EXISTING COMM VAULT, RUN 3 - 4" CONDUITS
FROM VAULT TO NEW IT ROOM. PROPERLY
SEAL CONDUITS WHERE THEY ENTER VAULT.
3"ø
T-14"ø
4" CONDUIT WITH (3) 1" INNERDUCTS, ONE
OF WHICH CONTAINS A 12 STRAND SINGLE
MODE FIBER OPTIC CABLE
4" CONDUIT WITH (3) 1" INNERDUCTS,
ONE OF WHICH CONTAINS A 25-PAIR
CATEGORY 6 COPPER CABLE
1 - 4" SPARE WITH PULL STRING
2" STUBBED OUT INTO THE
LANDSCAPE AREA FOR
IRRIGATION CONTROL CABLES2"ø
MTS
EH11
T3EL11
ELECTRICAL FIXTURE LEGEND
DUPLEX RECEPTACLE, TYPE AS SCHEDULEDR1
MAIN GROUND BUSSMGBB
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
GROUND ROD WITH GROUND WELL
GROUND ROD
EPO EMERGENCY POWER OFF
GR
GW
ICE SENSORIS
SS SNOW SENSOR
PIN AND SLEEVE 200 AMP RECEPTACLE
JUNCTION BOX FOR WIRING OF INDICATED
EQUIPMENT
Sto THERMAL OVERLOAD SWITCH, REQUIRED FOR
ALL 120 VOLT MOTORS AND EQUIPMENT UNLESS
NOTED OTHERWISE.
ELECTRIC EQUIPMENT LEGENDFUSED DISCONNECT SWITCH (DISCONNECT SWITCH,
COUNT OF TYPE, H=480 VOLT L=208 VOLT, AMPS- 3=
30, 6=60, 1=100, 2=200). EC TO PROVIDE THE
CORRECT FUSES FOR THE EQUPMENT, PANELS, ETC.
CONNECTED.
MANUAL TRANSFER SWITCH
ELECTRIC METER
T2 DRY STEP DOWN TRANSFORMER
PANELBOARD 480 VOLT
SWITCHBOARDSB
THERMAL OVERLOAD SWITCH
MTS
D1H1
D4L2
HP
LP PANELBOARD 208 VOLT
T-1UTILITY TRANSFORMER, 277/480 VOLT,
3 PHASE, 4 WIRE
MS*SHUNT TRIP BREAKER, SIZE AND VOLTAGE
AS SCHEDULED
JUNCTION BOX FOR WIRING OF INDICATED
EQUIPMENT
UPS UNINTERRUPTIBLE POWER SOURCE EQUIPMENT
CIRCUITS LEGENDLINE WITH HOOK INDICATES GROUND WIRE
LONG LINE INDICATES HOT WIRE
SHORT WIRE INDICATES NEUTRAL WIRE
INDICATES WIRE IN CONDUIT WITH NUMBER OF
GROUNDS, NEUTRALS AND HOTS AS SHOWN,
# 12 WIRE IN 3/4" UNLESS NOTED OTHERWISE
ON THE SCHEDULES OR ON THE PLANS
INDICATES HOME RUN CIRCUIT TO PANEL,
PANEL NAME AND CIRCUIT NUMBER(S) ARE
INDICATED
LP11-1
NOTE: ISOLATED GROUND CIRCUITS ARE REQUIRED
IN THIS PROJECT. THESE ARE INDICATED ON
THE PLANS. IN GENERAL THOSE RECEPTACLE
CIRCUITS TO PANEL LP13, LP21 AND LP11 AND
FEEDER FROM TRANSFORMER T2 TO LP11.
1' - 6"
NUMBER OF CONDUITS
AS SHOWN ON THE
PLANS
CONDUIT MARKER
TOPPING AS INDICATED
BACKFILL
0' -
6"
1' -
6"
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-100
ELECTRICAL SITE PLAN, ELECTRICAL EQUIPMENT,
CIRCUIT AND ELECTRICAL FIXTURE LEGEND,
TRENCHING DETAIL
1/16" = 1'-0"1
ELECTRICAL SITE PLAN
Sheet List
SheetNumber Sheet Name
E-100 ELECTRICAL SITE PLAN, ELECTRICAL EQUIPMENT, CIRCUIT AND ELECTRICAL FIXTURE LEGEND, TRENCHING DETAIL
E-101 LIGHTING SITE PLAN AND TYPE P INSTALLATION DETAIL
E-200 FIRST FLOOR LIGHTING PLAN, LIGHT FIXTURE AND LIGHTING DEVICE SCHEDULE
E-201 SECOND FLOOR LIGHTING PLAN. LIGHTING LEGEND, DIMMING SYSTEM AND WARNING LIGHT DETAILS
E-202 FIRST FLOOR POWER PLAN AND SWITHBOARD SB1 SCHEDULE
E-203 SECOND FLOOR POWER PLAN, SWITCHBOARD SCHEDULE SB2, ELEVATOR EQUIPMENT ROOM AND GROUND BUSS DETAIL
E-204 ELECTRICAL EQUIPMENT SCHEDULE
E-205 ELECTRICAL ONE LINE AND ELECTRICAL FEEDER SCHEDULE
E-206 GROUNDING ONELINE & GROUNDING ONELINE FOR SEPARATELY DERIVED SYSTEMS, HP11 PANEL SCHEDULE, BRANCH CIRCUITS LARGER THAN # 12
E-207 FIRST FLOOR HVAC POWER PLAN AND MECHANICAL EQUIPMENT SCHEDULE
E-208 SECOND FLOOR HVAC POWER PLAN
E-300 LIGHTNING PROTECTION PLAN GROUND LEVEL
E-301 LIGHTNING PROTECTION ROOF PLAN, OBSTRUCTION LIGHTS INFORMATION AND LIGHTNING PROTECTION 3D
E-302 GUTTER HEATER ROOF PLAN
E-500 FIRST AND SECOND FLOOR SECURITY PLAN, SECURITY DEVICE SCHEDULE AND SECURITY LEGEND
E-501 SECURITY SYSTEM INSTALLATION DETAILS
E-600 FIRST FLOOR TELE/DATA FLOOR PLAN, DATA DEVICE, CABLE TRAY & UNDER FLOOR RACEWAY SCHEDULES, TELE/DATA & CABLE TRAY & UNDER FLOOR RACEWAY LEGENDS
E-601 SECOND FLOOR TELE/DATA FLOOR PLAN, TV DEVICE SCHEDULE AND DATA OUTLET CONFIGURATION DETAIL
E-602 COMM ROOM CALLOUT, DETAILS AND RENDERINGS
E-603 RACK SECTION, DATA EQUIPMENT SCHEDULE AND PATCH PANEL DETAIL
E-604 DATA PANEL SCHEDULES
E-700 FIRST FLOOR FIRE ALARM AND MASS NOTIFICATION PLAN, FIRE ALARM DEVICE SCHEDULE AND FIRE ALARM AND MASS NOTIFICATION LEGENDS
E-701 SECOND FLOOR FIRE ALARM AND MASS NOTIFICATION PLAN
E-800 PANELBOARDS LP11, LP12 , EH11 AND EL11 SCHEDULES
E-801 PANELBOARDS LP13, LP21 AND LP22 SCHEDULES
E-900 3D VIEWS
3/4" = 1'-0"2
TYPICAL CONDUIT TRENCHINSTALLATION
RE
F.
DF
.
lv
2
E-101
OO
CONNECT FIRST
THROUGH
CONTACTOR (CON 2),
THEN TO PANEL
CONNECT FIRST
THROUGH
CONTACTOR (CON
2), THEN TO PANEL
L
L
L
L
L
L
L
L
CON2
CON1
HP11 - 1
HP11 - 1
CONNECT FIRST
THROUGH
CONTACTOR (CON 1),
THEN TO PANEL HP11 - 1
2' - 0"
P
P
P P P P
PC
SIGN LIGHTS AND WIRING
FOR SIGN LIGHTS TO BE
A BID OPTION
6 BOLLARD LIGHTS AND ALL WIRING
FOR THE LIGHTS SHALL BE A BID
OPTION
3' -
6"
3' -
6 1
/2"
1' - 0"
PEDISTALS99' - 6"
CONCRETE FOUNDATION
FOR MOUNTING FIXTURE
4 ANCHOR BOLTS PER MANUFACTURER
REQUIREMENTS
GRADE
TYPE P FIXTURE
CONDUIT
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-101
LIGHTING SITE PLAN AND TYPE P INSTALLATION
DETAIL
1/8" = 1'-0"1
SITE LIGHTING
1/4" = 1'-0"2
TYPE P INSTALLATION INFORMATION
lv
lv
lv
J
lv
lv lv
lv
DD
J J
J
JJ
J
J
J
JJ
J
lv
lv
lvlv
lvJ
lv
lvlv
lv
S1 (b)S1 (a)
EW
LP13
CW (c)
CW (c)
CW (c)
A (d)
E
J (b)
G
CD
S1
S1 (e)
S1
E
S1
S2
S2
EO
EO
EO
OS
OS OS
OSOS
OS
OS
OSOS
OS
OS
OS
GG
G G
M
S2 (a)
1
E-602
F (b)
F (a)
F (a)
F (b)
F (b) F (a)
F (a)
B
D
D
B
BB
B
A
A
A A
A
A
A A
F
D (a)
D (a)
A (d)
CL (e)
S2 S2
S2
H (b)H (a)H (b)H (b)
H (a)
H (a)
H (b)
H (a) H (b) H (a) H (b)
H (b)
H (a)
H (a)
CD (b)
S4 (c)S4 (b)
S2
S2 (a)
A
T2LP11
HP11
SB2 SB1
EH11
T3
EL11
D1H2
METER
LP12
D
EE
EE
EE
EE
EE
EE
EE
CON2
S2S2
S2 (d)
OS
CD (b)
CD (b)
CD (b)
TO UPPER LEVEL FIXTURES (SEE SECOND
FLOOR LIGHTING PLAN)
JRM
PCAW
PC
D (a)
E
E
EH11 - 2
J (a)
J (b)
J (a)
J (a)
J (a)
G
D
ALL SWITCHES IN RECEPTION AREA
SHALL BE CONFIGURED TO RESPOND
TO AREA OCCUPANCY SENSOR (OS)
S2 (b)
S2
CORRIDOR LIGHTS
SHALL BE CONTROLLED
BY POWER PAK RELAY
MODULE IN TYPE MARK
"JRM" JUNCTION BOX.
THERE WILL BE NO
DEDICATED WALL
SWITCH
H (b)
HP11 - 4
HP11 - 4
CON1
S1
UP TO LIGHTS
ABOVE
SWITCH FOR
UPPER LIGHTS
S3
HP11 - 3
EH11 - 6
L
ON AT ALL TIMES
S2 (d)
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-200
FIRST FLOOR LIGHTING PLAN, LIGHT FIXTURE AND
LIGHTING DEVICE SCHEDULE
LIGHTING FIXTURE SCHEDULELIGHTING FIXTURE SCHEDULELIGHTING FIXTURE SCHEDULELIGHTING FIXTURE SCHEDULE
TypeTypeTypeType
MarkMarkMarkMark CountCountCountCount ManufacturerManufacturerManufacturerManufacturer ModelModelModelModel DescriptionDescriptionDescriptionDescription
A 15 H.E. Williams DIG-S24-254T5HO-WPR-STEP
DIMMING-277
DIRECT/INDIRECT 2 LAMP RECESSED FIXTURE, DUAL
LEVEL SWITCHING
B 11 H.E. Williams DIG-S24-154T5HO-WPR-EB1-277 DIRECT/INDIRECT 1 LAMP RECESSED FIXTURE
CD 6 PRESCOLITE LFD6LED277HDM-CLFLED7-35K-WHWTB2
4
6" RECESSED LED CAN WITH LUTRON SERIES A LED
DRIVER AND 2000 LUMEN LED MODULE
CL 1 PRESCOLITE LFD6LED277-CLFLED5-35K-WHWTB24 6" RECESSED LED CAN WITH 1000 LUMEN OUTPUT
CW 3 PRESCOLITE LFD6LED277WW-6LFLED7-35K-WHWTB24 6" RECESSED LED CAN CONFIGURED TO WALL WASH
WITH LUTRON SERIES A DRIVER
D 16 Finelite Inc. S16WM-SSL-4-T5HO-SC-91W-277-FE-1.0 WALL MOUNTED LINEAR
E 10 DUAL LITE EVCUGWD4I CEILING MOUNTED EXIT SIGN, 277 VOLT
EE 13 DUAL LITE LZ20NI03L EMERGENCY LED WALLPACK, NICKEL CADMIUM
BATTERY, 6 VOLT,
EO 3 DUAL LITE EVO TWO LED OUTDOOR REMOTE EMERGENCY LIGHTING
HEADS
EW 1 DUAL LITE EVCUGWD4I WALL MOUNTED EXIT SIGN, 277 VOLT
F 10 HE WILLIAMS 73-4-154T5H-WG-73141-EB2-277 SINGLE LAMP STRIP FIXTURE WITH WIRE GUARD
FE 1 HE WILLIAMS 73-4-1-54T5H-WG-73141-EB2-277-EM SINGLE LAMP STRIP FIXTURE WITH WIRE GUARD AND
BATTERY BACKUP
G 12 HE WILLIAMS 73-4-2-54T5H-WG-73141-EB2-277 DUAL LAMP STRIP FIXTURE WITH WIRE GUARD
H 18 HE WILLIAMS CL-4-354T5H-F-KSH-34RF-AMW-EB3-277V 3 LAMP WALL MOUNTED CORNER LIGHT WITH CLEAR
ACRYLIC LENS
J 8 FINELITE S10-SSL-8-2T5HO-DC-91W-OPEN-277-AC-
EE-C4-1.0
SUSPENDED LINEAR PENDANT 8' NOMINAL LENGTH
K 3 FINELITE S16-SSL-12-2T5HO-DC-91W-OPEN-277-AC-
EE-C4-1.0
SUSPENDED LINEAR PENDANT 12' NOMINAL LENGTH
L 9 CROSSOVER XCHWM3-LED-WT LED 48 450-NW-UE-BLK LED EXTERIOR WALL SCONCE
M 1 HUBBELL NVX15GHGA-NVBA WALL MOUNTED VAPOR-TIGHT FIXTURE, TOSHIBA
8A19/27F-UP LED LAMP, 120 VOLT
N 2 CROUSE HINDS 43961-116-GR ROOF MOUNTED, TWO HEAD, AIRCRAFT WARNING LIGHT
O 2 Kim Lighting CFL1-27L3KUV-BL LED FLOODLIGHT WITH ADJUSTABLE BARN DOOR
LOUVERS (BD-CFL/BL), ON STANCHION MOUNT (SM18BL),
8" ABOVE GROUND
P 6 KIM Lighting GEM1C-36L3K277-LG-NG-C PERFORMANCE BOLLARD MOUNTED ON CONCRETE
SHAFT. TO BE BURIED 3' 6"
Grand total: 151
LIGHTING DEVICE SCHEDULE
Type Mark Count Manufacturer Model Description
CON1 1 4 CONTACT CONTACTOR FOR LIGHTING CIRCUITS WITH ON/OFF/AUTO SWITCH AND REMOTE PHOTOCELL
CON2 1 4 CONTACT CONTACTOR FOR LIGHTING CIRCUITS WITH ON/OFF/AUTO SWITCH AND REMOTE PHOTOCELL
JRM 2 LUTRON RMJ-16R-DV-B PULL BOX FOR LIGHTING SYSTEM WITH POWPAK RELAY MODULE
OS 27 LUTRON LRF2-OCR2B-P-WH CEILING-MOUNT WIRELESS OCCUPACY SENSOR WITH SURFACE OR RECESSED MOUNTING HARDWARE AS REQUIRED FOR LOCATIONS INSTALLED
PB 18 PULL BOX FOR LIGHTING SYSTEM, TYPICAL, FOR REFERENCE ONLY, MORE BOXES MAY BE REQUIRED
PC 1 PHOTOCELL FOR USE WITH SITE LIGHTING CIRCUITS
PCAW 1 PHOTO CELL FOR AIRCRAFT WARNING LIGHTS
S1 12 HUBBELL 1221 HEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE
S2 31 Lutron Electronics MRF2-6ANS-277-** WIRELESS SWITCH. WHEN DUAL LEVEL SWITCHING IS USED, ENSURE THAT BOTH SWITCHES ARE CONFIGURED TO RESPOND TO WIRELESS OCCUPANCY
SENSOR (OS) IN AREA.
S3 1 HUBBELL 1221 HEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE FOR GARBAGE DISPOSER CONTROL, WIRE TO RECEPTACLE
S4 2 Lutron Electronics MRF2-6ND-120-WH WIRELESS DIMMER
S5 1 HUBBELL 1221 HEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE FOR CONTROL OF EXHAUST FAN
Grand total: 98
1/8" = 1'-0"1
FIRST FLOOR LIGHTING PLAN
lv lv
lv
lv
lv
lv lv
lv
J
J
J
J
JJ
J lv
lv
lvlv
J
lv
lvlv
LF
JJ
K
KK
A
A
S1
S1
EE
E
E
OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
D
B
B
B
B
B
B
F
F
D
DD
D
DD
A
D
A
CD
S2
S2
S2
S2
S2 S2
S2
S2
H (c)
FE
EE
EE
EE
EES2
S2S2
S2FROM LOWER LEVEL
LIGHTING FIXTURES (SEE
FIRST FLOOR LIGHTING PLAN)
JRM
**SEE ROOF LIGHTENING
PROTECTION PLAN FOR
ROOF AIRCRAFT WARNING
LIGHTING**
L
S1 HP11 - 2
LP22
S1
ED
CORRIDOR LIGHTS
SHALL BE CONTROLLED
BY POWER PAK RELAY
MODULE IN TYPE MARK
"JRM" JUNCTION BOX.
THERE WILL BE NO
DEDICATED WALL
SWITCH
S2 (c)
H (c)
EH11 - 4
G G
G
G G
G
EH11 - 6
LIGHTS SWITCHED FROM
SNAP SWITCH ON 1ST
FLOOR
EE
S5
S2S2
BLACK
NEUTRAL
GREEN
GROUND
WHITE
WHITE
ORANGE
ORANGE
BLACK
BLACK
DIMMING DRIVER
DIMMING DRIVER
TO NEXT DIMMING
BALLAST/DRIVER...
CEILING MOUNTED
WIRELESS OCCUPANCY
SENSOR
WIRELESS DIMMER
CONTROL SWITCH
TYPICAL DIMMING SYSTEM
R
R
WARNING LIGHT WIRING DETAIL
1 POLE PHOTO CELL
CONTROL
WARNING LIGHTS
ON TOP OF BUILDING
120 VOLT
R
R
WARNING LIGHTS
ON TOP OF BUILDING
LIGHTING LEGEND
2X4 RECESSED DIRECT/INDIRECT CEILING FIXTURE
DIRECT/INDIRECT WALL FLUORESCENT FIXTURE
4'0" STRIP LIGHT WITH WIRE GUARD
EXTERIOR REMOTE EXIT LIGHT
CEILING MOUNTED LED EXIT SIGN
WALL MOUNTED LED EXIT SIGN
SINGLE POLE 120/277 VOLT SNAP SWITCH
LOW VOLTAGE SWITCH
"A" FIXTURE TYPE
A(a) FIXTURE TYPE WITH SWITCHING INFORMATION
ROOF MOUNTED OBSTRUCTION LIGHT
6" RECECCED CAN DOWNLIGHT
3 LAMP WALL MOUNTED CORNER FIXTURE
EXTERIOR WALL SCONCE
WALKWAY BOLLARD
FLOODLIGHT
PENDANT FLUORESCENT STRIP
lv
"S1" DEVICE TYPE
"S1(a)" DEVICE TYPE WITH SWITCHING INFORMATION
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-201
SECOND FLOOR LIGHTING PLAN. LIGHTING
LEGEND, DIMMING SYSTEM AND WARNING LIGHT
DETAILS
1/8" = 1'-0"1
SECOND FLOOR LIGHTING PLAN
LIGHTS ON AT
ALL TIMES
LIGHT ON AT ALL TIMES
to
J1 J1
J1J1
J
J
J1
J2
J2
SB1SB2
D1H2
LP13
R2
R2
R2
R2
R2 R2
R2
R2
R2
LP12
R1R1
R1
R1
R1
R1
R5
R2
R2
R2
R2
R2
R2
R2R2
R4
R4
R1
R1
MSEMM
SGBB
DUCT RUN
UNDERNEATH
SIMULATOR
MGBB
TGBB
R2
R2
R2
R2
R2
R2
R2
R2
R1
R1
R1
R17
R1R1
R1
R1R1R1
R1
R6
R6
R6
R6
R6
DISCONNECT FOR BRIDGE POWER
TVSS
MSA
D1
M2
R1
EMM
R2
R2R2
R7
R9R9
R8
LP13 -
15
LP12 -
1,3
LP12 - 3
LP12 - 5
LP12 - 2
LP12 -
4,6
LP13 -
13
LP13 -
15
METER
R10
R10
R10
R10R10
LP13 - 7
MSUPS
HCB1
MSSD
MSVAC
TVSS2
EPO
EPO
Sto
LP12 - 8
VacMSAW
LP11 -
13,15,17
EL11 -
21
R1
LP11 -
21
LP13 - 1
LP13 - 5
EL11 - 4
LP12 - 9
SB2 - 3
LP13 - 8
R6
EL11 -
10
R13 WIRE TO PIT
LIGHT & SWITCH
LP13 - 4
LP13 - 6
R2
R2
R2R2R2
R2
1
E-602
LP13 -
16,18,20
LP13 -
10,12,14
LP13 - 3
LP13 -
11
EL11 -
17
EL11 -
19
EL11 -
25EL11 -
23
HP11LP11
LP13 - 9
EL11
T3
EH11
LP12 -
11,13
NOTE: ALL CIRCUITS RUN TO PANEL LP13
SHALL HAVE AN ISOLATED GROUND AS
WELL AS AN EQUIPMENT GROUND
LP12 -
7,9
EL11 -
14
LP11 -
14,16,18
SGBB
R15
R15LP11 -
23
P1
GHCP
GHSCP
HP11 - 5HP11 - 6
S/P
MTS
T2
CRAC-1
MSS-1 -
1,3,5
UPS
MSUPS
- 1,3,5
UPS - 1
MSUPS
- 2,4,6
R16
LP12 -
10
NOTE: ALL CIRCUITS RUN FROM ROOM 117
TO PANEL EL11 SHALL HAVE AN ISOLATED
GROUND AS WELL AS AN EQUIPMENT GROUND
PROVIDE A LIMIT SWITCH (WITH NC CONTACTS)
ON THE CRANE RAIL AT THE PARKED POSITION.
PROVIDE WIRING IN CONDUIT FROM LIMIT SWITCH
BACK TO THE MOTION CONROL CABINET. FIELD
LOCATE PARKED POSITION.
SPACE FOR FUTURE ROOF
SOLAR COLLECTOR EQUIPMENT
MSS-1
LP11 -
20,22,24MSPDU
LP11 -
25
INSTALL 2" CONDUIT UNDERGROUND AND
EXTEND UP INTO MECHANICAL ROOM
FOR IRRIGATION CONDUCTORS.
WST HIGH BAY
116
WST SIM MAINT PARTS
STOR
114
MAINT SUPV
115
WST COMPUTOR ROOM
DATA STORAGE
113
CORR
106
STAIR
104
INSTRUCTORS SUITE
110
PO/QAR (GOV'T)
109
SITE MGR (CONTRACT)
108PO/QAR STOR
107
RECEPTION
105
LOBBY
101COMM
117
ELEV
102
VESTIBULE
100MECHANICAL/FIRE
PROTECTION
118
MEN
111
WOMEN
112
STAIR
103
EL11 -
34
VAVCP
VAVCP
VAVCP
FC
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-202
FIRST FLOOR POWER PLAN AND SWITHBOARD SB1
SCHEDULE
Notes:
Spare 64830 VA 100.00% 64830 VA
Receptacle 51010 VA 59.80% 30505 VA
Power 7800 VA 100.00% 7800 VA
Other 25554 VA 100.00% 25554 VA
Motor 78700 VA 106.83% 84078 VA Total Est. Demand: 499 A
Lighting 11157 VA 125.00% 13946 VA Total Conn.: 514 A
Heating 11200 VA 100.00% 11200 VA Total Est. Demand: 414974 VA
HVAC 113779 VA 100.00% 113779 VA Total Conn. Load: 427312 VA
Cooling 63282 VA 100.00% 63282 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 514 A 512 A 509 A
Total Conn. Load: 142126 VA 141796 VA 140856 VA
6
5
4
3
2
1 SB2 3 800 A 800 A 142126 VA 141796 VA 140856 VA
CKT Circuit Description # of Poles Frame Size Trip Rating
A B C
Remarks
Notes:
Enclosure: NEMA 1 MCB Rating: 800 A
Mounting: PAD Wires: 4 Mains Rating: 800 A
Supply From: T-1 Phases: 3 Mains Type:
Location: MECHANICAL/FIRE... Volts: 480/277 Wye A.I.C. Rating: 42000
Switchboard: SB1
1/8" = 1'-0"1
FIRST FLOOR POWER
23"
4"
.25"
J
J
J
J
J
J
J
J
J
toto
SH
J
J
J
GROUND BUSS - MGBB,
TGBB OR SGBB
LP21
R2
R2
R2
R2
R2R2
R4
R4
R1
R1
R1
R1
SGBB
LOCATE AT WIRING "WATERFALL"
ON TOWER
?
?
?
?
?
?
R7LP22 - 5
R11
R2
R2
R2
R2 R2
R2
R2 R2
R2
R2 R2
R2
R2
R2
R2 R2
R2
R2R2R2R2
R1
R1
R1
R1
R1
R12 R12 R12
R9 R9 R9 R9
LP22 -
6,8
LP22 -
2,4
LP22 - 2
R2
LP21 - 2
LP21 - 3
LP21 - 7
LP21 - 6
LP21 - 4
1
E-602
LP21 - 5
LP22 - 8
LP22 - 7
LP22 -
1,3
LP22 - 9
NOTE: ALL CIRCUITS RUN TO PANEL LP21
SHALL HAVE AN ISOLATED GROUND AS
WELL AS AN EQUIPMENT GROUND
R1
LP21 - 1
R2D9H3
CC
HP11 -
20,22,24
R15 R15
R15
R15
R15
LP22 -
13
GPB
GPB
GPB
GPB
GPB
GPB
GPB
LP22
D1H1
R5R5 R5
R5
MEN
209
CLASSROOM
210
CLASSROOM
211CLASSROOM
212
UNIT STORAGE
213
JAN.
214
CLASSROOM
215
EQUIPMENT PLATFORM
216
GALLY & VENDING
206
BREAK AREA
207
LOBBY
201
CORRIDOR
205
WOMEN
208
STAIRS
203
EL11 -
20,22,24
H SP
D1L1
Stoe
Stoe
SWITCHES TO BE USED
FOR ELEVATOR 120 VOLT
EQUIPMENT AND LIGHTING FE
S1
T1
EL11 -
16
EL11 -
12
R11
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-203
SECOND FLOOR POWER PLAN, SWITCHBOARD
SCHEDULE SB2, ELEVATOR EQUIPMENT ROOM AND
GROUND BUSS DETAIL
Notes:
Spare 64830 VA 100.00% 64830 VA
Receptacle 51010 VA 59.80% 30505 VA
Power 7800 VA 100.00% 7800 VA
Other 25554 VA 100.00% 25554 VA
Motor 78700 VA 106.83% 84078 VA Total Est. Demand: 499 A
Lighting 11157 VA 125.00% 13946 VA Total Conn.: 514 A
Heating 11200 VA 100.00% 11200 VA Total Est. Demand: 414974 VA
HVAC 113779 VA 100.00% 113779 VA Total Conn. Load: 427312 VA
Cooling 63282 VA 100.00% 63282 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 536 A 538 A 538 A
Total Conn. Load: 148544 VA 149028 VA 148918 VA
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8 D1H1 3 100 A 100 A 20400 VA 20400 VA 20400 VA
7 ACC-1 3 200 A 125 A 20633 VA 20633 VA 20633 VA
6 MTS 3 200 A 200 A 31546 VA 33368 VA 32267 VA
5 T2 3 200 A 175 A 34862 VA 31306 VA 30594 VA
4 TVSS 3 60 A 60 A 0 VA 0 VA 0 VA
3 MSEMM 3 100 A 100 A 19214 VA 19214 VA 19214 VA
2 HCB1 3 60 A 40 A 7834 VA 7834 VA 7834 VA
1 HP11 3 200 A 200 A 14054 VA 16273 VA 17976 VA
CKT Circuit Description # of Poles Frame Size Trip Rating
A B C
Remarks
Notes:
Enclosure: NEMA 1 MCB Rating:
Mounting: PAD Wires: 4 Mains Rating: 800 A
Supply From: SB1 Phases: 3 Mains Type:
Location: MECHANICAL/FIRE... Volts: 480/277 Wye A.I.C. Rating: 30000
Switchboard: SB2
1/8" = 1'-0"1
SECOND FLOOR POWER
1/8" = 1'-0"3
ELEVATOR LEVEL, POWER, LIGHTING,DATA AND FIRE ALARM
SPACE 3 200 ASPACE 3 200 ASPACE 3 200 A
SPACE 3 200 A
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-204
ELECTRICAL EQUIPMENT SCHEDULE
ELECTRICAL EQUIPMENT SCHEDULE
Type Mark CountHAS ISOLATEDGROUND BUS Description Comments
CC 1 No OVERHEAD CRANE CONNECTION POINT, PROVIDED BY GC, WIRED BY EC. FIELD LOCATE EXACT CONNECTION POINT
D1H1 1 No 100 AMP, 277/480 VOLT, 3 PHASE, 4 WIRE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.
D1H2 1 No 277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP, FUSED,NEMA 3R DISCONNECT
D1H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D1H6 1 No 60 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D1L1 1 No 100 AMP, 208 VOLT, 3 PHASE, FUSED FOR ELEVATOR MOTOR, FUSE TO MATCH MOTOR REQUIREMENTS
D1L3 1 30 AMP, 208 VOLT, 1 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.
D1L6 1 No 60 AMP, 208 VOLT, 1 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.
D2H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D2L3 1 30 AMP, 208 VOLT, 1 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.
D3H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D4H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D5H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D6H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D7H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTER
ABOVE AND WIRE AS REQUIRED
D8H3 1 No 30 AMP, 480 VOLT, 3 PHASE, NEMA 3R FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.
D9H3 1 No 30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC., LOCATE NEXT TO CRANE POWER
CONNECTION POINT, FIELD LOCATE
EH11 1 No 277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP, NEMA 1, 200 AMP MAIN BREAKER
EL11 1 Yes 120/208 VOLT, 3 PHASE, 4 WIRE, 200 AMP, NEMA 1, 30 SPACE
EMM 1 No ELECTRIC MOTION CABINET TO BE PROVIDED BY LOCKHEED
FC 1 FUSE CABINET BY EC TO STORE SPARE FUSES
GHCP 1 277/480V GUTTER HEAT CONTROL PANEL WITH 50A BREAKER
GHCPS 1 277/480V GUTTER HEAT SATELLITE CONTROL PANEL WITH 50A BREAKER CONNECTED TO MASTER CONTROL PANEL USING 12 AWG
3-WIRE CABLE
HCB1 1 No 277/480 VOLT, 3-PHASE, 4 WIRE, 40 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE OPEN
POSITION
WIRE SHUNT TRIP INTO EPO SWITCH
HP11 1 No 277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP, NEMA 1
LP11 1 Yes 120/208 VOLT, 3-PHASE, 4 WIRE, 400 AMP, 400 AMP MAIN PANELBOARD
LP12 1 No 120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARD
LP13 1 Yes 120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARD
LP21 1 No 120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARD
LP22 1 No 120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARD
METER 1 No NEW METER
MSA 1 No 120/208 VOLT, 3-PHASE, 4 WIRE, 50 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE OPEN
POSITION
WIRE SHUNT TRIP INTO BUILDING FIRE ALARM SYSTEM FOR SHUT DOWN
MSAW 1 No 120 VOLT, 20 AMP, 1 PHASE, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE OPEN POSITION WIRE SHUNT TRIP INTO BUILDING FIRE ALARM SYSTEM FOR SHUT DOWN
MSEMM 1 No 277/480 VOLT, 3-PHASE, 4 WIRE, 100 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCK DEVICE TO ENABLE PADLOCK IN THE OPEN
POSITION
WIRE SHUNT TRIP INTO BUILDING FIRE ALARM SYSTEM FOR SHUT DOWN
MSPDU 1 No 120/208 VOLT, 3-PHASE, 4 WIRE, 100 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE
OPEN POSITION
MSS-1 1 No 120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE
OPEN POSITION
MSSD 1 No 120 VOLT, 1-PHASE, 2 WIRE, 20 AMP, SHUNT TRIP BREAKER WIRE SHUNT TRIP INTO EPO SWITCH
MSUPS 1 No 120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE
OPEN POSITION
WIRE SHUNT TRIP INTO EPO SWITCH
MSVAC 1 No 120 VOLT, 1-PHASE, 2 WIRE, 20 AMP, SHUNT TRIP BREAKER WITH FRONT LOCKING DEVICE TO PADLOCK IN THE OPEN POSITION WIRE SHUNT TRIP INTO EPO SWITCH
MTS 1 No 277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP MANUAL TRANSFER SWITCH
P1 1 No WST POWER CABINET BY LOCKEED.
PDU 1 No 120/208 VOLT, 3 PHASE, 100 AMP PANEL BY OTHERS, WIRED TO MSPDU BY OTHERS
SB1 1 No 277/480 VOLT, 3 PHASE, 4 WIRE, 800 AMP MAIN BREAKER, CT SPACE FOR CLF&P METERING MAIN SWITCH AND CT SECTION OF MAIN SWITCHBOARD
SB2 1 No DISTRIBUTION SECTION, 277/480 VOLT, 3 PHASE, 4 WIRE , 800 AMP DISTRIBUTION SECTION OF MAIN SWITCHBOARD
T2 1 Yes 480 VOLT, DELTA PRIMARY - 120/208 VOLT WYE SECONDARY, 112.5 KVA DRY TYPE STEP DOWN TRANSFORMER, K4 RATING,
SHIELDED, 3% IMPEDANCE
T3 1 No 480 VOLT, DELTA PRIMARY - 120/208 VOLT WYE SECONDARY, 75 KVA DRY TYPE STEP DOWN TRANSFORMER, K4 RATING, SHIELDED,
3% IMPEDANCE
T-1 1 No TRANSFORMER BY CLF&P
UPS 1 No 75 KVA RATED AT ALTITUDE UPS, TO BE PROVIDED AND INSTALLED BY EC
Grand total: 48 48
UTILITY TRANSFORMER
277/480V, 3PH, 4W
ELECTRIC METER
A
MTS
E
S/PF
C
HCB1
I
T-1K
T-2
HP11
LP11
M
LP21 LP22
LP12 LP13
P
Q
T
O
MSUSP
R
MSEMM
EMM
UPS
CRAC-1
DISC-H1
N
WST COMPUTER ROOM FLOOR
FIRST FLOOR
ELECTRICAL ONE LINE
TVSS
J
TVSS2
Y
MSA
D1
S
V
P1
UW
MSS-1
Z
Z1
X
UPON COMPLETION OF PROJECT THE FOLLOWING MEASUREMENTS SHALL BE MADE OVER A PERIOD OF SEVERAL DAYS (THE RESULTS TO BE SENT TO CAE FOR ANALYSIS)
PREFERABLY WHEN THE AREA OF INTEREST AND ANY NEAR-BY AREAS HAVE THEIR FULL COMPLEMENT OF ELECTRICAL EQUIPMENT INSTALLED AND OPERATED:
MAIN INPUT VOLTAGE VARIATIONS, SAGS AND SURGES (ALL PHASES AND NEUTRAL)
FREQUENCY VARIATIONS
TRANSIENTS MAGNITUDE EXCEEDING 1.5 TIMES THE NOMINAL VOLTAGE
TRANSIENTS DURATION EXCEEDING 1/2 POWER CYCLE
NUMBER AND DURATION OF POWER OUTAGES
1" CONDUIT FOR METER WIRING
WST COMPUTER ROOM LOWERED FLOOR
EH11
EL11
SB1 SB2
D1H2
D
T3 HG
L
PDU
Z2
MSPDU
Z3
Z4
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-205
ELECTRICAL ONE LINE AND ELECTRICAL FEEDER
SCHEDULE
ELECTRICAL FEEDER SCHEDULE
FEEDERDESIGN
ATIONFOR
ONELINE Panel Circuit Number Load Name Wire Size
ConduitSize When
Larger Than1/2" Voltage
ASCI AtLoad Comments
A T-1 1 SB1 3 runs of 3-#300, 1-#300, 1-#1/0 3 - 3" 480 V 28739 GROUND WIRES (# 1/0) NOT REQUIRED FOR THESE RUNS
C SB2 6 MTS 3-#3/0, 1-#3/0, 1-#6 2" 480 V 24268
D MTS 2 D1H2 3-#3/0, 1-#3/0, 1-#6 2" 480 V LESS THAN 10000
E D1H2 1,3,5 S/P 3-#3/0, 1-#3/0, 1-#6 2" 480 V LESS THAN 10000
F MTS 1 EH11 3-#3/0, 1-#3/0, 1-#6 2" 480 V 22769
G EH11 1,3,5 T3 3-#3, 1-#3, 1-#6 1 1/4" 480 V 20728
H T3 1 EL11 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000
I SB2 2 HCB1 3-#8, 1-#8, 1-#10 1 1/4" 480 V 4561
J SB2 4 TVSS 3-#6, 1-#6, 1-#10 1" 480 V 19482
K SB2 1 HP11 3-#3/0, 1-#3/0, 1-#6 2" 480 V 27172
L SB2 5 T2 3-#2/0, 1-#2/0, 1-#6 2" 480 V 25064
M T2 1 LP11 2 runs of 3-#3/0, 1-#3/0, 1-#3 2 - 2" 208 V LESS THAN 10000 REQUIRES AND ADDITIONAL # 3 ISOLATED GROUND WIRE IN EACH CONDUIT
N SB2 3 MSEMM 3-#3, 1-#3, 1-#8 1 1/4" 480 V 7373
O LP11 1,3,5 LP12 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000
P LP11 2,4,6 LP21 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000 REQUIRES AND ADDITIONAL # 6 ISOLATED GROUND WIRE IN CONDUIT
Q LP11 8,10,12 LP22 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000
R LP11 14,16,18 MSUPS 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000
S LP11 13,15,17 MSA 3-#6, 1-#6, 1-#10 1" 208 V LESS THAN 10000
T LP11 7,9,11 LP13 3-#1/0, 1-#1/0, 1-#6 2" 208 V LESS THAN 10000 REQUIRES AND ADDITIONAL # 6 ISOLATED GROUND WIRE IN CONDUIT
U HCB1 1,3,5 CRAC-1 3-#8, 1-#8, 1-#10 1 1/4" 480 V LESS THAN 10000
V MSA 1 D1 HVAC WST HIGH BAY 124 3-#6, 1-#6, 1-#10 1" 208 V LESS THAN 10000 WIRING FROM BREAKER TO EQUIPMENT NOT REQUIRED IN THIS CONTRACT
W MSUPS 1,3,5 UPS 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000
X MSEMM 1 EMM 3-#3, 1-#3, 1-#8 1 1/4" 480 V LESS THAN 10000 WIRING FROM BREAKER TO EQUIPMENT NOT REQUIRED IN THIS CONTRACT
Y MSUPS 2,4,6 TVSS2 3-#10, 1-#10, 1-#10 1/2" 208 V LESS THAN 10000
Z UPS 1 MSS-1 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000
Z1 MSS-1 1,3,5 P1 3-#3/0, 1-#3/0, 1-#6 2" 208 V LESS THAN 10000 WIRING FROM BREAKER TO EQUPMENT NOT REQUIRED IN THIS CONTRACT
Z2 SB1 1 SB2 3 runs of 3-#300, 1-#300, 1-#1/0 480 V 28739 BUSSING BETWEEN SB1 AND SB2 TO EQUAL SIZE OF FEEDERS SHOWN
Z3 LP11 20,22,24 MSPDU 3-#3, 1-#3, 1-#8 1 1/4" 208 V LESS THAN 10000
Z4 MSPDU 1,3,5 PDU 3-#3, 1-#3, 1-#8 1 1/4" 208 V WIRING FROM BREAKER TO EQUPMENT NOT REQUIRED IN THIS CONTRACT
Grand total: 29
MAIN SERVICE
SWITCH
NEUTRAL BUSS
GROUND BUSS
BOND NEUTRAL BUSS TO GROUND BUSS
UFER GROUND TO
BAR IN FOUNDATION
# 4# 3/0 TO BUILDING STEEL
# 3/0 TO BUILDING WATER PIPING
2/0 GROUND LOOP AROUND
BUILDING, GROUND RODS
MINIMUM EVERY 20'0" AND AT
ALL CORNERS AS SHOWN
MGBB
SGBB
SGBB
SGBB
2/0
AT EMM
LOCATED WITHIN 78"
OF P1 CABINET
AT WIRING "WATER FALL"
TGBB
IN COMM RM
3/0
LIGHTNING PROTECTION SYSTEM SHALL
BE TIED INTO GROUND SYSTEM
BOND TO CABLE SUPPORT
WITH # 6
GROUNDING ONELINE
GENERATOR
DISCONNECT
NEUTRAL BUSS
GROUND BUSS
# 4
FIRE ALARM &
MASS NOTIFICATION
PANEL(S)
RADIO ANTENNA FOR
FIRE ALARM AND MASS
NOTIFICATION SYSTEM
LIGHTNING ARRESTOR
WITH ENCLOSURE
BOND TO EVERY FOURTH RISER OF
RAISED COMPUTER ROOM FLOOR
WITH #6
GROUNDING ONELINE FOR SEPARATELYDERIVED SYSTEMS
120/208 VOLT
CONDUIT, (TYPICAL)
NEUTRAL (TYPICAL)
EQUIPMENT GROUND
TYPICAL
ISOLATED GROUND
BONDING CONDUCTOR
480 VOLT CONDUIT
EQUIPMENT GROUND
# 4 COPPER (1/0 FOR 150 KVA
TRANSFORMER
480 DELTA/
120/208 Y
XFRM
GB2
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-206
GROUNDING ONELINE & GROUNDING ONELINE FOR
SEPARATELY DERIVED SYSTEMS, HP11 PANEL
SCHEDULE, BRANCH CIRCUITS LARGER THAN # 12
ELECTRIC CIRCUIT SCHEDULE, BRANCH CIRCUITS LARGER THAN # 12
PanelCircuitNumber
Conduit Size WhenLarger Than 1/2" Load Name Wire Size Voltage
VoltageDrop VD%
D1H1 1 1 1/4" H1 HUMIDIFIER 3-#3, 1-#3, 1-#8 480 V 0 V 0.020364
EH11 13,15,17 3/4" D1H6/AHU1R 3-#8, 1-#10 480 V 1 V 0.152308
EH11 14,16,18 1/2" D7H3/AHU1S 3-#10, 1-#10 480 V 2 V 0.251185
EL11 9,11 3/4" EUH-1 2-#8, 1-#10 208 V 1 V 0.28021
EL11 13,15 3/4" D1L6/EUH-2 2-#8, 1-#10 208 V 1 V 0.597805
EL11 20,22,24 1" ELEVATOR MOTOR 3-#6, 1-#10 208 V 2 V 0.599297
EL11 27 3/4" VAV CONTROL POWER 1-#8, 1-#8, 1-#8 120 V 2 V 1.481887
EL11 28 3/4" VAV CONTROL POWER 1-#8, 1-#8, 1-#8 120 V 2 V 1.837919
EL11 29 1/2" VAV CONTROL POWER 1-#10, 1-#10, 1-#10 120 V 2 V 1.332609
EL11 30 3/4" VAV CONTROL POWER 1-#6, 1-#6, 1-#6 120 V 2 V 1.353757
EL11 31 3/4" VAV CONTROL POWER 1-#6, 1-#6, 1-#6 120 V 2 V 1.260864
EL11 33 FAC WST COMPUTOR
ROOM DATA STORAGE
113
1-#8, 1-#8, 1-#8 120 V 2 V 1.321354
GHCP 1 1" GUTTER AND
DOWNSPOUT HEAT
TAPE
1-#4, 1-#4, 1-#6 277 V 4 V 1.517766
GHSCP 1 3/4" GUTTER AND
DOWNSPOUT HEAT
TAPE
1-#6, 1-#6, 1-#10 277 V 3 V 0.921089
HP11 5 3/4" GHSCP (GUTTER AND
DOWNSPOUT HEAT)
1-#6, 1-#6, 1-#10 277 V 0 V 0.084816
HP11 6 3/4" GHCP (GUTTER AND
DOWNSPOUT HEAT)
1-#6, 1-#6, 1-#10 277 V 0 V 0.133819
SB2 7 1 1/2" ACC-1 3-#1, 1-#6 480 V 1 V 0.116824
SB2 8 1 1/4" D1H1 3-#3, 1-#3, 1-#8 480 V 0 V 0
Grand total: 18
Notes:
Total Est. Demand: 58 A
Power 7500 VA 100.00% 7500 VA Total Conn.: 54 A
Other 11154 VA 100.00% 11154 VA Total Est. Demand: 48621 VA
Motor 16890 VA 108.96% 18404 VA Total Conn. Load: 44795 VA
Lighting 9251 VA 125.00% 11563 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 53 A 63 A 69 A
Total Load: 14768 VA 17045 VA 18781 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 Space -- -- 0 VA 0 VA -- -- Space 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 3718... 1933... 24
21 3718... 1933... 22
19
D8H3/DC-1 20 A 3
3718... 1933...
3 20 A DNH3
20
17 797 VA 797 VA 18
15 797 VA 797 VA 16
13
D6H3/DCP-1 20 A 3
797 VA 797 VA
3 20 A D5H3/DCP-2
14
11 2018... 2018... 12
9 2018... 2018... 10
7
D4H3/PCWP-2 20 A 3
2018... 2018...
3 20 A D3H3/PCWP-1
8
5 GHSCP (GUTTER AND DOWNSPOUT HEAT) 50 A 1 3000... 4500... 1 50 A GHCP (GUTTER AND DOWNSPOUT HEAT) 6
3 Room 101, 105, 108, 109, 106, 111, 107, 100, 11... 20 A 1 3172... 2592... 1 20 A Room 116 4
1 Lighting - Site 20 A 1 698 VA 2789... 1 20 A Room 212, 211, 210, 205, 214, 213, 215, 209, 20... 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: No MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: SB2 Phases: 3 Mains Type:
Location: MECHANICAL/FIRE... Volts: 480/277 Wye A.I.C. Rating: 30000
Branch Panel: HP11
B1 B2
EL11 - 7
PHWP-1
PHWP-2
BP-1
BP-2
EL11 - 6
EL11 - 8
D1H3
EH11 -
7,9,11
D2H3
PCWP-2 PCWP-1
DCP-1DCP-2
HP11 -
8,10,12HP11 -
7,9,11
HP11 -
14,16,18
HP11 -
13,15,17
D3H3
D4H3
D5H3
D6H3
T2LP11
HP11
SB2 SB1
EH11
T3
EL11
EH11 -
8,10,12
EUH-1
EL11 -
9,11
SB2 - 2
HCB1
ECH-1
EL11 -
18
HP11 -
19,21,23
D8H3
DC-1
ACC-1
LP11 -
19
HT
Vac
VAVCP
VAVCP
VAVCP
EL11 -
26
HCB1 -
1,3,5
HCB1
CRAC-1
MSVAC
MSVAC
- 1
EL11 -
32
EL11 -
30
EL11 -
28
SB2 - 7
EMM
MSEMM
MSAW
MSA
D1
LP12
M2
MSSD
UPS
MSUPS
MSS-1P1
LP13
GHSCP
GHCP
EL11 -
33
FAC
WST HIGH BAY
116
WST SIM MAINT PARTS
STOR
114
MAINT SUPV
115
WST COMPUTOR ROOM
DATA STORAGE
113
CORR
106
STAIR
104
INSTRUCTORS SUITE
110
PO/QAR (GOV'T)
109
SITE MGR (CONTRACT)
108PO/QAR STOR
107
RECEPTION
105
LOBBY
101COMM
117
ELEV
102
VESTIBULE
100MECHANICAL/FIRE
PROTECTION
118
MEN
111
WOMEN
112
STAIR
103
D1H2METER
MTSHP11
SCU-1B
WIRE TO SCU-1A IN THE
MECHANICAL ROOM ABOVE
EF-3
EL11 -
35
D2L3
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-207
FIRST FLOOR HVAC POWER PLAN AND
MECHANICAL EQUIPMENT SCHEDULE
1/8" = 1'-0"1
FIRST FLOOR HVAC POWER PLAN
MECHANICAL EQUIPMENT SCHEDULE
TypeMark Count Description
ACC-1 1 AIR COOLED CHILLER PROVIDED AND INSTALLED BY MC, WIRED BY EC. UNIT IS
PROVIDED WITH DISCONNECT SWITCH AND CIRCUIT BREAKERS
AHU1R 1 AHU-1 RETURN MOTOR, 20 HP, PROVIDED AND INSTALLED BY MC, WIRED BY EC
AHU1S 1 AHU-1 SUPPLY MOTOR, 15 HP. PROVIDED AND INSTALLED BY MC, WIRED BY EC
B1 1 GAS BOILER AND CONTOLS SUPPLIED BY MC, WIRED BY EC, EC TO PROVIDE Sto
(THERMAL OVERLOAD SWITCH) FOR CIRCUIT
B2 1 GAS BOILER AND CONTROLS SUPPLIED BY MC, WIRED BY EC, EC TO PROVIDE Sto
(THERMAL OVERLOAD SWITCH) FOR CIRCUIT
BP-1 1 BOILER PUMP PROVIDED AND INSTALLED BY MC, WIRE BY EC. EC SHALL PROVIDE
A Sto FOR DISCONNECTING AND OVERLOAD PROTECTION
BP-2 1 BOILER PUMP PROVIDED AND INSTALLED BY MC, WIRE BY EC. EC SHALL PROVIDE
A Sto FOR DISCONNECTING AND OVERLOAD PROTECTION
CRAC-1 1 AIR CONDITION UNIT FOR SWT ROOM, PROVIDED AND INSTALLED BY MC, WIRED BY
EC
D1 1 AIR CONDITIONING UNIT FOR FLIGHT TRAINEE STATION
DC-1 1 FLUID COOLER PROVIDED AND INSTALLED BY MC, EC TO WIRE
DCP-1 1 DRY COOLER PUMP AND STARTER BY MC, WIRED BY EC
DCP-2 1 DRY COOLER PUMP AND STARTER BY MC, WIRED BY EC
DDC 1 TEMPERATURE CONTROL PANEL BY MC, POWER PROVIDED TO PANEL BY EC
ECH-1 1 ELECTRIC CEILING HEATER PROVIDED AND INSTALLED BY MC, WIRED BY EC. EC
TO PROVIDE Sto FOR DISCONNECTION AND OVERLOAD PROTECTION
EF-1 1 EXHAUST FAN WITH INTERGRAL DISCONNECT SWITCH PROVIDED AND INSTALLED
BY MC, WIRED BY EC
EF-2 1 EXHAUST FAN PROVIDED AND INSTALLED BY MC, WIRED BY EC. EC TO PROVIDE
WALLS SWITCH TO WIRE TO EXHAUST FAN FOR CONTROL
EF-3 1 EXHAUST FAN PROVIDED AND INSTALLED BY MC, WIRED BY EC. EC TO PROVIDE
AND INSTALL A Sto FOR OVERLOAD AND DISCONNECTION
EUH-1 1 ELECTRIC UNIT HEATER PROVIDED AND INSTALLED BY MC, WIRED BY EC.
EUH-2 1 ELECTRIC UNIT HEATER PROVIDED AND INSTALLED BY MC, WIRED BY EC.
FAC 1 FIRE PROTECTION AIR COMPRESSOR PROVIDED AND INSTALLED BY FIRE
PROTECTION INSTALLER, WIRED BY EC, EC TO PROVIDE Sto FOR DISCONNECT
AND OVERLOAD PROTECTION
H-1 1 HUMIDIFIER PROVIDED AND INSTALLED BY MC, WIRED BY EC
HT 1 HEAT TAPE AT ACC-1, PROVIDED AND INSTALLED BY MC, WIRED BY EC, EC TO
PROVIDE WEATHERPROOF Sto FOR DISCONNECTION
M1 1 ELEVATOR MOTOR, PROVIDED AND INSTALLED BY GC. WIRED BY EC.
M2 1 BATTERY FOR DRAW BRIDGE, WIRED UNDER ANOTHER CONTRACT
PCWP-1 1 CHILLED WATER PUMP AND STARTER BY MC, WIRED BY EC
PCWP-2 1 CHILLED WATER PUMP AND STARTER BY MC, WIRED BY EC
PHWP-1 1 HOT WATER HEAT, PUMP AND STARTER BY MC, WIRED BY EC
PHWP-2 1 HOT WATER HEAT, PUMP AND STARTER BY MC, WIRED BY EC
SCU-1A 1 SPLIT SYSTEM AC UNIT FOR IC ROOM, PROVIDED AND INSTALLED BY MC, WIRED
BY EC
SCU-1B 1 SPLIT SYSTEM FAN COIL UNIT FOR IC ROOM, PROVIDED AND INSTALLED BY MC,
WIRED BY EC
Vac 1 BATTERY VACUUM PUMP, WIRED BY EC
VAVCP 6 VAV BOX CONTROL POWER. EC TO PROVIDE POWER TO A J-BOX ABOVE THE
CEILING AT LOCATIONS SHOWN. THESE ARE TO BE USED BY CONTROL
CONTRACTOR FOR POWER TO VAV BOXES
Grand total: 37
J
D1L6
EUH-2EL11 -
13,15
DDCEL11 - 2
AHU1S AHU1R
D1H6
EH11 -
13,15,17
EH11 -
14,16,18
D7H3
EF-1
LP22 -
11
H-1
D1H1
VAVCP
VAVCP
VAVCP
EL11 -
29
D1H1 - 1
EL11 -
31
EL11 -
27
SB2 - 8
CCD9H3
CLASSROOM
210
CLASSROOM
211
CLASSROOM
212
UNIT STORAGE
213
JAN.
214
CLASSROOM
215
CORRIDOR
205
MEN
209
WOMEN
208
LOBBY
201
STAIRS
203
BREAK AREA
207
ELEV
202
EQUIPMENT PLATFORM
216
GALLY & VENDING
206EF-2
LP22
LP22 -
10
WIRE TO SNAP SWITCH, SEE
LIGHTING PLAN FOR LOCATION
D1L3 - 1
SCU-1A
EL11 -
36,38
D1L3
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-208
SECOND FLOOR HVAC POWER PLAN
1/8" = 1'-0"1
SECOND FLOOR HVAC POWER PLAN
GRGW GR
GR
GR
GR
GW GR GR GR
GR GR GR GW
GR
GR
GRGR GR
GR
GR
GWGR
GRGRGR
GR
GR
GW
GR
MGBB
GRGW
GR
2/0 COPPER BARE CONDUCTOR CONTINUEOUS AROUND
BUILDING 2'6" TO 3'0" BELOW GROUND. 2'0" to 2'6" FROM
BUILDING FOOTING.
COPPER GROUND ROD, TYPICAL WHERE SHOWN.
2/0 TO BOND AT ALL GROUND RODS.
GROUND WELL WITH COPPER
GROUND ROD, TYPICAL WHERE SHOWN.
2/0 TO BOND AT ALL GROUND RODS.
CONNECTION POINT OF 2/0 COPPER GROUND
TO COPPER CONDUCTOR DROP FROM LIGHTNING
SYSTEM ON ROOF, TYPICAL WHERE SHOWN OR
AS REQUIRED.
1
E-602
TYPICAL LIGHTNING PROTECTION
CONDUCTOR UP TO ROOF
LIGHTNING RODS/SYSTEM.
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-300
LIGHTNING PROTECTION PLAN GROUND LEVEL
1/8" = 1'-0"1
GROUND LEVEL LIGHTNINGPROTECTION
RE
F.
1
E-602
OBSTRUCTION LIGHTS
CONTROLLED BY DEDICATED
PHOTO CELL PCAW
LA
LALA
LA
LA
LA
LA
LALA
LA
LA LA
LA
LA LALALA
LA LALA
LA LA LA
LA
LA
LA
LA
LA
LA
LA
LA
LALA
LALA
LA
LA
LA
LA
LA LA
LIGHTNING ROD ON METAL ROOF,
TYPICAL
DROP DOWN FROM ROOF SYSTEM
TO GROUND RING, TYPICAL AS SHOWN
LA
LALA
LALA
LA
LA
LA
LALA
LA
LA
LA
LA
LALALA
LA
LA
LALA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LAN
LAN
TYPICAL DROP2/0 AROUND BUILDING
LOCATIONS OF LIGHTNING RODS, APPROXIMATE
VIEW SHOWN FOR INTENT AND SHOULD NOT
BE USED AS A DESIGN GUIDE.
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-301
LIGHTNING PROTECTION ROOF PLAN,
OBSTRUCTION LIGHTS INFORMATION AND
LIGHTNING PROTECTION 3D
1/8" = 1'-0"1
ROOF LIGHTNING PROTECTION
2LIGHTNING PROTECTION 3D
JJ
J J
JJ
J
J
J
J
J
J
J
J
J
GHCP -
1
GHSCP
- 1
GPB
GPB
GPB
GPB
GPBGPB
GPB GPB
GPBGPB
GPBGPB
GPB
GPB
GPB
TYPICAL J-BOX USED TO SPLICE SUPPLY WIRES
WITH GUTTER HEATING CABLE. AFTER SPLICING,
PLACE GUTTER HEATING CABLE IN GUTTER, IN
ADDITION, RUN CABLE DOWN THE LENGTH OF
DOWNSPOUTS AND THEN BACK UP TO GUTTER.
INSTALL ENOUGH HEATING CABLE TO ENSURE
THAT EVERY HORIZONTAL AND VERTICAL LENGTH
OF GUTTERS AND DOWN SPOUTS ARE COVERED.
SEE ARCHITECTURALPLANS FOR EXACT
LOCATIONS, AND LENGTHS.
SS IS
IS
IS
LOCATE NEAR DOWNSPOUT
LOCATE NEAR DOWNSPOUT
LOCATE NEAR DOWNSPOUT
LOCATE NEAR
DOWN SPOUT
SS
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-302
GUTTER HEATER ROOF PLAN
1/8" = 1'-0"1
GUTTER HEATER ROOF PLAN
CR
J
CR
K
CR
CR
CR
CR
SECURITY LEGENDCARD READER
KEY PAD
SECURITY PANELSP
CR
K
PS PROXIMITY SWITCH
WM WALL MOUNTED MOTION SENSOR
CC CEILING CAMERA
OC OUTSIDE WALL MOUNTED CAMERA
CM CEILING MOTION DETECTOR
KP
CR
OC
OC
PS
SP
INSTALL 2 - 2" CONDUITS FROM
SECURITY PANELS DOWN INTO
IT ROOM BELOW
CR
EL11 - 1
CC
D9H3
LP22
LP21
CLASSROOM
210
CLASSROOM
211
CLASSROOM
212
UNIT STORAGE
213
JAN.
214
CLASSROOM
215
CORRIDOR
205
MEN
209
WOMEN
208
LOBBY
201
STAIRS
203
BREAK AREA
207
ELEV
202
EQUIPMENT PLATFORM
216
GALLY & VENDING
206
CR
KP
1
E-602
OC
CC
CR
PS
WM
WM
WM WM
WM
WM
WMWM
CM
CM
CM
CM
CM
CM
CM
LP11
T2
HP11
SB2
SB1
D1H2METER
LP12
OC
EMM
MSEMM
MSAW
MSA
MSSDHCB1
MSUPS
UPS
MSS-1P1
MSVAC
T3
EL11
GHSCPGHCP
EH11
MTS
D4H3
D3H3
D1H3
D2H3
D8H3
LP13
WST HIGH BAY
116
WST SIM MAINT PARTS
STOR
114
MAINT SUPV
115
WST COMPUTOR ROOM
DATA STORAGE
113
CORR
106
STAIR
104
INSTRUCTORS SUITE
110
PO/QAR (GOV'T)
109
SITE MGR (CONTRACT)
108PO/QAR STOR
107
RECEPTION
105
LOBBY
101COMM
117
ELEV
102
VESTIBULE
100MECHANICAL/FIRE
PROTECTION
118
MEN
111
WOMEN
112
STAIR
103
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-500
FIRST AND SECOND FLOOR SECURITY PLAN,
SECURITY DEVICE SCHEDULE AND SECURITY
LEGEND
SECURITY DEVICE SCHEDULE
Type Mark Count Manufacturer Description
CC 1 BY ADVANTOR DOME CEILING CAMERA, CABLE MAY BE RUN EXPOSED ABOVE DROP CEILING AND MAY RUN IN CABLE TRAY
CM 7 BY ADVANTOR CEILING MOTION SENSOR, RUN CABLE IN 3/4" CONDUIT BACK TO SECURITY PANEL
CR 6 BY ADVANTOR CARD READER, CABLE IN 3/4" CONDUIT BACK TO SECURITY PANEL
KP 1 BY ADVANTOR KEY PAD, RUN CABLE IN 3/4" CONDUIT BACK TO SECURITY PANEL
OC 4 BY ADVANTOR IMPACT-RESISTANT WALL MOUNTED DOME CAMERA, PROVIDE 3/4" FLEX FROM CAMERA TO BOX ON WALL THEN 3/4" CONDUIT WITH CAMERA CABLE BACK TO THESECURITY PANEL, CABLE MAY RUN IN CABLE TRAY
PS 2 BY ADVANTOR DOOR POSITION SENSOR, RUN CABLE IN 3/4" CONDUIT BACK TO SECURITY PANEL
SP 1 BY ADVANTOR SECURITY PANELS (2)
WM 9 BY ADVANTOR WALL MOTION SENSOR FOR SECURITY SYSTEM, MOUNT AT 9'0" AFF. RUN CABLE IN 3/4" CONDUIT BACK TO SECURITY PANEL
Grand total: 31
1/16" = 1'-0"2
SECOND FLOOR SECURITY
1/8" = 1'-0"1
FIRST FLOOR SECURITY
JUNCTION BOX
3/4" EMT CONDUIT TO SECURITY
CONDUIT SYSTEM
FINISHED CEILING
JUNCTION BOX
3/4" CONDUIT (TYP)
(6) REQUEST-TO-EXIT SENSOR (TYP)
SECURE SIDE OF
DOOR
FINISHED FLOOR
FLUSH BOLT
INACTIVE LEAF
2' - 6"
(5) EXIT BUTTON
3'-6"
DOUBLE ENTRY SECURITY DOOR DETAILNTS
(4) INCARD READER
REAR SIDE
(3) M62 MAGLOCK (TYP)
DOOR HEADER BLOC OUTJUNCTION BOX (TYP)
6" 6"
JUNCTION BOX
HEADER
DOOR M62
MAG LOCK
DOORSTOP
3/4" HOLE
3/4" CONDUIT
3/4" EMT CONDUIT TO SECURITY
CONDUIT SYSTEM
FINISHED CEILING
3/4" CONDUIT (TYP)
(1) 3/4" CONDUIT (TYP)
3/4" CONDUIT (TYP)
(3) M62 MAGLOCK (TYP)
JUNCTION BOX
JUNCTION BOX
EXIT BUTTON
3/4" CONDUIT (TYP)
REQUEST-TO-EXIT SENSOR
SECURE SIDE OF
DOORFINISHED FLOOR
UN-SECURE
SIDE OF
DOOR
(4) INCARD READER (TYP)
STRIKEPLATE
3'-6"
1.
2.
NTS
SINGLE ENTRY SECURITY DOOR DETAIL
NOTES:
(1) ALL SENSORS TO BE D2939 CEILING MOUNT
PIR INTRUSION DETECTORS WITH WIRE TO BE
RUN IN EMT TO MOTION SENSOR PANEL
(2) ALL WIRE SHALL BE RUN IN EMT.
(3) M62 MAG LOCK - WITH TSC-20 TAMPER
SWITCH INCLUDES DOOR POSITION SWITCH
(4) CARD READER - MULTICLASS CARD READER
(5) EXIT BUTTON - 5TH SERIES 2000 STOPPER
STATION
(6) REQUEST TO EXIT DETECTOR - DS150i / DS151i
(7) KEY PAD - INGRAGUARD TOUCH SCREEN KEY
PAD
(8) ALL JUNCTION BOXES TO CONTAIN TAMPER
SWITCHES
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-501
SECURITY SYSTEM INSTALLATION DETAILS
TV
M
s
TV
J1 J1
J1J1
RACK
CABLE TRAY AND UNDER FLOOR RACEWAY LEGEND
CABLE TRAY AND FLOOR DUCT WIDTH AND DEPTH AS INDICATED, LENGTH AS SHOWN24X12
LP13
SB2 SB1
D1H2
J2
J2
J2
16"x4"
16"x4"
12"x1 1/2"
12"x1 1/2"
12"x1 1/2"
J1
J1
J1J1
J1 J1 J1
J1
J1
J1J1J1
J1
J1
J1
J1
J1
J1
J1
J1
T2
E-6024
1
E-602
J1
J1
12"x1 1/2"
J1
J1
J1J1
J1
D2
PULL 32 CAT6 (24 BLUE AND 8 YELLOW)
AND 8 FIBER FOR FUTURE JACKS. CABLES
SHALL BE RUN TO JUNCTION BOXES
USING CABLE TRAY AND 1" CONDUIT. COIL
15' OF EACH ABOVE CEILING AND STORE
IN JUNCTION BOXES.TERMINATE COPPER
IN PANEL DP9 AND VP3 ACCORDING TO
PURPOSE AND FIBER IN FP2. SEE PANEL
SCHEDULES.
DUCT RUN
UNDERNEATH
SIMULATOR
BD1
EMM
MSEMM
MSA
LP12
UPS
MSS-1
P1
T3
EL11
GHCPGHSCP
D1H3
D2H3
D3H3
D4H3
D5H3
D6H3LP11 T2
HP11METER
MTS
EH11D8H3
MSAW
LOCATE IN FIRE
ALARM/MASS
NOTIFICATION
PANEL
BD2
BD1 AND BD2 JOIN
DESK DESK
DESK
S2 S1
S1
DESKS AND CABINET
ENCLOSURES TO BE
PROVIDED BY OTHERS
D1
D1
DESK
DESK12"x1 1/2"
VC1
S2
D1
CRAC-1
PDU
MSPDU
MSUPS
HCB1MSSD
M2WST HIGH BAY
116
WST SIM MAINT PARTS
STOR
114
MAINT SUPV
115
WST COMPUTOR ROOM
DATA STORAGE
113
CORR
106
STAIR
104
INSTRUCTORS SUITE
110
PO/QAR (GOV'T)
109
SITE MGR (CONTRACT)
108PO/QAR STOR
107
RECEPTION
105
LOBBY
101COMM
117
ELEV
102
VESTIBULE
100MECHANICAL/FIRE
PROTECTION
118
MEN
111
WOMEN
112
STAIR
103
D3
JBD JBD
JBDJBD
CABLE TRAY WATERFALL
SUPPORT CABLE TRAYS USING
TRIANGLE BRACKETS, WALL
ANGLES, AND CENTER SUPPORT
KITS.
THE E.C. SHALL INSTRUCT THE M.C. THAT
DUCTWORK MUST NOT INTERFERE WITH
ACCESS TO THE TOP LOADING CABLE
TRAY AT ANY POINT IN ITS TRAVELS. IF
THE DUCTWORK MUST GO OVER TOP OF
THE CABLE TRAY, A MINIMUM CLEARANCE
OF 1' MUST BE MAINTAINED
TEMPORARILY SEAL THE OPENING BETWEEN THE LOWERED
FLOOR AND THE FLOOR DUCT. PERMANENT SEAL WILL BE
REQUIRED AFTER THE SIMULATOR EQUIPMENT WIRING HAS
BEEN INSTALLED.
DUCT RUN UNDERNEATH
EMM
T3
TELE/DATA LEGEND
TV
COMBINATION VOICE/DATA WALL OUTLET
DATA WALL OUTLET
DATA OUTLET MOUNTED IN CEILING
CATEGORY TV OUTLET
VERTICAL CABLE MANAGER
2 POST FLOOR STANDING RACK
4 POST FLOOR STANDING RACK
J1 "J" DENOTES COMBINATION VOICE/DATA JACK, "1"
DENOTES SPECIFIC CONFIGURATION. SEE SCHEDULE
J1 JUNCTION BOX FOR FUTURE DATA CIRCUITS
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-600
FIRST FLOOR TELE/DATA FLOOR PLAN, DATA
DEVICE, CABLE TRAY & UNDER FLOOR RACEWAY
SCHEDULES, TELE/DATA & CABLE TRAY & UNDER
FLOOR RACEWAY LEGENDS
1/8" = 1'-0"1
FIRST FLOOR TELE/DATA
CABLE TRAY SCHEDULE
Type Width Height Description
Ladder Cable Tray 12" 1 1/2" TRAY WITH ALL REQUIRED FITTINGS
Ladder Cable Tray 18" 1 1/2" TRAY WITH ALL REQUIRED FITTINGS
Wire Mesh Cable Tray 16" 4" WIRE MESH TRAY WITH ALL REQUIRED FITTINGS
Grand total: 19
DATA DEVICE SCHEDULE
Type Mark Count Description
BEP 1 BUILDING ENTRANCE PROTECTOR FOR 25 PAIR COPPER TERMINATION, 110 IDC
D1 10 SHEILDED CATEGORY 6 DATA DROP
D2 5 CEILING MOUNTED SINGLE GANG 2 DATA LOCATION FOR PROJECTOR
D3 3 SINGLE CATEGORY 6 DATA DROP
FA 1 2RU RACK MOUNTED FIBER ENCLOSURE WITH (4) LC ADAPTER PLATES (5F100-4QL)AND (2) SPLICE TRAYS INSTALLED
HCM 18 Double Sided Cable Manager
J1 57 Single Gang Combination 3 Data/1 Voice/1 Duplex LC Fiber Outlet Location
J2 3 Single Gang Combination 3 Data/1 Voice/1 Duplex LC Fiber Outlet Location MOUNTED AT3' FOR RECEPTION DESK
JBD 4 J-BOX ABOVE CEILING WITH CIRCUITS FOR FUTURE DATA TO FURNITURE. RUN 1"CONDUIT BACK TO WITHIN 1' OF CABLE TRAY AND BOND AS SHOW IN SECTION 1 ONSHEET E-603
PR1 2 Universal Rack with Two Top Angles
PR2 1 Open Floor Mount Rack Supports 19inch EIA Wide Rack_Mount Equipment
S1 2 Cabinet and Enclosure System To Be Provided By Others
S2 2 Cabinet and Enclosure System To Be Provided By Others
T1 1 DUAL VOICE OUTLET MOUNTED AT TOP OF ELEVATOR SHAFT
T2 1 DUAL VOICE OUTLET MOUNTED IN FIRE ALARM PANEL
T3 1 DUAL VOICE OUTLET
TB 1 4X6 FIRE TREATED PLYWOOD BACKBOARD MOUNTED ON 2 INCH STAND OFFS
VC1 1 Cabinet and Enclosure System To Be Provided By Others
VCM1 5 Double-Sided Vertical Cable Management
Grand total: 119
UNDERFLOOR RACEWAY ASSEMBLY SCHEDULE
Type Mark Count Description
BD1 1 UNDERFLOOR RACEWAY 24" WIDE X 12" DEEP X LENGTH AS SHOWN
BD2 1 UNDERFLOOR RACEWAY 24" WIDE X 12" DEEP X LENGTH AS SHOWN
TV T
V
TV
TV
TV
J
J1J1
J1
J1 J1
J1
J1
J1
J1
J1J1 J1
J1
J1
J1
J1
J1J1
J1
J1
J1
J1
D1D1
D1
D1
D1
D1
D1
D1
1
E-602
J1
D2
D2
D2D2
D3
D3MOUNT DATA DROP
FOR USE WITH H-1
HUMIDIFIER
J1
J1
J1
J1
J1
J1
CLASSROOM
210
CLASSROOM
211
CLASSROOM
212
UNIT STORAGE
213
JAN.
214
CLASSROOM
215
CORRIDOR
205
MEN
209
WOMEN
208
LOBBY
201
STAIRS
203
BREAK AREA
207
ELEV
202
EQUIPMENT PLATFORM
216
GALLY & VENDING
206
J1
J1 & J2
D1 D2
T1 & T2
DATA 1
(BLUE)
DATA 3
(BLUE)
DATA 2
(BLUE)
FIBER 1
(BROWN)
VOICE 1
(YELLOW)
SECURED DATA 1
(GRAY)
DATA 1
(BLUE)
DATA 2
(BLUE)
VOICE 1
(YELLOW)VOICE 2
(YELLOW)LABELING EXAMPLE
212.2
212 = IT ROOM CONTAINING RACK ASSOCIATED
WITH THIS OUTLET 2= RACK NUMBER
4.1
4.3
4.5
4.2
4.4
4.6
GENERAL NOTES:
1. FILL ALL EMPTY PORTS IN FACEPLATES WITH BLANK MODULES
2. CABLES SHALL BE TERMINATED IN EACH JACK USING T568A PIN/PAIR ASSIGNMENT.
3. USE CENTER KEYED RJ-45 JACKS.
4. LABEL EACH PORT STARTING WITH THE FIRST RECEPTACLE TO THE LEFT WHEN
ENTERING A ROOM. LABEL PORTS FROM TOP LEFT TO BOTTOM RIGHT BEFORE
PROCEEDING TO NEXT RECEPTACLE IN A CLOCKWISE MANNER AROUND THE ROOM.
LAST TO BE LABELED ARE CEILING RECEPTACLES
DATA OUTLET CONFIGURATION DETAILNTS
D3
DATA 1
(BLUE)
TV
TV (ORANGE)
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-601
SECOND FLOOR TELE/DATA FLOOR PLAN, TV
DEVICE SCHEDULE AND DATA OUTLET
CONFIGURATION DETAIL
1/8" = 1'-0"1
SECOND FLOOR TELE/DATA
TV DEVICE SCHEDULE
Type Mark Count Description
TV 7 CABLE TV LOCATION MOUNTED AT 5' FOR WALL MOUNT TV WITH CAT 6 CABLE BACK TO IT ROOM
Grand total: 7
Level 1100' - 0"
Level 2114' - 0"
16"x4"
J1
TV (2)
J1
J1
J1
TYPICAL DATA/VOICE DROPS UTILIZE A 4
11/16" SQUARE BOX WITH 6-PORT SINGLE
GANG FACEPLATE OUTFITTED WITH (3)
BLUE RJ-45 DATA JACKS, (1) YELLOW RJ-
45 VOICE JACK, AND ONE BEIGE DUPLEX
LC FIBER JACK. FILL ADDITIONAL SPACES
IN FACEPLATES WITH BLANK MODULES
TYPICAL TV JACK LOCATION FEATURES BLACK RJ-
45 JACK WITH CATEGORY 6 CABLE BACK TO IT
ROOM
1' - 0"
#10AWG OR LARGER
GROUNDING WIRE
BRING CONDUITS TO
WITHIN 1' OF CABLE TRAY
ALL DROPS FEATURE 1"
CONDUIT FROM BOX BACK
TO CABLE TRAY
PEDISTALS99' - 6" *SEE CONDUIT DETAIL RENDERING FOR 3D REPRESENTATAION
MARK CABLE TRAY AND CONDUITS AT
5' WITH LABELS IDENTIFYING THEM AS
COMMUNICATIONS CABLING.
IDENTIFY CONDUITS AND
CABLE TRAY AT 10'
INTERVALS ACCORDING TO
SECTION 16075 IN THE
SPECIFICATIONS
CONDUIT DETAIL RENDERING
WIRE MESH CABLE TRAY
1" CONDUIT TO
WITHIN 1' OF
CABLE TRAY
DATA/VOICE/FIBER DROPS (J1)
**SEE JACK DETAIL
RACK RENDERING
WIRE MESH CABLE TRAY EXITS COMM ROOM AND IS THEN
SUPPORTED UNDERNEATH STAIRS TO 1ST FLOOR CEILING
PLENUM
WATERFALL TO ENSURE
PROPER BEND RADIUS
TERMINAL
BACKBOARD
BUILDING
ENTRANCE
PROTECTOR
(BEP)
SERVICE ENTRANCE**SEE RACK SECTION OF SHEET E-
603 FOR MORE INFORMATION ON
COMM ROOM CONFIGURATION
3
E-603
18"x1 1/2"
18"x1 1/2"
LINE ALL WALLS WITH VOID-FREE FIRE
RATED OR TREATED PLYWOOD, 8FT HIGH
WITH GRADE C SIDE FACING THE WALL.
TB
TGBB
VCM1
VCM1
PR2
PR1
FA
HCM
SERVICE IN
J1
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-602
COMM ROOM CALLOUT, DETAILS AND RENDERINGS
1/2" = 1'-0"1
JACK DETAIL
1" = 1'-0"4
Callout of FIRST FLOOR TELE/DATA
Level 1100' - 0"
TGBB
0' -
6"
0' - 10 15/16"
3' - 3 1/2"
CHATSWORTH LADDER
STYLE CABLE TRAY
SUPPORTED USING
TRIANGLE WALL
BRACKETS AND WALL
ANGLE KITS AS
NECESSARY
UL LISTED UNIVERSAL 2-POST RACK
(CHATSWORTH 48353-703 OR SIMILAR)
CHATSWORTH VELOCITY VERTICAL
CABLE MANAGEMENT SYSTEM OR
SIMILAR (VCM)
UNIVERSAL DOUBLE
SIDED HORIZONTAL
CABLE MANAGER
(CHATSWORTH 30530-719
OR SIMILAR)
*EVERY RACK AND CABLE TRAY
MUST BE GROUNDED. IN
ADDITION, GROUND EVERY PIECE
OF EQUIPMENT TO VERTICAL
BUSS BARS LOCATED ON RACKS
USING SUPPLIED JUMPER
CABLES. CONNECT VERTICAL
BUSS BARS TO TGBB USING 2/0
COPPER CABLE.
GROUND LADDER TRAY TO VERTICAL BUSS BAR
USING #6 WIRE. GROUND BUSS BAR TO TGBB
LOCATED ON TERMINAL BACKBOARD
FIBER ENCLOSURE WITH LC
FIBER ADAPTER PLATES AND
SPLICING TRAYS INSTALLED
LARGE RADIUS DROP (CHATSWORTH 34747-701)
4-POST FRAME (CHATSWORTH
50120-703 OR SIMILAR)
ANCHOR TRAY TO RACK USING
CHATSWORTH ELEVATION KIT (10506-
706) AND MOUNTING PLATE (10595-718)
CABLE RUNWAY RADIUS DROP
(CHATSWORTH 12100-718)
FA
HCM
HCM
HCM
HCM
HCM
HCMSERVICE ENTRANCE IN
(2) 4" CONDUITS FROM
IT VAULT
HCM
HCM
HCM
HCM
HCM
HCM
HCM
HCM
HCM
HCM
HCM
DP1
DP2
DP3
DP9DP4
FP1
FP2
DP5
DP6
DP7
DP8
VP1
VP2
VP3
SP1
DP# =DATA PATCH PANEL (PP)
FP# = FIBER PATCH PANEL(FPP)
VP# = VOICE PATCH PANEL (VPP)
SP# = SECURED DATA PATCH
PANEL (SPP)
TV# = TV PATCH PANEL (TVPP)
SEE DATA EQUIPMENT SCHEDULE
FOR DESCRIPTIONS OF EACH
PEDISTALS99' - 6"
BEP
TVP1
RESERVE FOR
NETWORK
EQUIPMENT TO
BE SUPPLIED
BY
CONTRACTING
OFFICER
TYPICAL DATA PATCH PANEL
TYPICAL VOICE PATCH PANEL
USE PORTS 1-24 FOR "DATA"
RUNS TO OUTLETS. LEAVE
REMAINING PORTS FOR
FUTURE EXPANSION
USE PORTS 1-24 FOR "VOICE"
RUNS TO OUTLETS. LEAVE
REMAINING PORTS FOR
FUTURE EXPANSION
GENERAL NOTES:
1. ALL CABLES FROM RECEPTACLES SHALL BE TERMINATED
ON BACK OF PATCH PANELS
2. LABEL EACH PATCH PANEL TO REFLECT NAME, EX. "DP1"
3. LABEL EACH PORT IN PATCH PANELS ACCORDING TO THE
PORT IT REPRESENTS IN A PARTICULAR FACEPLATE
4. ALLOW FOR SPARE CIRCUITS IN EACH PATCH PANEL (SEE
PANEL SCHEDULES FOR EXACT CONFIGURATION)
5. FIBER PATCH PANEL FEATURES DUPLEX LC (ZICONIA
CIRAMIC SLEEVED) PORTS.
6. TV PATCH PANELS ARE OUTFITTED WITH CATEGORY 6
JACKS.
PATCH PANEL DETAILNTS
TYPICAL SHEILDED PATCH PANEL
USE PORTS 1-24 FOR
"SECURED DATA" RUNS
OUTFIT FIBER ENCLOSURE WITH SPLICE
TRAYS AND ADAPTER PANELS FOR USE
WITH BACKBONE TERMINATION AND
PATCHING APPLICATIONS
TYPICAL FIBER ENCLOSURE
TYPICAL FIBER PATCH PANEL
USE PORTS 1-36 FOR "FIBER"
RUNS TO OUTLETS. LEAVE
REMAINING PORTS FOR
FUTURE EXPANSION
TYPICAL TV PATCH PANEL
USE PORTS 1-24 FOR
"TV" RUNS
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-603
RACK SECTION, DATA EQUIPMENT SCHEDULE AND
PATCH PANEL DETAIL
1" = 1'-0"3
RACK SECTION
DATA EQUIPMENT SCHEDULE
Type Mark Count Manufacturer Model Description
FPP 2 LEVITON 49255-D72 72-PORT PATCH PANEL WITH DUPLEX LC FIBER ADAPTERS
INSTALLED. FEATURING INTEGRADED CABLE MANAGEMENT BAR
PP 9 LEVITON 69270-U48 48 PORT CATEGORY 6 110-STYLE PATCH PANEL FEATURING
INTEGRATED CABLE MANAGMENT BAR
SPP 1 LEVITON 4S255-S24 24 PORT SHIELDED PATCH PANEL FEATURING CATEGORY 6
SHEILDED JACK MODULES
TVPP 1 LEVITON 69270-U24 24 PORT CATEGORY 6 PATCH PANEL, 110 IDC, INTENDED FOR TV
CIRCUITS
VPP 3 LEVITON 69270-U48 48 PORT CATEGORY 6 110-STYLE PATCH PANEL FEATURING
INTEGRATED CABLE MANAGMENT BAR. INTENDED FOR VOICE
CIRCUITS
Grand total: 16 16
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-604
DATA PANEL SCHEDULES
DATA PANELS SCHEDULE
CircuitNumber Load Name
DP1
1 Data RECEPTION 105
2 Data RECEPTION 105
3 Data RECEPTION 105
4 Data PO/QAR STOR 107
5 Data SITE MGR (CONTRACT) 108
6 Data SITE MGR (CONTRACT) 108
7 Data PO/QAR (GOV'T) 109
8 Data PO/QAR (GOV'T) 109
DP2
1 Data INSTRUCTORS SUITE 110
2 Data INSTRUCTORS SUITE 110
3 Data INSTRUCTORS SUITE 110
4 Data INSTRUCTORS SUITE 110
5 Data INSTRUCTORS SUITE 110
6 Data INSTRUCTORS SUITE 110
7 Data INSTRUCTORS SUITE 110
8 Data INSTRUCTORS SUITE 110
DP3
1 Data INSTRUCTORS SUITE 110
2 Data MAINT SUPV 115
3 Data MAINT SUPV 115
4 Data WST SIM MAINT PARTS STOR 114
5 Data WST SIM MAINT PARTS STOR 114
6 Data WST SIM MAINT PARTS STOR 114
7 Data WST SIM MAINT PARTS STOR 114
8 Data WST COMPUTOR ROOM DATA STORAGE 113
DP4
1 Data WST COMPUTOR ROOM DATA STORAGE 113
2 Data WST COMPUTOR ROOM DATA STORAGE 113
3 Data WST COMPUTOR ROOM DATA STORAGE 113
4 Data WST COMPUTOR ROOM DATA STORAGE 113
5 Data WST COMPUTOR ROOM DATA STORAGE 113
6 Data WST COMPUTOR ROOM DATA STORAGE 113
8 Data COMM 117
DP5
1 Data LOBBY 201
2 Data EQUIPMENT PLATFORM 216
3 Data WST HIGH BAY 116
4 Data CLASSROOM 210
5 Data CLASSROOM 210
6 Data CLASSROOM 210
7 Data CLASSROOM 210
8 Data CLASSROOM 210
9 Data CLASSROOM 210
10 Data CLASSROOM 210
DP6
1 Data CLASSROOM 211
2 Data CLASSROOM 211
3 Data CLASSROOM 211
4 Data CLASSROOM 211
5 Data CLASSROOM 211
6 Data CLASSROOM 211
7 Data CLASSROOM 211
DP7
1 Data CLASSROOM 212
2 Data CLASSROOM 212
3 Data CLASSROOM 212
4 Data CLASSROOM 212
5 Data CLASSROOM 212
6 Data CLASSROOM 212
7 Data UNIT STORAGE 213
8 Data UNIT STORAGE 213
9 Data
DP8
1 Data CLASSROOM 215
2 Data CLASSROOM 215
3 Data CLASSROOM 215
4 Data CLASSROOM 215
5 Data CLASSROOM 215
6 Data CLASSROOM 215
7 Data CLASSROOM 215
8 Data CLASSROOM 215
9 Data CLASSROOM 215
10 Data
DP9
1 Data INSTRUCTORS SUITE 110 (FOR FUTURE USE)
2 Data INSTRUCTORS SUITE 110 (FOR FUTURE USE)
3 Data INSTRUCTORS SUITE 110 (FOR FUTURE USE)
4 Data INSTRUCTORS SUITE 110 (FOR FUTURE USE)
FIBER PANELS SCHEDULE
CircuitNumber Load Name
FP1
1 Fiber RECEPTION 105
2 Fiber RECEPTION 105
3 Fiber RECEPTION 105
4 Fiber PO/QAR STOR 107
5 Fiber SITE MGR (CONTRACT) 108
6 Fiber SITE MGR (CONTRACT) 108
7 Fiber PO/QAR (GOV'T) 109
8 Fiber PO/QAR (GOV'T) 109
9 Fiber INSTRUCTORS SUITE 110
10 Fiber INSTRUCTORS SUITE 110
11 Fiber INSTRUCTORS SUITE 110
12 Fiber INSTRUCTORS SUITE 110
13 Fiber INSTRUCTORS SUITE 110
14 Fiber INSTRUCTORS SUITE 110
15 Fiber NSTRUCTORS SUITE 110
16 Fiber INSTRUCTORS SUITE 110
17 Fiber MAINT SUPV 115
18 Fiber MAINT SUPV 115
19 Fiber WST SIM MAINT PARTS STOR 114
20 Fiber WST SIM MAINT PARTS STOR 114
21 Fiber WST SIM MAINT PARTS STOR 114
22 Fiber WST SIM MAINT PARTS STOR 114
23 Fiber WST COMPUTOR ROOM DATA STORAGE 113
24 Fiber WST COMPUTOR ROOM DATA STORAGE 113
25 Fiber WST COMPUTOR ROOM DATA STORAGE 113
26 Fiber WST COMPUTOR ROOM DATA STORAGE 113
27 Fiber WST COMPUTOR ROOM DATA STORAGE 113
28 Fiber WST COMPUTOR ROOM DATA STORAGE 113
29 Fiber WST COMPUTOR ROOM DATA STORAGE 113
30 Fiber COMM 117
31 Fiber LOBBY 201
32 Fiber CLASSROOM 210
33 Fiber CLASSROOM 210
34 Fiber CLASSROOM 210
35 Fiber CLASSROOM 210
36 Fiber CLASSROOM 210
37 Fiber CLASSROOM 210
FP2
1 Fiber CLASSROOM 211
2 Fiber CLASSROOM 211
3 Fiber CLASSROOM 211
4 Fiber CLASSROOM 211
5 Fiber CLASSROOM 211
6 Fiber CLASSROOM 211
7 Fiber CLASSROOM 212
8 Fiber CLASSROOM 212
9 Fiber CLASSROOM 212
10 Fiber CLASSROOM 212
11 Fiber CLASSROOM 212
12 Fiber CLASSROOM 212
13 Fiber UNIT STORAGE 213
14 Fiber UNIT STORAGE 213
15 Fiber CLASSROOM 215
16 Fiber CLASSROOM 215
17 Fiber CLASSROOM 215
18 Fiber CLASSROOM 215
19 Fiber CLASSROOM 215
20 Fiber CLASSROOM 215
21 Fiber CLASSROOM 215
22 Fiber CLASSROOM 215
23 Fiber CLASSROOM 215
24 Fiber INSTRUCTORS SUITE 110 (FOR FUTURE USE)
25 Fiber INSTRUCTORS SUITE 110 (FOR FUTURE USE)
26 Fiber INSTRUCTORS SUITE 110 (FOR FUTURE USE)
27 Fiber INSTRUCTORS SUITE 110 (FOR FUTURE USE)
VOICE PANELS SCHEDULE
CircuitNumber Load Name
TVP1
1 Communication INSTRUCTORS SUITE 110
2 Communication INSTRUCTORS SUITE 110
3 Communication LOBBY 201
4 Communication CLASSROOM 210
5 Communication CLASSROOM 211
6 Communication CLASSROOM 212
7 Communication CLASSROOM 215
VP1
1 Telephone MECHANICAL/FIRE PROTECTION 118
2 Telephone RECEPTION 105
3 Telephone RECEPTION 105
4 Telephone RECEPTION 105
5 Telephone PO/QAR STOR 107
6 Telephone SITE MGR (CONTRACT) 108
7 Telephone SITE MGR (CONTRACT) 108
8 Telephone PO/QAR (GOV'T) 109
9 Telephone PO/QAR (GOV'T) 109
10 Telephone INSTRUCTORS SUITE 110
11 Telephone INSTRUCTORS SUITE 110
12 Telephone INSTRUCTORS SUITE 110
13 Telephone INSTRUCTORS SUITE 110
14 Telephone INSTRUCTORS SUITE 110
15 Telephone INSTRUCTORS SUITE 110
16 Telephone INSTRUCTORS SUITE 110
17 Telephone INSTRUCTORS SUITE 110
18 Telephone MAINT SUPV 115
19 Telephone MAINT SUPV 115
20 Telephone WST SIM MAINT PARTS STOR 114
21 Telephone WST SIM MAINT PARTS STOR 114
22 Telephone WST SIM MAINT PARTS STOR 114
23 Telephone WST SIM MAINT PARTS STOR 114
24 Telephone WST COMPUTOR ROOM DATA STORAGE 113
25 Telephone WST COMPUTOR ROOM DATA STORAGE 113
VP2
1 Telephone WST COMPUTOR ROOM DATA STORAGE 113
2 Telephone WST COMPUTOR ROOM DATA STORAGE 113
3 Telephone WST COMPUTOR ROOM DATA STORAGE 113
4 Telephone WST COMPUTOR ROOM DATA STORAGE 113
5 Telephone WST COMPUTOR ROOM DATA STORAGE 113
6 Telephone MECHANICAL/FIRE PROTECTION 118
7 Telephone COMM 117
8 Telephone ELEV 202
9 Telephone LOBBY 201
10 Telephone CLASSROOM 210
11 Telephone CLASSROOM 210
12 Telephone CLASSROOM 210
13 Telephone CLASSROOM 210
14 Telephone CLASSROOM 210
15 Telephone CLASSROOM 210
16 Telephone CLASSROOM 211
17 Telephone CLASSROOM 211
18 Telephone CLASSROOM 211
19 Telephone CLASSROOM 211
20 Telephone CLASSROOM 211
21 Telephone CLASSROOM 211
22 Telephone CLASSROOM 212
23 Telephone CLASSROOM 212
24 Telephone CLASSROOM 212
VP3
1 Telephone CLASSROOM 212
2 Telephone CLASSROOM 212
3 Telephone CLASSROOM 212
4 Telephone UNIT STORAGE 213
5 Telephone UNIT STORAGE 213
6 Telephone CLASSROOM 215
7 Telephone CLASSROOM 215
8 Telephone CLASSROOM 215
9 Telephone CLASSROOM 215
10 Telephone CLASSROOM 215
11 Telephone CLASSROOM 215
12 Telephone CLASSROOM 215
13 Telephone CLASSROOM 215
14 Telephone CLASSROOM 215
15 Telephone INSTRUCTORS SUITE 110 (FOR FUTURE USE)
16 Telephone INSTRUCTORS SUITE 110 (FOR FUTURE USE)
17 Telephone INSTRUCTORS SUITE 110 (FOR FUTURE USE)
18 Telephone INSTRUCTORS SUITE 110 (FOR FUTURE USE)
TV AND SECURED DATA PANEL SCHEDULES
CircuitNumber Load Name
SP1
1 Secured Data WST COMPUTOR ROOM DATA STORAGE 113
2 Secured Data WST COMPUTOR ROOM DATA STORAGE 113
3 Secured Data CLASSROOM 210
4 Secured Data CLASSROOM 210
5 Secured Data CLASSROOM 211
6 Secured Data CLASSROOM 211
8 Secured Data CLASSROOM 212
9 Secured Data CLASSROOM 212
10 Secured Data CLASSROOM 215
11 Secured DataCLASSROOM 215
TVP1
1 Communication INSTRUCTORS SUITE 110
2 Communication INSTRUCTORS SUITE 110
3 Communication LOBBY 201
4 Communication CLASSROOM 210
5 Communication CLASSROOM 211
6 Communication CLASSROOM 212
7 Communication CLASSROOM 215
MS
H
S
SD
RE
F.
S
S
S
S S
S
S S
SS
S
S
S
s
s
s
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SS
s
M
M
M
MM
M
M
M
M
M
M
M
M
s
M1
M1
M1
M
F
S
S MM
M
M
s
TV
M1
M1
M1
M1
M1
mmmmmm mm
FIRE ALARM AND MASS NOTIFICATION LEGEND
FACP FIRE ALARM CONTROL PANEL AND MASS NOTIFICATION
FARA FIRE ALARM REMOTE ANNUNCIATOR PANEL
M
FIRE ALARM STROBEFS
MONITOR MODULE
CONTROL MODULE
FLOW SWITCH WITH MONITOR MODULE
TAMPER SWITCH WITH MONITOR MODULE
FS
TS
SP ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR
ADDRESSABLE HEAT DETECTORHD
PS ADDRESSABLE PULL STATION
M1
MM
CEILING SPEAKER. FIRE ALARM/
MASS NOTIFICATIONFM
WALL SPEAKER HORN, FIRE ALARM/
MASS NOTIFICATION
SWS
HIGH POWERED EXTERIOR WALL SPEAKER HORN, FIRE ALARM/
MASS NOTIFICATION.SHPS
MS MASS NOTIFICATION STROBE
DUCT SMOKE DETECTOR
F EXTERIOR SPEAKER /STROBESS
LOC LOCAL OPERATING CONSOLE
FS
FS
FS
PS
PS
SP SP
FACPFARA
FLSTS
TS
SP
FM
FM
FM
FMFM
FM
FM
FM
WS
WS
LP12
SB2 SB1
LP13
D4
MSEMM
MSA
MSAW
PS
PS
PS
SP
SP
SP
SP
SP
TS
FS
FM
FM
FM
FS
FM
FS
FS
FS
FM FS
FS
FS
FM
D1H2
HPSMETER
MS
MS
MS
MS
MS
MS
MS
MSMSMS
MS
MS
FS
MS
FM
MSSD
MSVAC
MSUPS
HCB1
HPS
1
E-602
MMKB
SS
HP11
LP11
FS
FS MS
MS
MS
MS
EL11 - 3
LOC
HPS
NOTE: SEE THE CONTRACT SPECIFICATIONS FOR ALL
SURGE PROTECTION REQUIREMENTS FOR 120 VOLT TO
24 VOLT EQUIPMENT. PROVIDE EDCO # HSP-121A
SURGE PROTECTORS.
EL11T3
EH11
EMM
UPS
MSS-1P1
T2
MTS
GHCP
GHSCP
WOOD MOUNTING PLATE,
SEE ARCHITECTURAL
DRAWINGS
WST HIGH BAY
116
WST SIM MAINT PARTS
STOR
114
MAINT SUPV
115
WST COMPUTOR ROOM
DATA STORAGE
113
CORR
106
STAIR
104
INSTRUCTORS SUITE
110
PO/QAR (GOV'T)
109
SITE MGR (CONTRACT)
108PO/QAR STOR
107
RECEPTION
105
LOBBY
101COMM
117
ELEV
102
VESTIBULE
100MECHANICAL/FIRE
PROTECTION
118
MEN
111
WOMEN
112
STAIR
103
LOCATE ABOVE FIRE DEPARTMENT
HOSE CONNECTION, FIELD VERIFY
LOCATION.
M M
USE FOR PRESSURE SENSOR
AND PREACTION PANEL MONITORING
FLS
MMCMMC
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-700
FIRST FLOOR FIRE ALARM AND MASS
NOTIFICATION PLAN, FIRE ALARM DEVICE
SCHEDULE AND FIRE ALARM AND MASS
NOTIFICATION LEGENDS
FIRE ALARM DEVICE SCHEDULE
Type Mark Count Description
D4 1 SMOKE DETECTOR PANEL BY LOCKHEED
DD 2 ADDRESSABLE DUCT DETECTOR, INSTALL IN AHU ANDWIRE TO FIRE ALARM SYSTEM, PROVIDE REMOTE TEST ANDLIGHT IN ROOM AT THE UNIT. WIRE INTO DDC SYSTEM FORAHU-1 SHUT DOWN
FACP 1 ADDRESSABLE FIRE ALARM CONTROL PANEL AND MASSNOTIFICATION (PROVIDE EDCO # HSP-121A SURGEPROTECTION)
FARA 1 REMOTE FIRE ALARM ANNUNCIATOR PANEL
FLS 2 FIRE ALARM FLOW SWITCH WITH MONITER MODULE
FS 26 FIRE ALARM STROBE
H 1 ADDRESSABLE HEAT DETECTOR
LOC 2 LOCAL OPERATOR CONSOLE STATION FOR MASSNOTIFICATION SYSTEM
M 2 MONITOR MODULE
M1 8 ADDRESSABLE OUTPUT MODULE, WIRED TO CONTROLSHUNT TRIP BREAKER
MMC 2 MONITOR MODULE FOR CONNECTION TO DUCTDETETECTORS PROVIDED WITH THE CRAC- 1 UNIT
MMKB 1 MONITOR MODULE FOR KNOX BOX, LOCATED AT 5'0"
PS 8 PULL STATION, ADDRESSIBLE, MOUNT AT 3'4"
SP 10 CEILING MOUNTED SMOKE DETECTOR, ADDRESSIBLE
SS 1 SPEAKER STROBE WEATHERPROOF
TS 3 TAMPER SWITCH
Grand total: 71
1/8" = 1'-0"1
FIRST FLOOR FIRE ALARM/MASSNOTIFICATION SYSTEM
SS
S
S
S
S
S
S
S
S
S
S S
S
S
S
S
S
SS
S
S
S
S
S
M M
M
M
M
M
MM
M
M
M
TV
J
SD
SD
S
FS
FS
PS
PS
FM
FM
FM
FM
FM
FM
FM
FM
FM
FMFS
FS
FSFS
FS
FMFM
FM
FS
SP
MS
MS
FS
FS
MS MS
MSFS
MS
MS
MSMS
MS
MS
1
E-602
LOC
NOTE: SEE THE CONTRACT SPECIFICATIONS FOR ALL
SURGE PROTECTION REQUIREMENTS FOR 120 VOLT TO
24 VOLT EQUIPMENT. PROVIDE EDCO # HSP-121A
SURGE PROTECTORS.
D9H3
DD
DD
FS
PS
LP22
LP21
CLASSROOM
210
CLASSROOM
211
CLASSROOM
212
UNIT STORAGE
213
JAN.
214
CLASSROOM
215
CORRIDOR
205
MEN
209
WOMEN
208
LOBBY
201
STAIRS
203
BREAK AREA
207
ELEV
202
EQUIPMENT PLATFORM
216
GALLY & VENDING
206
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-701
SECOND FLOOR FIRE ALARM AND MASS
NOTIFICATION PLAN
1/8" = 1'-0"1
SECOND FLOOR FIRE ALARM/MASSNOTIFICATION SYSTEM
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-800
PANELBOARDS LP11, LP12 , EH11 AND EL11
SCHEDULES
Notes:
Total Est. Demand: 37 A
Total Conn.: 43 A
Receptacle 14220 VA 85.16% 12110 VA Total Est. Demand: 13310 VA
Other 0 VA 0.00% 0 VA Total Conn. Load: 15420 VA
HVAC 1200 VA 100.00% 1200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 54 A 38 A 37 A
Total Load: 6440 VA 4580 VA 4400 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 Receptacle Room 104, 106 20 A 1 1680... 14
11 Receptacle Room 107, 105, 106 20 A 1 2000... 12
9 Receptacle WST HIGH BAY 116 20 A 1 2000... 1200... 1 20 A Receptacle INSTRUCTORS SUITE 110,... 10
7 Receptacle WST HIGH BAY 116 20 A 1 2180... 1200... 1 20 A WST HIGH BAY 116 (MSAW - M2) 8
5 Receptacle CORR 106, GFCI BREAKER 20 A 1 1200... 1200... 1 20 A Receptacle INSTRUCTORS SUITE 110, KIT EQUIP 6
3 Receptacle WOMEN 112 20 A 1 180 VA 1200... 1 20 A Receptacle INSTRUCTORS SUITE 110, KIT EQUIP 4
1 Receptacle MEN 111 20 A 1 180 VA 1200... 1 20 A Receptacle INSTRUCTORS SUITE 110, REFRIG. 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: No MCB Rating:
Mounting: Recessed Wires: 4 Mains Rating: 200 A
Supply From: LP11 Phases: 3 Mains Type:
Location: Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: LP12
Notes:
Spare 64830 VA 100.00% 64830 VA Total Est. Demand: 331 A
Receptacle 43510 VA 61.49% 26755 VA Total Conn.: 378 A
Other 14400 VA 100.00% 14400 VA Total Est. Demand: 119397 VA
HVAC 12500 VA 100.00% 12500 VA Total Conn. Load: 136152 VA
Cooling 912 VA 100.00% 912 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 410 A 371 A 357 A
Total Load: 48967 VA 44261 VA 42788 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 Receptacle, IRRIGATION CONTROLLER 20 A 1 500 VA 26
23 Receptacle, TV'S 20 A 1 360 VA 7310... 24
21 Receptacles RM 100, 101, EXTERIOR 20 A 1 1680... 7310... 22
19 HEAT TAPE FOR ACC-1 20 A 1 1200... 7310...
3 100 A MSPDU
20
17 3367... 14300... 18
15 3367... 14300... 16
13
MSA 50 A 3
3367... 14300...
3 200 A MSUPS
14
11 6960... 4291... 12
9 6780... 4444... 10
7
LP13 150 A 3
6780... 6730...
3 150 A LP22
8
5 4400... 1800... 6
3 4580... 1800... 4
1
LP12 150 A 3
6440... 2340...
3 150 A LP21
2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: Yes MCB Rating: 400 A
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: T2 Phases: 3 Mains Type:
Location: MECHANICAL/FIRE... Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: LP11
Notes:
Receptacle 7500 VA 100.00% 7500 VA
Power 300 VA 100.00% 300 VA
Other 0 VA 0.00% 0 VA
Motor 61810 VA 108.70% 67188 VA Total Est. Demand: 127 A
Lighting 1906 VA 125.00% 2383 VA Total Conn.: 120 A
Heating 11200 VA 100.00% 11200 VA Total Est. Demand: 105617 VA
HVAC 16576 VA 100.00% 16576 VA Total Conn. Load: 99762 VA
Cooling 470 VA 100.00% 470 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 115 A 122 A 118 A
Total Load: 31730 VA 33601 VA 32457 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 Space -- -- 0 VA 0 VA -- -- Space 36
33 Space -- -- 0 VA 0 VA -- -- Space 34
31 Space -- -- 0 VA 0 VA -- -- Space 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 7170... 5577... 18
15 7170... 5577... 16
13
D1H6/AHU1R 35 A 3
7170... 5577...
3 30 A D7H3/AHU1S
14
11 425 VA 425 VA 12
9 425 VA 425 VA 10
7
D1H3/PHWP-2 20 A 3
425 VA 425 VA
3 20 A D2H3/PHWP-1
8
5 17563... 1296... 1 20 A Lighting, MECH/ELECT RM,, COMM 117 6
3 19744... 259 VA 1 20 A Emergency Lighting - Second Floor 4
1
T3 110 A 3
18022... 111 VA 1 20 A Emergency Lighting - First Floor 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: No MCB Rating: 200 A
Mounting: Surface Wires: 4 Mains Rating: 200 A
Supply From: MTS Phases: 3 Mains Type:
Location: MECHANICAL/FIRE... Volts: 480/277 Wye A.I.C. Rating: 14000
Branch Panel: EH11
Notes:
Receptacle 7500 VA 100.00% 7500 VA
Power 300 VA 100.00% 300 VA
Other 0 VA 0.00% 0 VA
Motor 21018 VA 119.80% 25179 VA Total Est. Demand: 171 A
Lighting 240 VA 125.00% 301 VA Total Conn.: 159 A
Heating 11200 VA 100.00% 11200 VA Total Est. Demand: 61526 VA
HVAC 16576 VA 100.00% 16576 VA Total Conn. Load: 57304 VA
Cooling 470 VA 100.00% 470 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 156 A 172 A 151 A
Total Load: 18595 VA 20576 VA 18133 VA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 1456... 38
35 EF-3 MECHANICAL/FIRE PROTECTION 118 20 A 1 470 VA 1456...2 20 A
SCU-1A AND B EQUIPMENT PLATFORM 216AND ROOM 117
36
33 FAC WST COMPUTOR ROOM DATA STORAGE... 20 A 1 1840... 0 VA 1 20 A Power FOR DOOR OPERATORS 34
31 VAV CONTROL POWER 20 A 1 1800... 1200... 1 20 A MSVAC 32
29 VAV CONTROL POWER 20 A 1 1800... 1800... 1 20 A VAV CONTROL POWER 30
27 VAV CONTROL POWER 20 A 1 1800... 1800... 1 20 A VAV CONTROL POWER 28
25 Receptacle, COMM SECURE 117 20 A 1 1500... 1800... 1 20 A VAV CONTROL POWER 26
23 Receptacle, COMM SECURE 117 20 A 1 1500... 5548... 24
21 Receptacle COMM SECURE 117 20 A 1 360 VA 5548... 22
19 Receptacle COMM SECURE 117 20 A 1 360 VA 5548...
3 60 A ELEVATOR MOTOR
20
17 Receptacle, COMM SECURE 117 20 A 1 360 VA 1500... 1 20 A ECH-1 18
15 2800... 180 VA 1 20 A POWER FOR ELEVATOR EQUPMENT 16
13D1L6/EUH-2 35 A 2
2800... 0 VA 1 20 A MSSD (FEED FOR FUTURE D4) 14
11 2800... 0 VA 1 20 A POWER FOR ELEVATOR LIGHTS 12
9EUH-1 35 A 2
2800... 1388... 1 20 A ELEVATOR PIT LIGHT AND RECEPTACLES 10
7 BOILER B1 AND B2 20 A 1 864 VA 667 VA 1 20 A BP-2 8
5 AIRCRAFT WARNING LIGHTS 20 A 1 232 VA 667 VA 1 20 A BP-1 6
3 FIRE ALARM CONTROL PANEL 20 A 1 200 VA 1860... 1 20 A Receptacles, RM 118, EXTERIOR 4
1 SECURITY PANEL POWER 20 A 1 100 VA 500 VA 1 20 A DDC 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: Yes MCB Rating: 200 A
Mounting: Surface Wires: 4 Mains Rating: 200 A
Supply From: T3 Phases: 3 Mains Type:
Location: MECHANICAL/FIRE... Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: EL11
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-801
PANELBOARDS LP13, LP21 AND LP22 SCHEDULES
Notes:
Total Est. Demand: 57 A
Total Conn.: 57 A
Total Est. Demand: 20520 VA
Receptacle 6120 VA 100.00% 6120 VA Total Conn. Load: 20520 VA
Other 14400 VA 100.00% 14400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 57 A 57 A 58 A
Total Load: 6780 VA 6780 VA 6960 VA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 2400... 20
17 Spare 20 A 1 0 VA 2400... 18
15 Receptacle Room 114 20 A 1 720 VA 2400...
3 20 A RM 110 POWER FOR FUTURE FURNITURE
16
13 Receptacle WST SIM MAINT PARTS STOR 114 20 A 1 360 VA 2400... 14
11 Receptacle MAINT SUPV 115 20 A 1 360 VA 2400... 12
9 Receptacle RECEPTION 105 20 A 1 360 VA 2400...
3 20 A RM 110 POWER FOR FUTURE FURNITURE
10
7 Receptacle RECEPTION 105 20 A 1 540 VA 720 VA 1 20 A Receptacle INSTRUCTORS SUITE 110 8
5 Receptacle Room 109, 108 20 A 1 1080... 720 VA 1 20 A Receptacle INSTRUCTORS SUITE 110 6
3 Receptacle SITE MGR (CONTRACT) 108 20 A 1 360 VA 540 VA 1 20 A Receptacle INSTRUCTORS SUITE 110 4
1 Receptacle PO/QAR (GOV'T) 109 20 A 1 360 VA 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: Yes MCB Rating:
Mounting: Recessed Wires: 4 Mains Rating: 200 A
Supply From: LP11 Phases: 3 Mains Type:
Location: INSTRUCTORS SUITE 110 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: LP13
Notes:
Total Est. Demand: 16 A
Total Conn.: 16 A
Total Est. Demand: 5940 VA
Total Conn. Load: 5940 VA
Receptacle 5940 VA 100.00% 5940 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 20 A 15 A 15 A
Total Load: 2340 VA 1800 VA 1800 VA
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Receptacle Room 210, 211 20 A 1 720 VA 0 VA 1 20 A Spare 8
5 Receptacle CLASSROOM 210 20 A 1 900 VA 900 VA 1 20 A Receptacle Room 211, 212 6
3 Receptacle, CLASSROOM 211 20 A 1 900 VA 900 VA 1 20 A Receptacle CLASSROOM 212 4
1 Receptacle CLASSROOM 215 20 A 1 720 VA 900 VA 1 20 A Receptacle CLASSROOM 215 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: No MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 200 A
Supply From: LP11 Phases: 3 Mains Type:
Location: JAN. 214 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: LP21
Notes:
Total Est. Demand: 37 A
Total Conn.: 43 A
Receptacle 14690 VA 84.04% 12345 VA Total Est. Demand: 13257 VA
Other 0 VA 0.00% 0 VA Total Conn. Load: 15602 VA
Cooling 912 VA 100.00% 912 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 56 A 37 A 37 A
Total Load: 6730 VA 4444 VA 4428 VA
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 Receptacle, TV'S 20 A 1 900 VA 0 VA 1 20 A Spare 14
11 EF-1 20 A 1 828 VA 0 VA 1 20 A Spare 12
9 Receptacle Room 205, 214, 213 20 A 1 2680... 84 VA 1 20 A Cooling, EF-2 10
7 Receptacle Room 201, 207 20 A 1 2500... 2400... 1 20 A Receptacle GALLY & VENDING 206 8
5 Receptacle for EWC, provide GFCI breaker 20 A 1 1200... 2400... 1 20 A Receptacle GALLY & VENDING 206 6
3 Receptacle MEN 209 20 A 1 180 VA 1500... 1 20 A Receptacle GALLY/VENDING 206, GFCI... 4
1 Receptacle WOMEN 208 20 A 1 180 VA 750 VA 1 20 A Receptacle GALLY/VENDING 206, GFCI... 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 Isolated Ground bus: No MCB Rating:
Mounting: Recessed Wires: 4 Mains Rating: 200 A
Supply From: LP11 Phases: 3 Mains Type:
Location: GALLY & VENDING 206 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: LP22
DR
AW
ING
TIT
LE
:
PR
OJE
CT
:
CHECKEDBY:
DATE:
DESIGNEDBY:
DRAWNBY:
JOBNO.:
DRAWINGNO.
PR
EP
AR
ED
FO
R:
RE
VIS
ION
NO
.D
AT
E
surveyingsurveyingsurveyingsurveyingplanningplanningplanningplanning
engineeringengineeringengineeringengineering
pppp....cccc....
PPPPHHHHOOOONNNNEEEE ((((333300007777)))) 666633337777----66660000111177771111111100003333 OOOOLLLLDDDD TTTTOOOOWWWWNNNN LLLLAAAANNNNEEEE,,,, SSSSUUUUIIIITTTTEEEE
101101101101CCCCHHHHEEEEYYYYEEEENNNNNNNNEEEE,,,, WWWWYYYY 88882222000000009999
AAAAVVVVIIII@@@@AAAAVVVVIIIIPPPPCCCC....CCCCOOOOMMMM
AUGUST 1, 2013
DPEZ 089017
DPEZ 089017
C-130 FLIGHT SIMULATOR TRAINING FACILITY
CHEYENNE, W
YOMING
U.S. PROPERTY & FISCAL OFFICE
FOR WYOMING
WYOMING AIR NATIONAL GUARD
153rd AIRLIFT WING
NOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTOR
INTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODEL
FOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR
ALL BUILDING CONSTRUCTION REQUIREMENTS
MHG / RCW
MHG / RCW
MHG
E-900
3D VIEWS
1NE VIEW
2SE VIEW
3SW VIEW
4NW VIEW