DESIGN BASIS FOR ELECTRICAL ITEMS
S.No. Description 110kV Chayadevi S/S
1.0 GENERAL
1.1 Standards : Relevant IS / IEC / IEEE / CBIP
standards & manuals
1.2 Service : Outdoor
1.3 System Voltage (kV rms) : 110
1.4 Highest system voltage (kV rms) : 123
1.5 Power frequency withstand capability (kV rms) : 230
1.6 Basic insulation level (kV peak) : 550
1.7 Creepage distance for insulators (mm/kV) : 25
2.0 MINIMUM CLEARANCES
2.1 Between Phase and earth (mm) : 1100
2.2 Between phases (mm) : 1100
2.3 Sectional clearance (mm) : 4000
2.4 Ground clearance (mm) : 4600
3.0 FAULT LEVEL PARAMETERS
3.1 Magnitude of Three Line fault current in kA : 31.5
3.2 Duration of fault current (Sec.) : 3
4.0 BUS BAR ARRANGEMENTS
4.1 Type of Bus : 2.5" IPS AL Tube (As per schedule
40)
4.2 ACSR Conductor : Lynx
5.0 EARTHING SYSTEM
5.1 Type : Solidly earthed system
5.2 Magnitude of earth fault current to be considered for earth
mat sizing (kA)
: 31.5 kA
5.3 Time duration for calculation of step & touch potentials
(Sec.)
: 0.5
5.4 Fault time duration for sizing the earthing conductor (Sec.) : 1
5.5 Type of joint for earth mats : Welded joints
5.6 Depth of buried conductor (mm) : 600
5.7 Average soil resistivity (Ohm-m) : Refer soil resistivity report
5.8 Area to be covered for laying earthmat : Complete fenced area.However
fence shall be isolated from main
earthing mate
5.9 Type of conductor & size : 75 X 8 GI
5.10 Material for treated earth electrodes : 3M long, 40 mm dia, GI Pipe
electrode with treated for
transformer neutral and Lightning
5.11 Material for un-treated earth electrodes : 3M long, 40 mm dia, MS Rod
electrode for others.
-
8/12/2019 Electrical Design Basis
2/11
S.No. Description 110kV Chayadevi S/S
6.1 System type : Lightning masts
6.2 Angle of coverage : As per Razevig method
6.3 Earthing down conductors for Lightning Arrestors and
Lightning Protection
: 25 x 3 GI flats
7.0 GENERAL
7.1 Details of relays and meters : -
7.2 Colour & finish of panels : -
7.3 Height of all panels with base channels : -
7.4 Control cabling philosophy : As in cable philosophy diagram
8.0 AVAILABLE AUXILIARY SUPPLIES
8.1 DC supply (V) : 110 V, -15% to +10%
8.2 AC supply (V) : 230 / 415 +/- 10% at 50 Hz +/- 5%
9.0 CIRCUIT BREAKER
9.1 Voltage : 123 kV
9.2 One Minute Power Frequency Voltage : 230 kV (rms)
9.3 Lightning Impulse withstand voltage : 550 kVP
9.4 Normal current : 1250 A
9.5 SC breaking current : 31.5 kA
9.6 Short time withstand current and duration : 31.5 kA for 3 secs
9.7 Operating sequence : O-0.3S-CO-3 min-CO
9.8 Operating Mechanism : Standalone spring charged.
9.9 Closing and opening device supply voltage : 110 V DC
9.10 Motor supply voltage : 230 V AC
9.11 Auxiliary supply voltage : 230 V AC
9.12 Frequency : 50 Hz
10.0 ISOLATOR :
10.1 Voltage : 110 kV
10.2 Maximum operating voltage : 123 kV
10.3 Power frequency with stand voltage : 230 kV
10.4 Lightning Impulse withstand voltage : 550 kVP
10.5 Normal current : 1250 A
10.6 Short time current rating : 31.5 kA for 3 secs
10.7 Operating voltage of main switch motor : 230 V AC
10.8 Switch type : Double break center rotating type
10.9 Creepage distance of insulator : 25 mm/kV
-
8/12/2019 Electrical Design Basis
3/11
S.No. Description 110kV Chayadevi S/S
10.0 Pole to Pole distance : 2.7 metre
10.11 Mechanical interlock : To be provided between main switch
and earth switch and respective CB
11.0 CURRENT TRANSFORMER :
11.1 Normal operating voltage : 110 kV
11.2 Highest system voltage : 123 kV
11.3 Basic insulation level : 550 kVP
11.4 Power frequency high voltage : 230 kV
11.5 Short time current rating & duration : 31.5 kA for 3 secs
11.6 Normal current : 175A for both line CTs and trafo
side CTs
11.7 Operating frequency : 50 Hz
11.8 CT ratio, No. of cores & accuracy classes : Refer single line diagram
12.0 POTENTIAL TRANSFORMER
12.1 Normal operating voltage : 110 kV
12.2 Highest system voltage : 123 kV
12.3 Basic insulation level : 550 kVP
12.4 Power frequency high voltage : 230 kV
12.5 Voltage factor : 1.2 continuous & 1.5 for 30 sec
12.6 Operating frequency : 50 Hz
12.7 PT Ratio, No. of Cores & accuracy classes for 132kV
side
: Refer single line diagram
13.0 LIGHTNING ARRESTOR :
13.1 Rated voltage 96 kV
13.2 Nominal discharge current : 10 kA, heavy duty
13.3 Frequency : 50 Hz
13.4 Discharge current class : 3
14.0 Control and relay panel :
14.1 Auxiliary supply for instruments & relays : -
14.2 Auxiliary supply for space heaters and illumination : -
14.3 Metering, relays & other devices : -
14.4 Type of construction : -
14.5 Painting : -
15.0 Power and control cables
15.1 Power cable
15.1.1 Voltage grade : 1100V
15.1.2 Conductor : Aluminium strands
15.1.3 Insulation : PVC
15.1.4 Innersheath material : Extruded PVC
-
8/12/2019 Electrical Design Basis
4/11
S.No. Description 110kV Chayadevi S/S
15.1.5 Armouring : a) Galvanized round MS wire / strips
for multi core cables
15.1.6 Outer Sheath of insulation : PVC
15.2 Control cable
15.2.1 Voltage grade : 1100V
15.2.2 Conductor : Copper strands.
15.2.3 Insulation : PVC
15.2.4 Innersheath material : Extruded PVC
15.2.5 Armouring : Galvanized round MS wire / strips
for multi core cables
15.2.6 Outer Sheath of insulation : PVC
16.0 Bay marshalling kiosk
16.1 Construction : Sheet steel enclosure with minimum
thickness of 2 mm.
16.2 Mounting arrangement : Free standing type
16.3 Enclosure protection : IP-65 with canopy arrangement
16.4 AC distribution : all be planned for switchyard equipme
16.5 Paint shade : Bhoruka to indicate
17.0 Insulators, Hardwares and Connectors
17.1 Post Insulator
17.1.1 Type : Solid Core
17.1.2 Nominal Voltage : 110 kV
17.1.3 Highest System Voltage : 123 kV
17.1.4 Creepage Distance : 25 mm/kV
17.1.5 Cantilever Strength : 800 kg for Bus Support
600 kg for Isolator
17.1.6 One (1) minute power frequency voltage : 230 kV
17.1.7 Impulse Voltage : 550 kVP
17.2 Clamps and Connectors
17.2.1 Sizes : Suitable for 2.5" IPS and Lynx ACSR
Conductor
17.2.2 Material : Aluminium
17.2.3 Finishes : Smooth Polished and Corona free
-
8/12/2019 Electrical Design Basis
5/11
110kV KPTCL S/S
Relevant IS / IEC / IEEE / CBIP standards
& manuals
Outdoor
110
123
230
550
25
1100
1100
4000
4600
31.5
3
2.5" IPS AL Tube (As per schedule 40)
Lynx
Solidly earthed system
31.5 kA
0.5
1
Welded joints
600
Refer soil resistivity report
Complete fenced area.However fence shall
be isolated from main earthing mate
75 X 8 GI
3M long, 40 mm dia, GI Pipe electrode with
treated for transformer neutral and
Lightning arrestor
3M long, 40 mm dia, MS Rod electrode for
others.
-
8/12/2019 Electrical Design Basis
6/11
110kV KPTCL S/S
Lightning masts
As per Razevig method
25 x 3 GI flats
As in the SLDs
Bhoruka to indicate
Bhoruka to indicate
As in cable philosophy diagram
220 V, -15% to +10%
230 / 415 +/- 10% at 50 Hz +/- 5%
123 kV
230 kV (rms)
550 kVP
1250 A
31.5 kA
31.5 kA for 3 secs
O-0.3S-CO-3 min-CO
Standalone spring charged.
220 V DC
230 V AC
230 V AC
50 Hz
110 kV
123 kV
230 kV
550 kVP
1250 A
31.5 kA for 3 secs
NA
Double break center rotating type
25 mm/kV
-
8/12/2019 Electrical Design Basis
7/11
110kV KPTCL S/S
2 metre
To be provided between main switch and
earth switch and respective CB
110 kV
123 kV
550 kVP
230 kV
31.5 kA for 3 secs
400A for both line CTs and trafo side CTs
50 Hz
Refer single line diagram
110 kV
123 kV
550 kVP
230 kV
1.2 continuous & 1.5 for 30 sec
50 Hz
Refer single line diagram
96 kV
10 kA, heavy duty
50 Hz
3
220 V DC
230 V AC
As per SLD
Simplex Type
Bhoruka to indicate
1100V
Aluminium strands
PVC
Extruded PVC
-
8/12/2019 Electrical Design Basis
8/11
110kV KPTCL S/S
a) Galvanized round MS wire / strips for
multi core cables
PVC
1100V
Copper strands.
PVC
Extruded PVC
Galvanized round MS wire / strips for multi
core cables
PVC
Sheet steel enclosure with minimum
thickness of 2 mm.
Free standing type
IP-65 with canopy arrangement
Shall be planned for switchyard equipment.
Bhoruka to indicate
-
-
-
-
-
-
-
Suitable for 2.5" IPS and Lynx ACSR
Conductor
Aluminium
Smooth Polished and Corona free
-
8/12/2019 Electrical Design Basis
9/11
DESIGN BASIS FOR ELECTRICAL ITEMS
S.No. Description 11kV borad
1.0 GENERAL
1.1 Standards : Relevant IS / IEC / IEEE / CBIPstandards & manuals
1.2 Service : Outdoor
1.3 System Voltage (kV rms) : 11
1.4 Highest system voltage (kV rms) : 28
1.5 Power frequency withstand capability (kV rms) : 28
1.6 Basic insulation level (kV peak) : 70
1.7 Creepage distance for insulators (mm/kV) : 25
2.0 FAULT LEVEL PARAMETERS
3.1 Magnitude of Three Line fault current in kA : 40
3.2 Duration of fault current (Sec.) : 3
3.0 BUS BAR ARRANGEMENTS
3.1 Type of Bus : Aluminium busbar rated for 2500 A
4.0 EARTHING SYSTEM
4.1 Type : Non-effectively earthed
4.2 Magnitude of earth fault current to be considered for earth
mat sizing (kA)
: 40 kA
4.3 Fault time duration for sizing the earthing conductor
(Sec.)
: 3
5.0 AVAILABLE AUXILIARY SUPPLIES
5.1 DC supply (V) : 110 V, -15% to +10%
5.2 AC supply (V) : 230 / 415 +/- 10% at 50 Hz +/- 5%
6.0 CIRCUIT BREAKER
6.1 Type : SF6/ VCB
6.2 Voltage : 12 kV
9 of 11
-
8/12/2019 Electrical Design Basis
10/11
6.3 One Minute Power Frequency Voltage : 28 kV (rms)
6.4 Lightning Impulse withstand voltage : 70 kVP
6.5 Normal current : 2500 A
6.6 SC breaking current : 40 kA
6.7 Short time withstand current and duration : 40 kA for 3 secs
6.8 Operating sequence : O-0.3S-CO-3 min-CO
6.9 Operating Mechanism : Standalone spring charged.
6.10 Closing and opening device supply voltage : 110 V DC
6.11 Motor supply voltage : 240 V AC
6.12 Auxiliary supply voltage : 240 V AC
6.13 Frequency : 50 Hz
7.0 LOAD BREAK SWITCH :
7.1 Voltage : 11 kV
7.2 Maximum operating voltage : 12 kV
7.3 Power frequency with stand voltage : 28 kV
7.4 Lightning Impulse withstand voltage : 70 kVP
7.5 Normal current : 200 A
7.6 Short time current rating : 40 kA for 3 secs
7.7 Operating mechanism : Manual
8.0 CURRENT TRANSFORMER :
8.1 Normal operating voltage : 11 kV
8.2 Highest system voltage : 12 kV
8.3 Basic insulation level : 70 kVP
8.4 Power frequency high voltage : 7028
8.5 Short time current rating & duration : 40 kA for 1 sec
10 of 11
-
8/12/2019 Electrical Design Basis
11/11
8.6 Normal current : 1800A for trafo CTs and 40 A for
UAT CTs
8.7 Operating frequency : 50 Hz
8.8 CT ratio, No. of cores & accuracy classes for 132kV
side
: Refer single line diagram
9.0 POTENTIAL TRANSFORMER
9.1 Normal operating voltage : 11 kV
9.2 Highest system voltage : 12 kV
9.3 Basic insulation level : 70 kVP
9.4 Power frequency high voltage : 28 kV
9.5 Voltage factor : 1.2 continuous & 1.5 for 30 sec
9.6 Operating frequency : 50 Hz
9.7 PT Ratio, No. of Cores & accuracy classes for 132kV
side
: Refer single line diagram