As per National Crime Records Bureau of India, around 15 people die every day due to electrical accidents ( Almost 3% total accident deaths) NFPA, USA studies reveal electricity to be the ignition source for 22% of total fires. ADVANCED ELECTRICAL SAFETY AUDIT For Manufacturing plants, Hotels, Hospitals, Hazardous installations and Commercial buildings…

Upload: somashekar-ag

Post on 12-Jan-2017

43 views

Category:

Documents


1 download

TRANSCRIPT

As per National Crime Records Bureau of India, around 15 people die every day due to electrical accidents ( Almost 3% total accident deaths) NFPA, USA studies reveal

electricity to be the ignition source for 22% of total fires.

ADVANCED ELECTRICAL SAFETY AUDIT For Manufacturing plants, Hotels, Hospitals, Hazardous installations and

Commercial buildings…

Fire hazards in India

On an average, in India, every year, about 25,000 persons die due to

fires and related causes. Female accounts for about 66% of those

killed in fire accidents. It is estimated that about 42 females and 21

males die every day in India due to fire. According to the statistics

released by the National Crime Records Bureau, fire accounts for

about 5.9% (23,281) of the total deaths reported due to natural and

un-natural causes during the year 2012. Probably many of these

deaths could have been prevented, had we taken enough fire

protection measures.

No comprehensive data is available in India on the economic losses

suffered on account of fires. However, according to one estimate the

major losses reported by the Indian Insurance Companies in the year

2007-2008 indicate, that about 45% of the claims are due to fire

losses. According to another estimate about Rs. 1000 crores are lost

every year due to fire. Fire losses are reported both in industrial and

non-industrial premises like hospitals, commercial complexes,

educational institutions, assembly halls, hotels, residential buildings,

etc… According to Fire Risk Survey (FRS) 2013, carried out by

Pinkerton & Federation of Indian Chambers and Industry, in India, fire

accounted for 8.45% of the overall ranking of risks. FRS also revealed

that fires has been rated as the 5th highest risk in industry in 2013.

The above survey also revealed that in industry wise risk ranking, fire

take 2nd place in hospitality, 4th place in IT/ITES, Manufacturing,

Security Service Providers and 6th place in infrastructure. As far as

the leading cause for the fire is concerned, according to the survey,

the electric defaults are regarded as the major cause of fires. In

Mumbai about 75% of fire-related incidents occur because of

short circuit caused by loose wiring.

The survey also point out that during the period 2009-2012, Mumbai

fire department had attended 13,185 incidents of fire out of which

9711 were caused due to defective electric circuit. The scenario for

other major cities are also not different.

Advanced Electrical Safety Audit

Advanced Electrical Safety Audit – First one of its kind in India, helps you to identify anomalies in Electrical installations which may lead to fire hazards, electric shocks, damage to equipments and lead to breakdown and production loss.

Advanced Electrical Safety Audit

Expert electrical scanning using Infrared thermography helps to identify hidden risk of fire, looseness or improper termination, improper crimping, inadequate earthing, thermal effects of harmonics, under rated or poor quality gadgets and accessories and many other issues which may lead to fire hazards, breakdown and energy wastage.

Electrical audit as per IEE / NEC standards helps to identify lapses in the electrical system and assures standard operation and maintenance . This would comply all local / Govt. standard practices and procedures to maintain an electrical system . Essential to protect human life and assets !

Audit start 14-Dec-12

High - Needs urgent attention Medium/Low - To be corrected during planned shutdown Audit end 18-Dec-12

S.N. Image

No

Severity Action Points Responsibility Completion

date

Status Remarks

6 IR 4291 High

Chiller plant - Secondary Pump No. 1 Power contactor outgoing

R phase cable improper crimping, needs

correction at the earliest. Y phase contact also to be checked

for any loose connection

Not Started

7 IR 4293 High

Chiller plant - Condenser water Pump 1 - Y phase cable loose

connection at delta contactor, improper contact

area of OLR/ Line relay connection. Needs urgent repairs

Not Started

8 IR 4297 High

Chiller plant - Secondary Pump No.2 Starter compartment - Y

phase cable at power contactor needs re crimping.

Contactor power wiring conductor size may be improved

reducing losses and to improve reliability

Not Started

10 IR 4301 HighSecondary Pump 1- Cable termination - 3 nos power cables

improper crimping - Needs re crimpingNot Started

11 IR 4303 High

Cooling tower fan # 1 starter panel. Power contactor looping

wire size may be increased to reduce energy loss

and check tightness of termination

Not Started

12 IR 4307 High

Chiller # 3 Cable termination - Y phase cable termination may

be recrimped to improve reliability during

continuous loading. Recommended to increase cable

conductor rating to reduce energy losses

Not Started

13 IR 4309 HighChiller # 3 Rear cable termination - Loose connection at R & Y

phases, needs immediate repairNot Started

14 IR 4311 HighHTP Blower motor temperature profile. Belt-Pulley alignment to

be checkedNot Started

15 IR 4313 HighSTP Plant Main incomer MCCB - Y & B phase cable termination,

loose connection to be repairedNot Started

16 IR 4314 High

STP - OL 20 panel - Highlighted power contactor to be

inspected for any loose connection. Panel cable dressing

to be improved and avoid usage of temperory connections to

improve fire safety

Not Started

17 IR 4317 High

STP - B2 Exhaust fan starter panel - OLR outgoing cable

termination to be checked for any loose connection.

Power contactor termination ( bottom) also needs check up.

Power & control wiring to be dressed properly and

unwanted Fuse switch to be removed

Not Started

18 IR 4319 High

Irrigation pump Electrical panel - Temperature profile. Power

contactor coil connections may be checked for any

loose connection

Not Started

19 IR 4321 High

Boiler control panel - Boiler # 2 Loose connection at connector,

replace B phase connection and re terminate

cable

Not Started

25 IR 4339 High UPS - Loose connection at Y 4 MCB termination. Needs repairs Not Started

26 IR 4347 High

Upper basement - B 1 NGA - Incomer cable termination - Loose

connection at Y phase cable termination, needs

immediate check up and repair

Not Started

27 IR 4349 High

Upper basement B1 NGA MCC Incomer - B phase busbar -

suspected abnormality in the cable alle, check

incomer cable termination for loose connection / improper

crimping

Not Started

Thermal Imaging Audit - Trident Hotel BKC

Severity rating

Intuitive report structure ! Crystal clear analysis and reporting as per NETA / FPA / Electrical Inspectorate standards ! Effective tracking and review methodology etc adds value to your maintenance management programme and ensures results.

Training, Coaching and Mentoring to Maintenance management team for improving skills and knowledge and to strengthen systematic electrical maintenance management activities . This assures healthiness of electrical equipments and prevents hazards due to fire and electric shock.

Benefits ? Electrical Safety Audit is examining the safety of electrical installations

of any industrial unit or organization. Electrical Safety Audit is performed

by enquiry, inspection, testing and verification. Electrical Safety Audits

are conducted by experienced professionals who assist clients in

reducing risk and help to ensure compliance with applicable Safety

Standards and Regulations

Electrical Safety Audits helps in identifying:

Electrical hazards to minimize the risk of accidents like fire due to loose

connection to short-circuiting, Areas of risk or vulnerability in electrical

systems and installations, on-compliance with the legislation and best

practices.

NO MORE FIRE RISKS

REDUCED ENERGY WASTAGE

IMPROVED ELECTRICAL SAFETY

IMPROVED LIFE OF EQUIPMENTS

IMPROVED PLANT O.E.E

IMPROVED MORALE

Infrared Thermal imaging scanning

[email protected]

Want to know more details or need a quick quote ? Please share your connected load details to

Every precaution has been taken to ensure this publication is accurate and up to date on the date it is printed. As part of its ongoing services improvement policy. Sustenergy Foundation reserves the right to modify specifications and contents at any time. The reproduction in any format and by any means of all or