Chapter 2 ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016 Page 34 CHAPTER 2 ELECTRIC SERVICE EQUIPMENT – METER CABINETS E200. TECHNICAL SPECIFICATIONS FOR METERING TRANSFORMER CABINETS AND CONDUCTOR TERMINATION BOXES. A. Approval Process Equipment manufactures application information, technical specifications and dimension drawings must be submitted to: Alliant Energy Standards Engineering Attn: Tony Porch 200 1st Street SE Cedar Rapids, Iowa 52401-1409 for review. The manufacturer will then be invited to bring their equipment to an ESR meeting to present their equipment. Equipment found to meet these requirements will be allowed for a one-time installation for a field test. Once the field test shows the equipment to be satisfactory, a letter verifying temporary approval will be provided. The equipment will be listed in the next edition of the Electric Service Rule Book. B. Modification/Continued Listing. If the specification is modified, manufacturers must verify their intent and submit new drawings by June 1 st each year for review and approval, to continue to be approved and listed in the Electric Service Information Manual for the following year. C. Listing/Labeling Current transformer cabinets shall be listed and labeled as “Metering Transformer Cabinets” and conductor termination boxes shall be listed and labeled as “Termination Boxes or Cabinets” by an independent testing laboratory (such as U.L. 414 for Current Transformer Cabinets and U.L. 1773 for Termination Boxes). In addition to this requirement, the cabinets must be inspected and approved by Alliant Energy, to ensure it meets our requirements. The equipment model number shall carry either an “Alliant Energy” suffix or prefix plus the complete catalog number, as shown in the Electric Service Equipment Book, and shall be included as part of the equipment nameplate. D. Doors Current Transformer Cabinets and Conductor Termination Cabinets are to have side-hinged doors with a two or three point handle operated locking device with a minimum 7/16 inch diameter sealing hole to accept a company pad-lock with a 3/8 inch shackle. The handle may not be operated when the lock is in place. The door(s) shall have a lockable wind-stop assembly installed. E. Enclosure Type As a minimum requirement, the cabinet type shall carry a NEMA 3R rating. For installations where a corrosive environment is present the cabinet shall be rated as a NEMA 4X. F. Electrical Clearances Clearances per the National Electrical Safety Code, Wisconsin Electrical Code, Volume 2, shall be maintained with the Current transformers and associated wiring installed and the cover(s) closed. The Alliant Energy minimum “H”, minimum depth and minimum width dimensions shall be maintained according to the Current Transformer Cabinet Specification Table (attached).

Upload: dokien

Post on 05-Jun-2018

253 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 34

CHAPTER 2

ELECTRIC SERVICE EQUIPMENT – METER CABINETS

E200. TECHNICAL SPECIFICATIONS FOR METERING TRANSFORMER CABINETS AND CONDUCTOR TERMINATION BOXES.

A. Approval Process Equipment manufactures application information, technical specifications and dimension drawings must be submitted to: Alliant Energy Standards Engineering Attn: Tony Porch 200 1st Street SE Cedar Rapids, Iowa 52401-1409 for review. The manufacturer will then be invited to bring their equipment to an ESR meeting to present their equipment. Equipment found to meet these requirements will be allowed for a one-time installation for a field test. Once the field test shows the equipment to be satisfactory, a letter verifying temporary approval will be provided. The equipment will be listed in the next edition of the Electric Service Rule Book.

B. Modification/Continued Listing. If the specification is modified, manufacturers must verify their intent and submit new drawings by June 1st each year for review and approval, to continue to be approved and listed in the Electric Service Information Manual for the following year.

C. Listing/Labeling Current transformer cabinets shall be listed and labeled as “Metering Transformer Cabinets” and conductor termination boxes shall be listed and labeled as “Termination Boxes or Cabinets” by an independent testing laboratory (such as U.L. 414 for Current Transformer Cabinets and U.L. 1773 for Termination Boxes). In addition to this requirement, the cabinets must be inspected and approved by Alliant Energy, to ensure it meets our requirements. The equipment model number shall carry either an “Alliant Energy” suffix or prefix plus the complete catalog number, as shown in the Electric Service Equipment Book, and shall be included as part of the equipment nameplate.

D. Doors Current Transformer Cabinets and Conductor Termination Cabinets are to have side-hinged doors with a two or three point handle operated locking device with a minimum 7/16 inch diameter sealing hole to accept a company pad-lock with a 3/8 inch shackle. The handle may not be operated when the lock is in place. The door(s) shall have a lockable wind-stop assembly installed.

E. Enclosure Type As a minimum requirement, the cabinet type shall carry a NEMA 3R rating. For installations where a corrosive environment is present the cabinet shall be rated as a NEMA 4X.

F. Electrical Clearances Clearances per the National Electrical Safety Code, Wisconsin Electrical Code, Volume 2, shall be maintained with the Current transformers and associated wiring installed and the cover(s) closed. The Alliant Energy minimum “H”, minimum depth and minimum width dimensions shall be maintained according to the Current Transformer Cabinet Specification Table (attached).

Page 2: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 35

G. Bus/Line Side Lug Specifications Ct’s shall be mounted vertically on cabinet bus bars. The Ct shall be bolted to a landing pad such that the conductors cannot be bolted directly to the CT’s. Line side Lugs shall be of the Allen-Set screw type, suitable for aluminum conductors. All lugs in termination cabinets shall be either lay-in or Allen-Set screw type.

H. PT Mounting PT'S may not be mounted directly in front or behind any other electrical components or utility conductors. An external, side attached PT box may be used and must have the minimum dimensions of 8” wide, 23” high, and 8” in depth.

I. Meter Socket Mounting on Wall-mounted Current Transformer Cabinets The proper height of 5’(+/- 6”) measured from the center of the meter to final grade shall be maintained. 400A through 800A cabinets shall be mounted with the bottom of the cabinet 24 to 30 inches above final grade and 1200A through 3000A cabinets shall be mounted with the bottom of the cabinet 20 to 24 inches above final grade.

J. Bonding The bonding of the Current Transformer Cabinet is in Chapter2 & 4. The bonding conductor sizes are shown at the end of chapter 2 & 4.

K. Fasteners No fasteners shall be able to be removed from the exterior of the cabinet. The only way to remove a fastener is by unlocking the door and gaining access to the inside of the cabinet.

L. Acceptable Voltages and Current Ranges 120/240 volts, single-phase, from 100 amps through 800 amps. 120/208 volts, single-phase, three-wire 200 amps max. 120/208 volts, three-phase, four-wire, from 100 amps through 3000 amps 277/480 volts, three-phase, four-wire from 100 amps through 3000 amps.

M. Service Configuration 1. Overhead Services, Top-In / Bottom-Out

Top feed installations can only be utilized for Overhead Services with a maximum rating of 1200 amps (See “L” above in this section). Load side conductors must exit below the load side lugs. The “H” dimension does not apply to this configuration, because the customer owns and installs all the conductors.

2. Overhead Services, Top-In / Top-Out Top feed installations can only be utilized for Overhead Services with a maximum rating of 1200 amps (See “L” above in this section). Load side conductors must be isolated from the line side The “H” dimension does not apply to this configuration, because the customer owns and installs all the conductors.

3. Underground Services, Bottom-In / Top-Out Underground feed installations (Alliant Energy conductors) shall enter and terminate on the bottom lugs of all Cabinets. The customer’s load side conductors shall terminate on the top lugs and exit above the load side lugs.

4. Underground Services, Bottom-In / Bottom-Out Underground feed installations (Alliant Energy conductors) shall enter and terminate on the bottom lugs of all Current Transformer (CT) Cabinet. Load side conductors shall terminate on the top lugs of the CT Cabinet and be routed either behind the CT bus work or to the left or right of the CT bus work down to the bottom of the cabinet to the load side conduits.

Page 3: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 36

If the cabinet is equipped with an external side gutter (pull box) or other external raceway, the load conductors shall be routed through this external side gutter (pull box) or raceway. Load side conductors exiting through an external gutter shall exit above the load side lugs. If the cabinet has internally mounted PT’s the exiting load side conductors shall be installed behind the PT’s pan.

5. Underground Services/Pad-Mount CT Cabinets, Bottom-In / Bottom-Out Metering Transformer Cabinets meeting the specifications for Bottom-In / Bottom-Out may be used in a free-standing, pad-mount configuration providing the following requirements are met: a) The cabinet shall be approved “Bottom-In / Bottom-Out” as listed in Chapter 2 of this

book. b) The cabinet shall have an Alliant Energy approved pedestal base mounted to the bottom

in order to bring the cabinet 9”-10” above the pad, unless this has been incorporated into the cabinet design. (If incorporated into the design the bottom of the access door shall be a minimum of 9 inches above grade.)

c) The entire assembly will be bolted to a suitable concrete pad, providing stable support and facilitating the required conduit for entrance and exit. Pad mounted CT cabinets shall be mounted on an isolated pad, adjacent to the transformer pad, to accommodate conduit elbow sweeps. Contact Alliant Energy engineering for pad design details and clearance requirements.

d) An approved meter socket may be mounted on the outside of the cabinet, as listed in Chapter 1 of this book. Meter socket shall be mounted only where it does not block or impede access at any time (open or closed) at a height consistent with the requirements in this book where possible.

e) In the event that customer request and Alliant Energy grants approval to reverse conductors (i.e., customer conductors on bottom and utilities wires on top), permanent signage shall note this change both outside and inside the cabinet (See section 432 E of the ESR Manual). Any additional cost will be borne by the customer.

N. Splices

Splices in meter sockets and instrument transformer cabinets are unacceptable. Current Transformer (CT) Cabinets shall not be used as raceways unless designed with such provisions.

Page 4: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 37

E201. CT BAR REQUIREMENTS

1/4"Fig.No 1

1/4"1/2"

1/4"Fig.

No. 2

3/4"

1/4"

7/8"W/2

W

1-11/16"

3/4"

6"

3/4"

1-11/16"

10-7/8"Fig.

No. 3

3/4"

1-11/16"

9/16" x 3/4"Slotted Holes

400-800 Amp Bus

Neutral TappedFor 10-24 Brass

Screw ForPotential Tap

Amps W W/2 #/PH Bars On Transf.

Fig.No.

Mounting Bolt Size

400 2 1 1 1 1 1/2x1-1/2

600 2-1/2 1-1/4 1 1 1 1/2x1-1/2

800 3-1/4 1-5/8 1 1 1 1/2x1-1/2

1000 3 1-1/2 1 1 1 1/2x1-1/2

1200 3 1-1/2 1 1 1 1/2x1-1/2

1600 3 1-1/2 2 2* 2 1/2x2-1/2

2000 3 1-1/2 2 2 2 1/2x2-1/2

3000 3 1-1/2 3 3 3 1/2x2-1/2

A single bar with adequate current capacity may be substituted

Customer shall furnish ½ mounting bolts for CT’s

Page 5: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 38

E202. CABLE SPACE REQUIREMENTS FOR CT CABINETS

E202B. PAD-MOUNTED CABINETS All stand-alone non-bussed pad-mounted service equipment cabinets are designed for Bottom Entry and Bottom Exit. Entry or exit thru either the top or side is not acceptable. Cabinets designed to be mounted against building or structure may be allowed to exit the top or side. Contact Alliant Energy for approval before installation.

Page 6: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 39

Table 1 Termination Cabinet Specification Table*

250 Volts Maximum

AmpacityLugs perPhase Lug Size

UnprotectedFault

CurrentRating(Amps)

MinimumWidth(Inches)

MinimumDepth(Inches)

Minimum "H"Dimension(Inches)

400 2 4/0 500 42,000 20 11 20600 2 4/0 500 65,000 24 14 20800 3 4/0 500 65,000 24 14 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26

Table 1A Termination Cabinets Specification Table600 Volt Maximum

AmpacityLugs perPhase Lug Size

UnprotectedFault

CurrentRating(Amps)

MinimumWidth(Inches)

MinimumDepth(Inches)

Minimum "H"Dimension(Inches)

400 2 4/0 500 42,000 20 15 20600 2 4/0 500 65,000 24 15 20800 3 4/0 500 65,000 24 15 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26

Specifications Table Requirements: States minimum criteria and can be exceeded to utilizemanufacturers’ available equipment.

“H” dimension refers to the distance from the bottom of line side lug to the bottom of theenclosure. See Diagram. For pad mounted cabinets the 9” or 10” mounting baserequirement is not included in the “H” dimension. For pad mounted cabinets it would be 9or 10 inches plus the listed “H” from the center of the lug to the pad.Minimumwidth does not include separate internal compartment for Bottom Feed/Bottomexit option. This edition became effective January 2016 and supersedes all earlier editions.

Page 7: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 40

Table 2 – Wall Mounted Current Transformer Cabinet Specification Table

250 Volts Maximum

AmpacityLugs perPhase Lug Size

UnprotectedFault

CurrentRating(Amps)

MinimumWidth(Inches)

MinimumDepth(Inches)

Minimum "H"Dimension(Inches)

400 2 4/0 500 42,000 20 11 20600 2 4/0 500 65,000 24 15 20800 3 4/0 500 65,000 24 15 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26

Table 2A – Residential Wall Mounted CT Cabinet Specification Table

250 Volts Maximum

AmpacityLugs perPhase Lug Size

UnprotectedFault

CurrentRating(Amps)

MinimumWidth(Inches)

MinimumDepth(Inches)

Minimum "H"Dimension(Inches)

400 2 4/0 500 42,000 20 8 14600 2 4/0 500 42,000 24 8 14

Page 8: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 41

Table 3 – Wall Mounted Current Transformer Cabinet Specification Table600 Volt Max. With Side Mounted PT Enclosure (Non integrated)

AmpacityCables

Per Phase Lug Size

UnprotectedFault

CurrentRating(Amps)

MinimumWidth(Inches)

MinimumDepth(Inches)

Minimum "H"Dimension(Inches)

400 2 4/0 500 42,000 24 15 20600 2 4/0 500 65,000 24 15 20800 3 4/0 500 65,000 24 15 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26

For pad mounted cabinets the 9” or 10” mounting base requirement is not included in the “H” dimension. Forpad mounted cabinets it would be 9 or 10 inches plus the listed “H” from the center of the lug to the pad.

Table 4 –Wall Mounted Current Transformer Cabinet Specification Table

600 Volt MaximumWith Integral PT Mounting

AmpacityCables

Per Phase Lug Size

UnprotectedFault

CurrentRating(Amps)

MinimumWidth(Inches)

MinimumDepth(Inches)

Minimum "H"Dimension(Inches)

400 2 4/0 500 42,000 32 15 20600 2 4/0 500 65,000 32 15 20800 3 4/0 500 65,000 32 15 201200 5 4/0 500 65,000 42 15 201600 4 500 1000 65,000 46 15 262000 5 500 1000 65,000 46 15 262500 7 500 1000 65,000 50 21 263000 8 500 1000 65,000 50 21 26

*Specifications are minimum criteria and can be exceeded to optimize manufactures’ available equipment. Minimum Width does not include separate internal compartment for Bottom Feed/Bottom Exit option or External PT. Enclosure. “H” dimension refers to the distance from the bottom of the line side lug(s) to the bottom of the enclosure. See diagram on page 32. For pad mounted cabinets the 9” or 10” mounting base requirement is not included in the “H”dimension. For pad mounted cabinets it would be 9 or 10 inches plus the listed “H” from the center of the lug to the pad.

Page 9: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Chapter 2

ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016

Page 42

Chapter 2 FOOTNOTES (Superscripts)

(1) Wall Mounted Transformer Cabinet 600 Volt Specifications Table with side mounted PT enclosure. (2) Wall Mounted Current Transformer Cabinet Specification Table with Integral PT Mounting. (3) An Optional Side wiring Gutter is required for Bottom Feed/Bottom Exit. The Side Gutter Wiring

Gutter may be located on either side Add suffix SGL (left) or SGR (right) to the catalog number. If American Midwest Power, order Pull Box style PB.

(4) Fill in # with B for CT at bottom configuration, or use T for CT at the Top configuration. (5) 400 - 800 Amp Wall Mounted Cabinets may be installed as a pad-mounted cabinet by adding a

CR12ES Ext. Kit. The ALIECT (A.M.P.) requires the CR15ECTS Extension kit. (6) Requires Stainless steel Mounting Base (PMB1624x10) when ordering pad-mounted cabinet. (7) Catalog Numbers can have CT section at bottom and disconnect at top, Change suffix CTA TO

CTB. (8) Mounting base factory installed for pad-mounted use. (9) Add optional Pad mount kit to convert wall mount to pad-mount where required 38' - PMR38 or

PMR42. (10) Add bottom plate for wall mount. (11) For Bottom-In/Bottom-out cabinets with internal raceways the letters (L-Left or R-Right) shall be

used to indicate which side of the cabinet the manufacturer will install the vertical raceway. The Standard Product for AMP & EMI will have the raceway installed on the right side, the standard for Galva Closure is with the raceway on the left side. The letter designation L or R will follow the manufacturer’s catalog number. Example ALICT4-L# would either be ALICT4-L3R (for right side or ALICT4-L3L for the left side).

(12) E-M-I --400 to 1200 Amp wall mounted cabinets may be installed as a pad-mounted cabinet by adding a FMR pad-mount riser.

(13) CM-8 suffix indicates 1200A horizontal bus. The suffix CM-9 (in place of CM-8 or added to the termination box catalog numbers) indicates 1600A horizontal bus. The suffix CM-7 indicates 800A horizontal bus.

(14)These CT cabinets are only allowed for 250 Volt applications, Residential Only. (15) For single phase three wire the 4 in the catalog number changes to 3. (16) Requires a separate cabinet for mounting Potential Transformers for 277/480. (17) Contains one 400 amp circuit breaker. (18) Contains 2-200 amp circuit breakers. (19) Contains 400 amp fused pull outs. (20) Contains one 600 amp circuit breaker (21) Contains 800 amp circuit breaker (22) Contains one 1200 amp circuit breaker (23)These devices may be pad-mounted but must also be anchored to building /wall to support the

enclosure. (24) All-in one combination units are limited to 1200 amps

I/W – Used with PMCTMS Cabinets: Follow the cabinet number with either I - Iowa; W - Wisconsin; for Meter Socket wiring designation. NA - Not applicable.

Page 10: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

E203 METERING TRANFORMER CABINETS - 400 AMP

400 A.M.P ALI6SCT4-4L 3 PH WALL/PAD (16)(23) MULTI 600

400 A.M.P ALICT4-3L 1 PH WALL (2)(5) 600

400 A.M.P ALICT4-4L 3 PH WALL (2)(5) 600

400 A.M.P ALIECT4-3L 1 PH WALL (5) 600

400 A.M.P ALIECT4-4L 3 PH WALL (16)(5) 600

400 A.M.P ALIMCT225 1 PH WALL (3)(4) 400 250

400 A.M.P ALIMCT225J 1 PH WALL/PAD (23) 400 250

400 A.M.P ALIMCT325 3 PH WALL (3)(4) 400 250

400 A.M.P ALIMCT325J 3 PH WALL/PAD (23) 400 250

400 A.M.P ALIMCT365J 3 PH WALL/PAD (16)(23) 400 600

400 A.M.P ALIPCT4-3L 1 PH PAD (2)(8) 600

400 A.M.P ALIPCT4-4L 3 PH PAD (2)(8) 600

400 A.M.P ALIRCT4-3L 1 PH WALL (14) 250

400 A.M.P ALIRCT4-4L 3 PH WALL (14) 250

400 A.M.P ALISCT4-3DT 1 PH WALL 400 250

400 A.M.P ALISCT4-3DTH 1 PH WALL 400 250

400 A.M.P ALISCT4-3L 1 PH WALL/PAD (23) MULTI 250

400 A.M.P ALISCT4-4DT 3 PH WALL 400 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 43

Page 11: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

400 A.M.P ALISCT4-4DTH 3 PH WALL 400 250

400 A.M.P ALISCT4-4L 3 PH WALL/PAD (23) MULTI 250

400 EMI ALICT140 1 PH WALL 250

400 EMI ALICT140P 1 PH PAD (2)(11)(12) 600

400 EMI ALICT340 3 PH WALL 600

400 EMI ALICT340P 3 PH PAD (2)(11)(12) 600

400 EMI ALIMSCT4 3 PH WALL 400 600

400 Erickson Electric ALICTAED3244N 1 PH WALL (18) 2-200 250

400 Erickson Electric ALICTAED4244N 3 PH WALL (18) 2-200 250

400 Erickson Electric ALICTAP3244N 1 PH WALL (18) 2-200 250

400 Erickson Electric ALICTAP4244N 3 PH WALL (18) 2-200 250

400 Erickson Electric ALICTBDK325N 1 PH WALL 400 250

400 Erickson Electric ALICTBDK425N 3 PH WALL 400 250

400 Erickson Electric ALICTBED3244N 1 PH WALL (18) 2-200 250

400 Erickson Electric ALICTBED4244N 3 PH WALL (18) 2-200 250

400 Erickson Electric ALICTBP3244N 1 PH WALL (18) 2-200 250

400 Erickson Electric ALICTBP325N 1 PH WALL 400 250

400 Erickson Electric ALICTBP4244N 3 PH WALL (18) 2-200 250

400 Erickson Electric ALICTBP425N 3 PH WALL 400 250

400 Erickson Electric ALICTBP4644N 3 PH WALL (18) 2-200 250

400 Erickson Electric ALICTDK325N 1 PH WALL 400 250

400 Erickson Electric ALICTDK425N 3 PH WALL 400 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 44

Page 12: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

400 Erickson Electric ALICTP325N 1 PH WALL 400 250

400 Erickson Electric ALICTP425N 3 PH WALL 400 250

400 Erickson Electric ALICTP465N-PT 3 PH WALL 400 250

400 Erickson Electric CT41-ALI 1 PH WALL/PAD (6) 250

400 Erickson Electric CT44-ALI 3 PH WALL/PAD (6) 250

400 Erickson Electric CT44-PT-ALI 3 PH WALL/PAD (6)(1) 600

400 Erickson Electric PMCTMS-425NMFALI 3 PH PAD (8) 400 250

400 Erickson Electric PMCTMS-465NMFPTALI 3 PH PAD (8) 400 600

400 Galva Closure ALI-413 1 PH WALL 250

400 Galva Closure ALI-413PM 1 PH PAD (8)(11) 250

400 Galva Closure ALI-413UGBX 1 PH WALL (11) 250

400 Galva Closure ALI-434 3 PH WALL 250

400 Galva Closure ALI-434PM 3 PH PAD (8)(11) 250

400 Galva Closure ALI-434UGBX 3 PH WALL (11) 250

400 Galva Closure ALI-464 3 PH WALL (2) 600

400 Galva Closure ALI-464PM 3 PH PAD (2)(8)(11) 600

400 Galva Closure ALI-464UGBX 3 PH WALL (2)(11) 600

400 Galva Closure ALI-CTDK12A-413 1 PH WALL (17) 400 250

400 Galva Closure ALI-CTDK12A-434 3 PH WALL (17) 400 250

400 Galva Closure ALI-CTHKD14A-464 3 PH WALL (17) 400 600

400 Galva Closure ALI-CTJGL224-464 3 PH WALL (18) 2-200 600

400 Galva Closure ALI-CTJGL22A-413 1 PH WALL (18) 2-200 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 45

Page 13: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

400 Galva Closure ALI-CTJGL22A-413PM 1 PH PAD (18) 2-200 250

400 Galva Closure ALI-CTJGL22A-413UGBX 1 PH WALL (18) 2-200 250

400 Galva Closure ALICTJGL22A-434 3 PH WALL (18) 2-200 250

400 Galva Closure ALI-CTJGL22L-413PM 1 PH PAD (18) 2-200 250

400 Galva Closure ALI-CTJGL22L-413UGBX 1 PH WALL (18) 2-200 250

400 Galva Closure ALI-CTJGL22L-434PM 3 PH PAD (18) 2-200 600

400 Galva Closure ALI-CTJGL22L-434UGBX 3 PH WALL (18) 2-200 600

400 Galva Closure ALI-CTJGL24A-464 3 PH WALL (18) 2-200 600

400 Galva Closure ALI-CTJGL24L-464PM 3 PH PAD (18) 2-200 600

400 Galva Closure ALI-CTJGL24L-464UGBX 3 PH WALL (18) 2-200 600

400 Galva Closure ALI-CTJJL24A-464 3 PH WALL (18) 2-200 600

400 Galva Closure ALI-CTJJL24L-464PM 3 PH PAD (19) 400 600

400 Galva Closure ALI-CTJJL24L-464UGBX 3 PH WALL 600

400 Galva Closure ALI-CTKDB14A-464 3 PH WALL (17) 400 600

400 Galva Closure ALI-CTLGL12A-413 1 PH WALL (17) 400 250

400 Galva Closure ALI-CTLGL14A-464 3 PH WALL (17) 400 600

400 Galva Closure ALI-CTLGL14L-413PM 1 PH PAD (17) 400 250

400 Galva Closure ALI-CTLGL14L-413UGBX 1 PH WALL (17) 400 250

400 Galva Closure ALI-CTLGL14L-434UGBX 3 PH WALL (17) 400 250

400 Galva Closure ALI-CTLGL14L-464PM 3 PH PAD (17) 400 600

400 Galva Closure ALI-CTPT12A-413 1 PH WALL (19) 400 250

400 Galva Closure ALI-CTPT12A-434 3 PH WALL (19) 400 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 46

Page 14: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

400 Galva Closure ALI-CTPT12L-413PM 1 PH PAD (19) 400 250

400 Galva Closure ALI-CTPT12L-413UGBX 1 PH WALL (19) 400 250

400 Galva Closure ALI-CTPT12L-434PM 3 PH PAD (19) 400 250

400 Galva Closure ALI-CTPT12L-434UGBX 3 PH WALL (19) 400 600

400 Galva Closure ALI-CTPT14A-464 3 PH WALL (19) 400 600

400 Galva Closure ALI-CTPT14A-464PM 3 PH PAD (19) 400 600

400 Galva Closure ALI-CTPT14A-464UGBX 3 PH WALL (19) 400 600

400 Galva Closure ALI-CTPT14L-464PM 3 PH PAD (19) 400 600

400 Galva Closure ALI-CTPT14L-464UGBX 3 PH WALL (17) 400 600

400 Galva Closure ALI-CTSFH22A413 1 PH WALL (18) 2-200 250

400 Galva Closure ALI-CTSFH22A-434 3 PH WALL (18) 2-200 250

400 Galva Closure ALI-CTSFH24A-464 3 PH WALL (18) 2-200 600

400 Galva Closure ALI-CTSFL24A-464 3 PH WALL (18) 2-200 600

400 Galva Closure ALI-CTSGD12A-413 1 PH WALL (17) 400 250

400 Galva Closure ALI-CTSGD12A-434 3 PH WALL (17) 400 250

400 Galva Closure ALI-CTSGH14A-464 3 PH WALL (17) 400 600

400 Galva Closure ALI-CTSGL14A-464 3 PH WALL (17) 400 600

400 Galva Closure ALI-RES-413 1 PH WALL 400

400 Galva Closure ALI-RES-434 3 PH WALL 400

E204 METERING TRANSFORMER CABINETS - 600 AMPS

600 A.M.P ALI6SCT6-4L 3 PH WALL/PAD (16)(23) MULTI 600

600 A.M.P ALICT6-3L 1 PH WALL (2)(5) 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 47

Page 15: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

600 A.M.P ALICT6-4L 3 PH WALL (2)(5) 600

600 A.M.P ALIECT6-3L 1 PH WALL (5) 600

600 A.M.P ALIECT6-4L 3 PH WALL (16)(5) 600

600 A.M.P ALIMCT226 1 PH WALL (3)(4) 600 250

600 A.M.P ALIMCT226J 1 PH WALL/PAD (23) 600 250

600 A.M.P ALIMCT326 3 PH WALL (3)(4) 600 250

600 A.M.P ALIMCT326J 3 PH WALL/PAD (23) 600 250

600 A.M.P ALIMCT366J 3 PH WALL/PAD (16)(23) 600 600

600 A.M.P ALIPCT6-3L 1 PH PAD (2)(8) 600

600 A.M.P ALIPCT6-4L 3 PH PAD (2)(8) 600

600 A.M.P ALIRCT6-3L 1 PH WALL (14) 250

600 A.M.P ALIRCT6-4L 3 PH WALL (14) 250

600 A.M.P ALISCT6-3L 1 PH WALL/PAD (23) MULTI 250

600 A.M.P ALISCT6-4L 3 PH WALL/PAD (23) MULTI 250

600 EMI ALICT160 1 PH WALL 250

600 EMI ALICT160P 1 PH WALL/PAD (2)(11)(12) 600

600 EMI ALICT360 3 PH WALL 600

600 EMI ALICT360P 3 PH WALL/PAD (2)(11)(12) 600

600 EMI ALIMSCT6 3 PH WALL 600 600

600 EMI ALIRCT160 1 PH WALL 250

600 Erickson Electric CT61-ALI 1 PH WALL/PAD (6) 250

600 Erickson Electric CT61-ALI-SEA 1 PH WALL 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 48

Page 16: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

600 Erickson Electric CT64-ALI 3 PH WALL/PAD (6) 250

600 Erickson Electric CT64-ALI-SEA 3 PH WALL 250

600 Erickson Electric CT64-PT-ALI 3 PH WALL/PAD (1)(6) 600

600 Erickson Electric PMCTMS-426NMFALI 3 PH PAD (8) 600 250

600 Erickson Electric PMCTMS-466NMFPTALI 3 PH PAD (8) 600 600

600 Galva Closure ALI-613 1 PH WALL 250

600 Galva Closure ALI-613PM 1 PH PAD (8)(11) 250

600 Galva Closure ALI-613UGBX 1 PH WALL (11) 250

600 Galva Closure ALI-634 3 PH WALL 250

600 Galva Closure ALI-634PM 3 PH PAD (8)(11) 250

600 Galva Closure ALI-634UGBX 3 PH WALL (11) 250

600 Galva Closure ALI-664 3 PH WALL (2) 600

600 Galva Closure ALI-664PM 3 PH PAD (2)(8)(11) 600

600 Galva Closure ALI-664UGBX 3 PH WALL (2)(11) 600

600 Galva Closure ALI-CTMGL12A-613 1 PH WALL (20) 600 250

600 Galva Closure ALI-CTMGL12A-634 3 PH WALL (20) 600 250

600 Galva Closure ALI-CTMGL12L-613PM 1 PH PAD 250

600 Galva Closure ALI-CTMGL12L-613UGBX 1 PH WALL (20) 600 250

600 Galva Closure ALI-CTMGL12L-634PM 3 PH PAD 250

600 Galva Closure ALI-CTMGL12L-634UGBX 3 PH WALL (20) 600 250

600 Galva Closure ALI-CTMGL14A-664 3 PH WALL 600

600 Galva Closure ALI-CTMGL14L-664PM 3 PH PAD 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 49

Page 17: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

600 Galva Closure ALI-CTMGL14L-664UGBX 3 PH WALL (20) 600 600

600 Galva Closure ALI-CTMJL14L-664PM 3 PH PAD 600

600 Galva Closure ALI-CTMJL14L-664UGBX 3 PH WALL 600

600 Galva Closure ALI-RES-613 1 PH WALL (14) 250

600 Galva Closure ALI-RES-634 3 PH WALL (14) 250

E205 METERING TRANSFORMER CABINETS - 800 AMPS

800 A.M.P ALI6SCT8-4L 3 PH WALL/PAD (16)(23) 600

800 A.M.P ALICT8-3L 1 PH WALL (2)(5) 600

800 A.M.P ALICT8-4L 3 PH WALL (2)(5) 600

800 A.M.P ALIECT8-3L 1 PH WALL (5) 600

800 A.M.P ALIECT8-4L 3 PH WALL (16)(5) 600

800 A.M.P ALIMCT227 1 PH WALL (3)(4) 250

800 A.M.P ALIMCT227L 1 PH WALL/PAD (23) 250

800 A.M.P ALIMCT327 3 PH WALL (3)(4) 250

800 A.M.P ALIMCT327L 3 PH WALL/PAD (23) 250

800 A.M.P ALIMCT367L 3 PH WALL/PAD (16)(23) 600

800 A.M.P ALIPCT8-3L 1 PH PAD (2)(8) 600

800 A.M.P ALIPCT8-4L 3 PH PAD (2)(8) 600

800 A.M.P ALISCT8-3L 1 PH WALL/PAD (23) MULTI 250

800 A.M.P ALISCT8-4L 3 PH WALL/PAD (23) MULTI 250

800 EMI ALICT180 1 PH WALL 250

800 EMI ALICT180P 1 PH PAD (11)(12) 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 50

Page 18: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

800 EMI ALICT380 3 PH WALL 600

800 EMI ALICT380P 3 PH PAD (2)(11)(12) 600

800 EMI ALIMSCT8 3 PH WALL 600

800 EMI ALIPM380 3 PH PAD (11) 600

800 Erickson Electric CT81-ALI 1 PH WALL/PAD (6) 250

800 Erickson Electric CT84-ALI 3 PH WALL/PAD (6) 250

800 Erickson Electric CT84-PT-ALI 3 PH WALL/PAD (1)(6) 600

800 Erickson Electric PMCTMS-427NMFALI 3 PH PAD (8) 250

800 Erickson Electric PMCTMS-467NMFPTALI 3 PH PAD (8) 600

800 Galva Closure ALI-813 1 PH WALL 250

800 Galva Closure ALI-813PM 1 PH PAD (8)(11) 250

800 Galva Closure ALI-813UGBX 1 PH WALL (11) 250

800 Galva Closure ALI-834 3 PH WALL 250

800 Galva Closure ALI-834PM 3 PH PAD (8)(11) 250

800 Galva Closure ALI-834UGBX 3 PH WALL (11) 250

800 Galva Closure ALI-864 3 PH WALL (2) 600

800 Galva Closure ALI-864PM 3 PH PAD (2)(8)(11) 600

800 Galva Closure ALI-864UGBX 3 PH WALL (2)(11) 600

800 Galva Closure ALI-CTMGL12A-813 1 PH WALL (21) 800 250

800 Galva Closure ALI-CTMGL12A-834 3 PH WALL (21) 800 250

800 Galva Closure ALI-CTMGL12L-813PM 1 PH PAD 250

800 Galva Closure ALI-CTMGL12L-813UGBX 1 PH WALL (21) 800 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 51

Page 19: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

800 Galva Closure ALI-CTMGL12L-834PM 3 PH PAD (21) 800 250

800 Galva Closure ALI-CTMGL12L-834UGBX 3 PH WALL (21) 800 250

800 Galva Closure ALI-CTMGL12L-864PM 3 PH PAD (21) 800 600

800 Galva Closure ALI-CTMGL12L-864UGBX 3 PH WALL (21) 800 600

800 Galva Closure ALI-CTMGL14A-864 3 PH WALL (21) 800 600

800 Galva Closure ALI-CTMGL14L-864PM 3 PH PAD 600

800 Galva Closure ALI-CTMJL14L-864PM 3 PH PAD 600

E206 METERING TRANSFORMER CABINETS - 800 AMPS

1200 Galva Closure ALI-PGL12L-1234PM 3 PH PAD (21) 800 250

1200 A.M.P ALICT12-4L 3 PH WALL (2)(11) 600

1200 A.M.P ALIECT12-4L 3 PH WALL/PAD (16) 600

1200 A.M.P ALIMCT368L 3 PH WALL/PAD (16)(23) 600

1200 A.M.P ALIPCT12-4L 3 PH PAD (2)(8)(11) 600

1200 A.M.P ALISCT12-4L 3 PH WALL/PAD (23) 600

1200 EMI ALICT312 3 PH WALL 250

1200 EMI ALICT312P 3 PH WALL/PAD (3)(11)(12) 600

1200 EMI ALIPM312 3 PH PAD (5)(11) 600

1200 Erickson Electric CT124-ALI 3 PH WALL (3) 250

1200 Erickson Electric CT124-PT-ALI 3 PH WALL (1)(3) 600

1200 Erickson Electric PMCT124MF-ALI 3 PH PAD (8) 250

1200 Erickson Electric PMCT124MF-PT-ALI 3 PH PAD (8) 600

1200 Erickson Electric PMCTMS-428NMFALI 3 PH PAD (8) 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 52

Page 20: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

1200 Erickson Electric PMCTMS-468NG6MFPTALI 3 PH PAD (8) 600

1200 Galva Closure ALI-1234 3 PH WALL 250

1200 Galva Closure ALI-1234PM 3 PH PAD (8)(11) 250

1200 Galva Closure ALI-1234UGBX 3 PH WALL 250

1200 Galva Closure ALI-1264 3 PH WALL (2) 600

1200 Galva Closure ALI-1264PM 3 PH PAD (2)(8)(11) 600

1200 Galva Closure ALI-1264UGBX 3 PH WALL (2) 600

1200 Galva Closure ALI-CTPGL12A-1234 3 PH WALL (22) 1200 250

1200 Galva Closure ALI-CTPGL12L-1234PM 3 PH PAD 600

1200 Galva Closure ALI-CTPGL12L-1234UGBX 3 PH WALL (22) 1200 250

1200 Galva Closure ALI-CTPGL12L-1264UGBX 3 PH WALL (22) 1200 600

1200 Galva Closure ALI-CTPGL14A-1264 3 PH WALL (22) 1200 600

1200 Galva Closure ALI-CTPGL14L-1264PM 3 PH PAD 600

1200 Galva Closure ALI-CTPJL14L-1264PM 3 PH PAD 600

E207 TRANSFORMER METERING CABINETS - 1600 AMP

1600 A.M.P ALICT16-4L 3 PH WALL (2)(11) 600

1600 A.M.P ALIECT16-4L 3 PH WALL/PAD (16) 600

1600 A.M.P ALIPCT16-4L 3 PH PAD (2)(8)(11) 600

1600 EMI ALICT316 3 PH WALL 250

1600 EMI ALIPM316 3 PH PAD (10)(11) 600

1600 Erickson Electric CT164-ALI 3 PH WALL (3) 250

1600 Erickson Electric CT164-PT-ALI 3 PH WALL (1)(3) 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 53

Page 21: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

1600 Erickson Electric PMCT164MF-ALI 3 PH PAD (8) 250

1600 Erickson Electric PMCT164MF-PT-ALI 3 PH PAD (8) 600

1600 Erickson Electric PMCTMS-429NMFALI 3 PH PAD (8) 250

1600 Erickson Electric PMCTMS-469G6MFPTALI 3 PH PAD (8) 600

1600 Galva Closure ALI-1634 3 PH WALL 250

1600 Galva Closure ALI-1634PM 3 PH PAD (8)(11) 250

1600 Galva Closure ALI-1634UGBX 3 PH WALL (11) 250

1600 Galva Closure ALI-1664 3 PH WALL (2) 600

1600 Galva Closure ALI-1664PM 3 PH PAD (2)(8)(11) 600

1600 Galva Closure ALI-1664UGBX 3 PH WALL (2)(11) 600

E208 TRANSFORMER METERING CABINETS - 2000 AMP

2000 A.M.P ALICT20-4L 3 PH WALL (2)(11) 600

2000 A.M.P ALIECT20-4L 3 PH WALL/PAD (16) 600

2000 A.M.P ALIPCT20-4L 3 PH PAD (2)(8)(11) 600

2000 EMI ALICT320 3 PH WALL 250

2000 EMI ALIPM320 3 PH PAD (10)(11) 600

2000 Erickson Electric CT204-ALI 3 PH WALL (3) 250

2000 Erickson Electric CT204PTALI 3 PH WALL (1)(3) 600

2000 Erickson Electric PMCT204MF-ALI 3 PH PAD (8) 250

2000 Erickson Electric PMCT204MFPTALI 3 PH PAD (8) 600

2000 Erickson Electric PMCTMS-4210NMFALI 3 PH PAD (8) 250

2000 Erickson Electric PMCTMS-4610NG6MFPTALI

3 PH PAD (8) 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 54

Page 22: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

2000 Galva Closure ALI-2034 3 PH WALL 250

2000 Galva Closure ALI-2034PM 3 PH PAD (11) 250

2000 Galva Closure ALI-2034UGBX 3 PH PAD (11) 250

2000 Galva Closure ALI-2064 3 PH WALL (2) 600

2000 Galva Closure ALI-2064PM 3 PH PAD (2)(11) 600

2000 Galva Closure ALI-2064UGBX 3 PH WALL (2)(11) 600

E209 TRANSFORMER METERING CABINETS - 2500 AMP

2500 A.M.P ALICT25-4L 3 PH WALL (2)(11) 600

2500 A.M.P ALIPCT25-4L 3 PH PAD (2)(8)(11) 600

2500 EMI ALIPM325 3 PH PAD (10)(11) 600

2500 Erickson Electric CT254ALI 3 PH WALL (3) 250

2500 Erickson Electric CT254PTALI 3 PH WALL (1)(3) 600

2500 Erickson Electric PMCT254MFALI 3 PH PAD (8) 250

2500 Erickson Electric PMCT254MFPTALI 3 PH PAD (8) 600

2500 Erickson Electric PMCTMS-4211NMFALI 3 PH PAD (8) 250

2500 Erickson Electric PMCTMS-4611NG6MFPTALI

3 PH PAD (8) 600

2500 Galva Closure ALI-2534 3 PH WALL 250

2500 Galva Closure ALI-2534PM 3 PH PAD (8)(11) 250

2500 Galva Closure ALI-2534UGBX 3 PH WALL (11) 250

2500 Galva Closure ALI-2564 3 PH WALL (2) 600

2500 Galva Closure ALI-2564PM 3 PH PAD (2)(8)(11) 600

2500 Galva Closure ALI-2564UGBX 3 PH WALL (2)(11) 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 55

Page 23: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

E210 TRANSFORMER METERING CABINETS - 3000 AMP

3000 A.M.P ALICT30-4L 3 PH WALL (2)(11) 600

3000 A.M.P ALIPCT30-4L 3 PH PAD (2)(8)(11) 600

3000 EMI ALIPM330 3 PH PAD (10)(11) 600

3000 Erickson Electric CT304-ALI 3 PH WALL (3) 250

3000 Erickson Electric CT304PTAL 3 PH WALL (1)(3) 600

3000 Erickson Electric PMCT304MFALI 3 PH PAD (8) 250

3000 Erickson Electric PMCT304MFPTALI 3 PH PAD (8) 600

3000 Erickson Electric PMCTMS-4212NMFALI 3 PH PAD (8) 250

3000 Erickson Electric PMCTMS-4612NG6MFPTALI

3 PH PAD (8) 600

3000 Galva Closure ALI-3034 3 PH WALL 250

3000 Galva Closure ALI-3034PM 3 PH PAD (11) 250

3000 Galva Closure ALI-3034UGBX 3 PH WALL (11) 250

3000 Galva Closure ALI-3064 3 PH WALL (2) 600

3000 Galva Closure ALI-3064PM 3 PH PAD (2)(11) 600

3000 Galva Closure ALI-3064UGBX 3 PH WALL (2)(11) 600

E211 TERMINATION BOXES 400 AMPS MAX.

400 A.M.P ALIPTB4-3L 1 PH PAD (8) 600

400 A.M.P ALIPTB4-4L 3 PH PAD (8) 600

400 A.M.P ALITB4-3L 1 PH WALL (5) 600

400 A.M.P ALITB4-4L 3 PH WALL (5) 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 56

Page 24: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

400 EMI ALITB140 1 PH WALL 600

400 EMI ALITB340 3 PH WALL 600

400 Erickson Electric ALITB-365N 1 PH WALL 250

400 Erickson Electric ALITB-465N 3 PH WALL 600

400 Galva Closure TBALI-413-1 1 PH WALL 600

400 Galva Closure TBALI-434-1 3 PH WALL 600

400 Galva Closure TBBXALI413-1 1 PH WALL (11) 600

400 Galva Closure TBBXALI434-1 3 PH WALL (11) 600

400 Galva Closure TBPMALI-413-1 1 PH PAD 600

400 Galva Closure TBPMALI-434-1 3 PH PAD 600

E212 TERMINATION BOXES 600 AMPS MAX.

600 A.M.P ALIPTB6-3L 1 PH PAD (8) 600

600 A.M.P ALIPTB6-4L 3 PH PAD (8) 600

600 A.M.P ALITB6-3L 1 PH WALL (5) 600

600 A.M.P ALITB6-4L 3 PH WALL (5) 600

600 EMI ALITB160 1 PH WALL 600

600 EMI ALITB360 3 PH WALL 600

600 Erickson Electric ALITB-366N 1 PH WALL 250

600 Erickson Electric ALITB-466N 3 PH WALL 600

600 Galva Closure TBALI613-2 1 PH WALL 600

600 Galva Closure TBALI634-2 3 PH WALL 600

600 Galva Closure TBBXALI613-2 1 PH WALL (11) 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 57

Page 25: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

600 Galva Closure TBBXALI634-2 3 PH WALL (11) 600

600 Galva Closure TBPMALI-613-2 1 PH PAD 600

600 Galva Closure TBPMALI-634-2 3 PH PAD 600

E213 TERMINATION BOXES 800 AMPS MAX

800 A.M.P ALIPTB8-3L 1 PH PAD (8) 600

800 A.M.P ALIPTB8-4L 3 PH PAD (8) 600

800 A.M.P ALITB8-3L 1 PH WALL (5) 600

800 A.M.P ALITB8-4L 3 PH WALL (5) 600

800 A.M.P ALITC8-3L 1 PH WALL 600

800 A.M.P ALITC8-4L 3 PH WALL 600

800 EMI ALITB180 1 PH WALL 600

800 EMI ALITB380 3 PH WALL 600

800 Erickson Electric ALITB365N 1 PH WALL 250

800 Erickson Electric ALITB467N 3 PH WALL 600

800 Galva Closure TBALI813-3 1 PH WALL 600

800 Galva Closure TBALI834-3 3 PH WALL 600

800 Galva Closure TBBXALI813-3 1 PH PAD (11) 600

800 Galva Closure TBBXALI834-3 3 PH PAD (11) 600

800 Galva Closure TBPMALI-813-1 1 PH PAD 600

800 Galva Closure TBPMALI-834-1 3 PH PAD 600

E214 TERMINATION BOXES 1200 AMPS MAX

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 58

Page 26: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

1200 A.M.P ALIPTB12-4L 3 PH PAD (8)(11) 600

1200 A.M.P ALITB12-4L 3 PH WALL (11) 600

1200 A.M.P ALITC12-4L 3 PH WALL 600

1200 EMI ALITB312 3 PH WALL 600

1200 Erickson Electric ALIPMTB-468N 3 PH PAD 600

1200 Erickson Electric ALITB468N 3 PH WALL 600

1200 Erickson Electric ALITB468NSG 3 PH WALL 600

1200 Galva Closure TBALI1234-5 3 PH WALL 600

1200 Galva Closure TBBXALI-1234-5 3 PH WALL 600

1200 Galva Closure TBPMALI-1234-5 3 PH PAD 600

E215 TERMINATION BOXES 1600 AMPS MAX.

1600 A.M.P ALIPTB16-4L 3 PH PAD (8)(11) 600

1600 A.M.P ALITB16-4L 3 PH WALL (11) 600

1600 A.M.P ALITC16-4L 3 PH WALL 600

1600 EMI ALITB316 3 PH PAD 600

1600 Erickson Electric ALIPMTB469N 3 PH PAD 600

1600 Erickson Electric ALITB469N 3 PH WALL 600

1600 Erickson Electric ALITB469NSG 3 PH WALL 600

1600 Galva Closure TBALI-1634-4 3 PH WALL 600

1600 Galva Closure TBBXALI-1634-4 3 PH WALL (11) 600

1600 Galva Closure TBPMALI-1634-4 3 PH PAD 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 59

Page 27: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

E216 TERMINATION BOXES 2000 AMPS MAX

2000 A.M.P ALIPTB20-4L 3 PH PAD (8)(11) 600

2000 A.M.P ALITB-20-4L 3 PH WALL (11) 600

2000 A.M.P ALITC20-4L 3 PH WALL 600

2000 EMI ALITB320 3 PH PAD 600

2000 Erickson Electric ALIPMTB4610N 3 PH PAD 600

2000 Erickson Electric ALITB4610N 3 PH WALL 600

2000 Erickson Electric ALITB4610NSG 3 PH WALL 600

2000 Galva Closure TBALI-2034-5 3 PH WALL 600

2000 Galva Closure TBBXALI-2034-5 3 PH WALL (11) 600

2000 Galva Closure TBPMALI-2034-5 3 PH PAD 600

E217 TERMINATION BOXES 2500 AMPS MAX.

2500 A.M.P ALIPTB25-4L 3 PH PAD (8)(11) 600

2500 A.M.P ALITB25-4L 3 PH WALL (11) 600

2500 EMI ALITB325 3 PH PAD 600

2500 Erickson Electric ALIPMTB4611N 3 PH PAD 600

2500 Erickson Electric ALITB4611N 3 PH WALL 600

2500 Erickson Electric ALITB4611NSG 3 PH WALL 600

2500 Galva Closure TBALI-2534-7 3 PH WALL 600

2500 Galva Closure TBBXALI-2534-7 3 PH PAD (11) 600

2500 Galva Closure TBPMALI-2534-7 3 PH PAD 600

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 60

Page 28: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

E218 TERMINATION BOX 3000 AMP MAX

3000 A.M.P ALIPTB30-4L 3 PH (8)(11) 600

3000 A.M.P ALITB30-4L 3 PH (11) 600

3000 EMI ALITB330 3 PH PAD 600

3000 Erickson Electric ALIPMTB4612N 3 PH PAD 600

3000 Erickson Electric ALITB4612N 3 PH WALL 600

3000 Erickson Electric ALITB4612NSG 3 PH 600

3000 Galva Closure TBALI-3034-8 3 PH WALL 600

3000 Galva Closure TBBXALI-3034-8 3 PH WALL 600

3000 Galva Closure TBPMALI-3034-8 3 PH PAD 600

E219 HORIZONTAL BUSSED CABINETS - 400AMPS, TERM.,BREAKER AND DISCO- METERING 250V MAX

400 Eaton-CH ALI-TRB-325N-CH 1 PH WALL

400 Eaton-CH ALI-TRB-425N-CH 3 PH WALL

400 Eaton-CH ALI-XMCBE-400R 3 PH WALL (14)

400 Siemens/Murray WEB1400BU 1 PH WALL

400 Siemens/Murray WEB3400BU 3 PH WALL

400 Siemens/Murray WES1400BU 1 PH WALL

400 Siemens/Murray WES3400BU 3 PH WALL

400 Eaton-CH ALI-CTA-P-4244N-CM8-CH 3 PH WALL (7)(13)(15)

400 Eaton-CH ALI-CTA-P-425N-CM8-CH 3 PH WALL (7)(13)(15)

400 Eaton-CH ALI-CTA-T-425N-CM8-CH 3 PH WALL (7)(13)(15)

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 61

Page 29: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

400 Erickson Electric ALI-CTA-DK-425N-CM8 3 PH (7)(15)

400 Erickson Electric ALI-CTA-P-425-CM8 3 PH WALL (7)(15)

400 Erickson Electric ALI-CTA-T-425N-CM8 3 PH WALL

400 Erickson Electric ALI-TRB-425N 3 PH WALL (13)(15)

E220 HORIZONTAL BUSSED CABINETS-600 AMP TERM BREAKER DISCO METERING-250V

600 Eaton-CH ALI-TRB-326N-CH 1 PH WALL (13)

600 Eaton-CH ALI-TRB-426N-CH 3 PH WALL (13)

600 Eaton-CH ALI-CTA-T-426N-CM8-CH 3 PH WALL (13)

600 Erickson Electric ALI-CTA-LD-426N-CM8 3 PH WALL (7)(15)(13)

600 Erickson Electric ALI-CTA-T-426N-CM8 3 PH WALL (7)(15)(13)

600 Erickson Electric ALI-TRB-426N 3 PH WALL (15)(13)

600 Siemens/Murray WEB1600BU-1PHASE 1 PH WALL

600 Siemens/Murray WEB3600BU-3PHASE 3 PH WALL

600 Siemens/Murray WES1600BU-1PHASE 1 PH WALL

600 Siemens/Murray WES3600BU-3PHASE 3 PH WALL

E221 HORIZONTAL BUSSED CABINETS-800 AMP TERM BREAKER DISCO METERING-250V MAX

800 Eaton ALI-TRB327N-CH 1 PH WALL

800 Eaton ALI-TRB427N-CH 3 PH WALL

800 Eaton-CH ALI-CTA-T-427N-CM8-CH 3 PH WALL

800 Erickson Electric ALI-CTA-MD-427N-CM8 3 PH WALL (7)(15)

800 Erickson Electric ALI-CTA-T-427N-CM8 3 PH WALL (7)(15)

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 62

Page 30: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

800 Erickson Electric ALI-TRB327N-LE 1 PH WALL

800 Erickson Electric ALI-TRB427N-LE 3 PH WALL

800 Siemens/Murray WEB1800BU-1PHASE 1 PH WALL

800 Siemens/Murray WEB3800BU-3PHASE 3 PH WALL

800 Siemens/Murray WES1800BU-1PHASE 1 PH WALL

800 Siemens/Murray WES3800BU-3PHASE 3 PH WALL

E222 HORIZONTAL BUSSED CABINETS-1200 AMP TERM BREAKER DISCO METERING-250V

1200 Eaton-CH ALI-TRB-428N-CH 3 PH WALL (13)

1200 Erickson Electric ALI-CTA-124-2-CM8 3 PH WALL (7)(15)(13)

1200 Erickson Electric ALI-TRB-428N 3 PH WALL (13)

1200 Siemens/Murray WEB11200BU-1PHASE 1 PH WALL

1200 Siemens/Murray WEB31200BU-3PHASE 3 PH WALL

1200 Siemens/Murray WES11200BU-1PHASE 1 PH WALL

1200 Siemens/Murray WES31200BU-3PHASE 3 PH WALL

E223 HORIZONTAL BUSSED CABINET- 1600 AMPS TERM. BREAKER & DISCO 250V MAX

1600 Eaton-CH ALI-TRB-429N-CH 3 PH WALL (13)

1600 Erickson Electric ALI-TRB-429N 3 PH (13)

E224 HORIZONTAL BUSSED CABINET- 2000 AMPS TERM. BREAKER & DISCO 250V MAX

2000 Eaton-CH ALI-TRB-4210N-CH 3 PH WALL (13)

2000 Erickson Electric ALI-TRB-4210N 3 PH (13)

E225 Horiz Bussed Term Box & Metering Trans Cabinets 600V Max

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 63

Page 31: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /

Btm OutBtm In/ Top Out

Btm In/ Btm Out

Pad- Mount

Wall-mount Configuration

1200 Erickson Electric ALI-CTA124-2-PT-6CM8 3 PH (7)(13)

400 Erickson Electric ALI-CTA-KD-465N-PT-6CM8 3 PH (7)(13)

600 Erickson Electric ALI-CTA-LD-466N-PT-6CM8 3 PH (7)(13)

800 Erickson Electric ALI-CTA-MD-467N-PT-6CM8 3 PH (7)(13)

400 Erickson Electric ALI-CTA-P-465-PT-6CM8 3 PH (7)(13)

400 Erickson Electric ALI-CTA-T-465N-PT-6CM8 3 PH (7)(13)

600 Erickson Electric ALI-CTA-T-466N-PT-6CM8 3 PH (13)

800 Erickson Electric ALI-CTA-T-467N-PT-6CM8 3 PH (7)(13)

2000 Erickson Electric ALI-TRB-42610N 3 PH

400 Erickson Electric ALI-TRB-465N 3 PH (13)

600 Erickson Electric ALI-TRB-466N 3 PH (13)

800 Erickson Electric ALI-TRB-467N 3 PH (13)

1200 Erickson Electric ALI-TRB-468N 3 PH (13)

1600 Erickson Electric ALI-TRB-469N 3 PH

E226 SWITCHBOARD STRUCTURES - 400 TO 3000 AMPS (250 VOLT MAX.)

0 A.M.P ALIFMURCTCB 3 PH PAD 250

0 A.M.P ALIFMURCTCT 3 PH PAD 250

0 A.M.P ALIFMURCTCTS 3 PH PAD (24) 250

0 A.M.P ALIFMURCTS 3 PH PAD (24) 250

0 A.M.P ALIFMURMCT 3 PH PAD 250

0 A.M.P ALIFMURMS 3 PH PAD 250

0 A.M.P ALIFMURTC 3 PH PAD 250

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 64

Page 32: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

Amps Manufacturer Catalog Number PH Mounting Foot Notes Voltage Range

250A.M.P. ALIRMR90 3 PH PAD

Chapter 2 EQUIPMENT- CABINETS

IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Footnotes on Pg. 42 Page 65

Page 33: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

ALLIANT ENERGY

ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Page 66

E227. DEADFRONT PRIMARY METERING ENCLOSURES – 15 KV Durham – Cabinet – No. PME-3P-15KV- 200A-XY-ALI PME- 3P-15KV-600A-XY-ALI IPME-3P-15KV-600A-XY-ALI a. JVM-5 PT’s (indoor w/fuse) & JKM-5a CT (Indoor) (Line bushing-(1)/Load bushing-(1))

ABB/Malton – Cabinet – No. MEF72652DFM-15 – 600 Amp. a. JVM-5PT’s (Indoor w/fuse) & JKW-5A CT’s (Indoor) (Line bushing – 1-600, 1-200)/Load bushing- (1))

Elliot – Cabinet – No. EPM-PMS – 15-3XYP-E2-ALI – 200 Amp EPM-PMS – 15-3XYP-E6-ALI - 600 Amp a. VW-5PT’s (Outdoor w/o fuse) and jkw-5A CT’s (Outdoor) (line bushing –(1 or 2)/Load bushing-(1 or 2) Shallbetter – Cabinet – No. SPMD-31511-66-GA

E228. DEADFRONT PRIMARY METERING ENCLOSURES – 25 KV

Durham – Cabinet – No. PME-3P-25KV-200A-XY-ALI PME-3P-25KV-600A-XY-ALI a. JVW-6PT”s (outdoor) and JKW-6A CT’s (Outdoor) (#Line bushing-(X)/#Load bushing-(Y)) Elliot – Cabinet – No. EPM – PMS – 25 – 3XYP-E2 – ALI EPM – PMS – 25 – 3XYP-E6 – ALI (Alliant Energy provides separate PT fuses) Shallbetter – Cabinet – No. SPMD-32511-66-GA

NOTE: WE WILL ONLY LIST POLE TOP(SITE ISOLATING DEVICES) AND GRADE

LEVEL TRANSFER SWITCHES WITH METER SOCKETS. ALL OTHER TRANSFER SWITCHES, 600 VOLTS OR LESS, WILL BE ALLOWED, PROVIDED THEY MEET THE REQUIREMENTS LISTED IN CHAPTER 12, U.L., AND MEET NEC REQUIREMENTS

E229. FARMSTEAD POLE TOP TRANSFER SWITCHES – 250 VOLTS MAX.

NEC 547.2 Site-Isolating Device MANUF. SIZE(AMPS) ITEM# REMARKS Ronk Electric Industries 400 9406 Single phase – 2 pole 400 9806 Three phase – 3 pole 800 R8208 Single phase – 2 pole 800 R8808 Three phase – 3 pole E230. FARMSTEAD POLE TOP TRANSFER SWITCHES – 600 VOLT MAX.

NEC 547.2 Site-Isolating Device MANUF. SIZE (AMPS) ITEM # REMARKS Ronk Electric Industries 400 9808 Three phase – 3 pole 800 R8808 Three phase – 3 pole E231. RESIDENTIAL GRADE LEVEL TRANSFER SWITCHES WITH METER SOCKET – 250 VOLT

Page 34: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

ALLIANT ENERGY

ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Page 67

MANUFACTURER SIZE(AMPS) ITEM# REMARKS Ronk Electric Industries 200 7215-MSH(*) – (**) Single phase – 2 pole Note: (*) = H / Horn Bypass or L / Lever Bypass. (**) = OH / Over Head, UG / Underground or SS / Side by Side (Overhead or Underground). Unit has 10,000 AIC rating only. E232. GRADE LEVEL OPERATED PRIMARY VOLTAGE POLE TOP LOAD BREAK

SWITCH MANUFACTURER SIZE (VOLTS) ITEM# REMARKS S&C 15KV 137032R1-S101 Single phase – 1 pole (ED-92AR-T200) (Horizontal) 15KV 137032R1-S101 Single phase – 1 pole (ED-7867) (Vertical) 25KV 147413/ED-701 Three phase – 3 pole Gang Operated

E233. 3 PHASE PADMOUNT TRANSFORMERS BOX PADS

E234. UNDERGROUND SERVICE WIREWAYS (Approved for maintenance use and where standard conduits are impractical only).

MANUFACTURER ITEM #.

A.M.P. WWPBXX & WWLPXX Galva Closure Model CC & CCL

Page 35: ELECTRIC SERVICE EQUIPMENT – METER CABINETS …int/documents/... · Chapter 2 ELECTRIC SERVICE EQUIPMENT ... for a field test. ... An external, side attached PT box may be used

ALLIANT ENERGY

ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016

Page 68

E235. EQUIPMENT MANUFACTURES PHONE NUMBERS

MANUFACTURER TECHNICAL SUPPORT PRODUCT INFORMATION A.M.P. 1-800-328-8658 1-800-328-8658

CONCAST 1-507-732-4094 1-507-732-4094

DURHAM/UPPER MIDWEST 1-417-532-7121 1-417-532-7121

EATON/CUTLER HAMMER 1-800-356-1243 1-800-356-1243

ELECTRIC GLASS INC 1-731-427-0433 1-731-427-0433

EMI 1-800-536-3678 1-800-536-3678

ERICKSON ELECTRIC 1-800-952-7225 1-800-952-7225

GALVA CLOSURE 1-608-873-3044 1-608-873-3044

GE 1-800-431-7867 1-800-431-7867

LANDIS & GYR 1-800-777-2774 1-800-428-7853

MIDWEST ELECTRIC PRODUCTS 1-507-345-2543 1-507-345-2543

MILBANK 1-816-410-7217 1-877-483-5314

SIEMENS/TALON 1-800-333-7732 1-800-333-7732

NORDIC 1-218-745-5095 1-218-745-5095

RONK 1-800-221-7665 1-800-221-7665

SQUARE D 1-888-778-2733 1-888-778-2733