC-□□□-A□00
■ SpecificationsModel Rated capactiy W/K (※1) Rated voltage
(※2)Current consumption Power consumption
50Hz 60Hz 50Hz 60Hz 50Hz 60Hz
OC-15-A100
OC-17-A100
8 10 6.2kg
Single phase 100-120VACSingle phase200-230VAC
Single phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VAC
Single phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VAC
Single phase100-120VACSingle phase200-230VAC
Single phase100-120VACSingle phase200-230VAC
0.50A 0.45A44W 42W 2
OC-17-A200 0.25A 0.23A
OC-12-A100
10 12 5.8kg0.5A 0.45A
44W 42W 2OC-12-A200 0.25A 0.23A
OC-15-A100
10 12 6.1kg0.50A 0.45A
44W 42W 2OC-15-A200 0.25A 0.23A
OC-28-A100
16 20 10.7kg1.00A 0.90A
88W 84W 4OC-28-A200 0.50A 0.45A
OC-31-A100
16 20 11.0kg1.00A 0.90A
88W 84W 4OC-31-A200 0.50A 0.45A
OC-30-A100
25 30 12.5kg1.40A 1.20A
100W 90W 2OC-30-A200 0.70A 0.60A
OC-20-A100
34 43 14.4kg1.40A 1.20A
100W 90W 2OC-20-A200 0.70A 0.60A
OC-37-A100
35 42 16.1kg2.80A 2.40A
200W 180W 4OC-37-A200 1.40A 1.20A
OC-40-A100
60 80 27.6kg
2.80A 2.40A
200W 180W 4OC-40-A200
1.40A 1.20A
(※1) Rated capacity means nominal cooling capacity when temperature difference between inside and outside the enclosure is 20K.(※2) These units are designed for100VAC or 200VAC single phase voltage supplies.
For different voltage specifications, please consult us.
– 3 –
Standard Series
Nil : Internal wall mountingS : External wall mountingSeries model BOX FAN
Connection Weight No. of fan motors
Screw terminal block
Internal lateral mounting
■ Specifications
OC-15S-A100
OC-17S-A100
8 10 6.2kg 0.50A 0.45A
44W 42W 2OC-17S-A200
0.25A 0.23A
OC-12S-A100
10 12 5.8kg
0.5A 0.45A
44W 42W 2OC-12S-A200
0.25A 0.23A
OC-15S-A100
10 12 6.1kg
0.50A 0.45A
44W 42W 2OC-15S-A200
0.25A 0.23A
OC-28S-A100
16 20 10.7kg
1.00A 0.90A
88W 84W 4OC-28S-A200 0.50A 0.45A
OC-31S-A100
16 20 11.0kg
1.00A 0.90A
88W 84W 4OC-31S-A200 0.50A 0.45A
OC-30S-A100
25 30 12.5kg
1.40A 1.20A
100W 90W 2OC-30S-A200
0.70A 0.60A
OC-20S-A100
34 43 14.5kg
1.40A 1.20A
100W 90W 2OC-20S-A200
0.70A 0.60A
OC-37S-A100
35 42 16.1kg2.80A 2.40A
200W 180W 4OC-37S-A200
1.40A 1.20A
OC-40S-A100
60 80 28.3kg
2.80A 2.40A
200W 180W 4OC-40S-A200
1.40A 1.20A
(※1) Rated capacity means nominal cooling capacity when temperature difference between cabinet and out air is 20K.(※2) Please use it with single phase AC100, AC200V.
For different voltage specifications, please consult us.
– 4 –
Screw terminal block
External Lateral Mounting
Single phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VAC
Single phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VAC
Single phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VACSingle phase100-120VACSingle phase200-230VAC
Model Rated capactiy W/K (※1) Rated voltage(※2)
Current consumption Power consumption50Hz 60Hz 50Hz 60Hz 50Hz 60HzConnection Weight No. of
fan motors
●AccessoriesFilter guard(OG-17FAN) • • 1Fin guard(OG-17FIN) • • • • 1Filter(OF-S1) • • • • • • • • • • 1
●AccessoriesFilter guard(OG-12FAN) • • 1
●Accessories
●Accessories
●Accessories
Packing
InternalAIR
ExternalAIR
Terminal block1637
1566
4
100
139.5
116
160
200
53
58
480
19
15
450
75
464
14
116
119.5
4-φ5.5 or M5 stud bolt
External air
Terminal blockInternalair
Packing
4
16 2260
680
58
56
664
182
75
277
116
14
100
140
116
170 19
650
15
15
4-φ5.5 or M5 stud bolt
InternalAIR
ExternalAIR
Packing
Terminal block
90 15 19 150
574
80
590
15
560
162
14
116
207
75
116
110
4
60
58
18.5 16
4-φ
Packing
19 280
110 20
15
560
200
574
90
590
110
15
18.5 16
51
58
4
116 11614
162
14
116
207
75
4-φ5.5 or M5 stud bolt
Internalair
Externalair
Externalair
Internalair
Packing
Terminal block
Terminal block
221615
4
280
116116 24
680
310
56
58
19 200
664
650
15
60
182
14
116
277
75
4-φ5.5 or M5 stud bolt
OC-17-A100OC-17-A200
OC-12-A100OC-12-A200
OC-15-A100OC-15-A200
OC-28-A100OC-28-A200
OC-31-A100OC-31-A200
– 5 –
Internal lateral mountingOutline drawing Mounting cutoutSpecifications
Rated capacity (W/K)
Mounting cutouts shows the view from the direction of arrow
Rated capacity (W/K)
Fin guard(OG-12FIN) • • • • 1Filter(OF-S1) • • • • • • • • • • 1
Rated capacity (W/K)
Filter guard(OG-15FAN) • • 1Fin guard(OG-15FIN) • • • • 1Filter(OF-S1) • • • • • • • • • • 1
5.5 or M5 stud bolt
Rated capacity (W/K)
Filter guard(OG-28FAN) • • 2Fin guard(OG-28FIN) • • • • 1Filter(OF-S1) • • • • • • • • • • 2
Rated capacity (W/K)
Filter guard(OG-31FAN) • • 2Fin guard(OG-31FIN) • • • • 1
Filter(OF-S1) • • • • • • • • • • 2
Standard Series
Internal lateral mounting
External air
External air
External air
External air
Internal air
Internal air
Terminal block
Terminal block
Packing
36
58
170
260
630
10
638
19300
650
12
207
200
9015
150
75
194
4616
4-φ5.5 or M5 stud bolt
Internal air
Internal air
Packing
15
630
19
170
644
160
100200
660
160
10216
69
58
95
15
150
309
75
4
4-φ
Terminal block
Terminal block
Packing
16 46
4
4
638
36
19382
650
12
207
200
340
170 17014
11
628
15 90
58
150
75
194
4-φ 5.5 or M5 stud bolt
Packing
16038160
19
17028170
150
309
75
240
95
15
644
160
400
660
16 102 4
58
69
632
14
6-φ5.5 or M5 stud bolt
OC-30-A100OC-30-A200
OC-20-A100OC-20-A200
OC-37-A100OC-37-A200
OC-40-A100OC-40-A200
– 6 –
Mounting cutouts shows the view from the direction of arrow
Rated capacity (W/K)
5.5 or M5 stud bolt
AccessoriesFilter guard(OG-30FAN) • • 1
Fin guard(OG-30FIN) • • • • 1
Filter(OF-S2) • • • • • • • • • 1
• • 1
• • • • 1
• • • • • • • • • 1
Rated capacity (W/K)
AccessoriesFilter guard(OG-20H FAN)Fin guard(OG-20H FIN)
Filter(OF-S2)
Rated capacity (W/K)
AccessoriesFilter guard(OG-37FAN) • • 2Fin guard(OG-37FIN) • • • • 1Filter(OF-S2) • • • • • • • • • • 2
Rated capacity (W/K)
AccessoriesFilter guard(OG-40H FAN) • • 2
Fin guard(OG-40H FIN) • • • • 2
Filter(OF-S2) • • • • • • • • • • 2
Outline drawing Mounting cutoutSpecifications
External lateral mounting
Standard SeriesMounting cutouts shows the view from the direction of arrow
Filter(OF-S1)
650
680
170
15
4 1560
16 7
100
14
116
277
75
53
78
51
40 40
140
116
664
71
58
19
4-φ5.5 or M5 stud bolt
Filter(OF-S1)19
450
15
51
58
1566
169.5
160
100
116
30
139.5
32
80
200
480
61.5
4
75
464
14
116
119.5
4-φ5.5 orM5 stud bolt
Filter(OF-S1) 46 46
80
574
70
40
52
58
590
80
15
560
1504 90 15
16
71.5
19
110
11675
14
116
207
4-φ5.5 or M5 stud bolt
Filter(OF-S1)
Packing
71.5
58
52
40
70
574
590
111111
110 11020
200
80
15
560
28015904
16
19
116 11614
75
14
116
207
4-φ5.5 or M5 stud bolt
Packing
Filter(OF-S1)19
650
15
65
78
200
40 110
664
24116 116
310
680
716
58
83
154 60
280
39
14
116
277
75
4-φ5.5 or M5 stud bolt
OC-17S-A100OC-17S-A200
OC-12S-A100OC-12S-A200
OC-15S-A100OC-15S-A200
OC-28S-A100OC-28S-A200
OC-31S-A100OC-31S-A200
– 7 –
Rated capacity (W/K)
AccessoriesFilter guard(OG-17FAN) 1
Rated capacity (W/K)
AccessoriesFilter guard(OG-12FAN) 1
Rated capacity (W/K)
Accessories Filter guard (OG-15FAN ) 1
Rated capacity (W/K)
Accessories Filter guard (OG-28FAN ) 1
Rated capacity (W/K)
Accessories Filter guard (OG-31FAN ) 1
Standard Series
External air
External air
External air
External air
External air
Terminal block
Terminal block
Internalair
Internalair
Internalair
Internalair
Internalair
Packing
Packing
Terminal block
Terminal block
Terminal block
Packing
Outline drawing Mounting cutoutSpecifications
Outline drawing Mounting cutoutSpecifications
Terminal block
Terminal block
Terminal block
Terminal block
Internalair
Internal air
Internal air
Internal air
Externalair
Packing
Filter(OF-S2)
4
170
630
10
84
90 15
19 121 12158
650
12
207
200
260
88
40
78
300
66
638
16
75
150
4-φ5.5 or M5 stud bolt
Filter(OF-S2)External air
External air
External air
Packing
100
160
698
170
35
40
74 78
75
309
150
15
71
200
714
32
667
4 160 15
16
100
58 7119
4-φ5.5 or M5 stud bolt
Filter(OF-S2)
Packing
170
207
84
16
19
1590
628
11
340
650
382 200
12
170
88
40
66
14
78
58
638
162162
150
75
4-φ5.5 or M5 stud bolt
Filter(OF-S2)
Packing
19
100
16
154
667
32 119 58
13
35
28 170170
74
40
78
16038160
75
309
150
240
15
698
400
714
160
6-φ5.5 or M5 stud bolt
OC-30S-A100OC-30S-A200
OC-20S-A100OC-20S-A200
OC-37S-A100OC-37S-A200
OC-40S-A100OC-40S-A200
– 8 –
External lateral mountingMounting cutouts shows the view from the direction of arrow
Rated capacity (W/K)
AccessoriesFilter guard(OG-30FAN) 1
Rated capacity (W/K)
Accessories
Filter guard(OG-20H FAN) 1
Accessories
Rated capacity (W/K)
Filter guard(OG-37FAN) 2
Rated capacity (W/K)
AccessoriesFilter guard(OG-40H FAN) 2
– 9 –
CE-marked models
Model Rated capactiy W/K (※1) Rated voltage(※2)
Current consumption Power consumption50Hz 60Hz 50Hz 60Hz 50Hz 60Hz
Connection Weight No. of fan motors
Mounting cutouts shows the view from the direction of arrow
Specifications
Internal lateral mounting
Internal lateral mounting
External lateral m
ounting
(*1) Rated capacity means nominal cooling capacity when temperature difference between enclosure interior and outer air is 20K.(*2) Use only within the range of 200 to 230VAC, single phase.
Rated capacity (W/K)
Rated capacity (W/K)
AccessoriesFilter guard
Fin guard
Filter
AccessoriesFilter guard
Fin guard
Filter
CE Series
Screw terminal block
5.8kg
10.7kg
16.1kg
5.8kg
10.7kg
16.1kg
200-230VAC 0.20-0.24A
0.40-0.48A
1.12-1.41A
0.18-0.21A
88W
44W
200W
84W
42W
180W
84W
42W
180W
2
4
4
2
4
4
10
16
35
10
16
35
12
20
42
12
20
42
44W
88W
200W
0.36-0.42A
1.14-1.21A
0.18-0.21A
0.36-0.42A
1.14-1.21A
0.20-0.24A
0.40-0.48A
1.12-1.41A
200-230VAC
200-230VAC
200-230VAC
200-230VAC
200-230VAC
Single phase
Single phase
Single phase
Single phase
Single phase
Single phase
Outline drawing Mounting cutoutSpecifications
OC-12-A200-CE
OC-28-A200-CE
OC-37-A200-CE
OC-12S-A200-CE
OC-28S-A200-CE
OC-37S-A200-CE
OC-12-A200-CE
OC-28-A200-CE
(OF-S1)
(OF-S1)
Packing
InternalAIR
ExternalAIR
Terminal block1637
1566
4
100
139.5
116
160
200
53
58
480
19
15
450
75
464
14
116
119.5
4-
φ5.5 or M5 stud bolt
Packing
19 280
110 20
15
560
200
574
90
590
110
15
18.5 16
51
58
4
116 11614
162
14
116
207
75
4-φ5.5 or M5 stud bolt
Externalair
Internalair
Terminal block
– 10 –
Outline drawing Mounting cutoutSpecifications
Rated capacity (W/K)
Rated capacity (W/K)
Rated capacity (W/K)
Rated capacity (W/K)
Internal lateral mounting
External lateral mounting
Accessories
Accessories
Accessories
Accessories
Filter guard
Filter guard
Filter guard
Filter guard
Fin guard
Filter(OF-S2)
OC-37-A200-CE
OC-12S-A200-CE
OC-28S-A200-CE
OC-37S-A200-CE
Outline drawing
4-φ5.5 or M5 stud bolt
4-φ5.5 or M5 stud bolt
4-φ5.5 or M5 stud bolt
4-φ5.5 or M5 stud bolt
Mounting cutouts shows the view from the direction of arrow
Mounting cutouts shows the view from the direction of arrow
Filter (OF-S1)
Filter (OF-S1)
Filter (OF-S2)
Filter retainer
Filter retainer
Filter retainer
BOXFANOHM ELECTRIC CO.,LTD.
1519
4 66
450
480
200
9.5 16
8032
139.5
61.5 30
10015
5158
75464
14116
119.5 116
160Packing
Packing
InternalAIR
InternalAIR
Packing
InternalAIR
ExternalAIR
ExternalAIR
ExternalAIR
Terminal block
Terminal block
Terminal block
Specifications Mounting cutout
盤内AIR
パッキン
OHM ELECTRIC CO.,LTD.
BOXFAN
端子台
9015
628
11
14 170170
340
200
207
12
650
382 19
36
836
4
4616
75194
150
58
BOXFANOHM ELECTRIC CO.,LTD.
15560
71.5
15904
16
19 58
5240
70574095
280
111111
110 11020
200
80
116 11614
7514
116
207
OHM ELECTRIC CO.,LTD.BOXFAN
162 162
638
58
78
14
664088
170
12
200382
650 340
11628
90 15
19
1684
207
170
75150
OC-153H-A100OC-153H-A200
OC–201L
■
OC-153H-A100
9 11 4.2kg
0.50A 0.45A
44W 42W 2OC-153H-A200
0.25A 0.23A
OC-201L 6.5 3.5kg DC24V 0.52A 12.5W 4
OC-0810HIL
6.5 8 3.0kgAC100V 0.44A 0.36A
28W 22W 2OC-0820HIL AC200V 0.22A 0.18A
– 11 –
Compact SeriesMinimal sized models for narrow spacesSpecifications
Internal lateral mounting
Semi-recessed
lateral mounting
Power cord
Power cord
(*1) Rated capacity means nominal cooling capacity when temperature difference between enclosure interior and outer air is 20K.(*2) OC-153H-A※※ models are designed for100VAC or 200VAC single phase voltage supplies. For different voltage specifications, please cosult us. For other models, voltage fluctuation range should be +/-10% from the rating.
Internal lateral mountingMounting cutouts shows the view from the direction of arrow
Rated capacity (W/K)
AccessoriesFilter guard(OG-153HFAN)Fin guard(OG-153HFIN) 2Filter(OF-S1) 1
1
Rated capacity (W/K)
Outline drawing Mounting cutoutSpecifications
Model Rated capactiy W/K (※1) Rated voltage(※2)
Current consumption Power consumption50Hz 60Hz 50Hz 60Hz 50Hz 60HzConnection Weight No. of
fan motorsSingle phase
Single phase
Single phase
100-120VACSingle phase200-230VAC
Screw terminal block
Rated capacity (W/K)
Accessories
Filter(OF-08HIL) 1
BOXFANOHM ELECTRIC CO.,LTD.
7719
5871
612195
5
125153
395
138
104,8
110
35280
35
110
300
3636
280
138
124
104.8
16150
150
4-M3
φ116
6-φ5.5
Packing
Packing
InternalAIR
InternalAIR
InternalAIR
ExternalAIR
ExternalAIR
ExternalAIR
Terminal block
4-M4
148
1704-φ4.5
4-φ4.5 or M4 tapping
58138.5
4031.5
160
Power cord L=1m
33
200 566
300
5
189
206
8765
176156
Power cord
152
L=1m
166
155
190
100
12
ThermostatFeatures
OTH-05
OTH-03
CE-conformed
Functions well even in an oily atmosphere
Applicable to any heat exchangers and fan motorsEffective for energy saving
ModelOutput contact rating
Contact current rating
Dimensions
Weight
Temperature setting range
Specifications
Outline drawing
Outline drawing
240VAC 5A (cosφ=1)
W49xH24xD24(Excluding cable)
190g (Including cable)
OPEN (OFF) 29±3℃CLOSE (ON) 37±4℃
Approx. 5A, Resistance load
OTH-05
Model
Output contact rating
Contact current rating
DimensionsWeight
Temperature setting range
Specifications
250/115/60/48/24VAC 60/48/24VDC
W70xH70xD25105g (Including cable)
+5 to +60℃ (variable)Terminal 5-3 (Heater) AC10A DC=30W, Resistance load
Terminal 5-4 (Heatexchanger) AC5A DC=30W, Resistance load
OTH-03
Crimp terminal M4
Insulation capOA-QM4 (Included in the supply)
Fitting
Fitting
Fixed temperature settingBimetal probe thermostatCE declared
Variable temperature settingBimetal probe thermostatCE conformed
Use a band or a M4 screw with washer
Install to a DIN rail using the enclosed attachment parts or directly to the enclosure surface
W:49mm
D:24mm
H:24mm
H:70mm
W:70mm
D:25mm
OC–17(S)–A※※
OC–12(S)–A※※
OC–15(S)–A※※
OC–28(S)–A※※
OC–31(S)–A※※
OC–30(S)–A※※
OC–20(S)–A※※
OC–37(S)–A※※
OC–40(S)–A※※
OC–12(S)–A200-CE
OC–28(S)–A200-CE
OC–37(S)–A200-CE
– 13 –
Filter guard, Fin guard, Filter and Fan motor list
Filter guardBOXFAN Model Fin guard Replacement filter Replacement fan
Standard series
(1 pc.)
(1 pc.)(1 pc.)
(1 pc.)
(1 pc.)
(1 pc.)
(1 pc.)(1 pc.)
(1 pc.)
CE series(1 pc.)(1 pc.)
(1 pc.)
OC–153H–A※※
OC–201L
OC–0810HIL
OC–0820HIL
(1 pc.)
Compact series
(5 pcs./set)
(5 pcs./set)
Replace or clean the filter periodically like every 2 to 3 weeks according to the environmental conditions.
Option
Outline drawing
Material
Filter guard part number Fin guard part number
Filter guard
Filter guard Material Material
MaterialFilter
Fin guard
Fin guard
129 129
157 183
159179129259299162279179359179
Nylon 66(Flame resistance : UL94 V-0)
Nylon 66(Flame resistance : UL94 V-0)
Polypropylene
Polyester
Filter Fin guard
Guide
Filter guard
Example: Example:
Standard series, OC-153H, CE series (accessories)
– 14 –
OF-S1
OG-17 FINOG-12 FINOG-15 FINOG-28 FINOG-31 FIN
OG-17 FINOG-12 FINOG-15 FINOG-28 FINOG-31 FIN
OG-30 FINOG-20H FINOG-37 FINOG-40H FIN
OG-30 FINOG-20H FINOG-37 FINOG-40H FIN
OG-153H FIN
OG-17 FANOG-12 FANOG-15 FANOG-28 FANOG-31 FAN
OG-17 FANOG-12 FANOG-15 FANOG-28 FANOG-31 FAN
OG-30 FANOG-20H FANOG-37 FANOG-40H FAN
OG-30 FANOG-20H FANOG-37 FANOG-40H FAN
OG-153H FAN
OG-153H FAN OG-153H FIN
OF-S2OF-08HIL
15
Model selectionApproaching method
Use the Graph
Use the Calculation formula
Is Calorific value insidethe cabinet (P) known?
Is Calorific value insidethe cabinet (P) known?
Yes
Yes
No
No
Heat-transfer coefficient of a cabinetCabinet matrial Heat transfer coefficient
Painted steel 5W/(sqm・K)3.7W/(sqm・K)Plastic
Note: The temperatures both inside and outside the cabinet shoudl have been measured.Example : External temperature (measured) T3 = 40℃
Example : Calorific value inside the cabinet P = 500W
Internal temperature (measured) T4 = 68℃
Condition
Condition
(1) Cabinet (painted steel) Heat-transfer coefficient U ≒5W(sqm・K) Outline dimensions = W630 x H1250 x D630 mm Effective radiation area S =3.55sqm *Bottom area is excluded(2) Max. External temperature T1 = 40℃(3) Allowable internal temperature T2 = 55℃
The required capacity of BOXFAN is found by the following formula.
(1) Cabinet (painted steel) Heat-transfer coefficient U ≒5W(sqm・K) Outline dimensions = W630 x H1250 x D630 mm Effective radiation area S =3.55sqm *Bottom area is excluded(2) Max. External temperature T1 = 40℃(3) Allowable internal temperature T2 = 55℃
The required capacity of BOXFAN is found by the following formula.
≒16(W/K)
Select a model that has 16W/K or larger capacity.
Select a model that has 16W/K or larger capacity.
≒16(W/K)
Note: The temperatures both inside and outside the cabinet shoudl have been measured.Example : External temperature (measured) = 40℃, Internal temperature (measured) = 68℃, Allowable temperature inside the cabinet = 55℃
Difference between Allowble internal temp. and Max. external temp. ΔT1 [K]
Difference between internal temp. and Max. external temp. ΔT2 [K]
Rated capacity of heat exchanger Q 「W/K]
Effec
tive radiation area
S [s
qm]
16
1) The temperature difference between inside and outside of the cabinet ΔT2 is 68-40 = 28[K]. ΔT1 is the difference between Allowable internal temp. and Max. external temp., that is 55-40 = 15K. Find the intersection point A of these two.
2) Draw a horizontal line from the point A to the right of the graph to find out the intersection point B of it with the effective radiation area S, 3.55sqm.
3) Draw a vertical line from the point B to find the required capacity Q, which is 16W/K. Select a model that has 16W/K or larger capacity.
1) The calorific value P is 500(W). ΔT1 is the difference between Allowable internal temp. and Max. external temp., that is 55-40 = 15K. Find the intersection point A of these two.
2) Draw a horizontal line from the point A to the right of the graph to find out the intersection point B of it with the effective radiation area S, 3.55sqm.
3) Draw a vertical line from the point B to find the required capacity Q, which is 16W/K. Select a model that has 16W/K or larger capacity.
Example : Calorific value inside the cabinet P = 500W Allowable temperature inside the cabinet = 55℃, Max. external temperature = 40℃
Difference between Allowble internal temp. and Max. external temp. ΔT1 [K]
Calorific value inside the cabinet P [W] Rated capacity of heat exchanger Q 「W/K]
The required rated capacity of BOXFANhas been found out.
Select a model which capacity isnot less than the result.
What is the unit W/K (watt per kelvin)?
W : Heat flow 1W = 1 J/S
1W/K means the ability to let heat flow of 1 W out from a cabinet when the temperaure difference between the cabinet interior and the external air is 1K.Thus, 5W/K is the ability to transfer heat of 5W from inside to outside when the temperature differentialbetween inside and outside of the cabinet is 1K.
<Caution> (1) The airtightness, location of heat gerators and dirts on heat radiation unit or filter can affect the performance of a heat exchanger. It is recommended to make selection with allowance for such losses.(2) The internal temperature of a cabinet should not exceed 60 deg. C. with operating a heat exchanger.(3) Because of its operating principle, heat exchanger’s performance declines when temperature gap between inside and outside narrows.(4) Each rated capacity of our heat exchangers indicates the nominal value when cabinet interior’s temperaure is higher than outside by 20deg. C. If temperature gap is smaller than this, the capability declines. Use of heat exchanger is not effective when such gap is less than 10 deg. C.
17
Technical data
Carorific values of electric components General note
(1)Minor componentsPilot lamps, cables and other components than listed here also generate heat in a cabinet but they are omitted for the reasons that thosevalues are small and not easily assessable.
(2)Carorific valuesThe values listed herei are rough standard for each component and can be variable depending on the state of load. Please use the datataking this into your account. Even the carorific value of a component is very small and therefore not mentioned here, the total value canbe nonnegligible if there are many. Always try to find appropriate values at the site for calculation.
(3)Unlisted itemsFor the components like PLC which are not listed here, refer to the data provided by the manufacturer. These components are often used in a cabinet but it is difficult to ouline their carorific values.
(4)Carorific values in the following tableThis table shows standard values of generally used components based on our study. Actual values may differ from them depending oneach specifications. See the information provided by the manufacturer.
Carorific value (Rough standard)
Note) All values are approximate and each actual value can differ from it.
1. Power supply Components Carorific value estimate Remarks
Small transformer
Rated capacity
Rated capacity
Rated capacity
Rated capacity
up to 100VA …15% 300VA …10% 1kVA … 7% 3kVA … 5% 5kVA … 4% 10kVA … 3%
・Calculated as Loss = Carorific value
・Calculated as Loss = Carorific value
・Calculated as Loss = Carorific value
・Calculated as Loss = Carorific value
Voltage regulatorup to 500VA …10%
1kVA … 7%10kVA … 5%
Constant-voltage power fupply up to 2kVA …15%
10kVA …10%
Uninterruptible power supply (UPS)up to 1kVA
up to 0.1kVA
… 20%20kVA …15% ・Values are at floating charge status of storage batteries
・Constant feeding by inverter
Switching regulator 20 to 30% of the rated capacity・Carofific value with 100% rated output
Low-voltage capacitor 0.2 to 0.3% of the rated capacity ・Capacities should be converted to kVA for calculation (100V 60Hz 1kVA= 265.3 μ F)
2.Amplifiers
AC Servo amplifier
Rated capacity
Rated capacity
… 50%0.5kVA … 15%
1kVA … 8%3kVA … 5%5kVA … 4%
11kVA … 3.5%22kVA … 3%
・Carorific values with 100% output of the rating per unit・The smaller the capacity, the bigger the heat generation ratio.
・The smaller the capacity, the bigger the heat generation ratio.
・The smaller the capacity, the bigger the heat generation ratio.
・The smaller the capacity, the bigger the heat generation ratio.
・The smaller the capacity, the bigger the heat generation ratio.
・The smaller the capacity, the bigger the heat generation ratio.
・With power supply equipped
Inverter
…12.5%0.75kW … 11%
1.5kW … 8%2.2kW … 7%3.7kW … 6%7.5kW … 6%11kW … 5%22kW … 4.5%30kW … 4%
・Carofific values with 100% rated output
・Carorific values at constant output of the rating
Thyristor
Rated current 1-phase 3-phaseup to 25A … 50W 90W
35A … 55W 115W50A … 75W 175W75A … 90W 250W
100A … 120W 320W150A … 200W 520W250A … 350W 930W350A … 400W 1150W450A … 560W 1600W600A … 700W 2000W
・Values in the right are carorific values・3-phase types have bigger values than 1-phase types
Components Carorific value estimate Remarks
up to 0.4kW
Note: These information are adapted from “Technical data No. 001-2004 “Carorific value guideline for electric components in cabinets” by Thermal Solution Equipment for Cabinet Technical Soociation , Japan.
3. Wiring components
Molded case circuit breaker(MCCB)
(MCCB)Rated capacity
Rated capacity
20A … 7W50A … 14W
100A … 21W225A … 45W400A …115W
・Carorific value with 100% rated current ・Proportional to the number of poles・Values are for 3P
Earth leakage circuit breaker(ELCB)
(ELCB)(※ 1)Rated current
Rated current
225A …MCCB + 5W400A …MCCB+30W
(Ground-fault electronic circuit, etc.)
・ELCB is unrelated to the number of poles(※ 1)Smaller components have smaller heat generation ratio.
Electromagnetic contactor
4kW … 7W11kW … 15W22kW … 30W37kW … 50W55kW … 90W
110kW …200W160kW …340W200kW …460W
・Carorific value with 100% rated current ・Values are for 3P・Values are for 220VAC
Thermal overload relay
15A … 2W/pole30A … 3W/pole
100A … 7W/pole150A … 9W/pole450A …10W/pole600A …12W/pole
・Carorific vales with max. stabilized current
Electromagnetic relay 5W ・Carorific values with 100% rated current
4.Control devices
Small relaysMiniature relay : 1W to 2W per piecePower relay : 2W to 3 W per piece
Solid-state relay(SSC、SSR) Load current value x 1.8W ・When voltage drop with closed circuit is 1.8VTemperature controller Power consumption is regarded as carorific value
PLC
Micro sequencer :・For AC power
10 to 40 I/O points 30 to 50W64 or more I/O points I/O poiints × 1W
・For DC powerI/O points × 0.5W
Other sequencers :See the output current value of the power supply unit. In designing phase, use the max. value of the power supply unit.
5.Information and telecommunication equipment
PCMonitorServer
Switching hubRouter
Media converter
Power consumption is regarded as carorific value
Booster Consumption current - Transmission power output
IndicatorLED indicator : Consumption current x 0.4
LC: Power consumption is regarded as carorific value
6.Others
Fan motor
90mm sq.size …10W120 mm sq.size …20W140 mm sq.size …40W150 mm dia.size …55W180 mm sq.size …55W
・Rated input is regared as carorific value・Values are for axial fans・Values are for AC power input・Sizes are for frames
〔Notes〕(1)When using rated capacities (VA) or rated outputs (VA), multiply those values by percentage to obtain the carorific value.(2)Actual values may differ from the above table. Check the values on the catalogs and technical information provided by the manufacturer.(3)Wires and other small components are heating source as well. Take those values into your account.
Components Carorific value estimate Remarks
Components Carorific value estimate Remarks
Components Carorific value estimate Remarks
Components Carorific value estimate Remarks
up to
up to
up to
up to
Technical data
18