    DESIGN BASIS FOR ELECTRICAL ITEMS

    S.No. Description 110kV Chayadevi S/S

    1.0 GENERAL

    1.1 Standards : Relevant IS / IEC / IEEE / CBIP

    standards & manuals

    1.2 Service : Outdoor

    1.3 System Voltage (kV rms) : 110

    1.4 Highest system voltage (kV rms) : 123

    1.5 Power frequency withstand capability (kV rms) : 230

    1.6 Basic insulation level (kV peak) : 550

    1.7 Creepage distance for insulators (mm/kV) : 25

    2.0 MINIMUM CLEARANCES

    2.1 Between Phase and earth (mm) : 1100

    2.2 Between phases (mm) : 1100

    2.3 Sectional clearance (mm) : 4000

    2.4 Ground clearance (mm) : 4600

    3.0 FAULT LEVEL PARAMETERS

    3.1 Magnitude of Three Line fault current in kA : 31.5

    3.2 Duration of fault current (Sec.) : 3

    4.0 BUS BAR ARRANGEMENTS

    4.1 Type of Bus : 2.5" IPS AL Tube (As per schedule

    40)

    4.2 ACSR Conductor : Lynx

    5.0 EARTHING SYSTEM

    5.1 Type : Solidly earthed system

    5.2 Magnitude of earth fault current to be considered for earth

    mat sizing (kA)

    : 31.5 kA

    5.3 Time duration for calculation of step & touch potentials

    (Sec.)

    : 0.5

    5.4 Fault time duration for sizing the earthing conductor (Sec.) : 1

    5.5 Type of joint for earth mats : Welded joints

    5.6 Depth of buried conductor (mm) : 600

    5.7 Average soil resistivity (Ohm-m) : Refer soil resistivity report

    5.8 Area to be covered for laying earthmat : Complete fenced area.However

    fence shall be isolated from main

    earthing mate

    5.9 Type of conductor & size : 75 X 8 GI

    5.10 Material for treated earth electrodes : 3M long, 40 mm dia, GI Pipe

    electrode with treated for

    transformer neutral and Lightning

    5.11 Material for un-treated earth electrodes : 3M long, 40 mm dia, MS Rod

    electrode for others.

  • 8/12/2019 Electrical Design Basis

    2/11

    S.No. Description 110kV Chayadevi S/S

    6.1 System type : Lightning masts

    6.2 Angle of coverage : As per Razevig method

    6.3 Earthing down conductors for Lightning Arrestors and

    Lightning Protection

    : 25 x 3 GI flats

    7.0 GENERAL

    7.1 Details of relays and meters : -

    7.2 Colour & finish of panels : -

    7.3 Height of all panels with base channels : -

    7.4 Control cabling philosophy : As in cable philosophy diagram

    8.0 AVAILABLE AUXILIARY SUPPLIES

    8.1 DC supply (V) : 110 V, -15% to +10%

    8.2 AC supply (V) : 230 / 415 +/- 10% at 50 Hz +/- 5%

    9.0 CIRCUIT BREAKER

    9.1 Voltage : 123 kV

    9.2 One Minute Power Frequency Voltage : 230 kV (rms)

    9.3 Lightning Impulse withstand voltage : 550 kVP

    9.4 Normal current : 1250 A

    9.5 SC breaking current : 31.5 kA

    9.6 Short time withstand current and duration : 31.5 kA for 3 secs

    9.7 Operating sequence : O-0.3S-CO-3 min-CO

    9.8 Operating Mechanism : Standalone spring charged.

    9.9 Closing and opening device supply voltage : 110 V DC

    9.10 Motor supply voltage : 230 V AC

    9.11 Auxiliary supply voltage : 230 V AC

    9.12 Frequency : 50 Hz

    10.0 ISOLATOR :

    10.1 Voltage : 110 kV

    10.2 Maximum operating voltage : 123 kV

    10.3 Power frequency with stand voltage : 230 kV

    10.4 Lightning Impulse withstand voltage : 550 kVP

    10.5 Normal current : 1250 A

    10.6 Short time current rating : 31.5 kA for 3 secs

    10.7 Operating voltage of main switch motor : 230 V AC

    10.8 Switch type : Double break center rotating type

    10.9 Creepage distance of insulator : 25 mm/kV

  • 8/12/2019 Electrical Design Basis

    3/11

    S.No. Description 110kV Chayadevi S/S

    10.0 Pole to Pole distance : 2.7 metre

    10.11 Mechanical interlock : To be provided between main switch

    and earth switch and respective CB

    11.0 CURRENT TRANSFORMER :

    11.1 Normal operating voltage : 110 kV

    11.2 Highest system voltage : 123 kV

    11.3 Basic insulation level : 550 kVP

    11.4 Power frequency high voltage : 230 kV

    11.5 Short time current rating & duration : 31.5 kA for 3 secs

    11.6 Normal current : 175A for both line CTs and trafo

    side CTs

    11.7 Operating frequency : 50 Hz

    11.8 CT ratio, No. of cores & accuracy classes : Refer single line diagram

    12.0 POTENTIAL TRANSFORMER

    12.1 Normal operating voltage : 110 kV

    12.2 Highest system voltage : 123 kV

    12.3 Basic insulation level : 550 kVP

    12.4 Power frequency high voltage : 230 kV

    12.5 Voltage factor : 1.2 continuous & 1.5 for 30 sec

    12.6 Operating frequency : 50 Hz

    12.7 PT Ratio, No. of Cores & accuracy classes for 132kV

    side

    : Refer single line diagram

    13.0 LIGHTNING ARRESTOR :

    13.1 Rated voltage 96 kV

    13.2 Nominal discharge current : 10 kA, heavy duty

    13.3 Frequency : 50 Hz

    13.4 Discharge current class : 3

    14.0 Control and relay panel :

    14.1 Auxiliary supply for instruments & relays : -

    14.2 Auxiliary supply for space heaters and illumination : -

    14.3 Metering, relays & other devices : -

    14.4 Type of construction : -

    14.5 Painting : -

    15.0 Power and control cables

    15.1 Power cable

    15.1.1 Voltage grade : 1100V

    15.1.2 Conductor : Aluminium strands

    15.1.3 Insulation : PVC

    15.1.4 Innersheath material : Extruded PVC

  • 8/12/2019 Electrical Design Basis

    4/11

    S.No. Description 110kV Chayadevi S/S

    15.1.5 Armouring : a) Galvanized round MS wire / strips

    for multi core cables

    15.1.6 Outer Sheath of insulation : PVC

    15.2 Control cable

    15.2.1 Voltage grade : 1100V

    15.2.2 Conductor : Copper strands.

    15.2.3 Insulation : PVC

    15.2.4 Innersheath material : Extruded PVC

    15.2.5 Armouring : Galvanized round MS wire / strips

    for multi core cables

    15.2.6 Outer Sheath of insulation : PVC

    16.0 Bay marshalling kiosk

    16.1 Construction : Sheet steel enclosure with minimum

    thickness of 2 mm.

    16.2 Mounting arrangement : Free standing type

    16.3 Enclosure protection : IP-65 with canopy arrangement

    16.4 AC distribution : all be planned for switchyard equipme

    16.5 Paint shade : Bhoruka to indicate

    17.0 Insulators, Hardwares and Connectors

    17.1 Post Insulator

    17.1.1 Type : Solid Core

    17.1.2 Nominal Voltage : 110 kV

    17.1.3 Highest System Voltage : 123 kV

    17.1.4 Creepage Distance : 25 mm/kV

    17.1.5 Cantilever Strength : 800 kg for Bus Support

    600 kg for Isolator

    17.1.6 One (1) minute power frequency voltage : 230 kV

    17.1.7 Impulse Voltage : 550 kVP

    17.2 Clamps and Connectors

    17.2.1 Sizes : Suitable for 2.5" IPS and Lynx ACSR

    Conductor

    17.2.2 Material : Aluminium

    17.2.3 Finishes : Smooth Polished and Corona free

  • 8/12/2019 Electrical Design Basis

    5/11

    110kV KPTCL S/S

    Relevant IS / IEC / IEEE / CBIP standards

    & manuals

    Outdoor

    110

    123

    230

    550

    25

    1100

    1100

    4000

    4600

    31.5

    3

    2.5" IPS AL Tube (As per schedule 40)

    Lynx

    Solidly earthed system

    31.5 kA

    0.5

    1

    Welded joints

    600

    Refer soil resistivity report

    Complete fenced area.However fence shall

    be isolated from main earthing mate

    75 X 8 GI

    3M long, 40 mm dia, GI Pipe electrode with

    treated for transformer neutral and

    Lightning arrestor

    3M long, 40 mm dia, MS Rod electrode for

    others.

  • 8/12/2019 Electrical Design Basis

    6/11

    110kV KPTCL S/S

    Lightning masts

    As per Razevig method

    25 x 3 GI flats

    As in the SLDs

    Bhoruka to indicate

    Bhoruka to indicate

    As in cable philosophy diagram

    220 V, -15% to +10%

    230 / 415 +/- 10% at 50 Hz +/- 5%

    123 kV

    230 kV (rms)

    550 kVP

    1250 A

    31.5 kA

    31.5 kA for 3 secs

    O-0.3S-CO-3 min-CO

    Standalone spring charged.

    220 V DC

    230 V AC

    230 V AC

    50 Hz

    110 kV

    123 kV

    230 kV

    550 kVP

    1250 A

    31.5 kA for 3 secs

    NA

    Double break center rotating type

    25 mm/kV

  • 8/12/2019 Electrical Design Basis

    7/11

    110kV KPTCL S/S

    2 metre

    To be provided between main switch and

    earth switch and respective CB

    110 kV

    123 kV

    550 kVP

    230 kV

    31.5 kA for 3 secs

    400A for both line CTs and trafo side CTs

    50 Hz

    Refer single line diagram

    110 kV

    123 kV

    550 kVP

    230 kV

    1.2 continuous & 1.5 for 30 sec

    50 Hz

    Refer single line diagram

    96 kV

    10 kA, heavy duty

    50 Hz

    3

    220 V DC

    230 V AC

    As per SLD

    Simplex Type

    Bhoruka to indicate

    1100V

    Aluminium strands

    PVC

    Extruded PVC

  • 8/12/2019 Electrical Design Basis

    8/11

    110kV KPTCL S/S

    a) Galvanized round MS wire / strips for

    multi core cables

    PVC

    1100V

    Copper strands.

    PVC

    Extruded PVC

    Galvanized round MS wire / strips for multi

    core cables

    PVC

    Sheet steel enclosure with minimum

    thickness of 2 mm.

    Free standing type

    IP-65 with canopy arrangement

    Shall be planned for switchyard equipment.

    Bhoruka to indicate

    -

    -

    -

    -

    -

    -

    -

    Suitable for 2.5" IPS and Lynx ACSR

    Conductor

    Aluminium

    Smooth Polished and Corona free

  • 8/12/2019 Electrical Design Basis

    9/11

    DESIGN BASIS FOR ELECTRICAL ITEMS

    S.No. Description 11kV borad

    1.0 GENERAL

    1.1 Standards : Relevant IS / IEC / IEEE / CBIPstandards & manuals

    1.2 Service : Outdoor

    1.3 System Voltage (kV rms) : 11

    1.4 Highest system voltage (kV rms) : 28

    1.5 Power frequency withstand capability (kV rms) : 28

    1.6 Basic insulation level (kV peak) : 70

    1.7 Creepage distance for insulators (mm/kV) : 25

    2.0 FAULT LEVEL PARAMETERS

    3.1 Magnitude of Three Line fault current in kA : 40

    3.2 Duration of fault current (Sec.) : 3

    3.0 BUS BAR ARRANGEMENTS

    3.1 Type of Bus : Aluminium busbar rated for 2500 A

    4.0 EARTHING SYSTEM

    4.1 Type : Non-effectively earthed

    4.2 Magnitude of earth fault current to be considered for earth

    mat sizing (kA)

    : 40 kA

    4.3 Fault time duration for sizing the earthing conductor

    (Sec.)

    : 3

    5.0 AVAILABLE AUXILIARY SUPPLIES

    5.1 DC supply (V) : 110 V, -15% to +10%

    5.2 AC supply (V) : 230 / 415 +/- 10% at 50 Hz +/- 5%

    6.0 CIRCUIT BREAKER

    6.1 Type : SF6/ VCB

    6.2 Voltage : 12 kV

    9 of 11

  • 8/12/2019 Electrical Design Basis

    10/11

    6.3 One Minute Power Frequency Voltage : 28 kV (rms)

    6.4 Lightning Impulse withstand voltage : 70 kVP

    6.5 Normal current : 2500 A

    6.6 SC breaking current : 40 kA

    6.7 Short time withstand current and duration : 40 kA for 3 secs

    6.8 Operating sequence : O-0.3S-CO-3 min-CO

    6.9 Operating Mechanism : Standalone spring charged.

    6.10 Closing and opening device supply voltage : 110 V DC

    6.11 Motor supply voltage : 240 V AC

    6.12 Auxiliary supply voltage : 240 V AC

    6.13 Frequency : 50 Hz

    7.0 LOAD BREAK SWITCH :

    7.1 Voltage : 11 kV

    7.2 Maximum operating voltage : 12 kV

    7.3 Power frequency with stand voltage : 28 kV

    7.4 Lightning Impulse withstand voltage : 70 kVP

    7.5 Normal current : 200 A

    7.6 Short time current rating : 40 kA for 3 secs

    7.7 Operating mechanism : Manual

    8.0 CURRENT TRANSFORMER :

    8.1 Normal operating voltage : 11 kV

    8.2 Highest system voltage : 12 kV

    8.3 Basic insulation level : 70 kVP

    8.4 Power frequency high voltage : 7028

    8.5 Short time current rating & duration : 40 kA for 1 sec

    10 of 11

  • 8/12/2019 Electrical Design Basis

    11/11

    8.6 Normal current : 1800A for trafo CTs and 40 A for

    UAT CTs

    8.7 Operating frequency : 50 Hz

    8.8 CT ratio, No. of cores & accuracy classes for 132kV

    side

    : Refer single line diagram

    9.0 POTENTIAL TRANSFORMER

    9.1 Normal operating voltage : 11 kV

    9.2 Highest system voltage : 12 kV

    9.3 Basic insulation level : 70 kVP

    9.4 Power frequency high voltage : 28 kV

    9.5 Voltage factor : 1.2 continuous & 1.5 for 30 sec

    9.6 Operating frequency : 50 Hz

    9.7 PT Ratio, No. of Cores & accuracy classes for 132kV

    side

    : Refer single line diagram