electromechanical boq forensic

Upload: hassan-adel-hassan

Post on 10-Mar-2016

23 views

Category:

Documents


1 download

DESCRIPTION

Scope of Work, refurbishment of forensic laboratory. Drainage, Water Supply, Hot and Cold, HVAC, Civil, Sanitary, Firefighting.

TRANSCRIPT

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    No. Description Unit Qty Unit Rate

    US$ Total US$

    1 Demolishing Works

    Preamble:

    The contractor should be aware that the proposed work will be

    carried out in the existing functioning building and that the his

    daily activities shall not interrupt others ongoing daily activities in

    the other floors of the existing building.

    Unit rates shall include, but not limited to, the following:

    a. Removing of demolished material out of site to an approved

    dump location.

    b. The dismantled material are the sole properties of the client.

    c. The contractor shall coordinate implementation of his daily

    work activities, working hours, throughout the construction period

    with the client and the supervising engineer

    d. The contractor shall protect and safe guard the existing

    facilities and building finishes, including the painting, the floor

    tiles, *etc. the contractor shall not use the existing elevator for

    loading the construction material

    e. The contractor shall make the necessary temporary water,

    electrical power connections ..etc to prevent interruption of the

    power and water supply for the existing functioning building.

    f. The contractor shall take all necessary measures to protect and

    minimize environmental hazards including pollution, noise, dust

    *etc

    1.1

    Demolishing of the existing internal partitions including block

    works, concrete,* etc, price to include dismantling of the

    electrical, mechanical installation; all as approved by the

    Engineer.

    m2 85

    1.2

    Dismantle of existing wall or floor tiles as shown on drawing A02

    and as per the Engineer instructions. Price should include

    removal of mortar, fill material below the floor tiles.

    m2 400

    1.3

    Dismantle and preserving the existing wooden or metal doors as

    shown on drawing A02 and A03. Price to include removal of the

    door leafs and frames, preserving and storing the doors; all as

    instructed by the Engineer.

    No. 8

    1.4

    Dismantle and preserve the existing kitchen cabinets, including

    careful removal of the counter tops and any associated

    electromechanical fixtures or installations.

    Job 1

    1.5Dismantle and preserve the existing mechanical fixtures including

    one toilet, one sink, water closet.Job 1

    Total Demolishing Works carried to summary

    1 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    No. Description Unit Qty Unit Rate

    US$ Total US$

    2 Block & Plaster Works

    The contractor shall, when pricing the rates of this bill, take into

    consideration including and allowing for the costs or expenses of

    all requirements stipulated in the preambles, drawings and

    technical specification of the tender.

    2.1

    Supply and install 10 cm thick hollow blocks with reinforced

    concrete tie beams over all block walls with steel reinforcement

    412mm and stirrups diameter 6mm@20cm, 20cm high and

    width equal to the wall thickness. The price should include

    412@20cm length steel dowels to be planted in the adjacent

    concrete or stone wall and fastened with the beam reinforcement

    Price shall also include properly fixing and anchorage of the block

    works with the adjacent concrete elements as approved by the

    engineer

    m2 160

    2.2

    Prepare surfaces, apply 13mm thick plaster on new or existing

    walls composed of 2 coats of cement sand plaster (rough and

    fine finish) over cement splashing coat. The price includes angles

    beads, wire mesh on all kinds of joints especially electro-

    mechanical. The price should include patching works on

    previously plastered walls for electro-mechanical installations.

    m2 340

    Total for Block and Plaster Works carried to summary

    2 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    No. Description Unit Qty Unit Rate

    US$ Total US$

    3 Tiling Works

    The contractor shall, when pricing the rates of this bill, take into

    consideration including and allowing for the costs or expenses of

    all requirements stipulated in the preambles, drawings and

    technical specification of the tender.

    Unit rate shall include all design pattern and cutting, cement

    mortars, cement sand filling bellow floor tiles and grouting.

    3.1.1

    Supply and install non-slip 30X30cm 7mm thick granite porcelain

    floor tiles, simlar to model "Coco from TAU CERAMICA" or

    equally approved Spanish or Italian tiles; all as per the Engineer's

    choice and approval. The price should include the installation of

    the tiles at 5mm spacing and to any pattern selected by the

    engineer, grouting with anti bacterial epoxy grout. Price shall

    include the cement mortar (1:3), sand with cement filling.

    m2 330

    3.1.2

    Supply and install glazed porcelain tiles first grade for wall tiling

    Spanish or Italian made and as approved by the Engineer. Tiling

    shall be to any pattern and color selected by the Engineer, with

    5mm spacing, pointing with water resistant grout like Mapei. Price

    shall include surface preparation, installation of the tiles, on new

    or existing walls, with approved adhesive material.

    m2 30

    Total for Tiling Works carried to summary

    4 Sealing Works

    The contractor shall, when pricing the rates of this bill, take into

    consideration including and allowing for the costs or expenses of

    all requirements stipulated in the preambles, drawings and

    technical specification of the tender.

    4.1

    Supply and apply three coat of Sika Top Seal 107 or equivalent

    on clean surfaces at the wet areas. The price include 5*5cm

    angle fillet with smooth sand cement mortar (1:3), applaying of

    smooth surface layer of cement- sand screed to recieve the

    sealing material.

    m2 25

    Total for Sealing Works carried to summary

    3 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    No. Description Unit Qty Unit Rate

    US$ Total US$

    5 Wooden and Carpentry Works

    The Contractor shall when pricing the rates of this bill, take into

    consideration including and allowing for the cost or expenses of

    all requirements stipulated in the preambles, drawings, and

    technical specifications.

    5.1 Wooden doors

    Supply and install the following 45mm thick PLY wooden doors.

    Price to include pine woode frames, three door hinges at each

    door leaf, 20 cm high stainless steel kick plates from both sides of

    the door leafs, door stoppers, door locks, cylinders (Wally or

    equally approved), and the accessories as approved by the

    Engineer.

    Price to include painting of the door leafs and frames by 2 coats

    of putty 2 coats of under coat ORANGE as made by APC or

    equaly approved,and 3 coats of APC ARAMAT; all as instructed

    and approved by the Engineer.

    5.1.1D01,clear leaf dimensions 80x210cm. Please refer to drawings

    details 34 + 35.No. 9

    5.1.2

    D02

    Dismantled , preserve and re-install the existing wooden doors

    as shown on drawing A03 and instructed by the Engineer. Price

    shall include, but not limited to, the followings:

    1- supply and install pine wooden doors frame 50mm thick and

    width equal to the wall thickness. 2- Fixing of the

    frames by galvanized steel anchors L75x100mmx40mm width

    and 1.5 mm thick ( 4 anchors for each side)

    3- Installing new handles, locks and cylinders as made by Wally

    or an approved equal.

    4- Painting of the new door frames and the dismanteled door

    leafs with oil paint including primer, 2 coats of putty, 1 coat of

    undercoat and three coats of oil based wooden paint.

    No. 8

    4 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    No. Description Unit Qty Unit Rate

    US$ Total US$

    5.2 Wooden Counters, benches and cabenits

    Supply and install laboratory cabinets with the following

    specifications:

    1- All handles are as made by TIRADOR 2012/14 Length of

    handle 96/160 mm, Color is NIROSTA MATT.

    2- All hinges are as made by BLOOM

    3- All Ply wood used is 17mm BARCELONA made or equivalent

    that should be approved by the site engineer.

    5.2.1

    Supply and install lower laboratory cabinets, as per the detailed

    drawings and instructed by the site engineer, price includes

    counter with granite tops as made by CAESAR color No. 7100,

    Preformed casements, upper and lower steel ends. Refer to

    Detail 6 + 7 + 8 + 9 +10 + 11 + 12 +13 + 14 +15 +16+18 +19 +21

    + 22 + 26

    mr 25

    5.2.2

    Supply and install lower laboratory cabinets, as per the detailed

    drawings and instructed by the engineer, price includes ready

    made Formica top counter c. Refer to Detail 2 + 3 + 4 + 5 + 6 + 9

    + 12 + 13 + 14 + 15 + 16 + 18 + 19 + 20 + 22 + 24 + 25

    mr 40

    5.2.3Ditto but upper cabinets, 40cm deep, without counter top part.

    Refer to Details 3 + 4 + 11 + 21 + 26 + 28mr 20

    5.2.4

    Ditto but to be installed back to back as a middle counter. Refer

    to Details 5 + 6 + 7 + 8 + 9 + 12 + 13 + 17 + 18 + 19+ 20 + 22 +

    23 + 24 +25

    mr 22

    5.2.5 Ditto but covers for electro-mechanical cabinets. m2 4

    5.2.6Ditto, but reception counter complete, as shown on drawings and

    approved by the Engineer.No. 1

    5.2.7

    Ditto but for shelving units. The price should include 4*4mm steel

    tubes for hanging the shelves from the ceiling. Refer to details 20

    + 22 + 25

    mr 10

    Total for Wooden and Carpentry Works carried to summary

    5 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    No. Description Unit Qty Unit Rate

    US$ Total US$

    6 False Ceiling Works

    The contractor shall, when pricing the rates of this bill, take into

    consideration including and allowing for the costs or expenses of

    all requirements stipulated in the preambles, drawings and

    technical specification of the tender.

    6.1

    Supply and install ECOPHONE ADVANTAGE E 15mm thick over

    fine line structure 60x60cm false ceiling, price to include structure

    and installation using special gloves as instructed and approved

    by the site engineer. The Price should include install paper

    corner and joints beads on all joints, corners, connections

    between walls and boards using putty (GOLD BOND BRAND),

    laying one layer of putty over the joints and corners and another

    one layer over all gypsum boards, sanding with sand paper and

    finishing all as approved by the site engineer. Refer to Details 30

    + 31 + 32

    m2 180

    6.1.1

    For Gypsum False ceiling Supply and install ORBOND water

    proofing (GREEN) gypsum board for false ceilings of 12.5 mm

    thick gypsum panels with studs at every 40cm in both directions

    including decorations, forms, trims with all connections supports ,

    fixing, putty sealer , wire mesh and special angles for edge of

    boards and all necessary accessories needed for the best

    completion of works . The contractor shall provide a shop

    drawing for architect approval.

    m2 160

    6.1.1.2For ORBOND water proofing (GREEN) gypsum Panels12.5 mm

    thick less than 50cm widem2 40

    Total for False Ceiling Works carried to summary

    6 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    No. Description Unit Qty Unit Rate

    US$ Total US$

    7 Painting Works

    The contractor should allow in his pricing that the engineer may

    use as many different colors or combination of colors to meet an

    approved color scheme.No hand made color mix is allowed.

    The contractor has to prepare a color sample 1.5x1.5m on site for

    each color asked by the Engineer

    The owner has the right to choose any color of or combination, no

    price difference will be measured for any color variation done

    All paint works should conform to manufacturer's instructions

    regarding number of coats, rate of application or drying time

    Painting to be carried out on new or old surfaces. Price shall

    include surface preparation , pealing off old defective paint,

    batching, ..etc

    On walls & ceiling

    7.1

    Supply all kinds of raw material and apply paint for internal walls,

    stairs walls, landings, and wherever needed or instructed by the

    site engineer, the price should include preparing surface, clean,

    remove dust and foreign matter, sanding with sand paper,

    checking the walls with Calcimo X and putty, applying one coat of

    APC FILL , laying two coats of putty (GOLD BOND brand or an

    approved equivalent), applying one coat of SUPER BOND ROLL

    and applying three coats of ARACRYL 2000 all as instructed and

    approved by the site engineer

    m2 350

    7.2

    Supply all kinds of raw material and apply paint for gypsum

    boards up to 3.6m high, and wherever needed or instructed by

    the site engineer, the price should include preparing surface,

    clean, remove dust and foreign matter, sanding it well with sand

    paper, checking the walls with putty, laying two coats of putty

    (GOLD BOND brand or an approved equivalent), applying one

    coat of SUPER BOND ROLL and applying three coats of

    ARACRYL 2000 all as instructed and approved by the site

    engineer

    m2 190

    Total for Painting Works carried to summary

    7 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Bill No. Description Total US$

    1 Total for Demolishing works

    2 Total for Block and Plaster works

    3 Total for Tiling works

    4 Total for Sealing Works

    5 Total for Wooden and Carpentry works

    6 Total for False Ceiling works

    7 Total for Painting works

    Total for Civil Works carried to grand summary

    Civil Works BoQ Summary

    8 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item

    NoDescription Unit QTY

    Unit Rate

    US$ Total US$

    1 DRAINAGE WORKS Connecting the new drainage pipes to the existing

    pipes includes all the workmanship and fittings (pipes

    will be paid for as per the corresponding bill item), as

    well as, any alteration of the drainage pipe passage

    through the demolished walls. Contractor should allow

    in his unit prices for pipes all such works and fittings.

    The smooth flow and continuity of the drainage system

    in the building from the upper floors through the lower

    floors and down to the basement is the contractor's

    responsibility. Hence, contractor should inspect the site

    before pricing the drainage system.

    1.1

    Supply and install (S&I) 4" PVC "Redi " floor drain

    (siphon), or approved equal, complete with floor

    collector and 110 mm diameter vertical extension from

    Huliot or equally apparoved to receive the 2" and 11/2"

    diameter PVC under floor drain pipes, and includes

    heavy duty stainless steel rim and cover 15x15 cm ,

    1.1.1 4" diameter NO 8

    1.2 Ditto but clean out NO 4

    1.3 Floor trap 2"/2" and 4"/2" NO 12

    1.4

    S&I UPVC pipe Royal SN6, or approved equal, for

    sewage, rain water and air condition drainage. The price

    includes also all fittings, elbows, nipples, digging, coring,

    plastering and connecting the pipes of the new fixtures

    to the existing drainage system.

    1.4.1 4" diameter LM 45

    1.4.2 2" diameter LM 145

    Total Drainage Works

    9 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item

    NoDescription Unit QTY

    Unit Rate

    US$ Total US$

    2 COLD AND HOT WATER The price for connecting the new cold water pipes to

    (taping-in) the existing pipes in the various floors and

    basement shall cover for all the needed fittings deemed

    necessary to do the job. Also, the continuity and smooth

    flow of the water in the building is the contractor's

    responsibility.

    2.1

    Supply and install water collector type Giacomini, NTM,

    or equally approved with branch valve for each exit,

    suspended in void above false ceiling. Price includes

    shut of valve of the same make, air vent Calcify, end-

    cap piece,collecter brackets, as a complete job

    2.1.1 12 eyes 1" NO 1

    2.1.2 10 eyes 1" NO 1

    2.1.3 8 eyes -3/4" NO 1

    2.1.4 4 eyes -3/4" NO 1

    2.2

    Supply and install galvanized steel oven painted cabinet

    for the collectors with hinged cover and brackets,

    designated for radiators meant at low level.

    NO 2

    2.3

    Supply and install electrical water heater as made by

    Original/Palestine, or equally approved, of high pressure

    quality plus enameled internal paint with all required

    fixation, operation and safety to be installed in void or

    hung on wall. Price includes shut off valve Sounders,

    safety valve 1" type (Califi) and connected to a drain

    pipe down to the floor trap to prevent splashing when

    activated, air vents (Califi), connection to power socket

    as a complete job

    2.3.1 80 L capacity NO 2

    2.3.2 40L capacity NO 1

    2.4

    Supply and install thermo pipes type pexgol,pexline with

    sleeve, price includes wall elbow, and connection to

    collectors and water supply under tiles or suspended to

    ceiling, under tiles pipes shall be covered with 5 cm

    mortar concrete and wall/ceiling-hung pipes shall be

    restrained with hilti holders at 1 meter intervals.

    2.4.1 32/50 LM 25

    2.4.2 25/32 LM 70

    2.4.3 20/25 LM 50

    2.4.4 16/25 LM 100

    Total Cold & Hot water system Items

    10 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item

    NoDescription Unit QTY

    Unit Rate

    US$ Total US$

    3 SANITARY FIXTURES

    3.1

    Supply and install the following sanitary fixtures with the

    required original fixing accessories and materials. The

    price of the sanitary fixture shall neither include the

    supply and installation of the corresponding 2" PVC

    pipes from the sanitary fixture to the floor drain

    connection box or sewage pipes, nor shall it include the

    price of the corresponding 16/25 mm pex pipes from

    collectors to each sanitary fixture. The waste water and

    supply water pipes from/to the sanitary fixture shall be

    measured and paid for as per the corresponding unit

    rate and conditions of the item under question.

    3.1.1

    S&I and install wall hung W.C bowl class A, Pargamon

    color .Jika made ref.21370 or equally approved with the

    necessary original connections, including Schwab made

    concealed flushing system ref. 8118502 9/6 L for wall or

    equally approved, with steel reinforcing legs. Price

    includes cover, seat, hardware from same make,

    connection to cold water and drainage, as well as,

    casting reinforced concrete B 250 20cm thick,

    8mmx20x20 cm around the tank.

    NO 3

    3.1.2

    Supply and install wash basin porcelain Pargamon

    color type Jika Ref 14312 or equally approved, with half

    leg of the same make, complete with chrome plated

    siphon of CE quality make.

    NO 3

    3.1.3

    Supply and install electronic water mixer hot and cold

    for the wash basin 220 volt type Ideal Standard or

    approved equal with all the necessary transformers

    and valves flexible hose 1/2-3/8 Neil angle valves, or

    equally approved.

    NO 3

    3.1.4

    Supply and install porcelain Pargamon color class A

    shower tray Creavit make or equally approved, size

    90x90 cm with Huliot siphon.

    NO 1

    3.1.5

    Supply and install inside wall chrome plated mixer for

    the shower Ideal Standard, or equally approved,

    including shower stand, hose and handset.

    NO 1

    3.1.6

    Supply and install stain less steel kitchen sink type

    ROCA size 60x40 complete with original siphon and

    1/2"-3/8" valve Neil and connection to cold & hot water

    as a complete job

    NO 1

    3.1.7

    Supply and install electronic water mixer hot and cold

    for the sink 220 volt type ideal standard or approved

    equal with all the necessary transformers and valves

    flexible hose 1/2-3/8 Neil angle valves

    NO 1

    3.2

    Supply and install robust heat & chemical resistance

    sink, Poly-propylene sinks for side working benches, A

    600x400x200H mm. polypropylene sink installed in the

    center of the washing stand working surface including

    drain valve and siphon valve and all required

    connections as made by POLYSINK, UK, Cat. No. PS-

    0543 S or an approved eq.

    NO 7

    11 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item

    NoDescription Unit QTY

    Unit Rate

    US$ Total US$

    3.3

    Supply and install bench mounted one hole mixer with

    swivel spout, ceramic head works and

    Detachable Nozzle as made by BROEN, Denmark, Cat.

    No. 15 274.009 or an approved eq.

    NO 7

    3.4

    Supply and install combined Body and eye shower, wall

    mounted in brass with chemical resistant BROEN Poly-

    coat with self-draining shower head. Water inlet at the

    top or bottom. Eye shower has built-in FLOWFIX (6.7

    g/pm). Eye shower, combined wall mounted with two

    heads in brass with chemical resistant BROEN Poly-

    coat. Water is regulated with a built-in FLOWFIX (6.7

    g/pm).Body shower 3/4 NPT male inlet in brass with

    chemical resistant BROEN Poly-coat Complete unit. as

    made by BROEN, Denmark, Cat No. 17 455.909 or an

    approved equal.

    NO 3

    3.5 Supply and install electronic hand dryer 2500 watt stainless steel body type Vortice or equally approved

    NO 3

    Total Sanitary Fixtures

    12 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item

    NoDescription Unit QTY

    Unit Rate

    US$ Total US$

    4 VENTILATION SYSTEM AND FIRE FIGHTING

    4.1

    Supply and install exhaust fans type S&P, Vortice or

    equally approved with all fixing cassowaries in the

    toilets and rooms, including coring with coring

    machine, and connecting to duct or PVC pipes for small

    fans. All galvanized duct, distribution boxes, PVC pipes

    and conduits, flexible ducts, grills, and what ever

    deemed necessary for the completion of the exhaust

    mechanism job should be included in the fan price.

    4.2

    Silent mixed flow fans with sound absorbent insulation

    price include coring in the wall by coring machine,

    installing exhaust grill with back draft shutter connection

    the fan with the exhaust grill with duct and flexible joint

    at both sides of the fan galvanized distributing box with

    all the opening and adapters ,flexible ducts to be

    connected to the circular exhaust diffusers, fresh air

    grill with filter 80-85 % efficiency and volume damper

    installed on the galvanized duct ,fresh air rain water

    grill , as per the drawings , as one complete job

    4.2.1 800m3/h @10 mm NO 2

    4.2.2 600 M3/H @10 mm NO 4

    4.2.3 450 M3/H @10 mm NO 4

    4.2.4 120 M3/H @4 mm with timer NO 5

    4.2.5

    Ditto as above specification 4.1-4.2 but for the

    basement floor water tank room 800 m3/h @15 mm

    including all the rain water grill fresh air grill with filter 80-

    85 %

    NO 1

    4.3

    Supply and install galvanized sheet metal duct 0.7 mm

    as per SMACNA standard, including all the bends,

    elbows, hangers, flexible canvas connectors, corig in

    the walls, wooden sleeves,etc. for the exhaust fans in

    the basement floor

    SQM 65

    4.4 Fume Hoods:

    4.4.1

    Supply and Install the following Fume Hood:

    Dimensions: Width: 1800mm x Depth: 750 mm Height:

    2620 mm.Structure:

    18 mm laminated UPVC or Poly-propylene with 63 mm-

    thick edges.Working surface:

    Ceramic Tiles. with a front 30 mm elevated threshold

    and tapering edge which provides a 10 mm elevation

    above the worktop, including preparing bores for valves

    and sink and water faucet* etc. the unit is equipped by

    4 power sockets type GEWISS and cut-off switch to

    operate the blower and the lights.

    13 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item

    NoDescription Unit QTY

    Unit Rate

    US$ Total US$

    Back of the hood:

    There will be a double back, allowing routing and

    regulating the air flow from the upper and the lower

    parts of the hood by means of upper and lower flues,

    the hood back is made of 6 mm-thick TRESPA, a

    polypropylene lattice will be mounted at the outlet of the

    air suction inlet to prevent foreign bodies from entering

    the blower.

    Status indication:

    An electrical mechanism for indicating the operation

    status of the air suction blower by means of red lamp

    and green lamp mounted on the front panel of the hood

    Vertical window:

    Made of 6 mm-thick safety glass and stainless-steel

    frame slides on polypropylene rails and balanced by

    means of ball bearing wheels, balancing bar and

    counter weight.

    Electrical accessories and wiring:

    A Thermo magnet drive for driving the blower motor, 2

    single phase power sockets, a lighting switch, a safety

    fuse and control lamp. All mounted on the hoods front

    panel.

    A 2 x 20 watts fluorescent lamps will be mounted on the

    upper cover outside hood, with a sealed transparent

    window to ensure that no gases enters the lamp area.

    A CL terminal box and marked terminal connections to

    the mains and to the blower will be mounted on the

    hidden upper part of the hood.

    Suction blower:

    Rigid PVC, UV resistance centrifugal polypropylene

    booster made by COLASIT, Swiss made.

    Motor:

    3-phase, Completely tight, TEFC, F isolation grade,

    1400 r/pm. hp. Manufactured by SIEMENS, Germany.

    Direct drive, model RN-250 protected by a safety switch.

    In-Line Carbon Filter:

    An Integrated sliding drawer containing micro-

    coalescing carbon filter with capacity to fit the fume

    hoods capacity.Manufacturer: P.V. Plast, Laboratory Equipment &

    Furniture, Plastic Engineering or an approved

    equivalent

    No. 1

    4.4.2 Ditto but 1200mm wide No. 2

    14 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item

    NoDescription Unit QTY

    Unit Rate

    US$ Total US$

    4.5

    Supply and install Fully Automatic Duplex Medical Oil-

    less Compressed Air System, Consists of two Base

    Mount Oil-less Stationary 2 stage Reciprocating Piston

    Compressors, each of single phase, with free air

    delivery of 205 L/min minimum, with a pressure output

    up to 6 bar, both connected to 100 liter medical grade

    horizontal receiver tank, made by hot galvanized steel.

    System includes all mechanical, electrical fittings

    pressure switches, orifices, valves, gauges, shock-

    absorbers, and all required components to start up and

    to shut down automatically and alternatively by means

    of electric control panel with all protection modes and

    functions. System also includes an in-line refrigerating

    Air Dryer with minimum capacity of 1000 LPM and a

    medical grade set of purification filters with by-pass. as

    made by ASOULINE COMPRESSORS, Cat. No.: SV-

    205X2PlusD or an approved eq.

    NO 1

    4.5 Supply and install 6 kg fire Extinguisher FM 200 NO 11

    Total Ventilation and Fire Fighting System

    5 AIR CONDITIONING WORKS

    5.1

    Supply and install Inverter high wall split unit air

    condition type Tadiran, or equal approved gas 410,

    price includes electrical wiring, copper piping with

    insulation and PVC band between the outdoor unit and

    the indoor unit drain pipe to the nearest drain point, and

    water proof on-off switch on the external unit,

    galvanized steel holder/stand ,opening in walls and

    slabs by coring machine for any wall type and thickness

    ,closing holes with sika sealant, gas and oil

    charging.NOMINAL CAPACITY

    5.1.1 24000BTU/H NO 2

    5.1.2 18000 BTU/H NO 7

    5.1.3 12000BTU/H NO 3

    5.1.4 9000 BTU/H NO 2

    5.2

    Dismantling the existing air conditions in the offices and

    reinstall and operate them in the required locations as

    per the owner's request, including all electrical works,

    pipes and hangers. The contractor is responsible for

    any damage that might be inflicted on the units during

    the relocation process.

    NO 4

    Total Air Conditioning Works

    15 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Bill No. Description Total US$

    1 Total Drainage Works

    2 Total Cold & Hot water system Items

    3 Total Sanitary Fixtures

    4 Total Ventilation and Fire Fighting System

    5 Total Air Conditioning Works

    Total Mechanical Works carried to Grand

    Summary

    Mechanical Works BoQ Summary

    16 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    1 Electrical and Communication WorksPreamble: The contractor shall, when pricing the rates of the

    following electrical bills take into consideration including and

    allow for the cost expenses of all requirements stipulated in the

    preambles, drawings and technical specifications of the tender.All supplied materials should be class A , new , not used and

    Free From any Defects, Having the Supervisor approval

    Certificate .

    The contractor's total price for works shall include for the supply,

    execution, completion and testing of the whole of electrical

    installation works and related systems in accordance with the

    drawings, bill of quantities and specifications.

    the rates includes connection to existing system were applicable

    and or adjustment of non removed or cancelled network to allow

    for new networks or system .

    The contractor shall coordinate his works with the decoration

    works, furniture, changes in the positioning of ceiling light

    fixtures due to partitioning changes and any other changes

    which require design changes on the tender drawings.The contractor must consider all these changes in the shop

    drawings which must be submitted and approved before

    commencement of works.Plates, labels and tags for the identification of plant, equipment,

    cables, switches ,sockets and a like.the unit rate including for forming or cutting holes, chases,

    channels etc. in reinforced concrete structures and block works the unit rate including for Jointing, saddles, clamps, brackets,

    hangers and providing steel pipes sleeves with plates.

    All electrical and low voltage conduits for all different items in the

    main B.O.Q. installed above false ceiling level must be colored,

    fire proof and first class taken quality and following the PCP

    standard for all main and sub main feeders circuits*etc.

    The contractor must consider keeping the system running where

    needed during the whole construction period.

    The contractor's rate must include the supply and install internal

    sea sand plastering for the electrical conduits on wall .

    composed of two coats base coat ,finish coat . The rate includes

    all necessary patching works ,expanded metal latch mesh ,

    plastering layers must be applied to meet plastering thickness

    The contractor shall submit all samples needed for all electrical

    and low voltage points, fittings , accessories and fixtures and

    following the PCP standard and to take the approval from the

    supervision engineer before starting works.

    The contractor shall submit a time schedule for all the works

    showing start and end dates for each item in B.O.Q..

    the contractor should have his electrical engineer available in a

    daily bases and on call to arrange with the Consultant

    representative engineer on site and for all written

    communications and works

    All electrical conduits under tiles, floor, wall should be protected

    by cement mortar or concrete layer and all electrical excavation

    works should be removed from site as specified in the technical

    specification and drawings.

    17 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    Making holes by hilti for all holes size where required including

    all necessary water proofing material ( Sikaflex).for any kind of

    electrical and low voltages works.The contractor's rate must include all measures to serve the

    smooth running of existing system and network through out the

    renovation works without any interruptions.The above mentioned shop drawings, electrical switchboards

    shop drawings, as built drawings and all other required detailed

    drawings are to be included in the rates for no additional cost.

    Access doors opening in false ceilings or gypsum board are

    included in the unit rate of installing of any kind of lighting

    fixtures and all different electrical, low voltage fixtures*etc.

    1 Electrical Distribution Boards:

    Supply install , connect and test the electrical switchboard to

    site including all associated materials and labor, as described in

    the technical specifications. Cabinets with no access from the

    rear , made up of transparent polycarbonate cells, Galvanized

    2mm sheet metal cabinets with 25% surplus space. Main supply

    lines enter from bottom , top or side, while out going lines exit the

    switchboard , from both its bottom and top only. Price to

    include all structural elements required in order to install the

    switchboard including all bus bars , terminals , wiring , bolts ,

    clamps, master keys for all different panels doors, etc. and for

    the equipments as per dwg specification.

    1.1 GMDB-Control Panel

    1.1.1

    Adding ,connect and test inside existing GMDB The main

    modeled case circuit breaker (MCCB) (3X100) A . with standing

    36KA cutout and short circuit current.

    No. 1

    1.2 GMDBUPS -Control Panel

    1.2.1

    Adding ,connect and test inside existing GMDBUPS MCB 3

    x40A rating 400V. Capable of switch-standing 15KA cutout and

    short circuit current.

    No. 1

    1.3 SMDB5 /DBUPS L.S. 1

    1.4 DB1 L.S. 1

    1.5 DB2 L.S. 1

    1.6 DB3 L.S. 1

    1.7 DB4 L.S. 1

    1.8 DB5 L.S. 1

    1.9 DB6 L.S. 1

    1.10 DBREC L.S. 1

    Total of Electrical Distribution Boards Carried to Summary

    Sheet

    18 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    2 Installation in the Building Points

    The following items are supply, installation of same, connection,

    wiring, commissioning and all other details, as specified in the

    technical specification and drawings.

    2.1

    Wall, ceiling or false ceiling mounted lighting point normal,

    waterproof, emergency or exit (Price includes 16mm diameter

    conduit hadash plats type or Approved equivalent, 3x1.5 mm2

    cross section cables cabels itac type or Approved equivalent ,

    price includes all switches, push button legrand type or approved

    equivalent, ceiling box and phase line for emergency lighting

    point , and leading from the switch panel to the point including

    any needed boxes or accessories).

    No. 120

    2.2

    Standard 1 ph socket outlet point normal (Price includes 16mm

    dia. conduits Nacy , hadash plats type or Approved equivalent,

    3x2.5mm2 cables intact , synenergy type or Approved

    equivalent , with 16A socket Legrand Type Arteor Model with

    Brilliant White Finish Color or Approved equivalent, Boxes,

    Supports & Plates and leading from the switch panel to the point

    , including all accessories).

    No. 35

    2.3 Ditto but waterproof No. 20

    2.4

    Standard 1 ph Double socket outlet point normal (Price

    includes 16mm dia. conduits Nacy , hadash plast type or

    Approved equivalent, 3x2.5mm2cables itac , synenergy type or

    Approved equivalent , with 16A socket Legrand Type Arteor

    Model with Brilliant White Finish Color or Approved equivalent,

    Boxes, Supports & Plates and leading from the switch panel to

    the point , including all accessories).

    No. 40

    2.5 Ditto but waterproof No. 2

    2.6

    16A Industrial three phase wall-mounted socket outlet point

    (Price includes sockets NISKO type N516.110 with lockable

    cover, IP 65 , three and single phase Legrand type or Approved

    equivalent, 5x2.5mm2 N2XY cable or Approved equivalent,

    23mm diameter conduits, and all accessories leading from

    distribution board to the point).

    No. 6

    2.7

    Emergency shut off push button kit outlet connection point, price

    includes 16 mm2 conduit, 3x2.5mm2 N2XY or Approved

    equivalent cable , push button Legrand Type Arteor Model with

    Brilliant White Finish Color or Approved equivalent and all

    accessories).

    No. 9

    2.8

    Single phase electrical connection of Split Unit (Price includes

    3x2.5mm2 N2XY or Approved equivalent cross section cables,

    A/C socket Legrand Type Arteor Model with Brilliant White

    Finish Color or Approved equivalent, flexible heat conduits,

    cable glands, connection boxes, adaptors and all connections

    and accessories from relevant panel to machine .

    No. 17

    2.9

    Standard 1 ph socket UPS outlet point normal (Price includes

    16mm dia. conduits Nacy , hadash plast type or Approved

    equivalent, 3x2.5mm2cables itac , synenergy type or Approved

    equivalent , with 16A socket Legrand Type Arteor Model with

    Brilliant White Finish Color or Approved equivalent, Boxes,

    Supports & Plates and leading from the switch panel to the point

    , including all accessories).

    No. 15

    2.10 Ditto but Double UPS No. 40

    19 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    2.11

    Double pole On-off switch with indication lamp ,including Price

    includes 16mm dia. conduit, 3x2.5mm2 N2XY cross section

    cable or Approved equivalent, with ON-OFF switch Legrand

    Type Arteor Model with Brilliant White Finish Color or Approved

    equivalent. Rates also includes Boxes, Supports & Plates and

    leading from the switch panel to the point , including all

    accessories).

    No. 2

    2.12

    1 ph power connection outlet point for infra red for sink (Price

    includes 16mm dia. conduits Nacy , hadash plast type or

    Approved equivalent, 3x1.5mm2 cables itac , synenergy type

    or Approved equivalent and leading from the switch panel to

    the point , including all accessories).

    No. 10

    2.13

    Telephone outlet connection point wall or table mounted (The

    price includes 16mm2 conduits with 4 pairs computer cable

    shielded type CAT6A and leading from computer HUB to the

    points as well an outlet with Easily terminated 10G 6A shielded

    RJ-45 style modular outlets/jacks. Meets or exceed all Cat6A

    channels requirements via an enhanced design , including alien

    crosstalk parameters. and / or 3M Modular CAT6A type or

    Approved equivalent including Boxes, Supports & Plates and all

    accessories).

    No. 35

    2.14

    T.V. antenna connection point (The price includes 16mm

    diameter conduits Nacy , hadash plast type or Approved

    equivalent, with American common scope coaxial cable RG6

    75 ohms,, as well an outlet with a plastic socket Legrand Type

    Arteor Model with Brilliant White Finish Color or Approved

    equivalent, Including Boxes, Supports & Plates and leading from

    point to the connection box on roof.

    No. 2

    2.15

    Satellite antenna connection point (The price includes 16mm

    diameter conduits Nacy , hadash plast type or Approved

    equivalent, with American common scope coaxial cable RG6 75

    ohms, leading from connection box to the points as well an outlet

    with a plastic socket Legrand Type Arteor Model with Brilliant

    White Finish Color or Approved equivalent , Including Boxes,

    Supports & Plates and leading from point to the connection box

    on roof.

    No. 2

    2.16

    CCTV connection point (Each outlet for indoor, out door camera

    , monitor, shall be measured as one point. Price includes

    16mm2 conduits Nacy , hadash plast type or Approved

    equivalent, and CAT6A computer cable teldor type or Approved

    equivalent and leading from point to the CCTV section in the

    communication cabinet with all accessories).

    No. 5

    2.17

    Fire detection system connection point, (Each outlet for smoke ,

    heat detectors, break glass , indoor or outdoor alarm horn, shall

    be measured as one point. Price includes 16mm2 conduits and

    cables 4x0.8 mm2 ITAC type or Approved equivalent, and

    leading from point to the fire detection section in the

    communication cabinet or to the nearest point and all

    accessories).

    No. 50

    20 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    2.18

    Computer outlet connection point wall or table mounted (The

    price includes 16mm2 conduits with 4 pairs computer cable

    shielded type CAT6A and leading from computer HUB to the

    points as well an outlet with Easily terminated 10G 6A shielded

    RJ-45 style modular outlets/jacks. Meets or exceed all Cat6A

    channels requirements via an enhanced design , including alien

    crosstalk parameters. and / or 3M Modular CAT6A type or

    Approved equivalent including Boxes, Supports & Plates and all

    accessories).

    No. 62

    2.19

    access outlet connection point wall or table mounted (The price

    includes 16mm2 conduits with 4 pairs computer cable shielded

    type CAT6A and leading from the Access control panel to the

    points t including Boxes, Supports & Plates and all accessories).

    No. 45

    Total of Installation Works Carried to Summary

    3 Lighting Fixtures and Accessories Note: work for lighting fixtures is to include supply of the fixtures

    specified, installation of same connection, wiring,

    commissioning, lamps OSRAM type, tubes, starters louvers,

    connections, suspension, clamps and all other accessories

    necessary to provide a complete fitting with all terminals and

    rates also includes all L,Z and omega profiles if needed , great

    opening for lighting fixtures in gypsum board and all other details

    , as specified in the technical specifications and drawings and as

    approved by the engineer.

    3.1

    Type (A)418W recessed fluorescent lighting fixture with

    electronic ballast and double prismatic polycarbonate diffuser

    triphosphore lamps, IP44 Gaa'sh type or Approved equivalent.

    Unit 53

    3.2Type (AE) Ditto but with emergency battery charger 3 hours

    duration Gaa'sh type or Approved equivalent.Unit 24

    3.3

    Type (B) 226w compact fluorescent recessed down light

    polycarbonate body and high purity metalized aluminum

    decorative reflector. IP44 Gaa'sh or Approved equivalent.

    Unit 16

    3.4Type (BE) Ditto but with emergency battery charger 3 hours

    duration or Approved equivalent.Unit 8

    3.5

    Type (C) 2*18 w compact fluorescent lamp round bulkhead with

    opal glass diffuser die cast aluminum body IP65. GAASH or

    Approved equivalent .

    Unit 4

    3.6Type (CE) Ditto but with emergency battery charger 3 hours

    duration Gaa'sh type or Approved equivalent.Unit 1

    3.7Type (D) 1x8w emergency exit sign with 3 hours maintained

    duration GAASH 580121 type or Approved equivalent.Unit 2

    3.8Type (F) 1x8w emergency exit sign with 3 hours duration

    DOUBLE SIDED GAASH 580501 or Approved equivalent.Unit 2

    3.9Type (G) 60W wall mounted light fixture in use sign GAASH

    type or Approved equivalentUnit 2

    3.10

    Type (G) 236w surfaced fluorescent lighting with electronic

    ballast and opal diffuser IP 65, GAASH type or Approved

    equivalent

    Unit 2

    Total of Lighting Fixtures and Accessories Carried to

    Summary

    21 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    4 Cables & Conductors / Leads Supply, install, test and connect the following electrical cables ,

    including insertion into conduit or attachment to structural

    elements or laying in ductwork, including all associated

    materials, insulation materials, unions, labeling and connection

    of cable at both ends and all accessories.

    4.1 3x35+16 sq.mm cross section XLPE/PVC/PVC cable. M.L. 30

    4.2 5x16 sq.mm cross section N2XY cable. M.L. 30

    4.3 5x6 sq.mm cross section N2XY cable. M.L. 170

    4.4 3x10 sq.mm cross section N2XY cable. M.L. 170

    4.5 3x2.5 sq.mm cross section N2XY cable. M.L 100

    4.6 3x1.5 sq.mm cross section N2XY cable. M.L 100

    4.7 5x2.5 sq.mm cross section N2XY cable. M.L 100

    4.8 5x1.5 sq.mm cross section N2XY cable. M.L 100

    4.9 7x1.5 sq.mm cross section N2XY cable. M.L 50

    4.10 Copper conductor with PVC insulation cross section 35sq.mm. M.L 150

    4.11 Copper conductor with PVC insulation cross section 16sq.mm. M.L 300

    Total of Cables & Conductors Works Carried to Summary

    Sheet

    5 Cable Conduit & Ducts

    Supply, install, test and connect the following standard conduits

    or color fire proof conduits, processed over or under plaster or

    over false ceiling, including junction boxes, unios, connectors,

    etc* including galvanized draw strings, ready for use "Pony last"

    type or Approved equivalent and all accessories).

    5.175 mm diameter heavy, bendable type NACY, Had ash Plast or

    Approved equivalent.M.L 50

    5.242mm diameter heavy, bendable type NACY, Had ash Plast or

    Approved equivalent.M.L 50

    5.329mm diameter heavy, bendable type NACY, Had ash Plast or

    Approved equivalent.M.L 200

    5.423mm diameter heavy, bendable type Had ash Plast or

    Approved equivalent.M.L 150

    5.516mm diameter heavy, bendable type Had ash Plast or

    Approved equivalent.M.L 200

    Total of Cable Conduit & Ducts Carried to Summary

    22 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    6 Telephone Cable and low voltage box

    Supply, install, test and connect metallic low voltage box for

    Telephone, TV , CCTV systems .The size of the low voltage

    shall be the same height and depth of the nearest electrical

    board with 45cm width .6.1 SMLV5 L.S. 1

    6.2 LVREC L.S. 1

    6.3 Lvbox on roof L.S. 1

    6.4

    Supply, install, test and connect Telephone cable 1NO. 10pairs

    Superior from main low voltage box to the floor low voltage

    boxes price includes terminal blocks, corona and all

    accessories.

    M.L 100

    6.5

    Supply, install, test and connect Fiber type: Single mode ,

    outdoor , optimized for 1310nm , ITU-TG.652. to server room

    through electrical shaft with PVC insulation cross section 23mm.

    labeling and Termination: SC connectors from each end on

    patch panel. and all accessories)

    M.L 100

    Total of Telephone Cable and low voltage box Carried to

    Summary Sheet

    23 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    7 Electrical Appliance & Motor connections & Special Works

    The following items are supply, installation of same, connection,

    wiring, and all other details and all electrical conduits should be

    protected by cement mortar or concrete layer as specified in the

    technical specification and drawings..

    7.1

    Electrical connection of Single phase Extract Fan (the Price

    includes 16mm diameter conduit, 3x1.5mm2 cables ITAC type

    or Approved equivalent, Isolator switch 10A cable glands,

    connection boxes w.p, labeling, adaptors and all accessories

    and leading from Relevant panel to machine to the satisfactory

    of the engineer.

    No. 4

    7.2

    Electrical connection of Single phase Extract Fan (the Price

    includes 16mm diameter flexible heat conduits, 3x1.5mm2

    cables ITAC type or equivalent, Isolator switch 10A cable

    glands, connection boxes w.p, labeling, adaptors and all

    accessories and leading from lighting point to extract fan.

    No. 10

    Total of Electrical Appliance Works Carried to Summary

    Sheet

    8 Grounding Works

    8.1

    Grounding Earthling loop including cold and hot water piping,

    fuel piping, air conditioning piping, ducts, all false ceiling systems

    in all floors and whole project elevator rails, main and sub main

    distribution boards, metallic sewage , supply trunks metallic

    cable ducts, Generator, EPABX and any other metallic service in

    the building. Rate to include copper conductors as shown on

    drawings, main and secondary potential equalizing bus-bar,

    protective conduit, junction box, complete with all necessary

    accessories that all for all project floors and all mechanical and

    metalic bodies at roof floors.

    L.S. 1

    Total of Grounding Works Carried to Summary Sheet

    9 Access & Integrated Security System Type

    Supply , install and connect the following Access Security

    System infinias IP-based Access Control or approved

    equivalent including outlet boxes , cover plates and all

    necessary connections, complete with operation, testing and

    commissioning works as shown on the drawings and as per

    specifications.

    9.1 Intelligent Controller or Approved equivalent. No. 1

    9.2Ethernet daughter board for TCP/IP communication or Approved

    equivalent.No. 1

    9.3power / communication daisy chain harness or Approved

    equivalent.No. 1

    9.4Closer (Wall-mount) Capacity: to handle 14 door . Power supply

    and battery included 7*PRO22 R2 or Approved equivalent.No. 1

    9.5PRO-2200 Dual Reader Module ( OP30 )

    Mini-Mullion Mullion or Approved equivalent.No. 13

    9.6 HID Proximity compatible reader wall or Approved equivalent. No. 13

    9.7 Strike electric lock S4 No. 13

    9.8 Bush button door release No. 13

    9.9WIN-PAK SE Access Control Software Server , 1 User win pak

    without H.W server or Approved equivalent.No. 1

    Total of Access & Integrated Security System Works Carried

    to Summary

    24 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    10 Fire Alarm System

    Supply install and connect fire alarm addressable system

    BOSCH or Approved equivalent including of the equipment

    specified, installation of same connection, wiring commissioning

    and all of the details as specified in the technical specifications

    and drawing with complete operation capacity 125 detectors.

    10.1Fire alarm control panel, 1 loop, expandable, 125 points, and

    230V, gray.No. 1

    10.2 Analogue addressable photoelectric smoke detector.V-PS No. 30

    10.3 Analogue addressable heat detector.V-HRD No. 9

    10.4 Analogue manual call break glass station.GSA-M270 No. 5

    10.5 Indoor fire siren.G1RF-P No. 5

    10.6 Fire alarm outdoor siren with strobe.757-7A-T No. 1

    10.7 Automatic telephone dialerDL-125C No. 1

    Total of Fire Alarm System Works Carried to Summary Sheet

    11 CCTV System

    Supply , install and connect the following IP Digital CCTV

    System including outlet boxes , cover plates, and all

    necessary connections , complete with operation, testing and

    commissioning works as shown on the drawings and as per

    specifications. The CCTV System shall include the following.

    Lens: View: 66 horizontal, F2.0VideoResolution: SVGA (800x600) to 120x90Compression: H.264 (MPEG-4 Part 10/AVC), Motion JPEGFrame rate: 30 fps in all resolutionsMulti-stream supportedVideo motion detectionSecurity: Password protection, IP address filtering, digest

    authentication, HTTPS encryption, IEEE 802.1X network access

    control, user access logProtocols: IPv4/v6, HTTP, HTTPS, QoS Layer 3 Diffuser, FTP,

    SMTP, SNMPv1/v2c/v3(MIB-II), DNS, NTP, RTSP, RTP, TCP,

    UDP, IGMP, RTCP, ICMP, DHCP, ARPCasing: Suitable indoor casing includedPower: Power over Ethernet (PoE) IEEE 802.3afOperating conditions: 0C to 50CDVR compatibilityTested and demonstrated full compatibility with ZoneMinder

    DVR under Linux OS (http://www.zoneminder.com/)Please see the Hardware compatibility list:

    http://www.zoneminder.com/wiki/index.php/Hardware_Compatibil

    ity_ListExample model: AXIS M3011 or approved equivalent

    http://www.axis.com/products/cam_m3011/

    Total of CCTV System Works Carried to Summary Sheet

    11.1 No. 4

    25 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    12 Computer Network

    12.1

    Supply, install and connect , testing and commissioning switch

    and patch panel and all necessary accessories with complete

    operation. As listed below

    12.1 Patch Panel:

    Unloaded Patch panel for Cat6A systems

    Provides Cat6A performance in a reliable and flexible modular

    solution.

    Compact design for 1U 48 Port high density application.

    Switch:

    48 x 10/100/1000 Ethernet LAN ports with automatic speed

    detection

    PoE+ 802.1at on all ports, minimum 380W available POE budget

    MDI/MDIX sensing: Automatic

    Form factor: 1U

    Switching bandwidth: 170 Gbit/s

    Features:

    Layer 2 switching

    IEEE 802.1Q

    Layer 3 routing

    IEEE 802.1X with a RADIUS server, multiple IEEE 802.1X users

    per port;1

    MAC-based port security with RADIUS server

    Source-port filtering;

    IGMPv3, LLDP, QoS

    IPv4, IPv6

    DHCP relay

    ACL

    Manageable: HTTP, SSH, SNMP

    Firmware: upgradeable

    Rack mount kit: Included

    Example model: HP E2910-48G-POE+ J97 29A + POE Power

    http://h18000.www1.hp.com/products/quickspecs/13280_na/132

    80_na.PDF

    12.3

    Supply, install, connect and programming Linksys cables less-

    N Gigabit Security Router with VPN Secure, high-

    speedcablesless networking or Approved equivalent.

    No. 2

    12.4Computer main feeders cable shielded type Teldor FTP CAT6A

    inside pvc conduits.ML 60

    Total of Computer Network Carried to Summary Sheet

    12.2 No.

    26 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    13 Fire Fighting SystemSupply install and connect complete in place and in an operable

    manner the Fire Fighting system Telefire / Mircom / Kidde or

    Approved equivalent For main distribution board at electrical

    room . The work is to include the supply of the equipment

    specified, installation of same connection, wiring commissioning

    and all of the details.

    13.1

    Automatic Valve Cylinder 3 KG Kidde FM 200 P/ N

    90100011001 ( 180 Degree Pendant Nozzle , 3/8" Check

    Valves , Bracket , Pressure Gauge , Copper pipe , Safe Cap

    *...with all accessories needed )

    No 1

    13.2Main Control Panel 4- Zone Telefire 2-B or Approved

    equivalentNo 1

    13.3Photoelectric Smoke Detector MIR-338H / TFO-440 or

    Approved equivalentNo 2

    13.4 Heat detector - S.S 5601 P / TFH-220F or Approved equivalent No 2

    13.5 Indication lamp TFL-1N or Approved equivalent No 2

    13.6 Break glass unit TPB-10 R or Approved equivalent No 1

    13.7 Fire Indoor Horn TIP-224A or Approved equivalent No 1Total of Fire Fighting System Works Carried to Summary

    Sheet

    14 Cable TraysSupply and install galvanize cable trays, cable trucking and

    sleeves as per drawings and specifications complete with

    supports, fixing devices, covers, separators, clamps, end caps,

    drawcabless, elbows, joints, branches, reducers, offsets *as

    show on drawings and specifications.

    14.1LV Cable Tray 100x85 mm Mesh galvanized iron, 6 mm

    thickness. M.L. 40

    14.2Power Cable Tray 200x85mm Mesh galvanized iron, 6 mm

    thickness. M.L. 40

    Total of Cable Trays Carried to Summary Sheet

    27 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    15 Trucking systemSupply and install and connect main SNAP -ON Trucking

    system -LEGRAND MODEL or approved equivalent, complete

    with Parttions,covers, spacers, internal and external angles ,

    end caps joints, body joints, base joints , flat angle 90 degree ,

    flat junctions branches, reducers, offsets , The work is to include

    the supply of the equipment specified, installation of same

    connection, commissioning and all of the details as listed below

    for the required complete job. SNAP-ON TRUNK 50X105 1COMP+45MM COVER 2M NO

    075602SNAP-ON TRUNK EXTRA PARTITION 2M NO 075609SNAP-ON TRUNK END CAP 50X105 NO 075612SNAP-ON TRUNK INTERNAL ANGLE 50X105 NO 075622SNAP-ON TRUNK EXTERNAL ANGLE 50X105 NO SNAP-ON TRUNK FLAT ANGLE 50X105 NO 075642SNAP-ON TRUNK COUPLING SET 50X105 NO 075688SNAP-ON TRUNK 45MM COVER JOINT NO 07 5669SNAP-ON TRUNK FLAT JUNCTION SIDE 17->50X105 NO

    075676SNAP-ON TRUNK FLAT JUNCTION SIDE 29->50X105 NO NO

    075676SNAP-ON TRUNK ANGLED JUNCTION->50X80/105/130SNAP-ON TRUNK SOLUCLIP NO 75690

    Total of Trunking system Carried to Summary Sheet

    16 Electrical Switchboards

    16.1 GMDB- Existing Control Panel

    16.1.1

    Replacing and connecting The Main Molded Case Circuit

    Breaker (MCCB) ( 3 x315 )A. Type ABB or approved equivalent

    with short circuit current protective coil and adjustable thermal

    over current protection capable of with standing 50KA cutout and

    short circuit current. Inside the existing GMDB control panel

    price includes Bridges , bus bar , cables and all accessories

    with complete operation.

    No. 2

    16.1.2

    Adding and connecting ,testing with complete operation A

    Motorized ATS 4 pole (4x400) A. Type Klockner Moller Complete

    set or equivalent.

    No. 1

    TOTAL of GMDB- Exist-Control Panel Carried to Summary

    17 Cables & Conductors / Leads Supply, install, test and connect the following electrical cables ,

    including insertion into conduit or attachment to structural

    elements or laying in ductwork, including all associated

    materials, insulation materials, unions, labeling and connection

    of cable at both ends and all accessories).17.1 3x185+95 sq.mm cross section XLPE/PVC/PVC cable. M.L. 70

    17.2 Copper conductor with PVC insulation cross section 95sq.mm. M.L 70Total of Cables & Conductors Works Carried to Summary

    Sheet

    15.1 M.L. 50

    28 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Unit Qty Unit Rate

    US$ Total US$

    18 Stand-By Power GeneratorSupply, install and connect in place and in an operable manner

    an automatic main failure emergency stand by diesel generating

    set, 225KVA 3-phase 380volt, 50C/S, 0.8 p.f complete with

    control panel, including complete set of digital analyzer controller

    unit, frequency meter ( package mounted control panel).The

    contractor should install the generator in the specified room,

    including radiator fan, fuel filter, engine-driven radiator with

    blower fan and all accessories, starting batteries -lead-acid

    storage battery- complete with battery charger and control panel

    when generator set is not operating and disconnect when

    generator set is in operation, original water proof canopy jacket, exhaust system, foundation,

    vibration isolators, silencer, earthling, foundation concrete base,

    a full tank of diesel fuel,... etc. with all fitting and accessories.

    The system should include the main Automatic Voltage

    Regulator (AVR) witch maintain the generator output voltage

    within +/-0.5% for any constant load between no load and full

    load. The contractor and supplier should provide one set of operation

    and maintenance manuals covering the generator, and auxiliary

    components, include all parts manuals, final as-built wiring

    interconnect diagrams and recommended preventative

    maintenance schedules. and accessories to complete the

    works.

    18.1

    Stand By Power Generator Set all as described above. All

    Manufacturer of original types as MBH Power Generator type ,

    Perkins or approved equivalent.

    No 1

    Total of Emergency Generator Carried to Summary Sheet

    19 Fire Fighting System

    Supply install and connect complete in place and in an operable

    manner the Fire Fighting system Telefire / Mircom / Kidde or

    Approved equivalent For main distribution board at electrical

    room . The work is to include the supply of the equipment

    specified, installation of same connection, wiring commissioning

    and all of the details.

    19.1

    Automatic Valve Cylinder 3 KG Kidde FM 200 P/ N

    90100011001 ( 180 Degree Pendant Nozzle , 3/8" Check

    Valves , Bracket , Pressure Gauge , Copper pipe , Safe Cap with

    all accessories needed )

    No 1

    19.2Main Control Panel 4- Zone Telefire 2-B or Approved

    equivalentNo 1

    19.3Photoelectric Smoke Detector MIR-338H / TFO-440 or

    Approved equivalentNo 2

    19.4 Heat detector - S.S 5601 P / TFH-220F or Approved equivalent No 2

    19.5 Indication lamp TFL-1N or Approved equivalent No 2

    19.6 Break glass unit TPB-10 R or Approved equivalent No 1

    19.7 Fire Indoor Horn TIP-224A or Approved equivalent No 1

    Total of Fire Fighting System Works Carried to Summary

    29 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Item Description Total amount $

    1 Total of Electrical Switchboards Works

    2 Total of Installation in the Building Points Works

    3 Total of Lighting Fixtures Works

    4 Total of Cables & Conductors / Leads Works

    5 Total of Cable Conduit & Ducts Works

    6 Total of Telephone Cable and low voltage box Works

    7 Total of Electrical Appliance Works

    8 Total of Grounding Works

    9 Total of Access & Integrated Security System Works

    10 Total of Fire Alarm System Works

    11 Total of CCTV System Works

    12 Total of Computer Network Works

    13 Total of Total of Fire Fighting System Works

    14 Total of Cable Trays Works

    15 Total of Trunking system Works

    16 Total of GMDB- Exist-Control Panel Works

    17 Total of Cables & Conductors Works

    18 Total of Emergency Generator Works

    19 Total of Fire Fighting System Works

    Total of Electrical Works..carried to Grand Summary

    Electrical Works BoQ Summary

    30 of 31

  • Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208

    Bill No. Description Total US$

    1 Summary of Civil Works Bills

    2 Summary of Mechanical Works Bills

    3 Summary of Electrical Works Bills

    Grand Total

    Name & Address of the Contractor:

    Authorized person Name :

    Signature & Stamp :

    BoQ Summary

    Net Grand Total in Words:

    Date:

    Net Grand Total Excluding Value Added Tax (VAT):

    Discount percentage (if any) :

    Discount Amount :

    31 of 31