RECEIVING SUBSTATION
(2 NOS)
33kV HT SUPPLY FROM- BEST CONVERSION FROM 33kV
TO 11kV
DISTRIBUTION SUBSTATION
(8 NOS)
CONVERSION FROM 11kV
TO 415V
LT PANEL
ENERGY METER FOR MEASUREMENT OF
POWER CONSUMPTION
BUS BAR SYSTEM
FLAT DB
COMMON AREA PANEL
LT PANEL
METERING PANEL
TYPICAL FOR RESIDENTIAL TOWER
FOR COMMERCIAL AND CLUBHOUSE
RSS 1LOC-T6 GR
FLOOR
DSS 411/0.415kV
DSS 311/0.415kV
DSS 211/0.415kV
DSS 111/0.415kV
TRANSFORMER YARDLOC-RG AREA2*20MVA TRANSFORMERS33/11KV RATING
LOC-TOWER2 GR FLOORTx-7*1600kVA (T1-3*1600kVA +T2-3*1600kVA +SPARE-1*1600kVA)
LOC-TOWER4 GR FLOORTx-8*1600kVA (T4-3*1600kVA +T3-3*1600kVA +BASEMENT AND INFRA-2*1600kVA)
LOC-TOWER6 GR FLOORTx-8*1600kVA (T5-3*1600kVA +T6-3*1600kVA +BASEMENT AND INFRA-2*1600kVA)
LOC-TOWER8 GR FLOORTx-10*1600kVA (T7-3*1600kVA +T8-3*1600kVA +T9-3*1600kVA +T10-1*1600kVA)
DISTRIBUTION FROM RSS1
RSS 2LOC-T10 GR
FLOOR
DSS 811/0.415kV
DSS 711/0.415kV
DSS 611/0.415kV
DSS 511/0.415kV
TRANSFORMER YARDLOC-RG AREA2*20MVA TRANSFORMERS33/11KV RATING
LOC-TOWER10 GR FLOORTx-2*1600kVA (T10-2*1600kVA)
LOC-COMMERCIAL TOWERTx-4*2500kVA
LOC-CLUB HOUSE(NORTH)Tx-4*1600kVA (T11-3*1600kVA +BASEMENT/INFRA/CH-1*1600kVA)
LOC-CLUB HOUSE(SOUTH)Tx-5*1600kVA (T12-3*1600kVA +BASEMENT/INFRA/CH-1*1600kVA +SPARE-1*1600kVA)
DISTRIBUTION FROM RSS2
TOWER 4
TRANSFORMER 1
TRANSFORMER 2 TRANSFORMER 7
TRANSROMER 5
1600 KVA 11/415 V
DRY TYPE TX 1600 KVA 11/415 V
DRY TYPE TX
1600 KVA 11/415 V
DRY TYPE TX
1600 KVA 11/415 V
DRY TYPE TX
2500A BUS RISER 1FROM 2ND-17TH FLRC.L-2748.63KWD.L-879.56KW
FEEDER PILLAR 1
2000A BUS RISER 2FRM 18TH -31ST FLRC.L-2421.70KWD.L-774.9KW
COMMON AREA METERING PANEL T3SPARE
FEEDER PILLAR 4
1600A BUS RISER 3FRM 32ND -46TH FLRC.L-2354.4KWD.L-753.41KW
BASEMENT AND RG LOADS
SPARE
FEEDER PILLAR 2
1600A BUS RISER 4FRM 47TH -53RD FLRC.L-1598.90KWD.L-511.65KWMETERING PANEL(T3 &T4 DUPLEXES)
SPARE
POWER FLOW FROM T4
TOWER 3
TRANSFORMER 8
TRANSFORMER 6 TRANSFORMER 4
TRANSROMER 3
1600 KVA 11/415 V
DRY TYPE TX 1600 KVA 11/415 V
DRY TYPE TX
1600 KVA 11/415 V
DRY TYPE TX
1600 KVA 11/415 V
DRY TYPE TX
SPARE
2500A BUS RISER 2FRM 14TH -27TH FLRC.L-2670.33KWD.L-854.51KW
2500A BUS RISER 3FRM 28TH -40TH FLRC.L-2674.45KWD.L-855.82KW
FEEDER PILLAR 3
COMMON AREA METERING PANEL T4
2500A BUS RISER 4FRM 41ST -53RD FLRC.L-2648.33KWD.L-847.47KW
2500A BUS RISER 1FRM 2ND -13TH FLRC.L-2736.26KWD.L-875.6KW
POWER FLOW FROM T3
BUS BAR SYSTEM
Power from utility meter is brought to each floor by means of bus duct or bus risers.•Advantages of bus bar system over normal cabling system are as follows: Saving in space and cost.Increased flexibility in designGreater safetyEasy estimation of costEase for accessing powerNo overheating and fire protectionHighly efficient and reliableEasier maintenance
BOOSTERPUMP PANEL
@ 55th FLR
1000AACB EDO
1000AACBEDO
630 KVA 630 KVA
4C*300 SQ.MM
BUS COUPLER
800AACB EDO
800AACB EDO
800AACB EDO
800AACB EDO
MDBCOMMON
AREAT4
1ST FLR
800A ATS
NORMAL SUPPLY FROM BEST
FIRE PANEL T4
32ND FLR
800A ATS
FIRE PANEL T3
32ND FLR
MDBCOMMON
AREAT3
1ST FLR
DG PANELC.L-721.73KWD.L-243.34KW
DG 1 DG 2DG SET POWER DISTRIBUTION SCHEME
C.L-808.67KWD.L-295.03KW
C.L-457.55KWD.L-344.3KW
FIRE PANELHYDRANT PUMPSPRINKLER PUMPJOCKY PUMPSTANDBY PUMPEXHAUST FANBOOSTER PUMP FOR GRND TO 32ND FLR
NORMAL SUPPLY FROM BEST
COMMON AREA
METER T4
FROM BEST
800AACB EDO
800AACB EDO
E/M
BUS COUPLER
200AMCCB
CT200/5A
WATERBODIESLIGHTING PANEL
250AMCCB
CT250/5A
NORMAL ELEVATORPANEL
FOR LIFTS 4-9@ GRND FLR
63AMCCB
160AMCCB
250AMCCB
CT63/5A
CT160/5A
CT250/5A
HPSPANEL
@ 54TH FLR
FIRE EMERGENCY ELEVATOR
PANEL@GRND FLR
EMERGENCY LIGHTING &VENTILATION
PANEL @ GRND FLR
FROM DG PANEL
HPS PANEL• DOMESTIC HYDRO SYSTEM• FLUSHING HYDRO SYSTEM• EXHAUST FAN
EMERGENCY LIGHTING &VENTILATION PANELEMERGENCY LIGHTING PANELVENTILATION PANEL AT 1ST &55TH FLR• DG AREA EXHAUST FAN• LT PANEL EXHAUST AIR FAN• PRESSURIZATION FAN
MDB COMMON AREA@ 1ST FLR