nettur boq

42
GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED STATION SUPPLY PORTION PARTICULARS Unit Qty A1 Nos 2 A2 Nos 4 Nos 3 33KV, 800A,25KA CT of ratio 200-100/1-1-1A Nos 9 11KV NCT of ratio 600-300/1-1-1A for REFR protection. Nos 2 A4 Nos 6 A5 (1) Nos 2 A5 (2) Nos 6 A5 (3) Nos 6 A5 (4) 11KV Isolators : b) 400A, Double Break Nos 11 A5 (5) Nos 1 A5 (6) Earth bonds (Copper) to GOS handles and 33KV LAs Nos 39 Price Sheet for ESTABLISHING 2X5MVA, 33/11KV SUB-STATION AT Nittur (B) IN Bha DISTRICT (Supply of Materials) Sl. No. Power Transformers: 33/11KV,5MVA, DELT/STAR, DY 11, 3Ph, 50Hz,Core type winding with OLTC, RTCC panel etc., complete filled with Transil Oil with spare oil of 10% SF6 Circuit Breaker with spring type semipneumatic / pneumatic operating mechanism, including mounting arrangements, rigid bi metallic terminal connector complete suitable for Coyote ACSR with Capacitor trip devices for instantaneous triping in case of D/C failure for power transformer. a) 33KV, 800A, 25KA Class with Capacitor trip device. (Make: ABB, CGL) A3 (1) Current Transformers with rigid terminal connector suitable for Lynx ACSR: 33KV, 800A,25KA CT of ratio 400-200/1-1-1A A3 (2) A3 (3) Potential Transformers with rigid terminal connector suitable for Lynx ACSR. -33KV single Phasse, Oil filled, outdoor type as per technical specification: Ratio 33KV/ v3 / 110V/v3-110/v3 core-3 Isolators including Marshalling Box and Terminal connectors, as per technical specification with Solid Core, cylindrical post insulators :33KV, 800A, 25 KA Class Double Break manually operated isolators with terminal connectors suitable for Lynx conductor, etc. complete. a) Upright mounting type with earth switch. 33KV, 800A, 25 KA Class Double Break manually operated isolators with terminal connectors suitable for Lynx conductor, etc. complete. b) Upright mounting type with out earth switch. (live point hight3570mm) 11KV Isolators : a) Single break 400A with roaster switch. 11KV Isolators : c) 200A, Single Break for Aux. Transformer

Upload: -

Post on 26-Oct-2014

206 views

Category:

Documents


15 download

TRANSCRIPT

Page 1: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

STATION SUPPLY PORTION

Sl. No. PARTICULARS Unit Qty unit price

A1 Nos 2

A2 Nos 4

A3 (1) Nos 3

A3 (2) 33KV, 800A,25KA CT of ratio 200-100/1-1-1A Nos 9A3 (3) 11KV NCT of ratio 600-300/1-1-1A for REFR protection. Nos 2

A4 Nos 6

A5 (1) Nos 2

A5 (2) Nos 6

A5 (3) Nos 6

A5 (4) 11KV Isolators : b) 400A, Double Break Nos 11

A5 (5) 11KV Isolators : c) 200A, Single Break for Aux. Transformer Nos 1

A5 (6) Earth bonds (Copper) to GOS handles and 33KV LAs Nos 39

Price Sheet for ESTABLISHING 2X5MVA, 33/11KV SUB-STATION AT Nittur (B) IN Bhalki TALUKA IN Bidar DISTRICT (Supply of Materials)

Power Transformers: 33/11KV,5MVA, DELT/STAR, DY 11, 3Ph, 50Hz,Core type winding with OLTC, RTCC panel etc., complete filled with Transil Oil with spare oil of 10%

SF6 Circuit Breaker with spring type semipneumatic / pneumatic operating mechanism, including mounting arrangements, rigid bi metallic terminal connector complete suitable for Coyote ACSR with Capacitor trip devices for instantaneous triping in case of D/C failure for power transformer.a) 33KV, 800A, 25KA Class with Capacitor trip device. (Make: ABB, CGL)

Current Transformers with rigid terminal connector suitable for Lynx ACSR: 33KV, 800A,25KA CT of ratio 400-200/1-1-1A

Potential Transformers with rigid terminal connector suitable for Lynx ACSR. -33KV single Phasse, Oil filled, outdoor type as per technical specification:Ratio 33KV/ v3 / 110V/v3-110/v3 core-3

Isolators including Marshalling Box and Terminal connectors, as per technical specification with Solid Core, cylindrical post insulators :33KV, 800A, 25 KA Class Double Break manually operated isolators with terminal connectors suitable for Lynx conductor, etc. complete. a) Upright mounting type with earth switch.

33KV, 800A, 25 KA Class Double Break manually operated isolators with terminal connectors suitable for Lynx conductor, etc. complete. b) Upright mounting type with out earth switch. (live point hight3570mm)

11KV Isolators : a) Single break 400A with roaster switch.

Page 2: Nettur BOQ

A6 Nos 12

A7 Nos 27

A8 (1) Nos 10

A8 (2) Stations Beams 3B1 - 0.25 MT Nos 5

A9 (1) Set 8

A9 (2) 33KV Current Trasformers - 0.142 MT Set 12A9 (3) 33KV Voltage Trasformers - 0.142 MT Set 6A9 (4) 33KV Lightning Arrestors - 0.07 MT Set 12A9 (5) 33 Kv Pedestal Insulator. Support - 0.07 MT Set 9A9 (6) 11KV NCT - 0.142 MT Set 2

0.3

Coyote Conductor 0.9

Mtrs 250

D Shackles Nos 12

Tension Clamps Nos 6

Nos. 54

45KN Disc Insulators (ball & socket type) Nos. 252

Strain clamps for Lynx ACSR (Bolted type) Nos. 12

Strain clamps for Coyote ACSR Nos 132

Suspension clamps for Lynx ACSR (Bolted type) Nos 6

T-Clamps for Lynx ACSR Nos 15

Surge Arrestors with Surge Monitor and insulating base Metal Oxide gap less type, as per Technical Specification. Polymeric type 30KV, 10KA normal duty metal oxide with terminal connectors suitable for Lynx Conductor (discharge class-II) LA's

Surge Arrestors: 9KV class Las for 11 KV ODS/ Feeders

33KV Station Structures with peak: Fabricated Galvanised steel structures 3T1 - 0.595MT

Mounting Structures:Mounting Structures for equipments made out of fabricated galvanised angle iron, SM Rails for transformer plinth, cable mounting structures made out of channels and angles including Bolts&Nuts, tubular pipes, as per approved drawing: 33KV Isolators - 0.24 MT

A10 (1) Conductors: Lynx ACSR K

Mtrs

A10 (2)

K Mtrs

A11 (1) Faraday's Caging: Earth wire 7/3.15 mm steel with clamps/lugs

A11 (2)

A11 (3)

A12 (1)

Insulators and Hardware: 70/90KN Disc Insulators (ball & socket type)

A12 (2)

A12 (3)

A12 (4)

A12 (5)

A12 (6)

Page 3: Nettur BOQ

T-Clamps for Coyote ACSR Nos 115

33KV Solid Core Insulators Unit 9

Nos 42

8 Mtr. Long, 115kg RCC pole for Station Yard lighting Poles Nos 10

Nos. 26

ii) 1B2 - 4.0 mtrs long-0.036 MT Nos. 20

Nos 20

A15 Set 6

A16 Set 2

Set 2

Set 2

A18 Set 2

A12 (7)

A12 (8)

A13 (1) 11KV ODS: 9 Mtr. Long, 145kg RCC pole for ODS

A13 (2)

A14 (1)

Beams out of channels 100x50mm with arrangements for stringing power conductor alongwith cleats, Bolts& Nuts, painted with two coats of metal primer and aluminium paint, etc, complete: i) 1B1 - 7.45 mtrs long- .068MT

A14 (2)

A14 (3)

Angles 65x65x6 mm with clamps, Bolts, painted with two coats of metal primer and aluminium paint, etc, complete. i) 2.50 mtrs long for fixing 11KV GOS handle support

D.P.Structures: D.P. Structures using 9 mtrs long RCC poles with hardware consisting of double power X-arms, horizonontal cross brace, cross braces, back cleat, strain plate, bolt & nuts, painted with two coats of metal primer and aluminium paint, etc as

11KV outdoor PCVCB: 11KV, 350MVA,800A,Out door type KIOSK comprising of 1I+4F+1AP3 PCVCBs ( 1 feeder should have OV/ UV, ND relay suitable for cap.Bank)( 11kV Bank with CT ratio 600-300/1-1/1A with Scada Compatability and 11kV Feeder 200-100/1-1-1A with Scada Compatability. (Make: MEI, ABB)

A17 (1)

33kV Control and relay panel: Simplex type as per technical specifications (Control Voltage 110V DC): 33/11KV Power Transformer C&R panel (Simplex): with SCADA compatibility with providing numerical differential relay, numerical REFR and 3 OCR+EFR (Static/electro_mechanical) and by providing additional sapre potential free contacts for master strip and transformer auxilary functional relay (make ABB, ER, AREVA)

A17 (2)

33KV line C&R panel (Simplex): With SCADA compatibility with 2 OCR+EFR (Static/ electro mechanical) and by providing additional potential free contact for master-trip relay. (make ABB, ER, AREVA)

LTAC Panel 14 way, indoor, with fuse cutouts, volt meter, ammiter, MCCB's etc., as per specifications.

Page 4: Nettur BOQ

A19 Nos 2

A20 Nos 2

Mtrs 90

1.1KV, 4 core 10 Sq.mm Copper cable with glands/lugs/ferrules. Mtrs 50

1.1KV, 2 core 10 Sq.mm Copper cable with glands/lugs/ferrules Mtrs 100

Mtrs 1000

ii) 2 Core 6 Sq.mm Mtrs 200

iii) 19 Core 2.5 Sq.mm Mtrs 750

iv) 10 core 2.5 Sq.mm Mtrs 250

v) 14 core 2.5 Sq.mm. Mtrs 250

Mtrs 140

ii) 75 mm dia (outer), 2 to 2.5 mm thick Mtrs 100

iii) 100 mm dia (outer), 2 to 2.5 mm thick Mtrs 50

A24 Set 1

A25 Set 1

AC Distribution box single front outdoor type 6 terminal 750x1350x300mm, 2 I/C of 100 Amp MCCB 20 kA + 6 O/G MCB 16 Amp + 1 O/G of 100 Amp, HRC fuse

DC distribution panel outdoor type with 2 I/C SFU 200 Amp + 10 O/G SFU 60 Amp + 10 O/G SFU 30 Amp with relays for DC failure and DC Bus Earth Fault as per technical specifications

A21 (1)

Power Cable LT (Armoured) as per specification & Drawing: 1.1KV PVC insulated 95 Sq.mm Aluminium Cable, 4core with glands/lugs/ferrules for Auxiliary Transformer.

A21 (2)

A21 (3)

A22 (1)

Control Cable(Armoured) with Accessories: (With glands/lugs/ferruels): i) 4 Core 6 Sq.mm

A22 (2)

A22 (3)

A22 (4)

A22 (5)

A23 (1)

Providing, laying and jointing PVC pipes conforming to IS 4085-1960 and approved makes with necessary specials such as collars, bends, elbows, Tee, Nipples, plugs etc., complete, whereever necessary as per the directions of the Field Engineer: i) 63 mm dia (outer), 2 to 2.5 mm thick

A23 (2)

A23 (3)

Auxiliary transformer with oil, outdoor type 63KVA, 11KV/440V, 3Ph, 9mtr RCC 145 kg W/L poles DOLO/HG-fuse Unit, L.T. protection Kit, Distribution Box and other accessories including testing and commissioning as per specification.

Station Battery (Tubular type) & Battery Charger: 110V, 100AH Battery set consisting of 55 Nos. Cells with float cum boost battery charger working on 230V single phase AC supply along with integral DCDB consisting of 4 Nos O/G feeders as per specification.(Lead Acid Stationary Cells Tubular positive plate type)

Page 5: Nettur BOQ

A26 Set 2

Nos 10

Nos 10

Nos 10

2 core , 6 Sq. mm, 1.1KV class armoured Al. Cable Mtrs 325

Nos. 10

Nos 4

Carbon dioxide type 4.5Kg capacity Nos 6

Nos 8

Nos 2

Nos 1

Name Board for S/S Nos 1

First Aid Box Nos 2

Rubber mat Nos 6

Shock treatment charts Nos 1

Water filter Nos 1

Capacitor bank with 0.2 % series reactor and NCT: Design, Engineering, Supply, erection (including civil work) testing and commissioning of 12.1 kV, 2.5 MVAR satr connected capacitor banks with internal fuses, terminal connector, suitable capacity Neutral CTs and 0.2 % series reactor on neutral side with elevating/mounting structure and with 10 % spare Capacitors cmplete. (This does not includes breaker, panel, civil works like excavation and foundation concreting works)

A27 (1)

Station yard lighting (outdoor): including Civil works complete: Supply of high pressure sodium vappor street light deep drawn aluminium canopy fuly cost with aluminium housing for control gear finished stove enemal gray golssy white conopy interrior wiht a pair of anodisied reflectors clear acrylic bowl gasket linni

A27 (2)

Supply of 32 mm dia class-A GI pipe bracket upto 2.7 mtrs long with reducing collar of 50 X 40 mm to which an extension of 250 mm pipe piece is fixed for 250 watts SV street light fittings using suitable clamps , blots and nuts and wiring suitable capacit

A27 (3)

Supplying Iron Clad DP 15 to 20 Amps with rewireable fuse Havels standards

A27 (4)

A27 (5)

Arial teak wood fuse board of size 300x150x12 mm with clamps and screws

A28 (1)

Fire fighting equipments with necessary mounting stand: Foam type extinguisher(Mech) 9.00 Ltr. Capacity.

A28 (2)

A29 (1) Sand type: G.I Bucket 9 Ltr. Capacity.

A29 (2)

Steel Mounting stand with rain sheds for above buckets.(Each stand for 4 buckets)

A30 (1) Station Service Equipments: Single line diagram

A30 (2)

A30 (3)

A30 (4)

A30 (5)

A30 (6)

Page 6: Nettur BOQ

Godrej make 7 Lever Door locks Nos 2

Wall clock Nos 1

Calling bell Nos 1

Name Plates for equipment/Earth Pit Nos 40

Name plate for feeders and capacitor bank Nos 20

Nos 40

Phase Plates Nos 12

Nos 1

Officer table Nos 1

Steel slotted angle rack( small size) Nos 1

Steel dust bins. Nos 2

S Type Chairs Nos 2

Plastic Chairs Nos 4

Nos 1

I. Ring Spanner set Nos 1

ii. DE spanner Nos 1

Tube spanner set Nos 1

Pipe wrench 24 inch Nos 1

Pipe wrench 18 inch Nos 1

Rubber hand gloves(15KV tested) Pairs 3

Hand torch Three Cell Nos 1

Chargeble Battery set Each 1

A30 (7)

A30 (8)

A30 (10)

A30 (11)

A30 (12)

A30 (13)

Danger Boards/Caution Boards (33 kV & 11 kV, 440 V, 4 Nos each for Line Clear, Load Shedding, Load Restriction, NBFC)

A30 (14)

A31 (1) Furniture: Steel Almirah 61/2 feet

A31 (2)

A31 (3)

A31 (4)

A31 (5)

A31 (6)

A32 (1)

Maintenance Tools and Plant: Telescopic ladder aluminium 6 mtr. Height.

A32 (2)

A32 (3)

A32 (4)

A32 (5)

A32 (6)

A32 (7)

A32 (8)

A32 (9)

Page 7: Nettur BOQ

Nos 2

b) 8"size Nos 2

A34 33 kV Line live tester Nos 2A35 Grounding Sticks Nos 9A36 Screw driver 18 inch Nos 2A37 Screw driver 12 inch Nos 2A38 Hammer 8 lbs Nos 1A39 Hammer 2 lbs Nos 1A40 allenkeys Nos 1A41 Box spanners Nos 1A42 Insulation Megger 2.5-5KV Nos 1A43 Insulation Megger 500V Nos 1A44 Digital clamp meter ( Tong Tester) Nos 1A45 Hydro meter for recording specific gravity of battery. Nos 1

Total

A33 (1) Insulated cutting player 12 inch & 8 inch: a) 12"size

A33 (2)

Page 8: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

STATION SUPPLY PORTION

total price

Bhalki TALUKA IN Bidar

Page 9: Nettur BOQ
Page 10: Nettur BOQ
Page 11: Nettur BOQ
Page 12: Nettur BOQ
Page 13: Nettur BOQ
Page 14: Nettur BOQ
Page 15: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

Sl. No. PARTICULARS Unit

1 2 3 4 5a

Errection Portion:

B (B1) Nos 2

B1 (1) 50

B1 (2) MT 30

B1 (3) Oil filling to the power transformer conservator, radiators Litre 1200

B1 (4) Litre 1200

B2 L/S 2

B3 L/S 2

B4 (1) Set 2

B4 (2) Each 2

B5 (1) Set 4

Price Sheet for ESTABLISHING 2X5MVA, 33/11KV SUB-STATION AT Nittur (B) IN Bhalki TALUKA IN Bidar DISTRICT (Errection of Materials)

Qty.to be supplied &

erected

Unit Charges

in Rs.Inclusive of Work

Contract Tax

Power Transformers: 33/11KV,5MVA, DELT/STAR, DY 11, 3Ph, 50Hz,Core type winding with OLTC, RTCC panel etc., complete filled with Transil Oil with spare oil of 10%

Moving the transformer on the plinth (maximum available distance is 50 Mtrs)

Per MT/Mtr

Assembly of transformer parts like bussings radiators, filling oil into Tr, etc. (for the total Wt of the Tr

Filter of oil using filter set of the contractor to bring the insulation level to I.E. specification

Wiring of Tr.marshalling box, bucholtz relay, fixing thurma meter, OLTC up to control panel and assisting in testing and commissioning by RTMT/ Engineers for 5MVA Tr.

Fabrication of Tr. Railing and embedding in Tr. Plenth (including supply of rails)

Wiring, testing & commisssioning of 5MVA, 33/11kV power Tr: Wiring "Identification of wires, ferruling crimping and termination of wires. Wiring of protective devise, cooling fans, oil flow pumps, OLTC, RTCC"

Testing:1) Ratio test.2) SC test.3) Excitation test.4) Magnetic balance test.5) Vector group test.6) Induced high voltage test.7) OLTC operation.8) Protective devises operation checks.

Erection of Breakers:(33kV Breakers/11kV Kiosks/11kV PCVCBs) with CTs/PTs on mounting structure: 33 kv breakers:Erection/Assembly/Alignment/Inter pole wiring of breakers with its connected equipments including movement from the point of unloading to the point of erection

Page 16: Nettur BOQ

B5 (2) Assisting in testing and commissioning Each 4

B5 (3) Each 4

B6 (1) Set 4

B6 (2) Set 4

B6 (3) Set 4

B6 (4) Set 2

B7 (1) Set 2

B7 (2) Assisting in testing and commissioning Set 2

B8 (1) Set 8

B8 (2) Assisting in testing and commissioning (Upright) Set 8

B9 Nos 12

B9 (1) Fixing solid core insulator 6

B10 Testing and commissioning of capacitor bank with reacter Each 2

B12 (1) 4

B12 (2) Wiring and assisting in testing of commissioning of panels 4

Testing and commissioning: Wiring "Identification of wires, ferruling crimping and termination of wires in breakers and wiring up to control panel / relay panels.Testing for insulation level gas leakage, testing for travel time, trip and close timing. local trip close test, remote trip and close test, tripping through relay, operation of interlocks etc.

Erection of 33 KV CTs and PTs: Erection of CTS and PTs and wiring including movement from the point of unloading to the point of erection (Set consists of 3 Nos)

Assembly in testing and commissioning (Set consists of 3 Nos)

Testing and commissioning: 1) Current Transformers.Wiring: Identification of wires, ferruling crimping of lugs connection up to marshelling box and control panel.Test: Insulation polarity, ratio, excitation. (Set consists of 3 Nos)

2) Potencial Transformers:Wiring: Identification of wires, ferruling crimping of lugs connection up to marshelling box.Test: Insulation polarity, ratio. (Set consists of 3 Nos)

Erection of NCTs: Erection of 11KV NCTs with ground including movement from the point of uploading to the point of erection

Erection of Isolators: 33KV Isolators:Assembly, erection alignment and wiring including movement from the point of unloading to the point of erection (Upright) and

Errection of 33 KV LA's:Errection of33 KV lighting arresters and wiring including movement from the point of unloading to the point of ereciton

Per Stack

Control panels: Erection of Control panels, Auxilary panels, carrier cabinet etc., alignment and fixing properly to foudation base including movement from the point of unloading to the pointof erection

Per Panel

Per Panel

Page 17: Nettur BOQ

B12 (3) Each 4

B13 (1) 8

B13 (2) 8

B13 (3) Per Set 1

B14 (1) Nos 6

B14 (2) b) 400A, Double Break Nos 11B14 (3) c) 200A, Single Break for Aux. Transformer Nos 1

B15 Nos 27

B16 (1) Nos 10

B16 (2) Stations Beams 3B1 - 0.25 MT Nos 5

B17 (1) Set 8

B17 (2) 33KV Current Trasformers - 0.142 MT Set 12B17 (3) 33KV Voltage Trasformers - 0.142 MT Set 6B17 (4) 33KV Lightning Arrestors - 0.07 MT Set 12B17 (5) 33 Kv Pedestal Insulator. Support - 0.07 MT Set 9B17 (6) 11KV NCT - 0.142 MT Set 2

B18 (1) Nos 42

B18 (2) Nos 10

Testing and commissioning:1) C&R panel wiring and testing:Wiring: Identification/ferruling/crimping, termination wires in C&R panel.Testing: testing for insualtion level, testing relays, control operations for closing triping etc., interlocks alarm annociation and indication checks.

11kV Switchgear: Erection, alignment and fixing to the foundation, indoor/outdoor 11kV switchgear panel/unit including movement from the point of unloading to the point of erection:i) 11kV indoor/outdoor switch.

Per Panel

Wiring and assisting and testing and commissioning:i) 11kV indoor/outdoor switchgear

Per Panel

Testing and commissioning:Wiring: Identification of wires, ferruling tripping and termination of wire for annociation etc., testing of relays CTs PTs and breaker.i) For indoor/outdoor panel comprising of 2I+8F+1BC+1AP3

Isolators including Marshalling Box and Terminal connectors, as per technical specification with Solid Core, cylindrical post insulators : 11KV Isolators : a) Single break 400A with roaster switch.

Surge Arrestors with Surge Monitor and insulating base Metal Oxide gap less type, as per Technical Specification. 9KV class Las for 11 KV ODS/ Feeders.

33KV Station Structures with peak: Fabricated Galvanised steel structures 3T1 - 0.595MT

Mounting Structures:Mounting Structures for equipments made out of fabricated galvanised angle iron, SM Rails for transformer plinth, cable mounting structures made out of channels and angles including Bolts&Nuts, tubular pipes, as per approved drawing: 33KV Isolators - 0.24 MT

11KV ODS: 9 Mtr. Long, 145kg RCC pole for ODS8 Mtr. Long, 115kg RCC pole for Station Yard lighting Poles

Page 18: Nettur BOQ

B19 (1) Nos. 26

B19 (2) ii) 1B2 - 4.0 mtrs long-0.036 MT Nos. 20

B20 Nos. 20

B21 (1) Per Bay 15

B21 (2) Per Bay 8

B22 Set 6

B23 Set 2

B24 Nos 2

B25 Nos 2

B26 (1) Mtrs 90

B26 (2) Mtrs 50

B26 (3) Mtrs 100

Beams out of channels 100x50mm with arrangements for stringing power conductor alongwith cleats, Bolts& Nuts, painted with two coats of metal primer and aluminium paint, etc, complete: i) 1B1 - 7.45 mtrs long- .068MT

Angles 65x65x6 mm with clamps, Bolts, painted with two coats of metal primer and aluminium paint, etc, complete. i) 2.50 mtrs long for fixing 11KV GOS handle support

Bus-Bar Formation (33 KV&11KV side): Mian bu/Cross bus (all the three phases in a segment) of using Lynx/Coyote single/double conductors with fixing of insulators, spacers, leveing of string conductors to the required hieght above the equipment, including providing jumps to inter connect different segments of the main bus .

Formation of corss bus in each individual bay using falcon/Drake/Lynx/Coyote-Single/Double conductor with fixing of insulator, spacers, levelling the strung conductors to the required height above the equipment including providing jumps to inter-connect different segments of the main bus.

D.P.Structures: D.P. Structures using 9 mtrs long RCC poles with hardware consisting of double power X-arms, horizonontal cross brace, cross braces, back cleat, strain plate, bolt & nuts, painted with two coats of metal primer and aluminium paint, etc as

LTAC Panel 14 way, indoor, with fuse cutouts, volt meter, ammiter, MCCB's etc., as per specifications.

AC Distribution box single front outdoor type 6 terminal 750x1350x300mm, 2 I/C of 100 Amp MCCB 20 kA + 6 O/G MCB 16 Amp + 1 O/G of 100 Amp, HRC fuse

DC distribution panel outdoor type with 2 I/C SFU 200 Amp + 10 O/G SFU 60 Amp + 10 O/G SFU 30 Amp with relays for DC failure and DC Bus Earth Fault as per technical specifications

Power Cable LT (Armoured) as per specification & Drawing: 1.1KV PVC insulated 95 Sq.mm Aluminium Cable, 4core with glands/lugs/ferrules for Auxiliary Transformer.

1.1KV, 4 core 10 Sq.mm Copper cable with glands/lugs/ferrules.

1.1KV, 2 core 10 Sq.mm Copper cable with glands/lugs/ferrules

Page 19: Nettur BOQ

B27 (1) Mtrs 1000

B27 (2) ii) 2 Core 6 Sq.mm Mtrs 200B27 (3) iii) 19 Core 2.5 Sq.mm Mtrs 750B27 (4) iv) 10 core 2.5 Sq.mm Mtrs 250B27 (5) v) 14 core 2.5 Sq.mm. Mtrs 250

B28 (1) Mtrs 140

B28 (2) ii) 75 mm dia (outer), 2 to 2.5 mm thick Mtrs 100B28 (3) iii) 100 mm dia (outer), 2 to 2.5 mm thick Mtrs 50

B29 Set 1

B30 Set 1

B30 (1) Errection of battery charger and wiring i) 110 Volts Set 1

B30 (2) Set 1

B31 (1) Nos 10

Control Cable(Armoured) with Accessories: (With glands/lugs/ferruels): i) 4 Core 6 Sq.mm

Providing, laying and jointing PVC pipes conforming to IS 4085-1960 and approved makes with necessary specials such as collars, bends, elbows, Tee, Nipples, plugs etc., complete, whereever necessary as per the directions of the Field Engineer: i) 63 mm dia (outer), 2 to 2.5 mm thick

Auxiliary transformer with oil, outdoor type 63KVA, 11KV/440V, 3Ph, 9mtr RCC 145 kg W/L poles DOLO/HG-fuse Unit, L.T. protection Kit, Distribution Box and other accessories including testing and commissioning as per specification.

Station Battery (Tubular type) & Battery Charger: 110V, 100AH Battery set consisting of 55 Nos. Cells with float cum boost battery charger working on 230V single phase AC supply along with integral DCDB consisting of 4 Nos O/G feeders as per specification. Installing, assembling,filling of acid, wiring, test-charging andcharging battery set. i) 110 Volts

ii) Testing of out put Dc Voltage in boost/Float/Tricle/Variations as per the order/requirment iii) Testing for Ripple factor Commissioning: i) Fixing of Boost Voltage level ii) Fixing of Float Voltage level iii) Fixing of Trickle Voltage level Station yard lighting (outdoor): including Civil works complete: Supply of high pressure sodium vappor street light deep drawn aluminium canopy fuly cost with aluminium housing for control gear finished stove enemal gray golssy white conopy interrior wiht a pair of anodisied reflectors clear acrylic bowl gasket linni

Page 20: Nettur BOQ

B31 (1) Nos 10

B31 (2) Nos 10

B31 (3) 2 core , 6 Sq. mm, 1.1KV class armoured Al. Cable Mtrs 325

B31 (4) Nos. 10

Total

Supply of 32 mm dia class-A GI pipe bracket upto 2.7 mtrs long with reducing collar of 50 X 40 mm to which an extension of 250 mm pipe piece is fixed for 250 watts SV street light fittings using suitable clamps , blots and nuts and wiring suitable capacit

Supplying Iron Clad DP 15 to 20 Amps with rewireable fuse Havels standards

Arial teak wood fuse board of size 300x150x12 mm with clamps and screws

Page 21: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

5b

Errection Portion:

TALUKA IN Bidar

Total in Rs.

Inclusive of Work Contract Tax

Page 22: Nettur BOQ
Page 23: Nettur BOQ
Page 24: Nettur BOQ
Page 25: Nettur BOQ
Page 26: Nettur BOQ
Page 27: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

Sl. No. PARTICULARS Unit

1 2 3 4 5aCivil Portion:

C1 (1) CMT 500

C1 (2) CMT 500

C2 CMT 50

C3 (1) Nos 10

C3 (2) 33 KV CT support structure Nos 12C3 (3) 33 KV surge arrestor support structure Nos 12C3 (4) 33 KV pedestal insulator support structure Nos 9C3 (5) 33KV isolator support structure Nos 8C3 (6) 33 KV Voltage transformer support structure Nos 6C3 (7) RCC poles 9m long Nos 42C3 (8) 11 KV NCT support structure Nos 2C3 (9) DP structure for auxiallary transformer Nos 1C3 (10) 8 mts RCC poles for yard lighting Nos 10C3 (11) capacitor bank Nos 2

Price Sheet for ESTABLISHING 2X5MVA, 33/11KV SUB-STATION AT Nittur (B) IN Bhalki TALUKA IN Bidar DISTRICT (Civil Portion of Station)

Qty.to be supplied &

erected

Unit Charges

in Rs.Inclusive of Service Tax/VAT on WC

Site levelling and construction of retaining wall: Yard levelling: Levelling the yard to required R.L including cutting and transporting the excavated stuff to the place shown in for all types of soil and strata and filling the same wherever required including all lead, lift and labour etc.,complete.

Levelling the yard to required R.L by filling with approved gravel/murrum with all lead and lifts transporting to site including cost of all material spreading compacting charges , labour etc., complete

Retaining wall :Construction of size stone masonry retaining wall in cement mortar (1:6) including cost of excavation and providing bed concrete (1:4:8) and pointing to the exposed faces with cement mortar (1:3) and providing weep holes with PVC pipes as per enclosed typical drawing and technical specification including cost of all material and labour etc., complete.

Foundation:Engineering supply of all labours, materials and construction of RCC Footings of any depth, pedestals including the cost of Excavation, Concreting , Cement, Reinforcement steel for all the works, Grouting, under pinning etc., for the following station towers and mounitng structures: Tower 33 KV ( vertical 3T1)

Page 28: Nettur BOQ

C4 (1) Rmt 50

C4 (2) Rmt 20

C4 (3) Rmt 40

C5 (1) Rmt 75

C5 (2) Rmt 75

C6 Nos. 14

C7 Nos. 2

Cable trenches including road crossing: RCC Cable duct: Providing and constructing RCC cable ducts using cement concrete M-20 grade concrete and steel reinforecement including cost of excavation, providing bed concrete( 1:4:8) cable tray supports and cable trays etc., complete as per technical specification enclosed drawing etc., including cost of all materials, labour,etc., complete. i] 'A' type duct ( 0.45mx0.75m)

ii] 'B' type duct ( 0.60mx1.00m)iii] 'C' type duct ( 0.90mx1.40m)

Hume Cable ducts: i] Providing and Laying RCC Hume pipe sub ducts using NP 2 class 150 mm dia Hume pipe including cost of Excavation, laying charges and back filling wherever required as per technical specification and enclosed drawings including cost of all materials, labour, etc., complete.

Hume Cable ducts: ii] Providing and Laying RCC Hume pipe sub ducts using NP 2 class 300 mm dia Hume pipe including cost of Excavation, laying charges and back filling wherever required as per technical specification and enclosed drawings including cost of all materials, labour, etc., complete.

Brick Masonry inspection chambers: Providing and constructing Brick masonary inspection chambers of size 600x600mm and 600mm depth wherever required as per enclosed drawing and technical specifications including earth work excavation, bed concrete (1:4:8), construction of BBM walls plastering to exposed faces, providing cast iron cover for chamber including cost of all materials, labour, etc., complete.

Cable duct road Crossing: Providing and constructing RCC cable ducts road crossing using cement concrete M-20 grade concrete and steel reinforcement including cost of excavation cable tray supports and cable trays etc., complete as per technical specification enclosed drawing etc., including cost of all materials, labour,etc., complete.

Page 29: Nettur BOQ

C8 (1) Smtr 2250

C8 (2) Smtr 2200

C9 Nos 2

C10 Nos 1

C11 Nos 4

Antiweed Treatment : Providing and supplying all labour material equipments etc. required for soil sterilization, antiweed treatment including excavation, mixing / injecting chemicals to achieve the guaranteed effectiveness of treatment at least up to three years, rolling, dressing, compacting the excavated earth within substation areas as per technical specification.

Site surfacing (Jelly spreding) :Providing laying two layers of hard broken crushed metal/ jelly (granite/basalt/trap) as per the instruction of egineer incharge and layout of station yard. The first layer of jelly shall be of 20mm size spread and consolidated to a thickness of 50mm rolled as per specification achieve the surface suitable for spreading second layer of jelly. The second layer shall be of 25mm jelly spread to uniform thickness of 50mm course of layer including cost all materials and labour charges the jelly used shall be free from dirt or organic material.

Transformer foundation and associated rail track: Design engineering supply of labours, materials and construction of tranformer foundations by providing all associted works rail tracks,jacking pads,anchor blocks RCC,PCC,Structural steel including MS grouting, gravel filling pylon support system and other items not mentioned here in but required for the completion of the work.

63 KVA,11KV/433 VLT distribution transformer:Design engineering supply of labours, materials and construction of tranformer plat form of size 1.50mx1.50mx2.00m above FGL and 1.20mx1.20mx1.0m below FGL in size stone masonry (1:6) including excavation laying coping concrete 1:2:4 and pointing exposed faces in CM 1:3 etc, complete.

SF6 circuit breaker foundation: Design engineering supply of labours, materials and construction of 33KV SF6 circuit breaker foundation by providing all associted works RCC,PCC, steel reinforcement including MS grouting, gravel filling and other items not mentioned herein but required for the completion of the work.

Page 30: Nettur BOQ

C12 Set 2

C13 Rmtr 220

C14 Unit 1

C15 Rmtr 150

C16 (1) Rmtr 210

C16 (2) No 1

Foundation for porcilain clad 11KV VCB switch gear outdoor type: 350MVA each with 1IC+4F+1CB+1AP3 PCVCB as per approved design engineering supply of labours, materials and construction of foundation by providing all associted works RCC,PCC ,steel reinforcement including MS grouting, gravel filling and other items not mentioned here in but required for the completion of the work.

Security fencing with entrance gate: Providing and constrution security fencing for the switch yard using RCC fencing poles and chain link mesh as per enclosed drawing and techincal specification including cost of Labour charge complete.

Control Room Building : Design, engineering and construction of Control Room building(framed structure) including necessary treatement to sub soil if necessary depending upon the soil condition including providing internal water supply arrangements, electrification to the control room building providing sanitary arrangements and internal cable ducts with cost of all materials, labour, etc., complete.

Road Works : Formation of approach road: Providing 5 mtr wide cement concrete road using M-20 grade concrete and steel reinforecement including cost of excavation, providing bed concrete( 1:4:8) walk ways, fixing RCC kerb stones, as per technical specification, layout and sectional detailed drawing etc., complete in all respect.

Storm Drainage System : Storm water drainage system: Providing and construcution of storm water drains using SSM in cement mortar 1:6 including earth work excavation, bed concrete (1:4:8) with pointing to the exposed faces all along the approach road as per the technical specification and enclosed drawings including cost of all materials, labour etc., complete.

Culverts across approach Road: Providing and constructing RCC hume pipe culvert using 750mm dia NP- 3 class pipe,(two rows ) with RCC wing walls of M-20 ( 1:1.5:3) grade concrete including earth work excavation, bed concrete (1:4:8) plastering to exposed faces with cement mortar (1:4) 12 mm thick as per technical specification and enclosed drawing.

Page 31: Nettur BOQ

C17 Unit 1

C18 No 1

C19 (1) Cum 565

C19 (2) Rmtr 1312

C19 (3) Rmtr 1350

C19 (4) Nos 41

C19 (5) Sodium bentonite clay Kgs 17100Total

Water Supply : Providing water supply for the substation including drinking water and water for fire fighting system and earthing pits with borewell, sinking and erection of submersible pump set and drawing pipe line from bore well to over head Sinthetic tank and providing distribution system inside the station yard servicing the pump set etc., complete.

Construction of Baffle Wall as per design drawing & specification

Earth mat formation: Excavation formation,refilling (earthmat design area 60mx50m is considered with 5m spacing between the adjacent earth flats approximately as per MS flat annexure) However during the execution,actual earthmat design has to be obtained from SEE R&D KPTCL by the Turnkey Agency only.

Earth mat formation: Supplying and laying of 50x6mm MS flat, welding applying ACB paint to welded portion and covering with sodium bentonite clay, should be provided as per the drawing standard specifications and consolidated .

Earth mat formation: Grounding of equipments with 50x6mm GI flat, and connecting equipment to the earthmat/ground pit. Each point of earhing with all formation of works like bending ,twisting, drilling of holes and connecting by welding ( inclusive of all T&P and consumables) to the earthmat/ground pit point of connection.

Cast Iron pipes electrode of 100mm internal dia,13mm thick 2.75m long including RCC collars of 450mm height and 450 dia and 2 inch thick.

Page 32: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

Total in Rs.

5b

Price Sheet for ESTABLISHING 2X5MVA, 33/11KV SUB-STATION AT Nittur (B) IN Bhalki TALUKA IN Bidar

Inclusive of Service Tax/VAT on WC

Page 33: Nettur BOQ
Page 34: Nettur BOQ
Page 35: Nettur BOQ
Page 36: Nettur BOQ
Page 37: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

LINE SUPPLY PORTION:

Sl. No. PARTICULARS Unit Qty Unit Rate

D1 9.5 Mtrs long RCC Poles 145kgs working load Nos 250 1800

D2 Nos 10 1600

D3 2 Pin LT cross arms for street pole bolt nut Nos 20

D4 Set 216

D5 Set 16

D6 33kV single top support nuts bolts washers etc. Nos 216D7 RCC DP Structure (Excluding poles) Set 24D8 RCC TP Structure (Excluding poles) Set 9D9 33kV Pin Insulators with pins Nos 783D10 Disc insulators 90KN Nos 486D11 Guy Sets( Including 2 DP's) Set 180D12 Coyote ACSR Conductor with 1.5% sag Km 36.45

D13 Nos 162

D14 PG Clamps for Coyote ACSR Nos 165D15 M.S.C. Joints for coyote ACSR Nos 30D16 Spiral Earth Electrode Nos 216D17 G.I Pipe Earthing for DP Structure Nos 24

D18 Set 243

D19 Set 259

D20 Phase Plates R Y B (Set of 3) color Nos 14

D21 Set 6

Total

Construction of 12 KMS OF 33KV single circuit line tapped from existing 33KV Bhalki-Halbarga line to THE PROPOSED 33/11KV Sub Station at Nittur (B) ON TOTAL TURNKEY BASIS including supply of all equipments/materials, erection (including Civil works), testing and commissioning. (Supply portion)

9 Mtrs long RCC Poles 145kgs working load as stud poles

Horizontal/V-Shape Cross arms with Clamps, Bolts, nuts and washers

33kV special 3pin X arms(3mtr long) with bolts and nuts etc

Single tention clamps with arcing horns for Coyote ACSR

Danger Boards with Pole Clamps, Nut bolts, Washers etc. complete

Number Plates with Pole Clamps, Nuts bolts, Washers etc. Complete

Guarding set complete for Road/P&T/HT/LT line crossing includes guarding cross lacing and its cross arms etcs.

Page 38: Nettur BOQ

LINE SUPPLY PORTION:

Vendor450000

16000

0

steel

0

0

0000

oblum000

0

0000

0

0

0

0

Construction of 12 KMS OF 33KV single circuit line tapped from existing 33KV Bhalki-Halbarga line to THE PROPOSED 33/11KV Sub Station at Nittur (B) ON TOTAL TURNKEY BASIS including supply of all equipments/materials, erection

Total Amount

Versatile / manchukonda

Page 39: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

Sl. No. PARTICULARS Unit

1 2 3 4 5aErection Portion:

E1 9.5 Mtrs long RCC Poles 145kgs working load Nos 250 1000

E2 Nos 10 800

E3 2 Pin LT cross arms for street pole bolt nut Nos 20 100

E4 Set 216 100

E5 Set 16 250

E6 33kV single top support nuts bolts washers etc. Nos 216 50E7 RCC DP Structure (Excluding poles) Set 24 5000E8 RCCTDP Structure (Excluding poles) Set 9 7000E9 Guy Sets( Including 2 DP's) Set 180 500

E10 Coyote ACSR Conductor with 1.5% sag Km 36.45 10000E11 Spiral Earth Electrode Nos 216 200E12 G.I Pipe Earthing for DP Structure Nos 24 300

E13 Set 243 50

E14 Set 259 50

E15 Phase Plates R Y B (Set of 3) color Nos 14 100

E16 Nos 30

E17 Rmtr 2000 100

E18 Set 6

E19 Km 12 10000

E20 Km 12 2000

Construction of 12 KMS OF 33KV single circuit line tapped from existing 33KV Bhalki-Halbarga line to THE PROPOSED 33/11KV Sub Station at Nittur (B) ON TOTAL TURNKEY BASIS including supply of all equipments/materials, erection (including Civil works), testing and commissioning. (Errection portion)

Qty.to be supplied &

erected

Unit rate including WCT (in

Rs.)

9 Mtrs long RCC Poles 145kgs working load as stud poles

Horizontal/V-Shape Cross arms with Clamps, Bolts, nuts and washers

33kV special 3pin X arms(3mtr long) with bolts and nuts etc

Danger Boards with Pole Clamps, Nut bolts, Washers etc. complete

Number Plates with Pole Clamps, Nuts bolts, Washers etc. Complete

Supplying and grounding at cut points and at Gurding poles using 3m long 2.5mm thick, 40mm dia GI pipe with 50x6mmGI flat of 3mtr length , salt, Charcoal, nutbolt etc., complete including cost of all material.

Supplying and fixing Anti-climbing Devices as per specification of 10RMtr per pole

Guarding set complete for Road/P&T/HT/LT line crossing includes guarding cross lacing and its cross arms etcs.

Check Survey By using their own equipments for Plain Terrain

Clearing of bushes, branches of tree & Crops for erection of tower & stringing of lines for full corridor with.(In thin jungle)

Page 40: Nettur BOQ

E21 CMT 173 300

E22 CMT 278

E23 CMT 170 150

E24 CMT 12

Total

Excavation of pits of size 0.75Lx0.60Bx1.6Depth for erection of 9.5mtr RCC poles, pits of size 0.9x0.75x2m for erection of 12mtr long MS I-beams and pits of size 0.75Lx0.5Bx1.2D for stud poles for Soft rock by blasting/DFR including as per direct

Concreting 1:4:8 & Curing including the cost of Materials with exposed portions of to be Plastered (i) 9.5 mtrs RCC poles (0.75Lx0.60Bx1.6H), (ii) MS I-beams (0.9x0.75x2), (iii) 9mtr. Stud Poles (0.75Lx0.5Bx1.2H) & (iv) Guys (0.8Lx0.5Bx0.8H).

Excavation of pits of size 0.8Lx0.50Bx1.5Depth for Guy Sets for Hard Soil/DFR as per directions of field Engineer.

Concreting 1:1½:3 & Curing including the cost of Materials with exposed portions of to be Plastered for Coping of 9.5 mtrs RCC poles (0.5Lx0.5Bx0.3H)

Page 41: Nettur BOQ

GULBARGA ELECTRICITY SUPPLY COMPANY LIMITED

5b=5a*4

250000

8000

2000

21600

4000

108001200006300090000

364500432007200

12150

12950

1400

0

200000

0

120000

24000

Construction of 12 KMS OF 33KV single circuit line tapped from existing 33KV Bhalki-Halbarga line to THE PROPOSED 33/11KV Sub Station at Nittur (B) ON TOTAL TURNKEY BASIS including supply of all equipments/materials, erection (including Civil works), testing and commissioning. (Errection portion)

Total Price with tax

Page 42: Nettur BOQ

51900

0

25500

0

1432200