en operation & maintenance...

60
TOPAX ® DX Multi-Channel Controller EN 01 Operation & Maintenance Instructions Read this operating instructions before start up! To be retained for future reference. Dosing Conveying Control Liquids Gases Systems

Upload: vandieu

Post on 08-Apr-2018

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

TOPAX® DXMulti-Channel Controller

EN01

Operation & Maintenance InstructionsRead this operating instructions before start up!

To be retained for future reference.

DosingConveying

Control

Liquids

Gases

Systems

Page 2: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

� | Operation Manual TOPAX DX | BA-40100

List�of�Contents1.�Safety�................................................................................................... 31.1 General ................................................................................................ 31.� Warnings used in this Operation & Maintenance Manual .......................... 31.3 Operators qualification and training ........................................................ 31.4 Electrical safety tips .............................................................................. 31.5 Hazards due to non-compliance with the safety instructions .................... 31.6 Safe operation ...................................................................................... 31.7 Safety instructions for the operator ......................................................... 31.8 Safety instructions for installation, maintenance and inspection................ 31.9 Self-made modifications and spares procurement ................................... 4

2.�Before�placing�in�operation�................................................................. 4�.1 Compliant use ...................................................................................... 4�.�. Scope of delivery .................................................................................. 4�.3 Steps to take for start-up ....................................................................... 4

3.�Technical�data�...................................................................................... 53.1 Cable recommendation ......................................................................... 63.� Order variants ....................................................................................... 6

4.�Mounting�build-in�housing�.................................................................. 74.1 General notes of instruction ................................................................... 74.� Wall mount ........................................................................................... 74.3 Product overview .................................................................................. 84.4 Technical components ........................................................................... 84.5 Power connections .............................................................................. 104.6 Terminal clips on the technical components .......................................... 1�4.7 Operation and keyboard layout ............................................................. 144.8 First set-up and programming guidelines .............................................. 144.9 Next steps .......................................................................................... 17

5.�Measuring�values�inputs�................................................................... 185.1 Free chlorine measurements input ....................................................... 185.� Measuring input pH value .................................................................... �05.3 Measurement output Redox potential .................................................. �15.4 Measuring input temperature ............................................................... ��5.5 Measurement input total chlorine and display of bonded chlorine ........... ��5.6 Conductivity measurements input......................................................... ��

6.�Explanation�of�digital�inputs�............................................................. 236.1 Start-up lag time ................................................................................. �36.� Deactivation of the controller function with alarm signaling in the case of lack of sample water ........................................................................................ �36.3 Controller function deactivation (filter cleaning) without alarm ................ �36.4 Pre-alarm, alarm and warning "level dosing pump" ............................... �3

7.�Explanation�measuring�values�outputs�............................................ 247.1 Output types ....................................................................................... �47.� Output limit switch .............................................................................. �47.3 Actuator elements ............................................................................... �4

8.�Controller�explanation�....................................................................... 258.1 Proportional controller (P controller) ...................................................... �58.� Proportional-integral-derivative controller ((PI, PID controller) ................. �58.3 Calculation of setable values ................................................................ �58.4 Controller parameters .......................................................................... �68.5 Controller direction .............................................................................. �68.6 Base load metering ............................................................................. �68.7 Manual operation ................................................................................ �6

9.�Alarms�................................................................................................ 279.1 Measuring values alarms ..................................................................... �79.� Emergency stop (Y-alarm) .................................................................... �7

10.�Analogue�power�outputs�0/4...20�mA�for�remote�display�.............. 27

11.�Night�operation�................................................................................ 28

12.�Economy�mode�-�DIN-contact�and�ECO-contact�............................ 281�.1. TOPAX® DX is responsable for economy mode ................................... �81�.�. TOPAX® DX controlled DIN-contact only ............................................. �8

13.�Control�of�the�flocking�pump�.......................................................... 29

14.�Log�book�function�............................................................................ 29

15.�Auto�setup�(First�system�self-setting)�............................................ 30

16�Menu�configuration�and�main�settings�............................................ 3116.1 Menu of TOPAX® DX ......................................................................... 3116.� configuration example and terminal connection ................................... 39

17.�Wiring�diagrams�.............................................................................. 4017.1 Examples overview ............................................................................ 40

18.�Software�updates�............................................................................. 4918.1 Firmware update ............................................................................... 4918.� Update for further menu languages .................................................... 49

19.�Default�settings�................................................................................ 49

20.�Spare�parts�and�options�.................................................................. 50

21.�MMC�(Multi-Media-Card)�memory�card�.......................................... 50

22.�Troubleshooting�and�diagnostics�.................................................... 51

23.�terminal�connection�diagram�for�own�configurations�................... 52

24.�Index�................................................................................................. 54

25.�Declaration�of�conformity�................................................................ 55

26.�Device�revision�................................................................................. 56

27.�Warranty�Application�....................................................................... 57

Page 3: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 3

Chapter�1:�Safety

1.�Safety

1.1�GeneralThis manual contains very important information for assembly, start-up, use and maintenance of the meter. Please have your staff and any person in charge of the unit read and understand this manual before starting any work with it. Store this manual safely in a place where mechanics, installers and other techni-cal staff as well as operators can rapidly access it in case of emergency. Pay special warning and provide compliance with all safety notices in this manual!

1.2�Warnings�used�in�this�Operation�&�Maintenance�ManualThis Operation & Maintenance Manual contains vital information which may endanger people and the unit if they are disregarded. These statements are identified by the following symbols:

WARNING!Refers to a potentially hazardous situation. Non-compliance can lead to death or extremely serious injury.

CAUTION!Refers to a potentially hazardous situation. Non-compliance can lead to minor injury or property damage.

IMPORTANT! or NOTICE!Appears in conjunction with safety instructions which may endanger the machine and its operation if disregarded.

IMPORTANT!Draws attention to supplementary information to make the work easier and ensure troublefree opera-tion. Appropriate reference attached directly on the unit or any of its other parts must absolutely be con-sidered and held in completely readable condition for future reference.

1.3�Operators�qualification�and�trainingYour assembly, operation, maintenance and inspection staff must be trained and have the appropriate qualification for use and op-eration of the unit. Area of responsibility, tasks and supervision of the personnel must be provided at all times by the customer. Unskilled operators must be duly trained and instructed. If neces-sary, this can also be undertaken by the manufacturer or certi-fied supplier on behalf of the owner. Operators who are to work with the meter must read and understand the manual in all of its parts.

1.4�Electrical�safety�tipsWhen installing and using this electrical equipment, basic safety precautions should always be followed, including the following:

WARNING!1.) Read and follow all instructions.

2.) To reduce the risk of injury, do not permit children to use this product unless they are closely super-vised at all times.

3.) Risk of Electric Shock. Ensure that the device is secured with a ground fault - circuit breaker (GFCI = earth-leakage circuit breaker). Contact a qualified electrician if you cannot verify that the receptacle is protected by a GFCI.

4.) Do not bury cord. Locate cord to minimize abuse from lawn mowers, hedge trimmers, and other equipment.

5.) To reduce the risk of electric shock, replace dam-aged cord immediately.

6.) To reduce the risk of electric shock, do not use extension cord to connect unit to electric supply; provide a properly located outlet.

7.) Keep this instruction at close for future refer-ence.

1.5�Hazards�due�to�non-compliance�with�the�safety�instructions

Failure to comply with the safety instructions may endanger not only people, but also the environment and the unit. Non com-pliance with the safety information will immediately cancel your rights of claiming for damages even during the warranty period.

The following hazards in particular may arise: - Failure of system functions. - Danger to people due to electrical, mechanical and chemical effects. - Danger to the environment due to leakage of hazardous substances.

1.6�Safe�operationThe safety instructions contained in this Operation & Maintenance Manual must be observed. The owner is responsible for ensuring compliance with local safety regulations. Disturbances suscepti-ble of impairing safety are to be eliminated immediately!

1.7�Safety�instructions�for�the�operatorStatutory regulations must be observed. A safe and ecologically beneficial disposal of process materials as well as replacement parts must be ensured. Danger due to electric current must be excluded (for further details, refer to the German VDE1) standards as well as local rules and regulations as well as chapter 1.4).

1) Association of German Electrotechnical Engineers

1.8�Safety�instructions�for�installation,�maintenance�and�inspection

The operator has to ensure that all assembly, maintenance and inspection works are done by authorized and qualified technical operators.

Page 4: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

4 | Operation Manual TOPAX DX | BA-40100

Chapter�2:�Before�placing�in�operation

WARNING!Assembly and maintenance of the equipment are to be strictly done after disconnecting the device from the power supply. It must be se-cured against reconnection during the works! Auxiliary assemblies and tools should be dismounted prior to maintaining. Cables are to be attached like-wise only in this condition.

Neglecting of these instructions can lead to severe damages of TOPAX® DX and loss of warranty.

All safety mechanisms and guards must be refitted and reacti-vated as soon as the work is complete.

NOTICE!Apart from an incorrect installation also wrong con-troller settings (default settings, data of the param-eter and configuration level, and internal changes of the instrument) can impair or damage the process normal functions.

There should always be a safety device that is independent of the controller. Configurations may only be carried out by technical personnel! If necessary use password protection! Always comply with the safety regulations and accident prevention laws of the country of use.

1.9�Self-made�modifications�and�spares�procurementTOPAX® DX may be converted or changed only by qualified tech-nical personnel.

If the configuration of the TOPAX® DX is wrongly made by as-sembly or service personnel, errors and dangers in the function of the machine can result. In this case, the manufacturer declines any liability.

NOTICE!Genuine spare parts and sensors authorized by the manufacturer ensure greater safety. Otherwise the guarantee expires.

2.�Before�placing�in�operation

2.1�Compliant�useDer TOPAX® DX is especially designed and meant for metering and control applications in swimming pools, SPA and bath wa-ters, water treatment plants and waste water management. The operational safety of the delivered unit can only be guaranteed when it is used in conformity with its intended use.

Other usage and modifications will determine the immediate can-cellation of the warranty and any other manufacturer’s liability.

2.2.�Scope�of�deliveryCarefully check the delivery before installation and refer to the delivery note to ensure the delivery is complete and to check for any transport damages. Contact the supplier and/or carrier regarding any questions concerning the delivery and/or transport damages.

Do not operate any defective devices.

The following belong within the scope of delivery:• TOPAX® DX casing (as per the model)• Tool (M4 screw) to open the casing• MMC memory card• Mounting material• Operation & Maintenance Instructions• Measuring protocol• Terminal plan for the sensors• Electrodes (optional)• Cable connection TOPAX® DX to the electrodes (optional)

The device is delivered either as detached or mounted onto a measuring water table.

2.3�Steps�to�take�for�start-upThe following steps are recommended by the manufacturer in order to install the TOPAX® DX successfully:• Reading the operation manual• Mount the device• Attach the sensors and actuating element (to the controlling

pumps and switch, etc.)• Initial configuration of the in- and output (see chapter 4.8)• Calibrate the sensors to the measuring output (see chapter

5 and 6)• Set up the set points (see chapter 16, menu 1.1)• Set up the control (see chapter 16, menu �.1)• Configuration of the regulating output (see chapter 7)

Page 5: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 5

Chapter�3:�Technical�data

3.�Technical�dataSupply voltage 90...�64 VAC, 47...63 Hz

Power consumption Approx �4 W

Housing dimensions 30� x �31 x 108 mm (W x H x D) wall mounted unit

Display Graphic colour display 5.7 inch, 3�0 x �40 pixels (RGB), with background lighting

Keyboard Glass keyboard with touch keys

Measuring inputs(potential-free)

- inputs for free chlorine, pH value, REDOX potential, temperature- 4...�0 mA input for the measurement of total chlorine and controlling of bonded chlorine with supply of the electrode (�4 VDC)- 4...�0 mA input for conductivity (passive) measurement and control

Regulating characteristic for 4 inputs (free chlorine, pH value, bonded chlorine, conductivity, depending of configuration level)

P, PI, PD or PID performancesFixed value regulation, standard channel selectable with disturbance variable feed forward�-side controller

Control parameter Xp: 1...500%, Tn: 1...�00 min., Tv: 1...1�00 sec.

Measuring input for free chlorine open amperimetric electrode with mechanical cleaning (excess chlorine detector with � electrodes, CS 1�0)Measuring range adjustable between 0-1,00 mg/l, 0-�,00 mg/l, 0-5,00 mg/l or 0-10,00 mg/l. connection via line-up terminals*

Potentiostat (PM)Measuring range adjustable between 0-1,00 mg/l or 0-�,00 mg/l

Encapsulated electrode �0 mA type, measuring range depending on type of electrode

Measuring input for pH value Measuring range pH 0..14 connection via line-up terminals*

REDOX potential measuring input Measuring range 0..1,000 mV connection via line-up terminals*

Temperature measuring input - Pt 100

Measuring range -10°C ... +100°C

two-leader connection by means of line-up terminals*

Total chlorine measuring input Encapsulated electrode �0 mA type, measuring range depending on type of electrode

Conductivity measurement Conductive and inductive with separate measuring amplifier

�0 mA type, measuring range depending on type of measuring amplifier

Disturbance factor input 0/4...�0 mA programmableDisturbance factor: 0.1...10 times amplification

Digital inputs - Early warning level input for metering pump 1- alarm level input for metering pump 1- Early warning level input for metering pump �- Alarm level input for metering pump �- Filter cleaning: disconnection of the controller function without alarm- measuring water shortage disconnection of the regulating function with alarm (external cut off)- activate night-time economy mode

Automatic controller outputs Electronic output(optocouplers)

- 48 VDC; �50 mA (pulse frequency 10... �00 impulses/min)

Relay output - ON/OFF- pulse frequency 10...100 Impulses/min- Pulse length 10…1�0 seconds- 3-point step output with- Position feedback value of the Potentiometer 1...10 kOhm

continuous output - 0/4...�0 mA, max. load 500 ohms

Alarm output Relay output as collective alarm for the measuring size of free and bonded chlorine, pH value, redox potential, temperature and conductivity as potential free changer

Measuring value alarm min. and max. alarm freely adjustable, time delay adjustable: max. �00 min

Safety shut off To prevent over metering (Y-alarm), time delay adjustable: max. �00 minutes

Current outputs to remote trans-mission of measuring values- Free and unbonded chlorines- pH value- Redox potential- temperature and conductivity

0/4...�0 mA possible spreading; max. load 500 ohms potential free

average spreading >50 % with measuring input free chlorine and 0/4...�0mA>10% during measurement input of pH-value and redox potential

Computer interface (optional) RS 485

Load capacity of the relay �30 V AC, 3A

Protection class IP 65 with locked screw connections

Ambient temperature -5°C ... +45°C

Atmospheric moisture 95 % non-condensing

*) max. 0,5 mm² with cable ends protection sleeve and max. 1,0 mm² without cable end sleeve.

Page 6: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

6 | Operation Manual TOPAX DX | BA-40100

Chapter�3:�Technical�data

3.1�Cable�recommendationRecommended cables for the different connections and applications:

Connections�and�applications dimensions TypesMains voltage M�0 X 1,5 NYM-I 3 x 1,5 mm ( 9,1 mm)

Relay output (ATE- engine) M�0 X 1,5 NYM-I 4 x 1,5 mm ( 9.8 mm)

Relay output (pulse frequency), (pulse length) M16 X 1,5 NYM- O �x 1,5 mm ( 8,7 mm)

Relay output alarm) M16 X 1,5 NYM- O 3x 1,5 mm ( 9,1 mm)

connection to PC, computer cable Cat 5 M1� X 1,5 Type �X�XAWG�4/1 ( 5,7 mm)

Connection of current outputs (remote communication cable) M1� X 1,5 J-Y (St) Y 4 x�x0,6 mm ( 6,5 mm)

Position feedback ATE- engine (remote communication cable) M1� X 1,5 J-Y (St) Y �x�x0,6 mm ( 5,0 mm)

Continuous controller output (remote communication cable) M1� X 1,5 J-Y (St) Y �x�x0,6 mm ( 5,0 mm)

Input chlorine measuring cell M1� X 1,5 LIYY �x 0,�5 mm

Digital inputs (for each input) (remote communication cable) M1� X 1,5 J-Y (St) Y �x�x0,6 mm ( 5,0 mm)

3.2�Order�variantsThe TOPAX® DX is available in different product variants upon request. The following five variants are standard articles:

Order�no. 40100001 40100002 40100003 40100004 40100005InputsComponent 78403 X X X X X

Component 78404 X X X X

Free chlorine Measuring cell (optional):

Amperometric (Excess chlorine detector with � electrodes CS1�0) X X X

Potentiostatic X X X X

Diaphragm-covered X X X

pH value X X X X X

Redox X X X X X

Temperature X X X X X

Position feedback with 3-point-steps controller 1 � � � �

Measurement of total chlorine by means of an encapsulated electrode with integrated electronic amplifier (4...�0 mA input with electrode electronics supply)

X X

Measurement of conductivity with a separate measurement amplifier (4...�0 mA input) X X

OutputsComponent 78399 X X X X X

Controller with 3-point stepping output with potentiometer feedback, pulse length output, Pulse frequency output, ON/OFF switching output or 0/40...�0 mA power output

1 � � � �

Controller with pulse length output, pulse frequency output, control output IN/OUT or current output 0/4...�0 mA

1 1 1 �

Page 7: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 7

Chapter�4:�Mounting�build-in�housing

4.�Mounting�build-in�housing

4.1�General�notes�of�instructionFor installation, the local directions and regulations have to be adhered to. Any mounting position is possible. The ambient con-ditions are to be maintained in accordance with the technical data. Exposure of the unit to direct heat and sunlight must be avoided.

Diagram�TOPAX®�DX�housingThe front housing ④ and the reare housing ① of TOPAX® DX are securely bolted together with two bolts (see ② and ③ in fig. 4.1). The construction is so arranged that the TOPAX® DX can be opened and accessed on both sides.

Fig. 4.1: Front and reare housing

Opening�the�casingThe bolts (hinge pivots) are purposely tightened so that they can only be removed using a tool. To unscrew, first release the nuts⑤ at the top with the help of a screwdriver at one axis, and this axis ⑥ can be pulled out downwards. The curled thumb M4 screw ⑦ provided serves as a tool for this, which is screwed in the axis from underneath (see fig 4.�).

When the reassembling, make sure to fit all nuts back in place.

NOTICE!In order to open the housing remove only one hinge pivot from the equipment. If both bolts are removed at the same time, the upper part and the lower part of the box will fall loose.

Fig. 4.�: Open the casing onto the casing fastener on the wall and/or onto the cable connection fastener.

NOTICE!The equipment is to be opened only when plugged off the power supply.

4.2�Wall�mountFor the wall assembly 4 mounting holes are to be found in the lower part of the housing. The hardware for wall fixation is pro-vided with the unit by the manufacturer (see fig. 4.3).

Page 8: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

8 | Operation Manual TOPAX DX | BA-40100

Chapter�4:�Mounting�build-in�housing

Fig. 4.3: Spacing of hole for monting the device (left) and the device dimensions

4.3�Product�overviewThe TOPAX® DX device is composed of two parts, a rear and a front housing (see Abb. 4.1). The rear shell of the housing is electrically connected with a flat cable with the front one.

reare�housingconsists of rear housing with the motherboard, in which the cable connections are screwed in.

On the motherboard there are the main modules for the function-ing. Depending upon the model, two input blocks are available together with an output block. For networking purposes with con-nection to a PC, an additional interface (RS485) is available. All blocks are connected by plug connectors to the motherboard and fastened with several nuts.

front�housingOn the front housing there are the display plate and the key-board. A colour display is available for displaying measurements and adjustments. The operation takes place with 6 function keys as well as a control cross with "OK" key. The keys are integrated in a glass keyboard and react to contact. All displays of the indi-vidual menus appear as plain text.

Fig. 4.4: Front and reare housing (left) with display and reare housing.

4.4�Technical�componentsBesides the main board, the following can be fitted in addition

• up to � input components• an output component and • an Interface module (RS 485)

(see Fig. 4.5) To operate the TOPAX® DX at least one entry com-ponent has to be built in.

Ausgangsbaugruppe

Hauptplatine

DO

4D

O3

DO

2D

O1

7840478403

78402

DO7 DO6 DO5

DO

0

78399

Rechnerschnittstelle (verdeckt)78406

+ -+ - + - + - + - + - + - + -

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

20 mA Stromausgänge Digitale Eingänge36 37 38

PE

N

L

Netzteil33 34

92

93

94

87

88

89

90

91

86

- +

81

82

83

84

85

- -+ +56 57 58 59 60

- +

51A

52A 53 54 55 61

51B

52B

- -+ + -+

71 72 73 74 75

76

77

78

Eingangsbaugruppe5-fach

Alarmrelais

39

40

41

43

44

45

46

42

35

95

96

B A

Eingangs-baugruppe3-fach

Steckverbindungzur Displayplatine

Fig. 4.5: Arranging the components on the main board

Main�board�(order�no.�78402)Besides this function, to incorporate the further components, the main board is made up of the following connections:• 8 analogue power inputs (0/4...�0mA)• 8 digital inputs• Alarm relay• power supply

5-fold�Input�block�(Code�78403):with 5 measurement inputs for:• free chlorine (amperometric or membrane covered elec-

trode) (0/4...�0 mA)• pH single-rod measuring cell• Redox single-rod measuring cell• Temperature sensor Pt100• Position feedback of an eventual servo motor with potenti-

ometer

171

mm

267 mm 302 mm

240

mm

171

mm

267 mm 302 mm

240

mmReverse side

Page 9: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 9

Chapter�4:�Mounting�build-in�housing

3-fold�Input�block�(Code�78404):with 3 measurement inputs for:• free chlorine (potentiostatic electrode)• Position feedback of an eventual servo motor with potenti-

ometer• a 0/4...�0 mA power entrance for the connection of a

disturbance factor or a conductivity measuring unit with upstream measuring amplifier

IMPORTANT!When free chlorine potentiostatic electrode is used in a 5-fold input block, it is possible to connect also a total-chlorine electrode. At the same time bonded chlorine is calculated by PC and displayed.

Output�board��(order�no.�78399)On the output block there are 5 integrated relay output and 3 electronic outputs (optocouplers).

The following output can be configured:• Controller output free chlorine

with different functions• Controller output pH value

with different functions• Controller output bonded chlorine

with different functions• Controller output conductivity

with different functions• DIN - contact: Free contact if all conditions of the DIN-

Standards are respected.• Contact for starting of the flocking pump.

The software configuration automatically assigns these outputs to the respective terminals in a sequential order- depending on the configuration of the TOPAXTOPAX® DX:1. Automatic controller free chlorine�. Automatic controller pH value3. Automatic controller bound chlorine4. Automatic controller conductivity5. DIN - contact6. Eco - contact7. Flocking contact

Depending upon output type, TOPAX® DXselects the next free relay output or optocoupler. The clamps are assigned in a firm order: clamps 87/88 to 95/96 for relays, or 81/8� bis 85/86 for optocouplers.

NOTICE!For further information on the terminal connection, refer to Chapter 4.6

Interface�board�RS�485�(order�no.�78406)The TOPAX® DX has the option of being fitted with a serial inter-face RS 485. The RS 485 allows you to transfer data to a PC. The data communication protocol installed is MODBUS.

With the RS 485 interface it is possible to connect more than one TOPAX® DX to a network. For this an address is to be assigned to each TOPAX® DX. In addition to this each TOPAX® DX is fitted with a computer-interface RS 485.

It is possible to have a maximum of 1000 m of data transfer with the RS 485 interface. Up to 14 TOPAX® DXs can be connected to a network with a PC.

An example of a network with more than one device is shown in chapter 17.

NOTICE!The data line is to be attached direct to the con-necting terminals of the TOPAX® DX (clip A and B). Separate clamping or branching boxes should not be set. The network address 10 is not permitted.

IMPORTANT!For the realization of a network with the TOPAX® DX and the structure of a bus system to a PC a computer cable "KAT.5 type 2X2XAWG24/1 (Lapp cable)" or better is to be used.

Using other cables can cause data errors and affect the data communication. The manufacturer is not liable for this.

Most modern computers are equipped with the serial computer interface R-S �3� and/or with USB - interfaces. For the connec-tion to a RS 485 network, an additional connector converter (RS 485 to RS �3� or RS 485 to USB) is necessary.

There are interface components in the under casing part of the main board in the TOPAX® DX. They are partially hidden from view by the output components (see diagram 4.6).

Fig. 4.6: RS 485 connections on the interface component’s board partially hid-den from view by the output components

Page 10: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

10 | Operation Manual TOPAX DX | BA-40100

Chapter�4:�Mounting�build-in�housing

NOTICE!The data line must be locked at both sides with a 120 Ohm line resistance and must be supplied a firm potential using the two link plugs on the two jumpers on the circuit board of the display of all la-test TOPAX DX versions.

Two link plugs/jumpers have to be connected to the TOPAX® DX (the last one in the network) for the 1�0 ohm switch, Pull-up and Pull-down resistances. The resistances are not active in its deliv-ered state. The resistance of 1�0 ohms on the PC side is applied via the connector converter.

The jumper plug-in slots are located in the upper casing on the display board, above the flat band-connection to the main board (see diagram 4.7).

resistances�are�NOT�activated(delivery�status)

resistances�are�activated(last�device�in�the�network)

Jumper position: OFF Jumper position: ON

The resistances are NOT active.jumpers are set DOWN

The resistances are active.jumpers are set UP

Fig. 4.7: Position and setting of the jumper to activate the RS 485 resistances on the last TOPAX® DX in the network.

TopView�SoftwareFor the remote indication a visualization program is offered in two versions. The program TopView mini is free of charge and can be downloaded from Internet.

4.5�Power�connectionsThe equipment may be installed and attached only by authorized and qualified electricians. Connections must be made according to the enclosed wiring diagrams.

NOTICE!Only work on electric connections when the device is disconnected from the power supply.

Insert the cables in the various connections screwed on the bot-tom side of the housing. After the installation, tighten all cable connections so that the required protection class is provided (see fig. 4.8).

Fig. 4.8: Cable connections for protected cable feedthrough on the rear side of the housing.

For the connection to the power supply and to the actuators, TOPAX® DX is equipped with special terminal clips (see fig. 4.9). For a better assembly these clamps are designed plug-ins (see fig. 4.10), whereby the maximum cross section is �.5 mm� for the power cord and 1.5 mm� for all other cable to the terminal clips.

Fig. 4.9 and 4.10: The principle of the connecting terminal to the technical com-ponents. Individual connecting terminals, removable for installation, of the technical components.

NOTICE!When choosing the line material, for installation and electrical connection of the device, observe the regu-lations of VDE 0100 “Provisions for setting up elec-tric power plants with nominal voltages below 1000 V“ or the individual national rules.

NOTICE!The equipment is not suitable for the installation in explosive conditions!

Page 11: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 11

Chapter�4:�Mounting�build-in�housing

Connection�of�the�in-�and�outputs

NOTICE!Terminal clips allocation depends on the software configuration of TOPAX® DX. Terminal clips alloca-tion depends on the delivered equipment.

The delivered equipment is listed in the protocol, which is at-tached to the device. Use this connection diagram to wire the device and to put it in operation.

If the current software-configuration is not correct, the device has to be new configured before connecting (see Chapter 4.8). The display will show the new terminal diagram.

Voltage�supplyThis instrument has no power switch and is immediately opera-tive after the creation of the operating voltage. For this reason an external switch and/or protective switch is to be planned.

For the connection to the power supply on the main board, refer to the enclosed wiring diagram (see Chapter 4.6).

NOTICE!DO NOT let power be switched on via timer opera-tion!

Internal�fuseThe TOPAX® DX is internally secured with a micro fuse T�A. The internal fuse interrupts the power supply in the case of a short-circuit. For an additional external power supply protector, the value should not be below � A (slow-blowing).

The fuse is located in the under casing on the power supply board (see diagram 4.11 and 4.1�). To change the fuse the guard over the power supply has to be removed with the help of a cross-slot screwdriver (4 screws).

Fig. 4.11: Position of the power supply unit in the under casing.

Fig. 4.1�: Position of the fuse on the power supply board.

Sensor�technologyMeasuring cables may not be parallel when too close (less than 15 cm) to power switches and/or cables for power installation. Separate cable channels are to be used. Disturbing stray effects could otherwise falsify the measurement. At close distances, power supply and measuring lines may only cross at a 90° an-gle.

The maximum permissible length of the measuring cables de-pends on the kind of the sensor. When performing very ohmic measurements (e.g. pH or REDOX measurements) the following is to be considered:• Connections and patch cords must be clean and dry.• The permissible bending radius of the cable must be

respected.• The quality of the holding wires must correspond to the

defaults from the data sheet of the sensor.

IMPORTANT!If possible a continuous cable is to be used from the sensor to the measuring entrance. An extension of the cable by plugs or terminal socket increases the risk of disturbances due to contamination, humidity or excessive transition resistances.

Connecting�the�actuatorsWhen connecting your actuator the equipment must be switched off to prevent uncontrolled starting and malfunctioning.

IMPORTANT!To prevent the output relays from bonding in the case of a short in the load circuit, it must be separatly protected with the maximum relay switching current. For inductive loads, apply a protective circuit to the contacts of the relays (spark quenching). The manu-facturer recommends the usage of the interference suppression /spark suppression module (article 78614).

Replacing�the�batteriesThe life of the batteries (Type VARTA, CR1/� AA, � Volt, Lithium) provided with the internal instrument clock is approx. 5 – 10 years. When the batteries wear out causing a power shortage, a warn-ing message will be displayed on the instrument. The bat-tery is welded on the display circuit board (see fig. 4.13). It must be replaced by a skilled technician.

Fig. 4.13: Battery for internal clock, on the display circuit board.

Page 12: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

1� | Operation Manual TOPAX DX | BA-40100

Chapter�4:�Mounting�build-in�housing

4.6�Terminal�clips�on�the�technical�components

output block

mainboardDO

4DO

3DO

2DO

1

7840478403

78402

DO7 DO6 DO5

DO0

78399

PC interface RS 485(hidden)78406

+ -+ - + - + - + - + - + - + -

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

20 mA Power Outputs Digitale Outputs

36 37 38

PE

N

L

power generator

33 34

929394

8788899091

86

- +

81 82 83 84 85

- -+ +56 57 58 59 60

- +

51A

52A 53 54 55 61

51B

52B

- -+ + -+

71 72 73 74 75

767778

5-fold input block

Alarm relays

394041

43444546

42

35

9596

B A

3-foldinput block

Plugin connector to the display circuit board

Fig. 4.14: Rear side of the housing with the main board, the input module 5-fold "78403", the input module 3-fold "78404", the output board "78399" and the partly hidden PC interface "78406".

Main�board�(order�no.�78402)

terminal FunctionAnalogue power outputs 0/4...�0 mA (see chapter 10 also)

1 + Measurement output0/4...�0 mA

Free chlorine

� -

3 + Measurement output0/4...�0 mA

pH value

4 -

5 + Measurement output0/4...�0 mA

Redox

6 -

7 + Measurement output0/4...�0 mA

Temperature or programmed as controller output8 -

9 + Measurement output0/4...�0 mA

bonded chlorine or programmed as controller output10 -

11 + Measurement output0/4...�0 mA

conductivity or programmed as controller output1� -

13 + Continuous controller output0/4...�0 mA

programmed as controller output

14 -

15 + Continuous controller output0/4...�0 mA

programmed as controller output

16 -

NOTICE!The constant regulating outputs 0/40...20 mA of the main board are also allocated automatically in the software configuration as per a fixed rank order of the terminals, in accordance with the allocation pro-cedure for the output components.

Ranking of the outputs for automatic allocation:1. automatic controller output free chlorine�. automatic controller output pH - value3. automatic controller output bound chlorine4. automatic controller output conductivity5. Flocking pump output

In the same the clamps are assigned in a firm order.• clips 15/16• clips 13/14• clips 11/1�• clips 9/10• clips 7/8

The clip allocation is automatically displayed at the end of the configuration (see chapter 11 also).

Page 13: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 13

Chapter�4:�Mounting�build-in�housing

terminal FunctionDigital inputs17 Potential free input measuring water shortage *)1819 Potential free input Filter cleaning *)�0�1 Potential free input Level pre-alarm Controller 1 **)���3 Potential free input Level alarm Controller 1 **)�4�5 Potential free input Level pre-alarm Controller � **)�6�7 Potential free input Level alarm Controller � **)�8�9 Potential free input Activate night-time reduced

operation3031 Potential free input not used3�*) normally ON or normally OFF**) normally ON or normally OFF or not active33 A Internal

PC interfaceInterface for software-update

34 B35 GND36 Alarm relay as com-

mon alarm normally closed (N.C.)

37 Middle contact

38 normally open (N.O.)39 PE Protection conductor Voltage: 90 up to �64VAC40 PE41 N Neutral conductor4� N43 N44 L Phase45 L46 L

5-fold�Input�block�(part�no.�78403):

terminal Function Cable�colour Remarks51A + Free chlorine

(amperimetric elec-trode Type CS 1�0)Electrode mating copper/platinum or silver/platinum possible

CS1�0 (Cu/Pt)Cu : blue (-)Pt : red (+)CS1�0 (Ag/Pt)Ag : purple(-)Pt : red (+)

Variant A and variant B can be only used as an alternative.

5�A -

51B + - Total chlorine measuring electrode (40...�0 mA)- Membrane-enclosed sensor free chlorine (4...�0 mA) (�0 mA input with �4 VDC sensor power)

5�B -

53 + pH value

54 -

55 + Redox

56 -

57 Temperature(Polarity at wish)58

59 Potentiometer with positional feedback for Servo motor(Polarity of clips 59 and 61 is at wish)60 Driver

61

3-fold�Input�block�(part�no.�78404):

terminal Function Cable�colour71 Reference electrode

(with integrated cable)free chlorine (potentiostatic electrode)

Reference electrode (Glass): blackCounter electrode (Stain-less steel): redMeasuring electrode (gold): violet

7� Counter electrodeStainless steel

73 Measuring electrode (gold)

74 + �0 mA passively (without supply to the sensor)- conductivity measurement or disturbance factor

75 -

76 Potentiometer with positional feedback for Servo motor. (Polarity of clips 76 and 78 is at wish)

77 Driver

78

Outputs�board�(order�no.�78399)

terminal Output81 + Electronic output

(DO7) (Optocoupler)programmable

8� -

83 + Electronic output (DO6) (Optocoupler)

programmable

84 -

85 + Electronic output (DO5) (Optocoupler)

programmable

86 -

87 Relay output (DO 4) programmable

88

89 Relay output (DO 3) programmable

90

91 Relay output (DO �) programmable

9�

93 Relay output (DO 1) programmable

94

95 Relay output (DO 0) programmable

96

NOTICE!The constant regulating outputs 0/40...20 mA of the output components are also allocated automatically in the software configuration as per a fixed rank or-der of the terminals, in accordance with the alloca-tion procedure for the main board.

The outputs are allocated according to the ranking:1. Automatic controller free chlorine�. Automatic controller pH value3. Automatic controller bound chlorine4. Automatic controller conductivity5. DIN - contact6. Eco - contact7. Flocking contact

Depending upon output type, TOPAX® DX selects the next free relay output or optocoupler. The clamps are assigned in a firm order: clamps 87/88 to 95/96 for relays, or 81/8� bis 85/86 for optocouplers.

Page 14: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

14 | Operation Manual TOPAX DX | BA-40100

Chapter�4:�Mounting�build-in�housing

4.7�Operation�and�keyboard�layout

Fig. 4.15: Housing of the TOPAX® DX with control panel. The keys are integrated in a glass keyboard and react to contact.

Keys FunctionsCrossed arrow keys

• Menu change-over in the menu "service";• Change-over between the individual numbers• Numerical values change, parameter adjustPress the key to change from one menu item to the other. Numeric values are entered and modi-fied continuously.

Key "OK" between the arrow keys

Input information are received and saved.Successful saving is notified by a longer beep

Key ①: „ESC“ Exit the menu, one level upTerminate input without storage

Key ①: „ESC“(hold 5 seconds)

Return to the main menu

Keys ② - ⑥ The functions of the keys vary according to the menu and are displayed respectively.

Key layout of TOPAX® DX

NOTICE!The glass keyboard of the TOPAX® DXis delivered with a protective transparent foil that must be re-moved after installation.

If no key is operated, the controller returns automatically to the measuring mode after approx. 5 minutes. Changed parameters, which were not confirmed with the “OK” key, are not stored.

Exception: During the calibration and with the configuration no “time out” takes place.

NOTICE!If no values are to be changed, "ESC" can be pressed and the selected menus left at any time. The controller uses the inital settings. Changed values are confirmed with the “OK” button. An exception are the functions clock and timer. Their modification does not require any confirmation.

General rules for entries:• The values can only be changed within the admissible value

range.• The function of the key is signalled with a tone.• A 60 seconds key lock allows a cleaning of the glass sur-

face. To activate the key lock in the main menu, press the top arrow and confirm with the key "OK".

• Some functions can be protected by a password against unauthorized access (see Chapter 16, Menu 5.9 „pass-word“).

4.8�First�set-up�and�programming�guidelinesAfter the correct installation, switch on the power supply.

The TOPAX® DX is programmed by the manufacturer based on customers’ specs before shipment and is supplied along with a terminal connection diagram. Failure of the customer to sup-ply instructions on his purchase order, TOPAX® DX shall be pro-grammed by the manufacturer to the standard default settings (see chapter 19).

For the initial start-up the operator has to configure the TOPAX® DX and set its sensors and the installed actuating elements as well as set special functions. TOPAX® DX will automatically as-sign the right inputs and outputs based on these data and the corresponding terminals will be indicated. Ineffective or impos-sible configurations (for instance double assignment of the out-puts) are not admissible.

After a successful configuration the TOPAX® DX starts up with a standard display (see chapter 16). A subsequent renewed con-figuration can be carried out via the Service-Menu (see chapter 16, menu 5 “Configuration”).

IMPORTANT!All menus of TOPAX® DX are shown a ID-number marked in the bottom line on the left display corner.(see Fig. 4.16).

Choice�of�LanguageAfter a short hardware test the TOPAX® DX during the initial start-up, the TOPAX DX displays the Home page for Configuration (see fig. 4.16). This screen is shown until a language has been chosen by pressing the key ② (German), ③ (English), ⑤ (French) or ⑥ (further languages “>>”) – see diagram 4.15 and 4.16.

Lutz-Jesco GmbHAm Bostelberge 1930900 WedemarkDeutsch

English

Francais

0.1 Software Version: ...........

TOPAX DX Start

Fig. 4.16: Home page for the configuration of language choice

Further�languages�-�MMC�Memory�cardBesides the fixed installed languages of German and English there is other language data for the TOPAX® DX. This can be writ-ten on an external data storage unit, a MMC Memory card, and

Page 15: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 15

Chapter�4:�Mounting�build-in�housing

then imported by the TOPAX® DX. For further questions regarding the availability of languages please ask the manufacturer.

The MMC (Multi-Media-Card) Memory card with the language data is inserted on the display board in the upper casing (see Diagram 4.17).

The additional languages are available in the Configuration under ⑥ (further languages “>>”).

Press the key ⑥ and chose the desired language with the ar-row keys ▲ and ▼. Confirm with the “OK” key. The language is loaded into TOPAX® DX.

Lutz-Jesco GmbHAm Bostelberge 1930900 Wedemark

Tel: 05130/58 [email protected]: 05130/5802-68http://www.jesco.de/

For help please press the “Help” button

help next

0.2

TOPAX DX configuration

Fig 4.18 / menu 0.�: Home page for the configuration of language choice

After having chosen the language the TOPAX® DX moves to the menu 0.� (see diagram 4.18). Now you can start directly with the configuration, select key ③ (“next”), and/or the Help-Menu, key ⑥ (“help”).

Help-MenuThe Help Menu is available as a point of help for many menu points. By pressing a random key the TOPAX® DX returns to the previous menu again.

Menu�0.4:�Configuration�of�the�terminals�for�sensors�and�actuating�elements.After choosing a language the TOPAX® DX goes to menu 0.� (see fig. 4.18). By pressing the “next” key, the TOPAX® DX goes to menu 0.4.1.

The TOPAX® DX checks by means of the installed components, which connections are possible and offers per the connections presents a choice in Options.

Menu�0.4.1:�Free�chlorine�inputWith the arrow keys ▲ and ▼ you can select between the fol-lowing options:• �-electrodes measuring cell CS 1�0• Potentiostat (PM)• Encapsulated electrode• Redox single-rod measuring cell

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

NOTICE!The configuration does not run automatically through all the menus shown here. It depends on the configuration of the TOPAX DX on delivery. The configurations are saved after running through all menus.

Menu�0.4.2:�Free�chlorine�outputWith the arrow keys ▲ and ▼ you can select between the op-tions:• Servomotor w. potentiometer • Servomotor without potentiometer • Pulse frequency (Optocoupler) • Pulse frequency (Relay) • Pulse length (Relay) • - Continuous control output (�0 mA-current output)• ON/OFF (Relay)• No controller function

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.3:�pH�outputWith the arrow keys ▲ and ▼ you can select between the op-tions:• Servomotor w. potentiometer • Servomotor without potentiometer • Pulse frequency (Optocoupler) • Pulse frequency (Relay) • Pulse length (Relay) • Continuous output (�0 mA)• �-sides pulse frequency (optocoupler) • �-sides pulse frequency (relay) • �-sides pulse length (relay) • ON/OFF (Relay)• No controller function

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.4:�Input�RedoxWith the arrow keys ▲ and ▼ you can select between the op-tions:• ON • OFF

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Page 16: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

16 | Operation Manual TOPAX DX | BA-40100

Chapter�4:�Mounting�build-in�housing

Menu�0.4.5:�Input�temperatureWith the arrow keys ▲ and ▼ you can select between the op-tions:• ON • OFF

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.6:�Total�chlorine�inputWith the arrow keys ▲ and ▼ you can select between the op-tions:• ON • OFF

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.7:�Bonded�chlorine�output(The menu is only availabe, if ON was selected for "Total chlorine input" in menu 0.4.6 )

With the arrow keys ▲ and ▼ you can select between the op-tions:• Pulse frequency (Optocoupler) • Pulse frequency (Relay) • Pulse length (Relay) • Continuous output (�0 mA)• ON/OFF (Relay)• No controller function

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.8:�Conductivity�input�With the arrow keys ▲ and ▼ you can select between the op-tions:• ON • OFF

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.9:�Conductivity�output(The menu is only availabe, if ON was selected for "Conductivity input" in menu 0.4.8 )

With the arrow keys ▲ and ▼ you can select between the op-tions:• Pulse frequency (Optocoupler) • Pulse frequency (Relay) • Pulse length (Relay) • Continuous output (�0 mA)• ON/OFF (Relay)

• No controller function

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.10:�Flocking�pump�outputWith the arrow keys ▲ and ▼ you can select between the op-tions:• Pulse frequency (Optocoupler) • Pulse frequency (Relay) • Pulse length (Relay) • Continuous output (�0 mA)• ON/OFF (Relay)• OFF

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.11:�DIN-Contact�outputWith the arrow keys ▲ and ▼ you can select between the op-tions:• Relay contact• Optocoupler• ECO control mode• OFF

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.12:�ECO�control�outputWith the arrow keys ▲ and ▼ you can select between the op-tions:• Optocoupler• Relay contact

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶. The TOPAX® DX then goes to the next menu.

The key "back" or ◀ leads to the previous menu.

Menu�0.4.13:�Disturbance�factor�input(The menu is only availabe, if OFF was selected for "Conductivity input" in menu 0.4.8)

With the arrow keys ▲ and ▼ you can select between the op-tions:• 0..0.�0mA• 4...�0 mA• OFF

The selected option is highlighted in grey. The entry is confirmed with the "OK", "next" key or ▶.

To go back to the previous menu, press the key "back" or ◀.

Page 17: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 17

Chapter�4:�Mounting�build-in�housing

Menu�0.5:�Completing�the�configurationThe TOPAX® DX moves immediately on to the configuration, at the latest after menu 0.4.13, in the finalising menu (menu 0.5) and shows the chosen configuration with all the previously cho-sen Options in the total overview.

The configuration is saved with the “save” key and the finalising confirmation key “OK” and the TOPAX® DX moves to the next menu 0.6.1.

The configuration starts from the beginning again with the key “back”. The TOPAX® DX then goes to menu 0.4.1.

news configurationfree chlorine

potentiostat3 point step with poti

ph value

Impulsefrequency (relais)

combined chlorine

flocculation

impulsefrequency (opto)

DIN-contact

OFF

saveimpulselength (relais)

back

conductivity sensor

impulselength (relais)

0.5

REDOX temperatureon on

eco control

off

flow input

off

Menu 0.5: Overview from all selected options. A changed configuration will be displayed red.

Menu�0.6:�Terminal�connection�clipsAccording to the chosen Options the TOPAX® DX determines the relevant terminal connections and shows this in menus 0.6.1 to 0.6.4 (each by number of connections).

freies Chlor

Eingangsklemmen Analog

weiter

Klemmen / Einstellung prüfen

pH-Wert

REDOX

Temperatur

neue Konfiguration

Gesamtchlormessung

71 - 72 - 73

53 - 54

55 - 56

57 - 58

Leitfähigkeitsmessung

51B - 52B

0.6.1

74 - 75

Nur im spannungsfreienZustand anklemmen

Menu 0.6.1: Example of a new configuration and the relevant terminal connec-tion plan. A changed configuration will be displayed red.

NOTICE!Make a note of the given connections on the pre-print in chapter 23.

In order to move between the individual menus 0.6.1 to 0.6.4, press either the “next” or the “back” key, or the arrow keys ▲ und ▼.

To finalise the total configuration confirm the connection plan with the “OK” key. After confirming the configuration the TOPAX DX restarts an switchs to the standard display (see fig. 4.19).

More information about the TOPAX DX menu structure are given in chapter 16.

mg/l

mV

ºC

comb. cl.

temp.

REDOX

free chlorine pH value7.040.39

719 mg/l0.0926.3

eff. cl. 0.30 mg/l

Topax DX

14:28 06.02.2007

Fig. 4.19: Standard display with the measuring values.

NOTICE!At start-up the controller outputs of your TOPAX® DX will be function-less for approx 60 seconds. This time is required to stabilize the electrochemical sen-sors connected. During this time the status display shows the message "starting in..... s" (countdown seconds are progressively shown). At the end of this time TOPAX® DX is fully operative.

NOTICE!In order to prevent unauthorised manipulation, the TOPAX® DX has a password protection (see Chapter 16, menu 5.9)

4.9�Next�stepsAfter a successful configuration the next steps should be:• Connect the sensors and the actuating elements - if not

already connected• Calibrate the sensors to the measuring output (see chapter

5 and 6)• Set up the set point of the measuring inputs (see chapter

16, menu 1.1)• Set up the control (see chapter 16, menu �.1)• Configuration of the regulating outputs (see chapter 7)

NOTICE!The configuration of the in- and output can be re-called via the point “configuration” in the menu “service” whilst in operation (see chapter 6, menu 5). Here the changes to the terminal plan are written in red figures.

Page 18: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

18 | Operation Manual TOPAX DX | BA-40100

Chapter�5:�Measuring�values�inputs

5.�Measuring�values�inputsThis chapter exemplifies the chemical and physical correlation, which is necessary to understand the behaviour of the input measuring values.

The input measuring values are examined for:• Free chlorine• pH value• Redox potential• Temperature• Total chlorine and display of bonded chlorine• Conductivity

In doing so an important element is the calibration of the sen-sors.

NOTICE!When set up the unit for the first time, care should be taken to perform individual calibration of each out-put immediately after connecting the sensors in the system. TOPAX® DX is designed to perform moni-toring of all calibration processes based on reason-able parameters (zero point and conductance) and the measurements are accurately documented. Non calibrated and „Roughly calibrated” value inputs are

marked out in clear text. „Roughly calibrated” values are shown on the main display in red.

NOTICE!Please note possible time delays due to the initial running times of the sensors.

The limits of „Roughly calibrated” are:

measurement�value limitsslope rate pH <53 mV/pH or

> 61 mV/pH

zero point pH < -40mV or> 40mV

slope rate Redox < 0,85 mV / mV or> 1,� mV / mV

slope rate chlorine atamperometric or potentiostatic measur-ing cell

< 3 µA / mg/l or> 100µA / mg/l

slope rate chlorine with encapsulated electrode (0..�.00 mg/l)

< 3mA / mg/l or> 13mA / mg/l

slope rate chlorine with encapsulated electrode (0...5.00/10.00 mg/l)

< 1mA / mg/l or> 5.�mg/l

The remark „roughly calibrated” sheds light on the calibration quality and the conditions of the electrochemical electrodes.

Look for calibration faults and eliminate them. Replace the sen-sors as soon as possible, if necessary. You can use the sensors unchanged until replacement.

5.1�Free�chlorine�measurements�inputThe value of „free chlorine“ is dependent on the Ph-value of the streaming water flow which results form the reaction of chloride ions to different Ph values. This relationship further determines the chlorine dissociation curve (see fig. 5.1).

Fig. 5.1: The dissociation curve shows the dependence regarding the pH value

For photometric measurements the pH-value of the sample is soaked in a pH-buffer of approx 6,5 in order to obtain a meas-urement of a higher content of effective chlorine than actually available in the water stream. In the presence of high pH-values significant differences will occur between expected and actual disinfection if assessed by photometric analysis. The main display will show therefore � free chlorine values: The results of photo-metric analysis and the content of effective chlorine to assure the germicide effect at the pH-value of the process medium.

Technical dataPower signal is received from excess chlorine detector using � electrodes, a potentiostat or a membrane-enclosed sensor (measuring signal 4...�0mA).

Following measuring ranges are possible:

Sensor�type Measuring�rangeAmperometric electrode (Excess chlorine detector with � electrodestype: CS1�0)

0...1.00 mg/l0...�.00 mg/l0...5.00 mg/l0...10.00 mg/l

potentialstatic electrode(Type: PM)

0...1.00 mg/l or0...�.00 mg/l

Encapsulated electrode(Type: Cl 4.1 A �)

�0 mA type;Set measuring range based on type of detector

Accuracy ± 1 % after calibration

Page 19: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 19

Chapter�5:�Measuring�values�inputs

Calibration of amperometric, excess chlorine detector with 2 electrodes ((CS120)Before starting the calibration, the upper value of the measuring range of the sensor must be defined at the TOPAX® DX (see Chapter 16, menu 5.1).

Then the input must be calibrated with a �-point calibration (see Chapter 16, menu 1.�):

The physical value (µA) measured at the sensor is shown on the display during calibration.

Calibration method 1: Zero-point calibration

To perform zero-point calibration, operate the detector in chlo-rine-free water or just stop the water flow through the instru-ment. The value of the physical quantity shown on the display (approx 5-10 µA) can be saved as soon as it stops changing. The device automatically changes to the next menu section.

Calibration method �: DPD

The sensor is operated with sample water. If the physical value on the display does not change anymore, the chlorine concentration in the sample water is determined by means of the DPD method. In order to avoid signal variations and consequent reading errors, water must be taken at the sensing element and the actual sig-nal must be saved directly in the TOPAX® DX upon taking of the water sample. The content of chlorine in water is measured by means of the DPD method. The value must be set in the control-ler and saved by pressing OK.

After storage the slope value of the chlorine sensor is shown. The typical resistivity value is approx. �5–35 µA (depending on water type) per mg/l of free chlorine. The accuracy of resistivity measurements is monitored throughout the process.

1-point calibration is sufficient (reference value �) for validation of the chlorine content after optimization.

Calibration of potentialstatic measuring cell (PM)Before starting the calibration, the upper value of the measuring range of the sensor must be defined at the TOPAX® DX (see Chapter 16, menu 5.1).

Then the input must be calibrated with a 1-point calibration (see Chapter 16, menu 1.�):

Reference value.-.DPD

The sensor is operated with sample water. A nearly stable physi-cal value should be displayed. In order to avoid signal variations and consequent reading errors, water must be taken at the sens-ing element and the actual signal must be saved directly in the TOPAX® DX upon taking of the water sample. The content of chlorine in water is measured by means of the DPD method. The value must be set in the controller and saved by pressing OK.

After storage the slope value of the chlorine sensor is shown. The typical resistivity value is approx. 35 µA (depending on water type) per mg/l of free chlorine.

The accuracy of resistivity measurements is monitored through-out the process.

After calibration of the free-chlorine is completed, you may even-tually switch to calibration of the “total chlorine detector” by sim-ply pressing on „continue".

NOTICE!When measuring the free chlorine with a potentio-stat it is possible to perform a compensation of the pH-value and temperature by simply connecting a pH-electrode and a temperature sensor to TOPAX® DX (see chapter 16, menu 5.1 "inputs").

Calibration of encapsulated electrodeBefore starting the calibration, the upper value of the measuring range of the sensor must be defined at the TOPAX® DX (see Chapter 16, menu 5.1).

Then the input must be calibrated with a 1-point or a �-point calibration (see Chapter 16, menu 1.� "Calibration"):

NOTICE!When measuring free chlorine by means of a fully encapsulated electrode, make sure to connect both terminal clips 51 B and 52 B. These clips are respec-tively used to feed the 20 mA signal of the electrode into the controller and to supply 24 VDC operating power to the sensing electronics of the electrode.

zero-point calibration (�-point calibration)

Zero point calibration of the sensing electrode is normally not a must-requirement, as tuning of the 4...�0 mA output signal of the electrode is done on input 4...�0 mA (4 mA corresponds to 0,00 mg/l free chlorine).

However, a zero-point calibration may be still required due to the tolerances of the sensing electronics of the electrode. For this reason the zero-point must be set upon first setup of the instru-ment. For this purpose the measuring water extraction must be operated with chlorine-free water.

Reference value.-.DPD

The sensor is operated with sample water. A nearly stable physi-cal value should be displayed. In order to avoid signal variations and consequent reading errors, water must be taken at the sens-ing element and the actual signal must be saved directly in the TOPAX® DX upon taking of the water sample. The content of chlorine in water is measured by means of the DPD method. The value must be set in the controller and saved by pressing OK.

After storage the slope value of the chlorine sensor is shown.

The accuracy of resistivity measurements is monitored through-out the process.

IMPORTANT!The signal from the excess-chlorine sensing detector is converted by the electrode into an impressed cur-rent pulse of 4...20 mA. Whenever your TOPAX® DX features a lower value than 3.5 mA, an alert message is displayed „total chlorine sensor failure", the alarm relay is switched.

Page 20: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

�0 | Operation Manual TOPAX DX | BA-40100

Chapter�5:�Measuring�values�inputs

5.2�Measuring�input�pH�value

Technical data

Power ValuesInput Voltage signal from a pH single-rod measuring cell

Input resistance 109 Ohm

Measuring accuracy 1 % (after calibration)

The voltage signal transmitted by the combination electrode is proportional to the pH value. This voltage is defined by the Nernst voltage. The Nernst voltage ist he change in voltage per pH unit. It depends on the temperature of the medium to be measured (see corresponding technical literature or German Standard DIN 19�61).

The following table shows the temperature dependence of the Nernst voltage:

t�(°C) U�(mV) t�(°C) U�(mV) t�(°C) U�(mV)0 54,�0 35 61.14 70 68,08

5 55,19 40 6�,13 75 69,08

10 56,18 45 63,1� 80 70,07

15 57,17 50 64,1� 85 71,06

�0 58,16 55 65,11 90 7�,05

�5 59,16 60 66,10 95 73,04

30 60,15 65 67,09 100 74,04

The Nernst voltage is measured between the pH glass electrode and a reference electrode. Mechanically these two electrodes are integrated in a pH combination electrode.

CalibrationCalibration of the electrode may be performed by ways of „�-point calibration“ with � buffer solutions or by „1-point calibra-tion” with final input of the resistivity value. The mandatory condi-tions for using „1-point calibration“, is that the resistivity of the sensing electrode must be priory measured in a lab.

The actual voltage of the electrode and the design value of buffer solution are displayed on the TOPAX® DX during calibration so that the electrode can be actually graded while performing the calibration process.

The reaction time for any brand new electrode is just a few sec-onds and the electrode is considered as fully adjusted when the physical reading becomes stable. In the case of older combina-tion electrodes the reaction time may be longer.

The single-rod measuring cell is directly connected to the input terminal of the board of the input module 5-fold (see section 4.3).

2-point calibrationThe physical measuring value (mV) on the electrode is displayed in the menu (see chapter 16, menu 1.� "calibration") along with the design measuring value that should be ideally assessed for the pH.

Buffer 1 - zero-point calibration

Submerge the pH combination electrode in a buffer solution which is equivalent or close to the zero point of the electrode. The ideal zero point (O mV) of the combination electrode is pH 7.00, the actual zero point, however, deviates slightly from this value. For zero-point calibration a Lutz-Jesco buffer solution of pH 6.80 is available. When soaking the Ph-electrode in this solution, a voltage of 1� mV should be displayed on the TOPAX® DX. The physical value actually measured is, however, always different from the theroretical one.

When the physical value on the display becomes stable, you may save the calibrated value by pressing „OK“.

IMPORTANT!Should the actual measured voltage strongly differ from the design zero-point of the electrode, it means there is a zero-point drift of the electrode. Zero-point drift should not exceed the specifications of the DIN Standards 19265. In the event of zero-point drift exceeding ± 40 mV, TOPAX® DX warns you about possible bad prove calibration.

Buffer � - slope calibration

Accurately clean the electrode with deionised or distilled water before calibration of the resistivity.

NOTICE!Avoid rubbing off glass electrodes as you may pro-voke accumulation of static electricity in the elec-trode which in turn would result into faulty readings!

For slope calibration a buffer solution must be used which differs at least � pH units from the zero point. For zero-point calibration a buffer solution of pH 9.�7 is available from the manufacturer. Should you use a different buffer solution for calibration of the resistivity, you first need to set TOPAX® DX to the pH of your other solution. When soaking the Ph-electrode in this buffer solution (Ph = 9.�7), a voltage of -134 mV should be displayed on the TOPAX® DX. The physical value actually measured is, however, always different from the theroretical one. Confirm presetting by pressing the “OK“ key.

Then the slope value of the combination electrode is displayed. In accordance with the DIN Standards 19�65 the resistivity if an electrode should range between 5� and 59 mV per pH-value.

Zero-point stability and accuracy of the measured resistivity are consistently monitored.

IMPORTANT!If the slope value differs considerably from these values, check the combination electrode or the connecting cable and the plug connectors. Should zero-point and resistivity values of the combination electrode exceed the admissible tolerances, the sys-tem notifies the operator with a warning message. In this case provide for immediate replacement of the electrode.

Page 21: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | �1

Chapter�5:�Measuring�values�inputs

buffer�solution voltage�value3,06 ��9,15 mV

4,65 136,68 mV

6,80 11,63 mV

9,�7 -13�,0� mV

Theroretical voltage value of different buffer solutions at �0°C

IMPORTANT!Store buffer solutions in a cool and dark place! Ob-serve its durability. The buffer solution must not be contaminated. Therefore do not put the single rod measuring cells directly from one buffer solution into another solution.

1-point calibrationThe 1-point calibration can also be used for the pH single rod measuring cell calibration (see Chapter 6, menu 1.�).

Submerge the pH combination electrode in a buffer solution which is equivalent or close to the zero point of the electrode. The ideal zero point (O mV) of the combination electrode is pH 7.00, the actual zero point, however, deviates slightly from this value. For the zero point calibration a buffer solution of pH 6.80 (TOPAX® DX default setting) is available from the manufacturer.

When soaking the Ph-electrode in this solution, a voltage of 1� mV should be displayed on the TOPAX® DX. The measured physi-cal value however always differs from the design one.

When the physical value on the display becomes stable, you may save the calibrated value by pressing „OK“.

Now enter the resistivity of the electrode.

IMPORTANT!Should the actual measured voltage strongly differ from the design zero-point of the electrode, it means there is a zero-point drift of the electrode. Zero-point drift should not exceed the specifications of the DIN Standards 19265 (±40 mV).

Offset compensationIn accordance with DIN 19643, the control of the pH value is to be made with an electrical metric pH value measurement.

By external influences it can be possible that the pH value of the electrical metric measurement, measured by hand with the pho-tometer, deviates by a constant value. The menu "offset align-ment" offers the posibility to eliminate the difference.

NOTICE!The offset value is set to „0“ after every new calibra-tion.

5.3�Measurement�output��Redox�potential

Technical data

Power ValuesInput Voltage signal of a Redox single-rod measuring cell

(0-1000 mV)

Input resistance 109 Ohm

Measuring accuracy 1 % (after calibration)

The Redox potential is measured with the help of the Redox sin-gle-rod measuring cell. It measures the voltage which exists in the water due to oxidizing and reducing ions.

CalibrationCalibrate the combination electrode during startup. For calibra-tion of the Redox single-rod measuring cell only one reference value must be set. The physical value (mV) measured at the sen-sor is shown on the display during calibration.

For calibration a buffer solution is required in order to meas-ure a defined voltage in connection with the REDOX combina-tion electrode. (given value: 468 mV). This value can be changed when using other buffer solutions and/or combination electrodes with other electrolytes. To change, use the buttons on the control panel. The voltage actually measured is shown on the display during calibration. This value has a small deviation from the given value of the buffer solution. The deviation should not be bigger than approx. 10%.

The accuracy of resistivity measurements is monitored through-out the process.

After a reaction time (approx. 1 minute) the physical value does not change anymore.

The reference value can be now entered and saved by pressing the “OK” button.

IMPORTANT!With old combination electrodes the response time can become larger and vary. Furthermore the meas-ured value can be largely different from that of the buffer solution. This signifies that the combination electrode must be checked and possibly replaced.

The single-rod measuring cell is directly connected to the input terminal of the board of the input module 5-fold (see section 4.3).

IMPORTANT!The measuring signal of the REDOX combination electrode can be also configured for controlling the disinfection.

Page 22: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

�� | Operation Manual TOPAX DX | BA-40100

Chapter�5:�Measuring�values�inputs

5.4�Measuring�input�temperature

Technical dataPower ValuesSensor Pt 100

Measuring range: -50°C – +150°C

Measuring accuracy 1 %

Do not use other than a two-wire "Pt 100" as sensor.

CalibrationThe zero point of the measuring input is set in the factory. This measuring input can be adjusted with the temperature of the measuring water of the TOPAX® DX (see chapter 16, menu 1.� "calibration").

For this purpose, measure the temperature of the measuring wa-ter with a comparative thermometer and set the measured value as reference in the TOPAX DX.

5.5�Measurement�input�total�chlorine�and�display�of�bonded�chlorine

Technical data

Power ValuesSensor Total chlorine measuring cell (encapsulated electrode)

Measuring signal 4...�0 mA corresponding measuring range of the measuring electrode

Measuring accuracy 1 % (after calibration)

CalibrationThe total chlorine measurement is pH and temperature-compen-sated. For the measurement of the free chlorine the potentiostatic measuring cell is necessary, otherwise a total chlorine measure-ment is not possible. In connection with the measurement of total chlorine and free chlorine the bonded chlorine is displayed in the TOPAX® DX.

Measurements of bonded chlorine are performed using and encapsulated electrode. This total chlorine measuring cell con-sists of a sensor part with integrated electronics and supplies a 4...�0 mA measuring signal according to the measuring range 0.00...�.00 mg/l.

Reference value.-.DPD

The sensor is operated with sample water. A nearly stable physi-cal value should be displayed. In order to avoid signal variations and consequent reading errors, water must be taken at the sens-ing element and the actual signal must be saved directly in the TOPAX® DX upon taking of the water sample. By means of the DPD method the total chlorine content in the measuring water is determined. The value must be set in the controller and saved by pressing OK. Afterwards the slope is indicated in the measur-ing cell. The accuracy of resistivity measurements is monitored throughout the process.

For the announcement of bound chlorine at the TOPAX® DX it is necessary that the total chlorine and the free chlorine, the pH

value and the temperature of the measuring water with the same TOPAX® DX DX are measured.

5.6�Conductivity�measurements�input

Technical data

Power ValuesSensor conductive or inductive conductivity electrode with

measurement amplifier

Measuring signal 4...�0 mA corresponding measuring range of the measuring amplifier

Measuring accuracy 1 % (after calibration)

Record the increasing trend after brine or sea water baths fol-lowing the quality of the brine. If an electrolytic cell, e.g. from Technopool, is used to generate the free chlorine concentration, brine water must be available as a precondition.

The conductivity of the measuring water can be measured and the concentration be kept constant. The measuring signal is con-verted into a standard 4...�0 mA current signal by a separate measuring amplifier.

CalibrationThe measuring input has to be calibrate (see chapter 16, menu 1.� "calibration"). Setting of the zero point is not necessary. Only the reference value is to be examined and adjusted if necessary. Afterwards the slope is indicated in the measuring cell. The ac-curacy of resistivity measurements is monitored throughout the process.

Computationally the measured value is indicated as %-salt con-tent and in mS/cm. Example: 4...�0 mA corresponding 0...�0 mS/cm.

current�(mA) salt�content�(mS/cm) salt�content�(%)4,00 0 0,00

4,80 1,0 0,05

5,60 �,0 0,10

6,40 3,0 0,15

7,�0 4,0 0,�0

8,00 5,0 0,�5

8,80 6,0 0,30

9,60 7,0 0,35

10,40 8,0 0,40

11,�0 9,0 0,45

1�,00 10,0 0,50

1�,80 11,0 0,55

13,60 1�,0 0,60

14,40 13,0 0,65

15,�0 14,0 0,70

16,00 15,0 0,75

16,80 16,0 0,80

17,60 17,0 0,85

18,40 18,0 0,90

19,�0 19,0 0,95

�0,00 �0,0 1,00

Page 23: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | �3

Chapter�6:�Explanation�of�digital�inputs

6.�Explanation�of�digital�inputs

GeneralIt is possible to interrupt the control process and to activate an alarm by external digital signals. These inputs can be configured in the menu as "normally close" or "normally open" and the level inputs must be additionally deactivated.

6.1�Start-up�lag�timeThe digital signal inputs causes alarm and/or auxiliary functions, which interferes with the normal functions of the automatic con-troller.

If a digital signal input is operated and if the appropriate func-tion is implemented, this has mostly effects on the quality of the measurement and the regulation will be set to "0%". After that the automatic work of the automatic controller is again config-ured; if a start-up lag time occurs, the sensors reset themselves to the automatic measuring procedure.

NOTICE!This start-up lag time is activated: • after filter cleaning • after a "remote switchoff" (measuring water shortage) • after the calibration of a measuring input • when switching on a supply voltage

6.2�Deactivation�of�the�controller�function�with�alarm�signaling�in�the�case�of�lack�of�sample�water

measuring�water�shortageBy an external flow contact the automatic controller functions activates. If the function "shortage of measuring water" is ac-tive and it arises a shortage of measuring water, all automatic controller outputs are set to "0 %", thus switching alarm relays; the announcement "shortage of measuring water” appears in the display.

6.3�Controller�function�deactivation�(filter�cleaning)�without�alarm

This function can be activated by an external contact during filter cleaning. The automatic controller functions are set to "0 %" and the "Filter backwash” appears in the display during this time. When the contact is released, the initial value of the time before the filter cleaning is set for a starting time. After this starting period, the control process is carried out automatically.

This starting lag time is necessary. After a filter cleaning the measured values are not to be used immediately for regulation, since these must reset themselves again to the measuring water. Therefore the regulation is set on the automatic controller power output, as it was prior the filter flushing. The regulation of the measured value begins only after the deceleration time is over.

6.4�Pre-alarm,�alarm�and�warning�"level�dosing�pump"By an external contact e.g. of the level switches of an intake, the connection between the clamps �1 and �� (intake dosing pump

free chlorine) and/or. �5 and �6 (intake dosing pump pH value) can be opened and/or closed. The announcement "free chlorine level early warning" and/or "pH value level early warning" appear in on the display and the alarm relay switches. The chemicals must be refilled.

No chemicals refilled can be opened and/or closed after a further contact of the intake connection between the clamps �3 and �4 (intake dosing pump free chlorine) and/or �7 and �8 (intake dosing pump pH value). The announcement “free chlorine level Alarm" and/or "pH value level Alarm" appears on the display and the alarm relay switches; at the same time the automatic control-ler output line of the respective input is set to 0.

NOTICE!If the level inputs in the menu "Service digital inputs" are activated, the level switches are to be attached to the clamps. If no level switch is attached, the inputs are to be deactivated.

Page 24: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

�4 | Operation Manual TOPAX DX | BA-40100

Chapter�7:�Explanation�of�measuring�values�outputs

7.�Explanation�of�measuring�values�outputs

GeneralWith the configuration of the TOPAX DX an input type was as-signed to each controller.

Possible are:• Servo motor with potentiometer (with feedback)• Servo motor without potentiometer (without feedback)• Pulse frequency (electronic / optocoupler) • Pulse frequency (Relay) • Continuous (current) output 0/4...�0 mA• ON/OFF (Relay)

7.1�Output�typesThe regulating outputs can be calibrate in several aspects (see chapter 16, menu 5.� "outputs"):

ON/OFF�(Relay)Relay output - if the adjusted value are excessive the relay switches, a hysteresis is adjustable.

Pulse�length10..1�0 seconds cycle duration, relay output (e.g. for solenoid valves).

Depending on the control deviation and the defined control pa-rameters, the relay pulls in or drops out for the set cycle dura-tion. If the cycle duration is 30 seconds and the controller output power is 40 % the relay pulls in for 1� seconds and it does not for 18 seconds.

Pulse�frequency10...�00 pulses per minute as a adjustable maximum

The pulse frequency depends on the deviation and the set con-troller parameters, i.e.: at a controller output of e.g. Y=�5% and a pulse frequency of 100 pulses/minute, the controller sends �5 pulses/minute.

Observe the maximum stroke frequency of the connected pump.

Electronic output (optocoupler output)Pulse frequency output for controlling solenoid-driven dos-ing pumps or motor-driven pumps (e.g. MAGDOS or MEMDOS pumps) with intelligent electronic control unit. Ensure the right polarity.

Relay outputPulse frequency output, pulse length output, 3-point-step output (for servo motors) or "ON/OFF" for the control of magnet dosing pumps, hose pumps or single solenoid valves.

3-point-step�output�for�servo�motorsRelay output (e.g. for chlorine control valve C7700).

A acknowledging potentiometer can not be connected with servo motors with position feedback (1-10 kOhm). The acknowledging potentiometer is to be adjusted. For calibration the servomotor is

started first. The voltage, which lines up over the acknowledging potentiometer, is indicated in the position of the potentiometers (voltage display between 0 and 3 V). After the stop position has been reached, the servomotor is stopped automatically. The alignment is accomplished and is to be stored in the TOPAX® DX.

The switching hysteresis can be set from 1-�0%.

A servo actuator without feedback can also be operated. This is to be selected with the configuration.

If no positional feedback is available, measure and adjust the motor life (see chapter 6, menu 5).

NOTICE!Entering a wrong motor life may prevent accurate controller functioning in which case you would re-ceive no warranty coverage by the manufacturer. The motor cycle time is set by the factory at 120 seconds which corresponds to the cycle time of the motor of the chlorine gas valve C7700.

Continuopus�control�output�(20�mA�current�output)For automatic controllers a continuous control output of 0/4...�0 mA can be configured for the control of continuous actuators.

The current varies between 0 and �0 mA depending on the de-viation. max. load: 500 Ohm

It can be selected between:• 0...�0 mA,• 4...�0 mA,• �0...0 mA and• �0...4 mA.

7.2�Output�limit�switchThe output of each automatic controller can be limited in its up-per value. For this reason, you must enter the maximum propor-tional value of the actuators.

Example: a value of 80% operates the automatic controller to a maximum of 80 %. The algorithm of the automatic control is however computed further on 100%. It is to be noted that the automatic controller parameters are selected accordingly.

The smallest adjustable value for the maximum limit is 50 %.

This limit is useful for example if you are running a very large chlorine regulator valve and you want to ensure a sensible regu-lation.

7.3�Actuator�elementsPumps, solenoid valves etc. which are controlled by the TOPAX DX are called control elements.

Depending on the final control element used, different control functions can be set. Possible options are a continuous output with an impressed current (0/4...�0 mA), or control outputs (with pulse frequency). The latter can be controlled as electronic (opto-coupler) or relay outputs.

Page 25: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | �5

Chapter�8:�Controller�explanation

8.�Controller�explanation

DefinitionsTerm Definitionactual value (X) The actual value of X of the measured value for the

respective sensor is constantly indicated.

Setpoint (W) Set point W of a control system defines the value at which the controller has to settle the process and keep it constant.

Control deviation (X-W)

Control deviation X-W occurs if the actual value X of the measurand differs from set point W. Control variable Y results from the control deviation and the control parameters set.

Control vari-able Y

Control variable Y of a control system defines the value which the controller transmits to the final control element depending on the parameters set and control deviation X-W (between 0 % and 100 %).

8.1�Proportional�controller�(P�controller)

Proportional range Xp(proportional effect or amplification of the controller)

The proportional range Xp (p-range) of a proportional controller indicates by which value the measured variable X must deviate from the default value W, so that the correcting variable is Y = 100%. If the control deviation is less, the control variable is re-duced as well in terms of percentage.

Control variable Y of a P-controller is influenced only by the con-trol deviation (X-W)in terms of percentage.

The P-range is indicated in "%" and always refers to the measur-ing range final value.

The proportional range is thus an indirect measure of the control-ler amplification K

R:

KR = 100% / Xp %

With a Xp range of 50 % the controller amplification is :

100 /50 = � -> controller amplification KR = �

Xp = 50 % means that the control variable Y changes around 100 % when the actual value deviates by 50 % from the default value (related to the measuring range final value).

8.2�Proportional-integral-derivative�controller�((PI,�PID�controller)

Reset time Tn(integral effect of PI controller)

The integral time of a PI- or PID-automatic controller is called reset time Tn. The integral time is the time required by the ma-nipulated variable Y in the case of a constant deviation between default and actual values in order to reach the same change of the output signal, which is immediately produced by the p-rate after the jump of the deviation between default and actual values.

�Example�for�proportional�range�and�reset�timeXp = 50 % (amplification = �)

Tn = 3min

(sudden change of the actual value by 15%)

After a sudden deviation of the actual value from the default val-ue by around 15 % (X-to-W), the correcting variable Y changes by the same rate as the controller amplification, that is twice the Xp value or by 30%.

Because of the integral behaviour, the manipulated variable continues to increase as long as the X-to-W deviation remains present and after a time Tn = 3 minutes reaches once again 30 % of correction variable increase.

control�variable Set�valueMeasuring range for free chlorine 1,00 mg/l

X (actual value) 0,15 mg/l

Set point (W) 0,30 mg/l

X - W 15 %

Xp (P-range) 50 %

Tn 3 minutes

Y (Immediate power output of the automatic controller)

30 % by Xp

Y (output power of the automatic controller after 3 minutes)

60 % through Tn

Derivative time Tv

(differential action of PID controller)

By a differential function a correction factor is entered in the controlled system when the controlled variable begins to differ from the default value. The correcting variable depends on the speed by which the default-to-actual deviation takes place (thus not the actual deviation). The duration of the correction factor is determined by the reproaching time Tv. If the controlled variable does not change, thus the rate of change is "0", the correction factor and the time constants Tv caused by the differential rate drop to "0" (even if the actual value keep deviating away from the default one). The fact that the regulation leads the actual value to match with the default one is caused mainly by the integrals por-tion of the automatic controller. The differential rate often helps implementing the controller result because it acts against the trend to deviate.

8.3�Calculation�of�setable�valuesIn order for the controller to process actual values of free chlorine and Ph even in the presence of very slight deviations (almost close to the default values), it must be adjusted to the controlled system. This is done via the control parameters Xp for the pro-portional area, Tn for the reset time of the integral range and the reproaching time Tv for the differential range.

The determination of these settings can take place by means of taking up the step response of the controlled system. In addition the control members must suddenly and manually change from "CLOSE" (0 %) to "OPEN" (100 %) or e.g. from 30 % to 50 %.

Page 26: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

�6 | Operation Manual TOPAX DX | BA-40100

Chapter�8:�Controller�explanation

The following formula can be used for calculation of reference values:

Xp ~ 0,83 · ΔX / Δt · Tu

Tn ~ 3,3 · Tu

Variable DescriptionYh setting range (e.g. valve fully up or 100% of the dosing pump

delivery)

Xmax maximum value of the controller variable at 100 % dosing rate

ΔX / Δt Gradient of the measured curve (see Fig. 8.�)

to Time of change of control variable Y

Tu lag time (s)

Vmax maximum increase rate of the measured variable

Vmax Xmax / Tg = ΔX / Δt

In order to meter chlorine gas, you need accounting for the speed of the chlorine gas valve. The value of Xp is computed for a drive speed from 0 % through 100 % in 60 seconds. A slower opera-tion would show the same trend as a bigger proportional range Xp. In order to adjust this, the Xp value must be first reduced at slower operation and vice versa.

The following formula can be used:

XP new = XP · 60 sec /Ty

Ty = Motor regulation time

As we are dealing here with approximate values, a certain im-provement of the controlled variable can sometimes be obtained by changing the Xp value after certain time. If the regulation should react too slowly or on the contrary too fast, smaller Xp and smaller Tn would result into a faster automatic controller action and in a larger Xp and/or Tn slower-acting settings.

t

Yh(auf) 100%

(zu) 0% t0

Fig. 8.1: State of the control variable, e.g. opening of a valve or dosing rate of a pump.

Here below, a diagram shows for the controlled variable X over the time t (see fig. 8.�):

t

X

X

t0

max

t

X

Tu

Fig. 8.�: Step response of a controller to a Y change of a control variable. (X = actual value, e.g. free chlorine or pH)

The control parameters can be automatically entered in the TOPAX® DX in the respective items (see chapter 16, menu 5).

8.4�Controller�parametersFor free chlorine, pH, bonded chlorine and conductivity inputs the following settings may be programmed:

Con-troller

Xp�value Tn�value pH�value

P 1 - 500 % -

PI 1 - 500 % 1 - �00 min

PD 1 - 500 % 1 - 1�00 s

PID 1 - 500 % 1 - �00 min 1 - 1�00 s

The following control parameters are set by the manufacturer before shipment:

Controller Xp Tn TvAutomatic controller free chlorine 35 % 15 min OFF

Automatic controller pH value 10 % 15 min OFF

Automatic controller bound chlorine(only article 40100004 a. 40100003)

10 % OFF OFF

Automatic controller conductivity(only article 40100004 a. 40100005)

10 % OFF OFF

8.5�Controller�directionThe control direction can be set for each controller. Possible options:• value boost (display arrow "up")• value drop and (display arrow "down")• �-side controller (only free chlorine and pH value)

The connection terminals are also marked with an arrow.

8.6�Base�load�meteringA basic load dosage can be configured outside of the range of control. This dosage takes place even if the PID automatic con-troller output is 0 %. If a basic load is configured, this value is represented in blue on the display screen in the y-display. The y-display of the automatic regulation is represented in green. In the status display, this condition is identified by a "+" after the y-display. It should be noted that this basic load is always effec-tive and independent of the regulation of a certain percentage of the control elements, although the automatic controller does not request any dosage. The basic load is separately adjustable for each output to a maximum of �0 % of the control range.

8.7�Manual�operationAutomatic controllers feature the possibility of a manual opera-tion mode.

If an automatic controller is hand-operated, then a large "M" behind the "Y" will appears in the status display and the y-dis-play on screen will be "blue". In addition the hand-operated is indicated in the lower line.

In the menu of the manual settings the controller output can be adjusted to any value between 0 % and 100 % and saved di-rectly.

NOTICE!Manual operation is not reset automatically.

Page 27: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | �7

Chapter�9�/�10:�Alarms�/�Analogue�power�outputs�0/4...20�mA�for�remote�display

9.�Alarms

9.1�Measuring�values�alarmsFor each measuring input a minimum and a maximum alarm can be set. In the case of a value falling above or below this value, the alarm is shown and an alarm relay as common alarm trig-gers. The alarm settings of the relay and the automatic controller belonging to this measuring input can be differently evaluated. The time delay of the alarm is adjustable (delay)

9.2�Emergency�stop�(Y-alarm)TOPAX® DX is equipped with a safety disconnect. Should the out-put power of the controller reach more than 95 % due to unex-pected events as for example a faulty sensor, a warning alarm is displayed for the controller to reset the controller power output to 0 %. This function is activated by default. The time is adjustable.

Moreover adjusted basic loads are switched off in the event of an emergency stop.

All alarms are displayed in clear text form on the screen. The alarm relay is activated and the measured value, which caused the alarm, is shown in red.

NOTICE!The alarms are represented in red on the display. After clearing, reset the alarms by pressing twice the OK key button.

(see chapter �1 "Troubleshooting/diagnostics" also)

10.�Analogue�power�outputs�0/4...20�mA�for�remote�displayFor the remote indication of the measured values, TOPAX® DX has a similar output for each measured value input 0/4... �0 mA.

The settings 0... �0 mA or 4... �0 mA see chapter 16, menu 5 "recorders". The adjustment of the outputs to external devices is done in menu � (see chapter 16, menu �.3 "Recorder"). Any measurement can be assigned to a minimum value or a maxi-mum value.

In order to check the outputs and for adjust it to the attached instruments and devices, you submit the �0 mA outputs to a test signal (see chapter 16, menu 5.� "outputs").

The signal can take each value between 0 and �0 mA. That is separately possible for the configured controllers and/or recorder outputs.

NOTICE!TOPAX® DX is equipped with a maximum of 8 power outputs. When switched on, the special functions of “total chlorine” and “conductivity” are already as-signed to 6 power outputs of the measured values.

If, additionally, the �0 mA controller outputs are configured, the maximum number of hardware outputs may be exceeded.

In this case the system is designed with internal priorities so that controller outputs and flocking pump outputs always receive priority. This means that no transmission of the measured values (0/4...�0 mA) is any longer available for temperature and con-ductivity.

When too many �0 mA outputs are selected, the disconnection sequence is:1. Temperature measurements�. Conductivity measurements

NOTICE!If the 0/4...20 mA continuous controller output is configured for an automatic controller, this can be manually adjusted to the actuator independently of the settings in the service menu - "recorder". It is possible to configure the 0...20 mA controller output and a 4...20 mA recorder output. It must be noticed that eventual changes in the „Service – Recorder menu“ will be reset after 20 mA outputs.

Page 28: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

�8 | Operation Manual TOPAX DX | BA-40100

Chapter�11/12:�Night�operation�/�Economy�mode

11.�Night�operationTOPAX® DX allows you to reduce use of Chlorine during night-time and/or after the closure of the SPA baths and pools. For this "economy operation mode", two timers can be defined. To automatically start the night-time mode, adjust these timers and assign them to the individual weekdays. These settings are ad-justed in the "service - timer menu ".

The desired value, which you need to reduce, can be adjusted in the main "night-time" menu. Moreover it is possible to reduce the capacity of the recirculation system. Adjust the parameters of the controller, based on the default settings for reduced recirculation power. Afterwards the night operation mode can be started. This can happen automatically when the timer is activated or when the night-time is directly switched on.

A second possibility is the activation of the night-time by an ex-ternal contact. This contact switches the night-time "ON" and "OFF" independently from the settings in the menu.

The night-time command is effective also for flocking.

12.�Economy�mode�-�DIN-contact�and�ECO-con-tactFor the "economy mode" a DIN - contact is defined. The DIN contact is generally used for the reduction of the recirculation capacity.

According to the DIN 19643, SPA baths and pools must follow and adhere to all hygiene auxiliary parameters. The active char-coal and the flocculation central dosage can be subsequently turned off."

parameter AreaFree chlorine: Minimum 0.30 and adjustable maximum between

0.60 and 1.�0 mg/l(adjustable, as the DIN Standards 19643 do not clearly indicate the upper limit value)

pH value: 6.5 – 7.6 pH

Redox: > 700 mV

Bonded chlorine: < 0,�0 mg/l

Parameter for DIN-Contact

For all measuring outputs the hysteresis must be known.

The DIN contact is closed when all the measured values are in the adjusted range.

NOTICE!If no total chlorine was measured and thus no bond-ed chlorine was determined, the contact can be used when bonded chlorine is proven to be within the DIN range by means of photometric analysis.

In the economy mode there are two variants:

12.1.�TOPAX®�DX�is�responsable�for�economy�modeDuring the initial configuration of the in- and outputs, the TOPAX DX asks for the "DIN-contact". For the DIN-contact, one of the options is "ECO-control". If this mode is switched on, the follow-ing functions are activated:

Save the "ECO - control" and enter the following menu to select the type of contact (relay or optocoupler). This contact is called "ECO - contact".

The DIN values are internally compared. If all DIN values are re-spected, the ECO-contact is set as "ECO-default mode" and will be activated every time when the night-time mode or timer is manually switched on.

Use the “night-time” menu (see chapter 16, menu �.4) to re-duce the recirculation capacity the lowered default value of the measurement "free chlorine". If you enter this lowest value as a percentage figure, all controller parameters will be adjusted accordingly to this lower percentage. Reduction rate up to 50% are admissible.

When set on night-time reduced operation mode with TOPAX® DX, the “Night-time operation” contact must be externally set to provide a feedback confirming that the recirculation capacity was actually reduced. The economy mode is effective only when a confirmation is given. Lack of compliance to DIN - parameters at the time of switching to night-time saving mode, will activate ongoing comparative timer check-up and the ECO–contact will be actually active as soon as the DIN-parameters are in place.

12.2.�TOPAX®�DX�controlled�DIN-contact�onlyShould the DIN-contact be switched on from outside, the in-strument will process the contact in the system but in this case TOPAX® will not be responsible for the performance. The „Night-time operation“ menu will have to be reset as well as the recir-culation capacity.

Page 29: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | �9

Chapter�13/14:�Control�of�the�flocking�pump�/�Log�book�function

13.�Control�of�the�flocking�pumpFor the control of the flocculation central pump different pos-sibilities can be selected.

Variant�1:�control�of�the�pump�proportionally�to�the�pure�water�flowInput signal 0/4...�0 mA

adjustment range 0...100 %

(Disturbance factor input)

Variant�2:�Control�of�the�metering�pump�by�direct�input.In the night operation mode the dosing pump can be operated for reduced flocculation capacity. The following operation modes can be selected in the "service" menu for the control of the flock-ing pump:• operation mode: off• Operation mode: "on" with setting of power output in %• Operation mode: "Night operation" with setting of separate

%-wise output capacity for day and night operation.• Operation mode: "flow-dependent" (disturbance variable)

with setting of power output in %• Operation mode: "flow-dependent” (disturbance value) and

night-time reduced service" with setting of power output into separate % for day-time and night-time.

The night operation mode is activated by the timers (setting of the timers in the service menu). The configuration of the output signal for the dosing pump is made in the configuration menu. The following outputs can be configured:• pulse frequency with optocoupler• pulse frequency with relay• pulse length with relay• Constant output 0/4...�0 mA• ON/OFF with relay

NOTICE!The night-time economy mode of the flocking pump does not depend on the DIN parameters!

14.�Log�book�functionThe following activities are stored in the logbook:• Configuration of the initial delivery with date and time• default configuration of date and time• Change of the automatic controller parameters (Xp, Tn,

Tv), basic load, delimitation, being, alarm parameters, and calibration data at start-up with date and time

• Change of the automatic controller parameters (Xp, Tn, Tv), basic load, delimitation, being, alarm parameters, and calibration data with date and time

• Configuration of the digital inputs

These data are stored on the MMC memory card and can be directly selected in the TOPAX® DX or with a PC.

The software version is stored as is and a file (* LOG) as text file and DATE (* DAT) as recorder file per day.

Furthermore, the configuration can be saved.

For the installation of the MMC memory card refer to chapter �1.

For the handling of the logbook, refer to chapter 16, menu 5.6 "Logbook".

Page 30: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

30 | Operation Manual TOPAX DX | BA-40100

Chapter�15:�Auto�setup

15.�Auto�setup�(First�system�self-setting)Menu for the automatic determination of the parameters of the automatic controller of free chlorine

(duration max. 4 hours and 33 minutes)

NOTICE!System self-setting starts when the actual value is stable near the desired value.

The pH value of the water basin must range between 6,8 and 7,3.

The current settings of the automatic controller parameters are shown in the self-setting menu. The process includes 4 main functions. Each function unit must run off in a certain time. If the new value is not reached within this time, an automatic calculation of the automatic controller data cannot be accomplished and the system self-setting process is stopped.

NOTICE!Do not alter the recirculation capacity during system self-setting.

Fig. 15.1: Autosetup process

Start(measuring range 1,00 mg/l)

Wait for 3 minutes(stand-by-time)

Output on 0%

Output on 100%

Confirmed with “OK”

News settings are imported

90 minutes

90 minutes

90 minutes

Stop

Back to the existingold settings

End of process

Wait till free chlorine is 10 %than the default value.Minimum wait: 3 minutesMaximum wait: 90 minutes

Wait till free chlorine reachesthe inital valueMaximum wait: 90 minutes

The system displays all parametersthat have been programmed by theoperator and waits for a confirmation.The controller keeps operating at the existing settings till the new ones are confirmed!

Wait till free chlorine reachesby another 10%Maximum wait: 90 minutes

Page 31: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 31

Chapter�16:�Menu�configuration�and�main�settings

16�Menu�configuration�and�main�settings

16.1�Menu�of�TOPAX®�DXIn this chapter all of the TOPAX® DX menus are presented and their operation exemplified. The Menus are as a result shown on the display with its coloured presentation and high resolution in clear text and clearly arranged.

Standard�displayIf there are no entries in the TOPAX DX within 5 minutes, the device turns to the standard display (see diagram 16.1).

mg/l

mV

ºC

comb. cl.

temp.

REDOX

free chlorine pH value7.040.39

719 mg/l0.0926.3

eff. cl. 0.30 mg/l

Topax DX

14:28 06.02.2007

Fig. 16.1: Standard display of TOPAX® DX - with total chlorine measurement

The bars below the digits of the measured values indicate the strength of the respective output signal. The colour of the display changes, depends on the signal power, from green (0-85 %) to orange (85 – 95 %) and rot (95 – 100 %).

By pressing a random key you go to the main menu (menu 1).

IMPORTANT!All menus of TOPAX® DX are shown a ID-number marked in the bottom line on the left display corner.(see menu 1). The sub-chapters are named according to this numbering for better understanding.

Menu�1�and�2:�Main�menu�and�sub-main�menu

mg/l mVpH mg/l

menu 2

trend

calibration

setpoint

ESC

status

039 702 719 090main-menu

1

Menu 1: The TOPAX® DX main menu and output point to reach all further sub-menus and their functions: With the displays for ① free chlorine, ② pH value and ③ Redox. Depending on the configuration, ④ indicates bonded chlorine (mg/l), temperature (SDgrC) or conductivity (%).

Menu � serves as a sub-main menu (see menu �)

mg/l mVpH

alarms

controller

ESC

039 702 719 090

menu 2recorder

night mode

service

mg/l

2

Menu �: Extension of the main menu

Through the main menu (menu1) and the sub-main menu (menu �) you can access all other sub-menus (see fig.16.�).

Menu Key Remakrs�for�sub-menu1 Main�menu

ESC Return to the standard display

1.1 Nominal values

Set the default values of the configured controller

1.� Calibrate Calibrate all sensors connected to the system

1.3 Trend Show measurements as line diagram and zoom at wish

1.4.1 Status Display of all important settings

� Menu � Change to the following menus

2 Menu�2ESC Return to the main menu

�.1 Controller Optimization of the parameters of all configured controllers (access to this menu can be protected by a password).

�.� Alarms Assigning the alarms to the related measurement signals

�.3 Recorder Optimization of the analogue output loop (0/4...�0 mA)

�.4 Night opera-tion

Selection auto switch ability and adjustment of the new default value.

5 Service Further adjustment options(access to this menu can be protected by a password):

• Configuration• Inputs• Autosetup• Network• Clock• Password• DIN - contact• Alarm settings• Recorder• Display

• Hardware status (HW-Status)

• Outputs• Reset• Log file• Timer• Service code• Flocking• Start• Digital inputs• Language

Fig. 16.�: Overview of the sub-menus of TOPAX DX

On the following pages all sub-menus are presented in ascending order and exemplified by means of a demonstrative example.

① ② ③ ④

Page 32: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

3� | Operation Manual TOPAX DX | BA-40100

Chapter�16:�Menu�configuration�and�main�settings

Menu�1.1:�Nominal�values

controller

mg/l mVpH039 702 719 090

pH value

free chlorine

ESC

comb. cl

% Salt

setpoint

mg/l

1.1

Main menu >> default values

With the menu “default value” each control unit assigns the de-sired default value to each output. According to the configuration the target values can be fixed for the following control units:

Menu Controller Key1.1.1 Automatic controller free chlorine Free chlorine

1.1.� Automatic controller pH value pH value

1.1.3 Automatic controller bound chlorine bonded chlorine

1.1.4 Automatic controller conductivity % salt

Select a control unit to set up the set value. The device switches to the relative menu 1.1.1 … 4.

The first digit of the set value is highlighted in grey and can be adjusted. Use the arrow keys to set up the value:

◀ / ▶ switch over between the individual positions

▲ / ▼ alter numerical values

„OK“ to save

Menu�1.2:�Calibrate

mg/l mVpH039 702 719 090

ESC

free chlorine

pH value

REDOX

temp.

next

calibration

input

mg/l

1.2

Main menu >> calibration

mg/l mVpH039 702 719 090

ESC

total chlorine

conductivity

input

calibration

mg/l

1.2

Main menu >> calibration >> next: Page � of callibration (with more than five inputs)

With the Menu “Calibration” the sensors are calibrated with the inputs. According to the setting the following inputs can be se-lected:

Menu Input Key1.�.1 Free chlorine Free chlorine

1.�.� pH value pH value

1.�.3.3 Redox Redox

1.�.4.3 Temperature Temperature

1.�.7.3 Total chlorine measuring electrode Total chlorine

1.�.8.3 conductivity measuring system Conductivity

Select one of the inputs for calibration. The device switches to the relevant menu 1.�.1 ... 1.�.8.3.

The type of calibration (1-point calibration or �-point calibration) depends on the attached sensor (see also chapter 5), which was defined in the start-up configuration.

Input 1-point�calibration

2-point�calibration

Free chlorine

Amperometric electrode *) Menu 1.�.1

potentialstatic electrode Menu 1.�.1.3

Encapsulated electrode *) Menu 1.�.1

pH value

pH single-rod measuring cell - without specifications about slope rate

Menu 1.�.�

pH single-rod measuring cell- with specifications about slope rate

Menu 1.�.�

Redox Menu 1.�.3.3

Temperature Menu 1.�.4.3

Total chlorine measuring electrode Menu 1.�.7.3

conductivity measuring system Menu 1.�.8.3

*) For start-up the sensors require a �-point calibration. For inspection/post-calibration a 1-point calibration is sufficient. Therefore, menu 1.�.1 offers both types of calibration.

Please note the messages on the display. After the calibration has been selected the TOPAX DX requests one and/or two refer-ence values. At this stage keep the sensor in the relevant meas-uring water or buffer solution (see chapter 5).

Page 33: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 33

Chapter�16:�Menu�configuration�and�main�settings

Enter the requested reference value for the water / solution: The first digit of the set value is highlighted in grey and can be ad-justed.

Use the arrow keys to set up the value:

◀ / ▶ switch over between the individual positions

▲ / ▼ alter numerical values

Confirm and save with the “OK” key.

Confirm the measuring water extraction with the “OK” key.

After the calibrating off free chlorine and pH-value the sensor’s slope rate is shown.

Special feature for the calibration of the pH valueThe actual voltage of the electrode AND the design voltage of the pH buffer solution are indicated on the display during calibration of the pH value. These two values allow the operator to monitor the accuracy of the measuring electrode.

The deviation between the measurement of the pH value with the photometer and the electrometric measurement can be compensated with the "offset compensation" option (see menu 1.�.�.6).

mg/l mVpH039 702 719 090

ESC pH valueenter offset

new value pH 7,07

acknowledge with (OK)

0,05 pH

input 2

mg/l

1.2.2.6

Hilfe

Main menu >> calibration >> pH value >> offset

Menu�1.3:�Trend�representations

mg/l mVpH

Zoom-

Zoom+

ESC

039 702 719 090mg/l

1.3

display24 h.

Main menu >> trend

The actual trend of the measurements is represented by coloured curves that can be constructed at different time intervals but over a range varying from 4 – �4 hours. To change the desired time

to a respectively bigger or smaller interval use the „Zoom +“ and „Zoom -“.

Menu�1.4�Status�display

mg/l mVpH

next

preset

ESC

039 702 719 090status controller

mg/l

1.4.1

W1: 0,45 mg/lXp1: 50 %W2: 7,10 pHXp2: 20 %l

Y1: 25 %Tn1: 25 min.

Y2: 20 %Tn2: 25 min.

Main menu >> status

Several values are shown in the status display, these are essen-tial for the function of the TOPAX DX:

Menu Status�displays1.4.1 Main parameters of all configured controllers

1.4.� Switching status of all outputs

1.4.3 Physical values and calibrated resistivity values of all inputs

1.4.4 • used software version• serial number• hardware identification data• input identification• outputs identification• number of operating hours

By pressing the “next” key, the TOPAX DX switches to menu 1.4.1 bis 1.4.4.

Save and activate presettingsIt is also possible for certain applications to save the adjusted values and activate them when needed. For this presettings sev-eral names can be allocated:

2 Set 2

mg/l mVpH ∞C

ESC

039 702 719 632

1 Set 1define

3 Set 3aktivate

preselects

4 (Autosetup)

1.4.8

Main menu >> status >> presettings

Press the “pre-adjust” key and the device switches to menu 1.4.8. Select from one of the four presettings that you want to

Page 34: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

34 | Operation Manual TOPAX DX | BA-40100

Chapter�16:�Menu�configuration�and�main�settings

activate or overwrite with the actual values. To select press the arrow keys ▲ and ▼.

To activate an existing presetting press the “activate” key. Con-firm the entry with the “OK” key.

To save the actual entries press the “apply” key. The device goes to menu 1.4.8.1:

mg/l mVpH ∞C

ESC

039 702 719 632

ab<=> 01

Set_2

preselects

1.4.8.1

edit name and save

ab<=> AB save

Main menu >> status >> presettings >> apply

Enter the name of the pre-adjustment using the arrow keys ▲ and ▼ . For this it is necessary to:

Keys Function▲ and ▼: Change individual letters and numbers

◀ and ▶: shift cursor

ab <=> 01 change small letters to numbers/symbols

ab <=> AB change small into capital letters

Press the “save” key to save up to this point the adjusted regulat-ing characteristics. Confirm the procedure with the “OK” key.

The following adjustments are saved and can be re-activated at any time:• regulating characteristics of configured controller• set values of configured controller

Menu�2.1:�adjust�controller

mg/l mVpH

pH value

free chlorine

ESC

039 702 719 090setup

comb. cl.

% salt

controller

2.1

mg/l

Main menu >> menu � >> controller

The TOPAX DX is able to command up to four control units (see chapter 8). The basic adjustments of every single control unit are configured in this menu:

Menu Controller�setting Required�specifications2.1.1 Free�chlorine�.1.1.1 Controller direction boosting/dropping/� sites

�.1.1.� Disturbance variable Disturbance variable, ON/OFF

�.1.1.3 overview of settings

�.1.1.3.1 Parameter Xp % value

�.1.1.3.� Parameter Tn ON or OFF + time

�.1.1.3.3 Parameter Tv ON or OFF + time

�.1.1.4 basic load ON or OFF + time

�.1.1.5 Manual operation %-value, ON/OFF, impact chlorination

2.1.2 pH�value�.1.�.1 Controller direction boosting/dropping/� sites

�.1.�.� Disturbance variable Disturbance variable, ON/OFF

�.1.�.3 overview of settings

�.1.�.3.1 Parameter Xp % value

�.1.�.3.� Parameter Tn ON or OFF + time

�.1.�.3.3 Parameter Tv ON or OFF + time

�.1.�.4 basic load ON or OFF + time

�.1.�.5 Manual operation %-value, ON/OFF

2.1.3 bonded�chlorine�.1.3.1 Controller direction boosting/dropping/� sites

�.1.3.� Disturbance variable Disturbance variable, ON/OFF

�.1.3.3 overview of settings

�.1.3.3.1 Parameter Xp % value

�.1.3.3.� Parameter Tn ON or OFF + time

�.1.3.3.3 Parameter Tv ON or OFF + time

�.1.3.4 basic load ON or OFF + time

�.1.3.5 Manual operation %-value, ON/OFF

2.1.4 controller�for�salt�content�.1.4.1 Controller direction boosting/dropping/� sites

�.1.4.� Disturbance variable Disturbance variable, ON/OFF

�.1.4.3 parameter

�.1.4.3.1 Parameter Xp % value

�.1.4.3.� Parameter Tn ON or OFF + time

�.1.4.3.3 Parameter Tv ON or OFF + time

�.1.4.4 basic load ON or OFF + time

�.1.4.5 Manual operation %-value, ON/OFF

Select one of the four control units. The device switches to the relative menu �.1.1 … �.1.4.Apply the adjustments relevant to your requirements in the fol-lowing sub-menus to the control unit.Adjust the parameters accordingly with the arrow keys ▲ and ▼ and confirm your entries with the “OK” key.

Adjustment�of�impact�chlorination�For impact chlorination, the controller "Free Chlorine" is switched to manual operation for an adjustable time and an adjustable dosing rate. When the time has elapsed, the controller automati-cally switches to automatic operation.

Page 35: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 35

Chapter�16:�Menu�configuration�and�main�settings

NOTICE!The operator must empirically define the time and the dosing rate for impact chlorination before this function is performed.

mg/l mVpH ∞C039 702 719 632

ESC

Handbetrieb

100 %

EIN

AUS

Regler 1freies Chlor

2.1.1.5(OK) zum Speichern

6 min

Timer 200 s

Zeit

%

Stoßchlor

Main menu >> menu � >> controller >> free chlorine >> manual operations

The key "Impact Chlorine" is at the same time used for the con-figuration and the starting of impact chlorination. Set the time with the "Time" key. Set the maximum output capacity with the "%" key.

Press the "OK" key to save the settings. The impact chlorina-tion is indicated on the status display. The timer counts down and indicates the remaining time in minutes. When the time has elapsed, the system switches to automatic operation.

Menu�2.2:�Alarms

mg/l mVpH039 702 719 090

ESC

free chlorine

pH value

REDOX

temperature

next

setup

mg/l

alarms

2.2

Main menu >> menu � >> alarms

mg/l mVpH039 702 719 090

ESC

comb. cl.

% salt

alarms

setup

2.2

Main menu >> menu � >> alarms >> next >> page � of alarms (with more than five inputs)

The TOPAX DX monitors its inputs (see chapter 9). If an unwanted alteration appears on an input value, the alarm is set off. The alarm-setting is configured in this menu:

Menu Function Required�specifications2.2.1 Free�chlorine�.�.1.1 Maximum alarm ON or OFF + limit value

�.�.1.� Minimum Alarm ON or OFF + limit value

�.�.1.3 Y-Alarm ON or OFF + time

�.�.1.4 Alarm delay ON or OFF + time

2.2.2 pH�value�.�.�.1 Maximum alarm ON or OFF + limit value

�.�.�.� Minimum Alarm ON or OFF + limit value

�.�.�.3 Y-Alarm ON or OFF + time

�.�.�.4 Alarm delay ON or OFF + time

2.2.3 Redox�potential��.�.3.1 Maximum alarm ON or OFF + limit value

�.�.3.� Minimum Alarm ON or OFF + limit value

�.�.3.4 Alarm delay ON or OFF + time

2.2.4 Temperature�.�.4.1 Maximum alarm ON or OFF + limit value

�.�.4.� Minimum Alarm ON or OFF + limit value

�.�.4.4 Alarm delay ON or OFF + time

2.2.5 bonded�chlorine�.�.5.1 Maximum alarm ON or OFF + limit value

�.�.5.� Minimum Alarm ON or OFF + limit value

�.�.5.3 Y-Alarm ON or OFF + time

�.�.5.4 Alarm delay ON or OFF + time

2.2.6 salt�content�.�.6.1 Maximum alarm ON or OFF + limit value

�.�.6.� Minimum Alarm ON or OFF + limit value

�.�.6.3 Y-Alarm ON or OFF + time

�.�.6.4 Alarm delay ON or OFF + time

Select one of the six inputs. The device goes to the current menu �.�.� … �.�.5 and shows the actual configuration of the input alarm.

Select one of the (up to) four available alarm functions of the input for configuration.

alarm Alarm�is�set�off,�if�… KeyMaximum measuring value

Input value > max. value max alarm

Minimum measuring value

Input value < min. value min alarm

Y-Alarm after a given time for the input of the relevant control unit in the compu-ter’s output service is > 95%.

Y-Alarm

Alarm delay the alarm’s delay time has run out Delay

Possible alarm functions of the six inputs.

Press on “OFF” to turn off the chosen alarm function. Confirm twice with the “OK” key.

Page 36: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

36 | Operation Manual TOPAX DX | BA-40100

Chapter�16:�Menu�configuration�and�main�settings

Press on “ON” to turn the chosen alarm function on.

Enter the requested limit value.

The first digit of the limit value is highlighted in grey and can be adjusted. Use the arrow keys to set up the value:

◀ / ▶ switch over between the individual positions

▲ / ▼ alter numerical values

Confirm the entry twice with the "OK" key.

Menu�2.3:�Recorder�(analog�outputs�0/4...20�mA)

mg/l mVpH039 702 719 090

ESC

free chlorine

pH value

REDOX

temperature

next

inputs

mg/l

recorder

2.3

Main menu >> menu � >> recorder

mg/l mVpH039 702 719 090

ESC

comb. cl.

% salt

recorder

input

2.3

Main menu >> menu � >> recorder>> next >> page � of recorder (with more than five inputs)

For remote display of measured values, TOPAX DX has a analog output 0/4... �0 mA, named "recorder output", for each meas-ured value input.

This menu is used for the adjustment of the TOPAX DX to the ex-ternal devices which are connected to the outputs. An allocation / standardization takes place between each measurements input and analogue output:

Minimum measurement input = 0/4 mA

Maximum measurement input = �0 mA

There are recorder outputs for the inputs:

Menu Inputs Key Required�input Unit�.3.1 Free chlorine Free chlorine Minimum, Maximum mg/l

�.3.� pH value pH value Minimum, Maximum pH

�.3.3 Redox potential Redox Minimum, Maximum mV

�.3.4 Temperature Temperature Minimum, Maximum ºC

�.3.5 bonded chlorine bonded chlorine Minimum, Maximum mg/l

�.3.6 salt content % salt Minimum, Maximum %

Select an input for the standardization of the analogue output. Select "Minimum" or "Maximum" to define the lower limit or re-spectively the upper limit of the measuring value.

Enter the requested limit value.

The first digit of the limit value is highlighted in grey and can be adjusted. Use the arrow keys to set up the value:

◀ / ▶ switch over between the individual positions

▲ / ▼ alter numerical values

Confirm the entry twice with the "OK" key.

Menu�2.4:�Night�operation

mg/l mVpH039 702 719 090

ESC timer

off

night modeon

setpoint

setup

AUS

2.4

mg/l

circulation

Main menu >> menu � >> night operation

For night operation:• it can be switched on and off manually or controlled by

means of a timer.• the default value for the "free chlorine" controller has to be

set.• the percentage value can be set for reduction of recircula-

tion power.• the setting of the timer is done in menu 5.8 "Timer".

Page 37: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 37

Chapter�16:�Menu�configuration�and�main�settings

Menu�5:�Service

flocculation

configurationinputsautosetup

clock

DIN-contact

network

code

HW - Status

restart

timerservice code

logfile

outputs

mg/l mVpH mg/l039 702 719 090

ESC

recorderalarm action startup

digital inputslanguagedisplay

5

Main menu >> menu � >> service

The Menu 5 “Service” covers �0 functions for the basic setting of the TOPAX DX:

Menu Key Function

0.4.4 Configuration Return to the basic configurationSaving and loading of a configuration

5.01 hardware status Hard-/software equipment

5.1 Inputs adjusting the input measuring ranges

5.� Outputs Outputs settings

5.3 Autosetup Automatic determination of the parameters of the "free chlorine" controller

5.4 Reset reset and factory settings

5.5 Network Configuration of RS 485 network address

5.6 Log file write/read the logbook

5.7 Clock Setting of date and time

5.8 Timer Setting of control timer

5.9 Password Setting of an access code for the individual menus

5.10 Service code Setting a code for menu 5 „service“

5.11 DIN - contact Setting ECO mode

5.1� Flocking Setting of flocking

5.13 Alarm settings Configuration of alarm settings

5.14 Start Setting of start-up lag time

5.15 Recorder Choise 0...�0 mA/4...�0 mA or test signal

5.16 Digital inputs Settings of digital inputs

5.17 Display Display settings

5.18 Language Changing language and units

On the following pages the individual pages are described.

To select the menus press the arrow keys ▶, ◀, ▲ and ▼. Confirm the selection with the “OK” key.

Menu�0.4.0:�Configuration�Configurations of the TOPAX DX can be modified, saved and loaded at any time. Existing configuration files are saved on the MMC card or loaded from it.

Main menu >> menu � >> service >> configuration ...

... >> change Menu 0.4 (see chapter 4.8)

... ... >> load menu 0.4.�0, select an existing configura-tion with the ▲ and ▼ keys and confirm with "OK".

... >> save menu 0.4.�1, save the present configura-tion on the MMC card. The file named can be chosen freely.

In this way, the configuration of the TOPAX DX can for instance be done for several swimming pools circuits once and then be transferred to the other, identical TOPAX DX controllers via the MMC card. All settings are transferred.

Furthermore, the configuration files can be saved on a PC and transferred to an identical TOPAX DX if required.

Menu�0.4.1:�Configuration

next

CS120 cell (direct)

potentiostat

membrane covered cell

REDOX-Sensor

0.4.1

input free chlorine

Main menu >> menu � >> service >> configuration

TOPAX® DX can be reprogrammed at wish by the customer ac-cording to own configuration requirements.

The configuration of inputs and outputs can be done modified if necessary. Before it is saved, the newly set configuration is indi-cated in red and must be saved. Use the „ESC“ button to exit the menu without saving and return to the default settings.

When new settings are performed and a new configuration is saved, make sure to check all terminal clips. The new wiring diagram is displayed. The system will in fact display the new connection diagram and all terminal clips having been changed will be marked out in red. The new connection diagram must be confirmed.

Inadmissible settings and configurations that are not compatible with the system, will be locked out and a clear text failure mes-sage will be displayed on screen.

For easier proofing of your configuration, check the terminal clips and their assignment to the outputs in the menu 5.01 “Hardware status”.

All TOPAX® DX versions are supplied with a measuring protocol and a terminal connection diagram referred to the actual con-figuration.

(See configuration example in 16.�).

Menu�5.0.1:�hardware�statusMain menu >> menu � >> service >> HW status

The menu of the TOPAX DX indicates:• Software version• Running time• integrated components• Terminal connection• hardware status

Page 38: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

38 | Operation Manual TOPAX DX | BA-40100

Chapter�16:�Menu�configuration�and�main�settings

Menu�5.1:�InputsMain menu >> menu � >> service >> inputs

Input FunctionsFree chlorine Defining the measuring ranges for the configured sen-

sor and switching on the measured value compensation for the pH value and chlorine (Compensation of the chlorine value is only possible for the measurement with a potentiostatic measuring cell)

Total chlorine Settings of measuring ranges

bonded chlorine Settings of measuring ranges

Menu�5.2:�OutputsMain menu >> menu � >> service >> outputs

The menu permits:• Adjusting the parameters for the current configured type of

output (see chapter 7 “control unit outputs”).• Adjusting the maximum limits for the outputs.

Menu�5.3:�Auto�setup�(First�system�self-setting)Main menu >> menu � >> service >> autosetup

This menu allows you to perform automatic determination of the settings of the free-chlorine controller (see chapter 15). The time for performing eventual adjustments depends on the actual con-ditions of the control system (max time is approx 4 hours).

Menu�5.4:�ResetMain menu >> menu � >> service >> reset

The menu permits• Reset: Restart the instrument using the same configuration• default settings: Restart the instrument using the original

default settings (see chapter 19)• switch off: defined switching off of the controller before a

disconnection from power supply.

Menu�5.5:�NetworkMain menu >> menu � >> service >> network

The menu permits the setting of the RS 485 network address to connect the TOPAX DX with any PC and TOPAX device in an network (see Chapter 4.4, 8 and 17).

Menu�5.6:�Log�fileMain menu >> menu � >> service >> log file

The data logger contains the full list of all settings done on your TOPAX® DX and can be viewed as clear text on your TOPAX® DX screen or on your PC but in this case you must replace the exist-ing MMC memory card (sieh chapter �1).

Menu�5.7:�ClockMain menu >> menu � >> service >> clock

Any time when you replace the batteries of your instrument you need to access in this menu in order to reset the instrument clock.

The time is automatically changed from summer time to winter time and vice versa. This menu also offers the possibility to de-activate this automatic change-over.

Menu�5.8:�TimerMain menu >> menu � >> service >> timer

In this menu you can adjust the timer of your instrument so that night-time functions are automatically switched on and you al-locate to individual week days.

Menu�5.9�and�5.10:�code�und�Service�codeMain menu >> menu � >> service >> code and service code

In these menus you can block the various levels by using a 4-digits numeric password. Information menus will remain free.

Only 5 minutes after the entry, the password is activated

Menu Function5.9 code After entering the code, menus „calibrate“ and „set

values“ and "menu �" are only accessible via this code.

5.10 Service code

Enter this code to protect the menu „service" and make accessible only to password users.

If no code is set all program levels are accessible.

NOTICE!If you enter a protection code, the related menu will be only accessible after entering the password. Enter the protection code and press „OK“ to confirm.

Menu�5.11:�DIN�contact�/�ECO�contactMain menu >> menu � >> service >> DIN contact

This menu allows you to adjust the values and the lag time of switching contact for energy-saving operation.

Menu�5.12:�FlockingMain menu >> menu � >> service >> flocking

Set the parameters required to operate and start the flocking pump. It is possible to select among the following operation modes:

Operation�mode DescriptionOFF -

On with output capacity in %

Night-time economy mode with setting of separate %-wise output capac-ity for day and night time operation.

flow-dependent (distur-bance variable)

with output capacity in %

flow-dependent (distur-bance variable) and night-time economy mode

with setting of separate %-wise output capac-ity for day and night time operation.

Night-time operation is activated either by the timer or "exter-nally" by the user.

Page 39: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 39

Chapter�16:�Menu�configuration�and�main�settings

Menu�5.13:�Alarm�settingsMain menu >> menu � >> service >> alarm settings

Use this menu to set the behaviour of the controller and the func-tioning of the alarm relay in case of any alarm to be switched on.• Controller ON: the controller remains on if an alarm goes on• Controller OFF: the controller goes off when an alarm goes

on and the control valve is overdriven• Relay ON: the relay is activated when the alarm goes on• Relay OFF: the relay is activated when energized by the

operating current and is deactivated if an alarm goes on.

Menu�5.14:�StartMain menu >> menu � >> service >> startup

In this menu you can adjust the start-up lag time of controller functions. The new time is effective after you have successfully:• calibrated the individual sensors• measuring water shortage• Filter cleaning• after switching the power on

Menu�5.15:�Recorder�outputsMain menu >> menu � >> service >> recorder

In this menu you can change the analogue 0...�0 mA or 4...�0 mA outputs (recorder outputs) used for transferring the measur-ing values or a test signal for testing trial purposes.

Menu�5.16:�Digital�inputsMain menu >> menu � >> service >> digital inputs

Menu for the switching on and activation of the digital inpuuts. They can be defined as "normally ON" or "normally OFF". If they are not assigned, the digital inputs used for the fill-level gauge of the metering container (that is to switch off the free-chlorine or the ph controller) can be also set on “not active”.

Menu�5.17:�DisplayMain menu >> menu � >> service >> display

The menu permits:• Assign a name to the device on the display• Switching on / off additional information on the standard

display• Set the brightness of the display.

Menu�5.18:�LanguageMain menu >> menu � >> service >> language

Menus for setting of menu languages. You can activate additional languages from the MMC memory card (see chapter 4.8).

16.2�configuration�example�and�terminal�connection

Example�1:

Controller�output Control�ele-ment�

Setting Terminal�con-nection�clips

Automatic controller free chlorine

C7700 Servomotor with potentiometer (relay contact)

87/88 (OPEN)89/90 (CLOSED)

Automatic controller pH value

MAGDOS Pulse frequency (Optocoupler)

81/8�

Automatic controller bound chlorine

Solenoid valve

(Relay contacts)ON/OFF

91/9�

Automatic controller conductivity

OFF

DIN - contact Relay contact 93/94

Flocking MAGDOS Pulse frequency optocoupler

83/84

Still free connections:

terminal Output85 + Electronic output

(optocouplers)86 -

93 Relay output

94

95 Relay output

96

Example�2:

Controller�output Control�element

Setting Terminal�con-nection�clips

Automatic controller free chlorine

MAGDOS Pulse frequency (Optocoupler)

81/8�

Automatic controller pH value

MAGDOS Pulse frequency (Optocoupler)

83/84

Controller bonded chlorine

OFF

Automatic controller conductivity

Relay contact Solenoid valve 87/88

DIN - contact Relay contact 89/90

Flocking Relay contact 91/9�

Still free connections

terminal Output85 + Electronic output

(optocouplers)86 -

93 Relay output

94

95 Relay output

96

All other terminal connections are assigned to the outputs as per actual configuration and are displayed by TOPAX® DX.

Page 40: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

40 | Operation Manual TOPAX DX | BA-40100

Chapter�17:�Wiring�diagrams

17.�Wiring�diagrams

17.1�Examples�overviewExample 1 2 3 4 5 6 7 8TOPAX�DX�Order�no.40100001 X X4010000� X X X X40100003 X X X X X40100004 X X X X40100005 X X X X X X40100006 *) X X X40100007 *) X X X X X X40100008 *) X X X X X X X40100009 *) X X X X X X40100010 *) X X X X X X X XTechnical�components78403Input board 5-fold

X X X X X X X

78404Input board 3-fold

X X X X X

78399Output board

X X X X X X

78406PC interface

X X

Inputs/measuring�electrodes/sensorsFree chlorine Amperometric

electrode potentialstatic electrode

potentialstatic electrode

potentialstatic electrode

potentialstatic electrode

encapsulated electrode with integrated electronic amplifier

potentialstatic electrode

Total chlorine encapsulated electrode with integrated electronic amplifier

encapsulated electrode with integrated electronic amplifier

pH value single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

Redox single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

single-rod measuring cell

Conductivity conductive or inductive with separate elec-trode amplifier

Outputs/controllers/actuating�elementsFree chlorine C7700

(Servo motor w. potentiometer )

Continuous controller output0/4 - �0 mA

C7700(Servo motor w. potentiometer )

C7700(Servo motor w. potentiometer )

C7700(Servo motor w. potentiometer )

C7700(Servo motor w. potentiometer )

pH value Solenoid-driven dosing pumps(Pulse frequency optocoupler)

Solenoid-driven dosing pumps(Pulse frequency optocoupler)

Solenoid-driven dosing pumps(Pulse frequency optocoupler)

Solenoid-driven dosing pumps(Pulse frequency optocoupler)

Solenoid-driven dosing pumps(Pulse frequency optocoupler)

Solenoid-driven dosing pumps(Pulse frequency optocoupler)

OtherPC interface RS 485

NetworkRS 485Network

*) 40100006 to 40100010 correspond 40100001 to 40100005, add with option „RS 485 interface“

Page 41: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 41

Chapter�17:�Wiring�diagrams

Example�1:

Sensors connectionFree chlorine: Open amperimetric measuring electrode CS1�0

pH value: single-rod measuring cell

Redox: single-rod measuring cell

Terminal plan

output block

DO4 DO3 DO2 DO1

78399

DO7DO6

DO5

DO0

free chlorine

pH value

Redox

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

20 mA pow

er outputsdigital inputs

363738 PE N L

3334

92 93 9487 88 89 90 91

86

-+

8182838485

--

++

5657585960

-+

51A52A

535455

61

--

++

CPRT(ATE) 5.fach

alarm relays

39 40 41 43 44 45 4642

35

95 96

mainboard

78403

78402

power generator

5-fold input block

90 to 264 V AC

Page 42: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

4� | Operation Manual TOPAX DX | BA-40100

Chapter�17:�Wiring�diagrams

Example�2:

Sensors connectionFree chlorine: potentialstatic electrode

pH value: single-rod measuring cell

Redox: single-rod measuring cell

Controller connectionFree chlorine: C7700 (servo motor with potentiometer)

pH value: Solenoid-driven dosing pumps

(Pulse frequency - optocoupler)

Terminal plan

free cholrine(potentiostatic electrode)

pH-value

Redox

DO4 DO3 DO2 DO1

DO7

DO6

DO5

DO0

reference electrodecounter electrode (stainless steel)measuring electrode (Gold)

C7700

23

111

1012

OPEN

CLOSED

pH-valuedosing pump

temperature

water-shortage

90 to 264 V AC

78399

CPRT(ATE) 5.fach

78404

3-foldinput block

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

363738 P

E N L

3334

92 93 9487 88 89 90 91

86

-+

8182838485

--

++

5657585960

-+

51A52A

535455

61

51B52B

--

++

-+

7172737475

76 77 78

C(P) 20mA(ATE)

39 40 41 43 44 45 4642

35

95 96

78403

78402

output block

20 mA pow

er outputsdigital inputs

alarm relays

mainboard

power generator

5-fold input block

Page 43: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 43

Chapter�17:�Wiring�diagrams

Example�3:

Sensors connectionFree chlorine: potentialstatic electrode

pH value: single-rod measuring cell

Redox: single-rod measuring cell

Controller connectionFree chlorine: Continuous regulating output 0/4...�0 mA

pH value: Solenoid-driven dosing pumps

(Pulse frequency - optocoupler)

Terminal plan

DO4 DO3 DO2 DO1

DO7

DO6

DO5

DO0

20 mA controller outputfree chlorine

90 to264 V AC

+-

78399

CPRT(ATE) 5.fach

78404

C(P) 20mA(ATE)

78403

free cholrine(potentiostatic electrode)

pH-value

Redox

reference electrodecounter electrode (stainless steel)measuring electrode (Gold)

pH-valuedosing pump

temperature

water-shortage

3-foldinput block

78402

output block

20 mA pow

er outputsdigital inputs

alarm relays

mainboard

power generator

5-fold input block

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

363738 P

E N L

3334

92 93 9487 88 89 90 91

86

-+

8182838485

--

++

5657585960

-+

51A52A

535455

61

51B52B

--

++

-+

7172737475

76 77 78

39 40 41 43 44 45 4642

35

95 96

Page 44: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

44 | Operation Manual TOPAX DX | BA-40100

Chapter�17:�Wiring�diagrams

Example�4:

Sensors connectionFree chlorine: potentialstatic electrode

pH value: single-rod measuring cell

Redox: single-rod measuring cell

Controller connectionFree chlorine: C7700 (servo motor with potentiometer)

pH value: Solenoid-driven dosing pumps

(Pulse frequency - optocoupler)

OtherConnection of PC interface RS 485

Terminal plan

DO4 DO3 DO2 DO1

DO7

DO6

DO5

DO0

C7700

23

111

1012

OPEN

CLOSED

90 to 264 V AC

RS 485

78399

CPRT(ATE) 5.fach

78404

C(P) 20mA(ATE)

78403

free cholrine(potentiostatic electrode)

pH-value

Redox

reference electrodecounter electrode (stainless steel)measuring electrode (Gold)

pH-valuedosing pump

temperature

water-shortage

3-foldinput block

78402

output block

20 mA pow

er outputsdigital inputs

alarm relays

mainboard

power generator

5-fold input block

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

363738 P

E N L

3334

92 93 9487 88 89 90 91

86

-+

8182838485

--

++

5657585960

-+

51A52A

535455

61

51B52B

--

++

-+

7172737475

76 77 78

39 40 41 43 44 45 4642

35

95 96

AB

AB

interface card78406

Page 45: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 45

Chapter�17:�Wiring�diagrams

Example�5:

Sensors connectionFree chlorine: potentialstatic electrode

Total chlorine: membrane-enclosed sensor

with integrated amplified electronic

pH value: single-rod measuring cell

Redox: single-rod measuring cell

Controller connectionFree chlorine: C7700 (servo motor with potentiometer)

pH value: Solenoid-driven dosing pumps

(Pulse frequency - optocoupler)

Terminal plan

pH value

DO4 DO3 DO2 DO1

DO7DO6

DO5

DO0

C7700

23

111

1012

OPEN

CLOSED

90 to 264 V AC

total chlorine electrode4...20 mA

78399

CPRT(ATE) 5.fach

78404

C(P) 20mA(ATE)

78403

Redox

reference electrodecounter electrode (stainless steel)measuring electrode (Gold)

pH-valuedosing pump

temperature

water-shortage

3-foldinput block

78402

output block

20 mA power outputs

digital inputsalarm

relays

mainboard

power generator

5-fold input block

free cholrine(potentiostatic electrode)

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

363738 PE N L

3334

92 93 9487 88 89 90 91

86

-+

8182838485

--

++

5657585960

-+

535455

61

51B52B

-+

-+

7172737475

76 77 78

39 40 41 43 44 45 4642

35

95 96

+-

Page 46: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

46 | Operation Manual TOPAX DX | BA-40100

Chapter�17:�Wiring�diagrams

Example�6:

Sensors connectionFree chlorine: membrane-enclosed sensor

with integrated amplified electronic

pH value: single-rod measuring cell

Redox: single-rod measuring cell

Controller connectionFree chlorine: C7700 (servo motor with potentiometer)

pH value: Solenoid-driven dosing pumps

(Pulse frequency - optocoupler)

Terminal plan

pH value

Redox

DO4 DO3 DO2 DO1

DO7

DO6

DO5

DO0

C7700

23

111

1012

OPEN

CLOSED

temperature

water shortage

90 to 264 V AC

membrane covered electrode

4...20 mA

free chlorine

78399

CPRT(ATE) 5.fach

78403

pH-valuedosing pump

78402

output block

20 mA pow

er outputsdigital inputs

alarm relays

mainboard

power generator

5-fold input block

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

363738 P

E N L

3334

92 93 9487 88 89 90 91

86

-+

8182838485

--

++

5657585960

-+

535455

61

51B52B

-+

39 40 41 43 44 45 4642

35

95 96

+-

Page 47: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 47

Chapter�17:�Wiring�diagrams

Example�7:

Sensors connectionFree chlorine: potentialstatic electrode

Total chlorine: membrane-enclosed sensor

with integrated amplified electronic

pH value: single-rod measuring cell

Redox: single-rod measuring cell

Conductivity: conductiv or inductive

with separate measuring amplifier

(Input signal 4...�0 mA)

Controller connectionFree chlorine: C7700 (servo motor with potentiometer)

pH value: Solenoid-driven dosing pumps

(Pulse frequency - optocoupler)

Terminal plan

DO4 DO3 DO2 DO1

DO7

DO6

DO5

DO0

C7700

23

111

1012

OPEN

CLOSED

90 to 264 V AC

Total chlorine electrode4...20 mA

Conductivity4...20 mA

78399

CPRT(ATE) 5.fach

78404

C(P) 20mA(ATE)

78403

free cholrine(potentiostatic electrode)

pH-value

Redox

reference electrodecounter electrode (stainless steel)measuring electrode (Gold)

pH-valuedosing pump

temperature

water-shortage

3-foldinput block

78402

output block

20 mA pow

er outputsdigital inputs

alarm relays

mainboard

power generator

5-fold input block

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

363738 P

E N L

3334

92 93 9487 88 89 90 91

86

-+

8182838485

--

++

5657585960

-+

535455

61

51B52B

-+

-+

7172737475

76 77 78

39 40 41 43 44 45 4642

35

95 96

+-

Page 48: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

48 | Operation Manual TOPAX DX | BA-40100

Chapter�17:�Wiring�diagrams

Example�8:

PC - connection to computer network

NOTICE!The data line must be locked at both sides with a 120 Ohm line resistance and must be supplied a firm potential using the two link plugs on the two jumpers on the circuit board of the display of all la-test TOPAX DX versions.

For this reason, two link plugs have to be installed on the display circuit board of the last TOPAX® DX (see chapter 4.4).

On the sides of the PC; the load resistor has to be

plugged at the connector converter.

DO4 DO3 DO2 DO1

7840478403

78402

DO

7D

O6

DO

5

DO0

78399

BA

78406interface board

+-

+-

+-

+-

+-

+-

+-

+-

123456789

10111213141516

17181920212223242526272829303132

20 mA

power outputs

digital inputs

363738 P

E N L

power generator

3334

92 93 9487 88 8990 91

86

-+

8182838485

--

++

alarm relays

39 40 41 43 44 45 4642

35

95 96

BA

Max. length of the netw

ork: 1000m

Auxiliary pow

er 5 VD

C(U

SB

plug connector)

120 Ohm

terminator

Converter

RS

232 <=

> R

S485

Order-N

r. 44300101

RS

232 (9pin)

Com

puter(TopV

iew S

oftware)

Display circuit board

120 Ohm

terminator: O

NP

ull-Up / P

ull-Dow

n resistances:ON

-> both jum

per at ON

(see chapter 4.4)

Last TO

PA

X D

X in the netw

ork(m

ax.14 devices)

TO

PA

X(D

X, D

E, L, LF, N

, NT

)BA

TO

PA

X(D

X, D

E, L, LF, N

, NT

)

Page 49: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 49

Chapter�18/19:�Software�updates�/�Default�settings

18.�Software�updatesThe installation of new software for an update of the firmware or the languages is done with the help of the MMC card.

NOTICE!The MMC card must only be inserted when the pow-er supply is switched off (see chapter 21).

18.1�Firmware�update

IMPORTANT!For a firmware update, all software files on the MMC card must be deleted and replaced by the updated files.

Firmware update procedure:• Switch off the power supply of the TOPAX DX• Remove the MMC card• Connect the MMC card to a PC with a reading device• Delete the existing directories / files on the MMC card:

Directory „lang“ (language files) file „DX_D1--.EEP“ file „DX_M1--.EEP“ file´ „DX_D1--.HEX“ file „DX_M1--.HEX“

• Transfer the new files (software- and language files) to the MMC card via the PC

• Insert the MMC card in the TOPAX DX• Switch on the power supply of the TOPAX DX

When the operating voltage is supplied, the software is automati-cally installed and started on the TOPAX® DX DX.

NOTICE!For a firmware update to software version 1.13 or older, all settings of the TOPAX DX are overwritten. All settings of the TOPAX DX have to be written down before the update and be restored after the update.

18.2�Update�for�further�menu�languagesThe menu languages "German" and "English" are installed by default. They are automatically updated with a firmware update.

Further languages can be loaded at any time by transferring the respective language files for the software version installed on the TOPAX DX from the MMC card to the TOPAX DX (see chapter 4.8).

The language files can be found in the "lang" directory which is supplied together with the firmware update and have to be transferred from a PC to the MMC card (see 18.1). An overview of the languages, language files and software versions is given in chapter �6. Further languages are available on request.

IMPORTANT!Make sure that the correct software version for the language files is installed on the TOPAX DX!

19.�Default�settingsThe default configuration by the manufacturer includes the fol-lowing settings. The inputs are activated according to the part number.

• Y-Alarm (safety stop) works for all controllers and lasts 60 minutes

• Start-up lag time: 60 seconds• all measuring alarm values are deactivated• all special functions are deactivated

Digital signals• measuring water alarm: ON when the contact is opened• Filter cleaning: ON when the contact is closed• Night-time economy mode: ON when the contact is closed• Level inputs: not active

Free chlorine input Single electrode CS1�0

Part-no. 40100001

Potentiostat PM Part no. 40100003 ...40100005

Disturbance factor input OFF not for conductivity measurements

Flocking pump output OFF

DIN-Contact output OFF

Free chlorine output Servo motor with potentiometer

pH output Pulse frequency (optocoupler) 100 pulses/min

Bonded chlorine output ON/OFF (Relay) Part no. 40100003, 40100005

Conductivity output ON/OFF (Relay) Part no. 40100004, 40100005

Automatic controller free chlorine

W: 0.50 mg/lXp: 35 %Tn: 15 minutesTv: OFF

Automatic controller pH value

W: pH 7.10Xp�: 10 %Tn�: 15 minutesTv�: OFF

Automatic controller bound chlorine

W: 0.�0 mg/lXp3: 10 %Tn3: OFFTv3: OFF

Part no. 40100003, 40100005

Automatic controller conductivity

W: 0,5 % SaltXp3: 10 %Tn3: OFFTv3: OFF

Part no. 40100004, 40100005

Page 50: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

50 | Operation Manual TOPAX DX | BA-40100

Chapter�20/21:�Spare�parts�and�options�/�Memory�Card

20.�Spare�parts�and�options

Components,�options,�spare�parts�and�function Order�no.

Output board 5 relays, 3 optocoupler 78399

input board 5-fold

free chlorine (CS1�0 or encapsulated electrode), pH-value, Redox, temperature, position feedback servo motor, controller 1

78403

input board 3 fold

free chlorine (potentiostat), 0/4...�0 mA, position feedback, servo motor controller �

78404

Interface module RS 485 78406

Extension module for metering of total chlorine content and controlling of bonded chlorine

78438

Extension module for metering and controlling of the conduc-tivity 78439

Srew M4 x 6 (tool to open the casing) 38341

Hinge pivot 38336

fixing hing pivot at the top 38337

fixing hing pivot below 38338

MMC (Multi-Media-Card) memory card 78405

21.�Memory�cardThe memory card transfers and stores language data, firmware-updates and logfiles.

The data which is saved on the card can be transferred to a PC by means of a reading device. For the removal of the MMC card, the TOPAX® DX must be switched off definedly: press the "Switch Off" key in the "service-reset" menu. All controllers are set to an output capacity of "0%" and all unsaved data is saved on the MMC card. The TOPAX® DX can continue to operate without the card.

Fig. ��.1: Slot for the MMC Memory card on the display board. The card is inserted on the display circuit board in the front housing.

NOTICE!The memory card must only be inserted or removed when the device is voltage-free. Switch off the TOPAX DX on the "service-reset" menu (see chapter 16, menu 5.4).

On its website, the manufacturer provides the free software "TopReader" for the readout of the MMC with the recorder and configuration data.

NOTICE!Make sure that no additional data is saved on the MMC and that the saved data are not modified (data loss). The MMC must only be formatted in "FAT" format.

Page 51: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 51

Chapter�22:�Troubleshooting�and�diagnostics

22.�Troubleshooting�and�diagnosticsAll errors are indicated in clear text on the display of the TOPAX® DX. If there are several errors at the same time, the error messages can be called up with the ▲ and ▼ keys.

The system displays the following alarm and messages:

Self-setting�alarmsDisplay Possible�causes Failures�and�troubles�caused�to�TOPAX�DX

Alarm�relay Controller�output�0%System Start Not activated Yes (all)

Keyboard locked Keyboard lock is ON (max. 60 sec) Not activated No

Sensor alarm Input power < 4mAInput power > �1mAor faulty input module

activated Yes –Inputallocated

"measurand " not calibrated Calibrate corresponding input Not activated No (the measurement input works with standard values)

"measurand" calibration not OK The corresponding input cannot be calibrated to the requirements Not activated No

Faulty potentiometer compensa-tion "measurand"

Position feedback with 3-point-steps controllers: compensation was not done Not activated Yes

Manual operation manually started Not activated

Filter backwash manually started (external contact) Not activated Yes

measuring water shortage (not during calibration)

water is not enoughthrough-flow contact is defective

activated Yes (all)

Night-time economy mode Night time economy mode is activated Not activated

Low level alarm signaling Chemicals container is nearly empty activated No

Low level main alarm Chemicals container is empty activated Yes

Messages�that�must�be�confirmed�with�"OK"Display Possible�causes Failures�and�troubles�caused�to�TOPAX�DX

Alarm�relay Controller�output�0%Max-Alarm Measuring value max settings were exceeded activated programmable

Min-Alarm Measuring value min settings falled below activated programmable

Y-Alarm Safety shut off (see paragraph 9.�) activated programmable

Suggestion�of�possible�remediesDisplay Possible�causes Suggestion�of�possible�remediesSystem Start System trigs back to normal operation after lag time

Keyboard locked Keyboard lock is ON (max. 60 sec) System trigs back to normal operation after lag time

Sensor alarm Input power < 4mAInput power > �1mAor faulty input module

• Check sensors connection• Replace input module

"measurand " not calibrated corresponding input not calibrated Calibrate corresponding input

"measurand" calibration not OK • Insufficient resistivity of the electrode• Zero point drift too large

Change buffer solution or replace electrode

Sensor or single-rod measuring cell not compliant to DIN Standards

Check and eventually replace the input sensor

Defective input module Check and eventually replace the input sensor

Faulty potentiometer compensation Position feedback with 3-point-steps controllers: com-pensation was not done

Perform a position feedback adjustment in the "outputs" menu

Filter backwash manually started (external contact) The system sets automatically after due lag time a

measuring water shortage water is not enough orthrough-flow contact is defective

• Provide bigger water flow• Check through-flow contact

Low level alarm signaling Chemicals container is nearly empty Fill up chemical agents or change container

Low level main alarm Chemicals container is empty Fill up chemical agents or change container

Max-Alarm Measuring value max settings were exceeded • Check measurement or sensor• Adjust controller’s parameterMin-Alarm Measuring value min settings falled below

Y-Alarm Safety shut off (see paragraph 9.�)

Page 52: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

5� | Operation Manual TOPAX DX | BA-40100

Chapter�23:�Terminal�connection�diagram�for�own�configurations

23.�Terminal�connection�diagram�for�own�configurationsSelect here your connection requirement for terminal clips configuration of your TOPAX® DX.

Part.-no.:_______________________

Description Part-no. assembledinput module 5-fold 78403

input module 3-fold 78404

Output board 78399

PC interface - RS 485 78406

measurandsTerminal�connection�clipsInput 20�mA�power�outputs

Free chlorine

CS1�0

Potentiostat

Encapsulated electrode

pH value

Redox

Temperature

Total chlorine

bonded chlorine

Conductivity

Types�of�output

Free�chlorine�outputTypes�of�output) Terminal�connection�clips

Servo motor with potentiometerMotorPotentiometer with position feedback

Servo motor without potentiometer

Pulse frequency (Optocoupler)

Pulse frequency (Relay)

Pulse length (Relay)

Continuous regulating output 0/4...�0 mA

ON/OFF (Relay)

No controller function

pH�outputTypes�of�output) Terminal�connection�clips

Servo motor with potentiometerMotorPotentiometer with position feedback

Servo motor without potentiometer

Pulse frequency (Optocoupler)

Pulse frequency (Relay)

Pulse length (Relay)

Continuous regulating output 0/4...�0 mA

�-sides pulse frequency (optocoupler)

�-sides pulse frequency (relay)

�-sides pulse length (relay)

ON/OFF (Relay)

No controller function

Page 53: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 53

Chapter�23:�Terminal�connection�diagram�for�own�configurations

Bonded�chlorine�outputTypes�of�output) Terminal�connection�clipsPulse frequency (Optocoupler)

Pulse frequency (Relay)

Pulse length (Relay)

Continuous regulating output 0/4...�0 mA

ON/OFF (Relay)

No controller function

Conductivity�outputTypes�of�output) Terminal�connection�clipsPulse frequency (Optocoupler)

Pulse frequency (Relay)

Pulse length (Relay)

Continuous regulating output 0/4...�0 mA

ON/OFF (Relay)

No controller function

Flocking�pump�outputTypes�of�output) Terminal�connection�clipsPulse frequency (Optocoupler)

Pulse frequency (Relay)

Pulse length (Relay)

Continuous regulating output 0/4...�0 mA

ON/OFF (Relay)

OFF

DIN�contact�and�ECO�mode�OutputOutput Terminal�connection�clipsOptocoupler

Relay

ECO mode controlOptocoupler

Relay

OFF

Digital�inputs(„Service“ menu – digital inputs)

Function Terminal�connection�clips Configurated

measuring water shortage 17, 18„OK“ = closed

„OK“ = opened

Filter cleaning 19, �0„OK“ = closed

„OK“ = opened

Chemical tankFree chlorine

Level – warning Level – alarm

�1, �� �3, �4

„OK“ = closed

„OK“ = opened

Not active

dosing container pH value

Level – warning Level – alarm

�5, �6 �7, �8

„OK“ = closed

„OK“ = opened

Not active

Night operation �9,30 only if activate

ECO mode control �9,30 only if activate

Page 54: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

54 | Operation Manual TOPAX DX | BA-40100

Index

Aactual value (X) .............................................. �5

Alarm delay ................................................... 35

Alarms .......................................................... �7

Alarm settings .......................................... �7,39

Auto setup ..................................................... 30

BBase load metering ........................................ �6

Battery .......................................................... 11

Croughly calibrated; ......................................... 18

calibration free chlorine .................................. 19

Calibration pH ................................................ 3�

Calibration total chlorine measuring electrode .. 19

Casing............................................................. 8

Clock ............................................................ 38

Conductivity ................................................... ��

Conductivity measurements input.................... ��

Configuration ................................................. 11

Controller / 3-point-step ................................. �4

Controller continuous output ........................... �4

Controller direction ......................................... �6

Controller pulse frequency .............................. �4

Controller pulse length ................................... �4

Control variable Y ........................................... �5

CS1�0 .......................................................... 19

Ddata line ................................................... 10,48

Date and time ................................................ �9

Default settings .............................................. 49

Deviation (X-W) ............................................. �5

Digital inputs ................................................. 39

Digital signal inputs ........................................ �3

Dimensions ..................................................... 5

DIN - contact ................................................. �8

EEco - contact ................................................. �8

ECO mode control .......................................... �8

Economy operation mode ............................... �8

Electronic output ............................................ �4

Encapsulated electrode .................................. 19

Error messages.............................................. 51

FFilter cleaning ................................................ �3

Firmware ....................................................... 49

Flocking ........................................................ 38

Flocking pump ............................................... �9

Free chlorine ................................................. 5�

Free chlorine measurements input .................. 18

HHardware status............................................. 37

IImpact chlorination......................................... 34

Inputs module .................................................. 8

Installation ....................................................... 7

KKey layout ..................................................... 14

key lock ......................................................... 14

LLanguage ...................................................... 39

Level dosing pump ......................................... �3

Level inputs ................................................... �3

Log file .......................................................... �9

MManual operation ........................................... �6

Measuring input for “pH value” ....................... �0

Measuring input for temperature ..................... ��

measuring water shortage .............................. �3

menu structure .............................................. 31

Motor life ....................................................... �4

NNetwork address ............................................ 38

Night operation .............................................. �8

OON/OFF controller .......................................... �4

Optocoupler output ........................................ �4

Output board ................................................... 9

Output limit switch ......................................... �4

PPassword ...................................................... 38

PC interface ..................................................... 9

pH value ........................................................ �0

PI or PID controller ......................................... �5

Potentiostat ................................................... 19

Product overview ............................................. 8

Proportional range Xp ..................................... �5

Pulse length .................................................. �4

RRecycling capacity ......................................... �8

Redox calibration ........................................... �1

Redox measurements input ............................ �1

Redox potential .............................................. �1

Relay output .................................................. �4

Reset ............................................................ 38

Reset time Tn ................................................ �5

SSafety ............................................................. 3

Safety shut off ............................................... �7

Sensor technology ......................................... 11

Service code .................................................. 38

Setpoint (W) ................................................... �5

Start-up lag time ............................................ �3

Status displays .............................................. 33

TTechnical specifications .................................... 5

Temperature .................................................. ��

Temperature calibration .................................. 3�

Temperature compensation ............................ 19

Terminal clips diagrams .................................. 1�

Total chlorine and bonded chlorine .................. ��

Total chlorine measurements input .................. ��

Trend representations ..................................... 33

WWall mount ...................................................... 7

Wiring diagrams ............................................ 40

Page 55: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

25.�Declaration�of�conformityThis declaration is no assurance of characteristics in the sense of the product liability law. The safety instructions in the Operation & Maintenance Manual must be observed.

CE

-TO

PA

X_D

X-V

04

TOPAX DX

2006/95/EG2004/108/EG

EU-KonformitätserklärungDer Unterzeichnete Lutz-Jesco GmbH, Am Bostelberge 19, 30900 Wedemark, bestätigt, dass die nachfolgend bezeichneten Geräte in der von uns in Verkehr gebrachten Ausführung die Anforderungen der harmonisierten EU-Richtlinien, EU-Sicherheitstandards und produktspezifischen Standards erfüllen. Bei einer nicht mit uns abgestimmten Änderung der Geräte verliert diese Erklärung ihre Gültigkeit.

(EN) EU Certificate of ConformityThe undersigned Lutz-Jesco GmbH, Am Bostelberge 19, 30900 Wedemark. hereby certifies that, when leaving our factory, the units indicatedbelow are in accordance with the harmonised EU guidelines, EU standards of safety and product specific standards. This certificate becomesvoid if the units are modified without our approval.

(FR) Certificat de conformité aux directives européennesLe constructeur, soussigné: Lutz-Jesco GmbH, Am Bostelberge 19, 30900 Wedemark, déclare qu’à la sortie de ses usines le matériel neuf désigné ci-dessous était conforme aux prescriptions des directives européennes énoncées ci-après et conforme aux règles de sécurité et autres règles qui lui sont applicables dans le cadre de l’Union européenne. Toute modification portée sur ce produit sans l’accord express deJesco supprime la validité de ce certificat.

(ES) Declaración de conformidad de la UEEl que subscribe Lutz-Jesco GmbH, Am Bostelberge 19, 30900 Wedemark, declara que la presente mercancía, objeto de la presente declaración, cumple con todas las normas de la UE, en lo que a normas técnicas, de homologación y de seguridad se refiere, En caso de realizar cualquier modificación en la presente mercancía sin nuestra previa autorización, esta declaración pierde su validez.

(NL) EU-overeenstemmingsverklaringOndergetekende Lutz-Jesco GmbH, Am Bostelberge 19, 30900 Wedemark, bevestigt, dat het volgende genoemde apparaat in de door ons inde handel gebrachte uitvoering voldoet aan de eis van, en in overeenstemming is met de EU-richtlijnen, de EU-veiligheidsstandaard en de voor het product specifieke standaard. Bij een niet met ons afgestemde verandering aan het apparaat verliest deze verklaring haar geldigheid.

(HU) EG (EK)– Egyezőségi nyilatkozatA Lutz-Jesco GmbH, Am Bostelberge 19, 30900 Wedemark ezúton kijelenti, hogy a szóban forgó termék annak tervezése és szerkezeti módja, valamint forgalomba hozott kivitele alapján a vonatkozó alapvető biztonság technikai és egészségügyi követelményeknek és az alábbifelsorolt EG –irányelveknek minden szempontból megfelel. A terméken engedélyünk nélkül végrehajtott módosítások következtében jelen nyilatkozat érvényét veszíti.

Mess- und RegeleinheitMeasuring and control unitMesure et regulationmMedicion y controlMeet- en regelsysteemMéro- és szabályozó egység

Bezeichnung des Gerätes:Description of the unit:Désignation du matériel:Descripción de la mercancía:Omschrijving van het apparaat:A termék megnevezése:

Typ / Type / Tipo / Típusjelölés: EU-Richtlinie / EU directives/Directives européennes / Normativa UE /EU-richtlijnen / Vonatkozó EG-irányelvek

EN 61000-6-2 : 03.06EN 61000-6-3 : 06.05EN 61000-4-2 : 12.01EN 61000-4-3 : 12.06EN 61000-4-4 : 07.05EN 61000-4-5 : 12.01EN 61000-4-11 : 02.05EN 61000-4-6 : 12.01EN 55022 : 2003EN 55011 : 08.03

Harmonisierte Normen / harmonizedstandards / Normes harmonisées /Estándares acordemente / Toegepastenormeringen / Hatályos normák

i.V. Dipl. Ing. Klaus AlbertLutz-Jesco, Wedemark, 01.02.2008

Technische Leitung / Technical Departement Manager / Direction technique /Dirección Técnica / Hoofd technische dienst / Műszaki irodavezető

CE-TOPAX_DX-V04

Page 56: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

56 | Operation Manual TOPAX DX | BA-40100

Chapter�26:�Device�revision

26.�Device�revisionThis operation manual apply to following units:

Device�type: Revision Software�versionTOPAX DX 11/�008 1.13

Languagefile

Software Version Languages

1.0.� < 1.11 07/�007 DE, EN, ES, PO, NL, FR, CZ

1.0.3 1.11 0�/�008 DE, EN, ES, PO, NL, FR, CZ, RU

1.0.4 1.13 ff. 11/�008 DE, EN, ES, PO, NL, FR, CZ, RU, NO

It contains all the technical information required for installation, start-up and maintenance. Should you have any questions or require further informations regarding these operating instruc-tions, please contact the manufacturer or its official national rep-resentative.

Page 57: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 57

Chapter�27:�Warranty�Application

27.�Warranty�ApplicationPlease copy and send it back with the unit!

If the device breaks down within the period of warranty, please return it in a cleaned condition

with the complete warranty application, filled out.

SenderCompany: .............................................................................................................................................................................

Address: ...............................................................................................................................................................................

............................................................................................................................................................................................

............................................................................................................................................................................................

............................................................................................................................................................................................

Date: ....................................................................................................................................................................................

Contact person: ....................................................................................................................................................................

Phone: .................................................................................................................................................................................

The�deviceManufacturer order-no.: ........................................................................................................................................................

Date of delivery: ....................................................................................................................................................................

Device type: ..........................................................................................................................................................................

Serial number: ......................................................................................................................................................................

Description of fault: ...............................................................................................................................................................

............................................................................................................................................................................................

............................................................................................................................................................................................

............................................................................................................................................................................................

Type�of�fault:1. Mechanical fault ...........................................................................................................................................................

Premature wear ............................................................................................................................................................

Wear parts ....................................................................................................................................................................

Breakage / other damage ..............................................................................................................................................

Corrosion ......................................................................................................................................................................

Damage in transit..........................................................................................................................................................

�. Electrical fault ...............................................................................................................................................................

Connections, plug connectors or cables loose .................................................................................................................

Operating elements (e.g. switches / push-buttons) ..........................................................................................................

Electronic unit ...............................................................................................................................................................

More�specificationsPoint of use / system designation: ..........................................................................................................................................

Accessories used (e.g. sensors, etc.): .....................................................................................................................................

............................................................................................................................................................................................

Commissioning (date): ...........................................................................................................................................................

Duty period (approx. operating hours): ....................................................................................................................................

Please describe the specific installation and enclose a simple drawing of the chemical feed system, showing materials of construction, diameters, lengths and heights of suction and discharge lines.

Page 58: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

58 | Operation Manual TOPAX DX | BA-40100

Page 59: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

BA-40100 | Operation Manual TOPAX DX | 59

Page 60: EN Operation & Maintenance Instructionshesperia.be/sites/default/files/documents-produits/topax_dx-en-ba.pdf · Operation & Maintenance Instructions ... mechanical and ... Der TOPAX®

Lutz-Jesco�GmbHAm Bostelberge 1930900 WedemarkGermany

Phone: +49 5130 5802-0Fax: +49 5130 [email protected]/de

24h-Hotline: +49 5130 580 280

Austria

Lutz-Jesco GmbHAredstraße 7/22544 LeobersdorfAustria

Phone: +43 2256 62180Fax: +43 2256 [email protected]

Netherlands

Lutz-Jesco Nederland B.V.Nijverheidstraat 14 C2984 AH RidderkerkNetherlands

Phone: +31 180 499460Fax: +31 180 [email protected]

USA

Lutz-JESCO America Corp.55 Bermar ParkRochester, NY 14624USA

Phone: +1 585 426-0990Fax: +1 585 [email protected]

East�Asia

Lutz-Jesco East Asia Sdn Bhd6 Jalan Saudagar U1/16Hicom Glenmarie Industrial Park40150 Shah Alam /SelangorMalaysia

Phone: +603 5569 2322Fax: +603 5569 [email protected]

Middle�East

Lutz-Jesco Middle East FZEP.O. Box 9614SAIF-Free Zone CenterSharjahUAE

Phone: +971 6 5572205Fax: +971 6 [email protected]

Best.-Nr. BA-40100-02-V06Subject to technical changes.© Lutz-Jesco GmbH 05.2010Printed in Germany

Hungary

Lutz-Jesco ÜzletágVasvári P. u. 9.9024 GyörHungary

Phone: +36 96 523046Fax: +36 96 [email protected]

Great�Britain

Lutz-Jesco (GB) Ltd.Gateway EstateWest Midlands FreeportBirmingham B26 3QDGreat Britain

Phone: +44 121 782 2662Fax: +44 121 782 [email protected]

TOPAX® is a registered trade mark of Lutz-Jesco GmbH, Wedemark