Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 34
CHAPTER 2
ELECTRIC SERVICE EQUIPMENT – METER CABINETS
E200. TECHNICAL SPECIFICATIONS FOR METERING TRANSFORMER CABINETS AND CONDUCTOR TERMINATION BOXES.
A. Approval Process Equipment manufactures application information, technical specifications and dimension drawings must be submitted to: Alliant Energy Standards Engineering Attn: Tony Porch 200 1st Street SE Cedar Rapids, Iowa 52401-1409 for review. The manufacturer will then be invited to bring their equipment to an ESR meeting to present their equipment. Equipment found to meet these requirements will be allowed for a one-time installation for a field test. Once the field test shows the equipment to be satisfactory, a letter verifying temporary approval will be provided. The equipment will be listed in the next edition of the Electric Service Rule Book.
B. Modification/Continued Listing. If the specification is modified, manufacturers must verify their intent and submit new drawings by June 1st each year for review and approval, to continue to be approved and listed in the Electric Service Information Manual for the following year.
C. Listing/Labeling Current transformer cabinets shall be listed and labeled as “Metering Transformer Cabinets” and conductor termination boxes shall be listed and labeled as “Termination Boxes or Cabinets” by an independent testing laboratory (such as U.L. 414 for Current Transformer Cabinets and U.L. 1773 for Termination Boxes). In addition to this requirement, the cabinets must be inspected and approved by Alliant Energy, to ensure it meets our requirements. The equipment model number shall carry either an “Alliant Energy” suffix or prefix plus the complete catalog number, as shown in the Electric Service Equipment Book, and shall be included as part of the equipment nameplate.
D. Doors Current Transformer Cabinets and Conductor Termination Cabinets are to have side-hinged doors with a two or three point handle operated locking device with a minimum 7/16 inch diameter sealing hole to accept a company pad-lock with a 3/8 inch shackle. The handle may not be operated when the lock is in place. The door(s) shall have a lockable wind-stop assembly installed.
E. Enclosure Type As a minimum requirement, the cabinet type shall carry a NEMA 3R rating. For installations where a corrosive environment is present the cabinet shall be rated as a NEMA 4X.
F. Electrical Clearances Clearances per the National Electrical Safety Code, Wisconsin Electrical Code, Volume 2, shall be maintained with the Current transformers and associated wiring installed and the cover(s) closed. The Alliant Energy minimum “H”, minimum depth and minimum width dimensions shall be maintained according to the Current Transformer Cabinet Specification Table (attached).
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 35
G. Bus/Line Side Lug Specifications Ct’s shall be mounted vertically on cabinet bus bars. The Ct shall be bolted to a landing pad such that the conductors cannot be bolted directly to the CT’s. Line side Lugs shall be of the Allen-Set screw type, suitable for aluminum conductors. All lugs in termination cabinets shall be either lay-in or Allen-Set screw type.
H. PT Mounting PT'S may not be mounted directly in front or behind any other electrical components or utility conductors. An external, side attached PT box may be used and must have the minimum dimensions of 8” wide, 23” high, and 8” in depth.
I. Meter Socket Mounting on Wall-mounted Current Transformer Cabinets The proper height of 5’(+/- 6”) measured from the center of the meter to final grade shall be maintained. 400A through 800A cabinets shall be mounted with the bottom of the cabinet 24 to 30 inches above final grade and 1200A through 3000A cabinets shall be mounted with the bottom of the cabinet 20 to 24 inches above final grade.
J. Bonding The bonding of the Current Transformer Cabinet is in Chapter2 & 4. The bonding conductor sizes are shown at the end of chapter 2 & 4.
K. Fasteners No fasteners shall be able to be removed from the exterior of the cabinet. The only way to remove a fastener is by unlocking the door and gaining access to the inside of the cabinet.
L. Acceptable Voltages and Current Ranges 120/240 volts, single-phase, from 100 amps through 800 amps. 120/208 volts, single-phase, three-wire 200 amps max. 120/208 volts, three-phase, four-wire, from 100 amps through 3000 amps 277/480 volts, three-phase, four-wire from 100 amps through 3000 amps.
M. Service Configuration 1. Overhead Services, Top-In / Bottom-Out
Top feed installations can only be utilized for Overhead Services with a maximum rating of 1200 amps (See “L” above in this section). Load side conductors must exit below the load side lugs. The “H” dimension does not apply to this configuration, because the customer owns and installs all the conductors.
2. Overhead Services, Top-In / Top-Out Top feed installations can only be utilized for Overhead Services with a maximum rating of 1200 amps (See “L” above in this section). Load side conductors must be isolated from the line side The “H” dimension does not apply to this configuration, because the customer owns and installs all the conductors.
3. Underground Services, Bottom-In / Top-Out Underground feed installations (Alliant Energy conductors) shall enter and terminate on the bottom lugs of all Cabinets. The customer’s load side conductors shall terminate on the top lugs and exit above the load side lugs.
4. Underground Services, Bottom-In / Bottom-Out Underground feed installations (Alliant Energy conductors) shall enter and terminate on the bottom lugs of all Current Transformer (CT) Cabinet. Load side conductors shall terminate on the top lugs of the CT Cabinet and be routed either behind the CT bus work or to the left or right of the CT bus work down to the bottom of the cabinet to the load side conduits.
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 36
If the cabinet is equipped with an external side gutter (pull box) or other external raceway, the load conductors shall be routed through this external side gutter (pull box) or raceway. Load side conductors exiting through an external gutter shall exit above the load side lugs. If the cabinet has internally mounted PT’s the exiting load side conductors shall be installed behind the PT’s pan.
5. Underground Services/Pad-Mount CT Cabinets, Bottom-In / Bottom-Out Metering Transformer Cabinets meeting the specifications for Bottom-In / Bottom-Out may be used in a free-standing, pad-mount configuration providing the following requirements are met: a) The cabinet shall be approved “Bottom-In / Bottom-Out” as listed in Chapter 2 of this
book. b) The cabinet shall have an Alliant Energy approved pedestal base mounted to the bottom
in order to bring the cabinet 9”-10” above the pad, unless this has been incorporated into the cabinet design. (If incorporated into the design the bottom of the access door shall be a minimum of 9 inches above grade.)
c) The entire assembly will be bolted to a suitable concrete pad, providing stable support and facilitating the required conduit for entrance and exit. Pad mounted CT cabinets shall be mounted on an isolated pad, adjacent to the transformer pad, to accommodate conduit elbow sweeps. Contact Alliant Energy engineering for pad design details and clearance requirements.
d) An approved meter socket may be mounted on the outside of the cabinet, as listed in Chapter 1 of this book. Meter socket shall be mounted only where it does not block or impede access at any time (open or closed) at a height consistent with the requirements in this book where possible.
e) In the event that customer request and Alliant Energy grants approval to reverse conductors (i.e., customer conductors on bottom and utilities wires on top), permanent signage shall note this change both outside and inside the cabinet (See section 432 E of the ESR Manual). Any additional cost will be borne by the customer.
N. Splices
Splices in meter sockets and instrument transformer cabinets are unacceptable. Current Transformer (CT) Cabinets shall not be used as raceways unless designed with such provisions.
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 37
E201. CT BAR REQUIREMENTS
1/4"Fig.No 1
1/4"1/2"
1/4"Fig.
No. 2
3/4"
1/4"
7/8"W/2
W
1-11/16"
3/4"
6"
3/4"
1-11/16"
10-7/8"Fig.
No. 3
3/4"
1-11/16"
9/16" x 3/4"Slotted Holes
400-800 Amp Bus
Neutral TappedFor 10-24 Brass
Screw ForPotential Tap
Amps W W/2 #/PH Bars On Transf.
Fig.No.
Mounting Bolt Size
400 2 1 1 1 1 1/2x1-1/2
600 2-1/2 1-1/4 1 1 1 1/2x1-1/2
800 3-1/4 1-5/8 1 1 1 1/2x1-1/2
1000 3 1-1/2 1 1 1 1/2x1-1/2
1200 3 1-1/2 1 1 1 1/2x1-1/2
1600 3 1-1/2 2 2* 2 1/2x2-1/2
2000 3 1-1/2 2 2 2 1/2x2-1/2
3000 3 1-1/2 3 3 3 1/2x2-1/2
A single bar with adequate current capacity may be substituted
Customer shall furnish ½ mounting bolts for CT’s
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 38
E202. CABLE SPACE REQUIREMENTS FOR CT CABINETS
E202B. PAD-MOUNTED CABINETS All stand-alone non-bussed pad-mounted service equipment cabinets are designed for Bottom Entry and Bottom Exit. Entry or exit thru either the top or side is not acceptable. Cabinets designed to be mounted against building or structure may be allowed to exit the top or side. Contact Alliant Energy for approval before installation.
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 39
Table 1 Termination Cabinet Specification Table*
250 Volts Maximum
AmpacityLugs perPhase Lug Size
UnprotectedFault
CurrentRating(Amps)
MinimumWidth(Inches)
MinimumDepth(Inches)
Minimum "H"Dimension(Inches)
400 2 4/0 500 42,000 20 11 20600 2 4/0 500 65,000 24 14 20800 3 4/0 500 65,000 24 14 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26
Table 1A Termination Cabinets Specification Table600 Volt Maximum
AmpacityLugs perPhase Lug Size
UnprotectedFault
CurrentRating(Amps)
MinimumWidth(Inches)
MinimumDepth(Inches)
Minimum "H"Dimension(Inches)
400 2 4/0 500 42,000 20 15 20600 2 4/0 500 65,000 24 15 20800 3 4/0 500 65,000 24 15 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26
Specifications Table Requirements: States minimum criteria and can be exceeded to utilizemanufacturers’ available equipment.
“H” dimension refers to the distance from the bottom of line side lug to the bottom of theenclosure. See Diagram. For pad mounted cabinets the 9” or 10” mounting baserequirement is not included in the “H” dimension. For pad mounted cabinets it would be 9or 10 inches plus the listed “H” from the center of the lug to the pad.Minimumwidth does not include separate internal compartment for Bottom Feed/Bottomexit option. This edition became effective January 2016 and supersedes all earlier editions.
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 40
Table 2 – Wall Mounted Current Transformer Cabinet Specification Table
250 Volts Maximum
AmpacityLugs perPhase Lug Size
UnprotectedFault
CurrentRating(Amps)
MinimumWidth(Inches)
MinimumDepth(Inches)
Minimum "H"Dimension(Inches)
400 2 4/0 500 42,000 20 11 20600 2 4/0 500 65,000 24 15 20800 3 4/0 500 65,000 24 15 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26
Table 2A – Residential Wall Mounted CT Cabinet Specification Table
250 Volts Maximum
AmpacityLugs perPhase Lug Size
UnprotectedFault
CurrentRating(Amps)
MinimumWidth(Inches)
MinimumDepth(Inches)
Minimum "H"Dimension(Inches)
400 2 4/0 500 42,000 20 8 14600 2 4/0 500 42,000 24 8 14
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 41
Table 3 – Wall Mounted Current Transformer Cabinet Specification Table600 Volt Max. With Side Mounted PT Enclosure (Non integrated)
AmpacityCables
Per Phase Lug Size
UnprotectedFault
CurrentRating(Amps)
MinimumWidth(Inches)
MinimumDepth(Inches)
Minimum "H"Dimension(Inches)
400 2 4/0 500 42,000 24 15 20600 2 4/0 500 65,000 24 15 20800 3 4/0 500 65,000 24 15 201200 5 4/0 500 65,000 34 15 201600 4 500 1000 65,000 38 15 262000 5 500 1000 65,000 38 15 262500 7 500 1000 65,000 42 21 263000 8 500 1000 65,000 42 21 26
For pad mounted cabinets the 9” or 10” mounting base requirement is not included in the “H” dimension. Forpad mounted cabinets it would be 9 or 10 inches plus the listed “H” from the center of the lug to the pad.
Table 4 –Wall Mounted Current Transformer Cabinet Specification Table
600 Volt MaximumWith Integral PT Mounting
AmpacityCables
Per Phase Lug Size
UnprotectedFault
CurrentRating(Amps)
MinimumWidth(Inches)
MinimumDepth(Inches)
Minimum "H"Dimension(Inches)
400 2 4/0 500 42,000 32 15 20600 2 4/0 500 65,000 32 15 20800 3 4/0 500 65,000 32 15 201200 5 4/0 500 65,000 42 15 201600 4 500 1000 65,000 46 15 262000 5 500 1000 65,000 46 15 262500 7 500 1000 65,000 50 21 263000 8 500 1000 65,000 50 21 26
*Specifications are minimum criteria and can be exceeded to optimize manufactures’ available equipment. Minimum Width does not include separate internal compartment for Bottom Feed/Bottom Exit option or External PT. Enclosure. “H” dimension refers to the distance from the bottom of the line side lug(s) to the bottom of the enclosure. See diagram on page 32. For pad mounted cabinets the 9” or 10” mounting base requirement is not included in the “H”dimension. For pad mounted cabinets it would be 9 or 10 inches plus the listed “H” from the center of the lug to the pad.
Chapter 2
ELECTRIC SERVICE EQUIPMENT EQUIPMENT - METER CABINETS Issued Jan. 2016
Page 42
Chapter 2 FOOTNOTES (Superscripts)
(1) Wall Mounted Transformer Cabinet 600 Volt Specifications Table with side mounted PT enclosure. (2) Wall Mounted Current Transformer Cabinet Specification Table with Integral PT Mounting. (3) An Optional Side wiring Gutter is required for Bottom Feed/Bottom Exit. The Side Gutter Wiring
Gutter may be located on either side Add suffix SGL (left) or SGR (right) to the catalog number. If American Midwest Power, order Pull Box style PB.
(4) Fill in # with B for CT at bottom configuration, or use T for CT at the Top configuration. (5) 400 - 800 Amp Wall Mounted Cabinets may be installed as a pad-mounted cabinet by adding a
CR12ES Ext. Kit. The ALIECT (A.M.P.) requires the CR15ECTS Extension kit. (6) Requires Stainless steel Mounting Base (PMB1624x10) when ordering pad-mounted cabinet. (7) Catalog Numbers can have CT section at bottom and disconnect at top, Change suffix CTA TO
CTB. (8) Mounting base factory installed for pad-mounted use. (9) Add optional Pad mount kit to convert wall mount to pad-mount where required 38' - PMR38 or
PMR42. (10) Add bottom plate for wall mount. (11) For Bottom-In/Bottom-out cabinets with internal raceways the letters (L-Left or R-Right) shall be
used to indicate which side of the cabinet the manufacturer will install the vertical raceway. The Standard Product for AMP & EMI will have the raceway installed on the right side, the standard for Galva Closure is with the raceway on the left side. The letter designation L or R will follow the manufacturer’s catalog number. Example ALICT4-L# would either be ALICT4-L3R (for right side or ALICT4-L3L for the left side).
(12) E-M-I --400 to 1200 Amp wall mounted cabinets may be installed as a pad-mounted cabinet by adding a FMR pad-mount riser.
(13) CM-8 suffix indicates 1200A horizontal bus. The suffix CM-9 (in place of CM-8 or added to the termination box catalog numbers) indicates 1600A horizontal bus. The suffix CM-7 indicates 800A horizontal bus.
(14)These CT cabinets are only allowed for 250 Volt applications, Residential Only. (15) For single phase three wire the 4 in the catalog number changes to 3. (16) Requires a separate cabinet for mounting Potential Transformers for 277/480. (17) Contains one 400 amp circuit breaker. (18) Contains 2-200 amp circuit breakers. (19) Contains 400 amp fused pull outs. (20) Contains one 600 amp circuit breaker (21) Contains 800 amp circuit breaker (22) Contains one 1200 amp circuit breaker (23)These devices may be pad-mounted but must also be anchored to building /wall to support the
enclosure. (24) All-in one combination units are limited to 1200 amps
I/W – Used with PMCTMS Cabinets: Follow the cabinet number with either I - Iowa; W - Wisconsin; for Meter Socket wiring designation. NA - Not applicable.
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
E203 METERING TRANFORMER CABINETS - 400 AMP
400 A.M.P ALI6SCT4-4L 3 PH WALL/PAD (16)(23) MULTI 600
400 A.M.P ALICT4-3L 1 PH WALL (2)(5) 600
400 A.M.P ALICT4-4L 3 PH WALL (2)(5) 600
400 A.M.P ALIECT4-3L 1 PH WALL (5) 600
400 A.M.P ALIECT4-4L 3 PH WALL (16)(5) 600
400 A.M.P ALIMCT225 1 PH WALL (3)(4) 400 250
400 A.M.P ALIMCT225J 1 PH WALL/PAD (23) 400 250
400 A.M.P ALIMCT325 3 PH WALL (3)(4) 400 250
400 A.M.P ALIMCT325J 3 PH WALL/PAD (23) 400 250
400 A.M.P ALIMCT365J 3 PH WALL/PAD (16)(23) 400 600
400 A.M.P ALIPCT4-3L 1 PH PAD (2)(8) 600
400 A.M.P ALIPCT4-4L 3 PH PAD (2)(8) 600
400 A.M.P ALIRCT4-3L 1 PH WALL (14) 250
400 A.M.P ALIRCT4-4L 3 PH WALL (14) 250
400 A.M.P ALISCT4-3DT 1 PH WALL 400 250
400 A.M.P ALISCT4-3DTH 1 PH WALL 400 250
400 A.M.P ALISCT4-3L 1 PH WALL/PAD (23) MULTI 250
400 A.M.P ALISCT4-4DT 3 PH WALL 400 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 43
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
400 A.M.P ALISCT4-4DTH 3 PH WALL 400 250
400 A.M.P ALISCT4-4L 3 PH WALL/PAD (23) MULTI 250
400 EMI ALICT140 1 PH WALL 250
400 EMI ALICT140P 1 PH PAD (2)(11)(12) 600
400 EMI ALICT340 3 PH WALL 600
400 EMI ALICT340P 3 PH PAD (2)(11)(12) 600
400 EMI ALIMSCT4 3 PH WALL 400 600
400 Erickson Electric ALICTAED3244N 1 PH WALL (18) 2-200 250
400 Erickson Electric ALICTAED4244N 3 PH WALL (18) 2-200 250
400 Erickson Electric ALICTAP3244N 1 PH WALL (18) 2-200 250
400 Erickson Electric ALICTAP4244N 3 PH WALL (18) 2-200 250
400 Erickson Electric ALICTBDK325N 1 PH WALL 400 250
400 Erickson Electric ALICTBDK425N 3 PH WALL 400 250
400 Erickson Electric ALICTBED3244N 1 PH WALL (18) 2-200 250
400 Erickson Electric ALICTBED4244N 3 PH WALL (18) 2-200 250
400 Erickson Electric ALICTBP3244N 1 PH WALL (18) 2-200 250
400 Erickson Electric ALICTBP325N 1 PH WALL 400 250
400 Erickson Electric ALICTBP4244N 3 PH WALL (18) 2-200 250
400 Erickson Electric ALICTBP425N 3 PH WALL 400 250
400 Erickson Electric ALICTBP4644N 3 PH WALL (18) 2-200 250
400 Erickson Electric ALICTDK325N 1 PH WALL 400 250
400 Erickson Electric ALICTDK425N 3 PH WALL 400 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 44
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
400 Erickson Electric ALICTP325N 1 PH WALL 400 250
400 Erickson Electric ALICTP425N 3 PH WALL 400 250
400 Erickson Electric ALICTP465N-PT 3 PH WALL 400 250
400 Erickson Electric CT41-ALI 1 PH WALL/PAD (6) 250
400 Erickson Electric CT44-ALI 3 PH WALL/PAD (6) 250
400 Erickson Electric CT44-PT-ALI 3 PH WALL/PAD (6)(1) 600
400 Erickson Electric PMCTMS-425NMFALI 3 PH PAD (8) 400 250
400 Erickson Electric PMCTMS-465NMFPTALI 3 PH PAD (8) 400 600
400 Galva Closure ALI-413 1 PH WALL 250
400 Galva Closure ALI-413PM 1 PH PAD (8)(11) 250
400 Galva Closure ALI-413UGBX 1 PH WALL (11) 250
400 Galva Closure ALI-434 3 PH WALL 250
400 Galva Closure ALI-434PM 3 PH PAD (8)(11) 250
400 Galva Closure ALI-434UGBX 3 PH WALL (11) 250
400 Galva Closure ALI-464 3 PH WALL (2) 600
400 Galva Closure ALI-464PM 3 PH PAD (2)(8)(11) 600
400 Galva Closure ALI-464UGBX 3 PH WALL (2)(11) 600
400 Galva Closure ALI-CTDK12A-413 1 PH WALL (17) 400 250
400 Galva Closure ALI-CTDK12A-434 3 PH WALL (17) 400 250
400 Galva Closure ALI-CTHKD14A-464 3 PH WALL (17) 400 600
400 Galva Closure ALI-CTJGL224-464 3 PH WALL (18) 2-200 600
400 Galva Closure ALI-CTJGL22A-413 1 PH WALL (18) 2-200 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 45
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
400 Galva Closure ALI-CTJGL22A-413PM 1 PH PAD (18) 2-200 250
400 Galva Closure ALI-CTJGL22A-413UGBX 1 PH WALL (18) 2-200 250
400 Galva Closure ALICTJGL22A-434 3 PH WALL (18) 2-200 250
400 Galva Closure ALI-CTJGL22L-413PM 1 PH PAD (18) 2-200 250
400 Galva Closure ALI-CTJGL22L-413UGBX 1 PH WALL (18) 2-200 250
400 Galva Closure ALI-CTJGL22L-434PM 3 PH PAD (18) 2-200 600
400 Galva Closure ALI-CTJGL22L-434UGBX 3 PH WALL (18) 2-200 600
400 Galva Closure ALI-CTJGL24A-464 3 PH WALL (18) 2-200 600
400 Galva Closure ALI-CTJGL24L-464PM 3 PH PAD (18) 2-200 600
400 Galva Closure ALI-CTJGL24L-464UGBX 3 PH WALL (18) 2-200 600
400 Galva Closure ALI-CTJJL24A-464 3 PH WALL (18) 2-200 600
400 Galva Closure ALI-CTJJL24L-464PM 3 PH PAD (19) 400 600
400 Galva Closure ALI-CTJJL24L-464UGBX 3 PH WALL 600
400 Galva Closure ALI-CTKDB14A-464 3 PH WALL (17) 400 600
400 Galva Closure ALI-CTLGL12A-413 1 PH WALL (17) 400 250
400 Galva Closure ALI-CTLGL14A-464 3 PH WALL (17) 400 600
400 Galva Closure ALI-CTLGL14L-413PM 1 PH PAD (17) 400 250
400 Galva Closure ALI-CTLGL14L-413UGBX 1 PH WALL (17) 400 250
400 Galva Closure ALI-CTLGL14L-434UGBX 3 PH WALL (17) 400 250
400 Galva Closure ALI-CTLGL14L-464PM 3 PH PAD (17) 400 600
400 Galva Closure ALI-CTPT12A-413 1 PH WALL (19) 400 250
400 Galva Closure ALI-CTPT12A-434 3 PH WALL (19) 400 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 46
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
400 Galva Closure ALI-CTPT12L-413PM 1 PH PAD (19) 400 250
400 Galva Closure ALI-CTPT12L-413UGBX 1 PH WALL (19) 400 250
400 Galva Closure ALI-CTPT12L-434PM 3 PH PAD (19) 400 250
400 Galva Closure ALI-CTPT12L-434UGBX 3 PH WALL (19) 400 600
400 Galva Closure ALI-CTPT14A-464 3 PH WALL (19) 400 600
400 Galva Closure ALI-CTPT14A-464PM 3 PH PAD (19) 400 600
400 Galva Closure ALI-CTPT14A-464UGBX 3 PH WALL (19) 400 600
400 Galva Closure ALI-CTPT14L-464PM 3 PH PAD (19) 400 600
400 Galva Closure ALI-CTPT14L-464UGBX 3 PH WALL (17) 400 600
400 Galva Closure ALI-CTSFH22A413 1 PH WALL (18) 2-200 250
400 Galva Closure ALI-CTSFH22A-434 3 PH WALL (18) 2-200 250
400 Galva Closure ALI-CTSFH24A-464 3 PH WALL (18) 2-200 600
400 Galva Closure ALI-CTSFL24A-464 3 PH WALL (18) 2-200 600
400 Galva Closure ALI-CTSGD12A-413 1 PH WALL (17) 400 250
400 Galva Closure ALI-CTSGD12A-434 3 PH WALL (17) 400 250
400 Galva Closure ALI-CTSGH14A-464 3 PH WALL (17) 400 600
400 Galva Closure ALI-CTSGL14A-464 3 PH WALL (17) 400 600
400 Galva Closure ALI-RES-413 1 PH WALL 400
400 Galva Closure ALI-RES-434 3 PH WALL 400
E204 METERING TRANSFORMER CABINETS - 600 AMPS
600 A.M.P ALI6SCT6-4L 3 PH WALL/PAD (16)(23) MULTI 600
600 A.M.P ALICT6-3L 1 PH WALL (2)(5) 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 47
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
600 A.M.P ALICT6-4L 3 PH WALL (2)(5) 600
600 A.M.P ALIECT6-3L 1 PH WALL (5) 600
600 A.M.P ALIECT6-4L 3 PH WALL (16)(5) 600
600 A.M.P ALIMCT226 1 PH WALL (3)(4) 600 250
600 A.M.P ALIMCT226J 1 PH WALL/PAD (23) 600 250
600 A.M.P ALIMCT326 3 PH WALL (3)(4) 600 250
600 A.M.P ALIMCT326J 3 PH WALL/PAD (23) 600 250
600 A.M.P ALIMCT366J 3 PH WALL/PAD (16)(23) 600 600
600 A.M.P ALIPCT6-3L 1 PH PAD (2)(8) 600
600 A.M.P ALIPCT6-4L 3 PH PAD (2)(8) 600
600 A.M.P ALIRCT6-3L 1 PH WALL (14) 250
600 A.M.P ALIRCT6-4L 3 PH WALL (14) 250
600 A.M.P ALISCT6-3L 1 PH WALL/PAD (23) MULTI 250
600 A.M.P ALISCT6-4L 3 PH WALL/PAD (23) MULTI 250
600 EMI ALICT160 1 PH WALL 250
600 EMI ALICT160P 1 PH WALL/PAD (2)(11)(12) 600
600 EMI ALICT360 3 PH WALL 600
600 EMI ALICT360P 3 PH WALL/PAD (2)(11)(12) 600
600 EMI ALIMSCT6 3 PH WALL 600 600
600 EMI ALIRCT160 1 PH WALL 250
600 Erickson Electric CT61-ALI 1 PH WALL/PAD (6) 250
600 Erickson Electric CT61-ALI-SEA 1 PH WALL 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 48
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
600 Erickson Electric CT64-ALI 3 PH WALL/PAD (6) 250
600 Erickson Electric CT64-ALI-SEA 3 PH WALL 250
600 Erickson Electric CT64-PT-ALI 3 PH WALL/PAD (1)(6) 600
600 Erickson Electric PMCTMS-426NMFALI 3 PH PAD (8) 600 250
600 Erickson Electric PMCTMS-466NMFPTALI 3 PH PAD (8) 600 600
600 Galva Closure ALI-613 1 PH WALL 250
600 Galva Closure ALI-613PM 1 PH PAD (8)(11) 250
600 Galva Closure ALI-613UGBX 1 PH WALL (11) 250
600 Galva Closure ALI-634 3 PH WALL 250
600 Galva Closure ALI-634PM 3 PH PAD (8)(11) 250
600 Galva Closure ALI-634UGBX 3 PH WALL (11) 250
600 Galva Closure ALI-664 3 PH WALL (2) 600
600 Galva Closure ALI-664PM 3 PH PAD (2)(8)(11) 600
600 Galva Closure ALI-664UGBX 3 PH WALL (2)(11) 600
600 Galva Closure ALI-CTMGL12A-613 1 PH WALL (20) 600 250
600 Galva Closure ALI-CTMGL12A-634 3 PH WALL (20) 600 250
600 Galva Closure ALI-CTMGL12L-613PM 1 PH PAD 250
600 Galva Closure ALI-CTMGL12L-613UGBX 1 PH WALL (20) 600 250
600 Galva Closure ALI-CTMGL12L-634PM 3 PH PAD 250
600 Galva Closure ALI-CTMGL12L-634UGBX 3 PH WALL (20) 600 250
600 Galva Closure ALI-CTMGL14A-664 3 PH WALL 600
600 Galva Closure ALI-CTMGL14L-664PM 3 PH PAD 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 49
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
600 Galva Closure ALI-CTMGL14L-664UGBX 3 PH WALL (20) 600 600
600 Galva Closure ALI-CTMJL14L-664PM 3 PH PAD 600
600 Galva Closure ALI-CTMJL14L-664UGBX 3 PH WALL 600
600 Galva Closure ALI-RES-613 1 PH WALL (14) 250
600 Galva Closure ALI-RES-634 3 PH WALL (14) 250
E205 METERING TRANSFORMER CABINETS - 800 AMPS
800 A.M.P ALI6SCT8-4L 3 PH WALL/PAD (16)(23) 600
800 A.M.P ALICT8-3L 1 PH WALL (2)(5) 600
800 A.M.P ALICT8-4L 3 PH WALL (2)(5) 600
800 A.M.P ALIECT8-3L 1 PH WALL (5) 600
800 A.M.P ALIECT8-4L 3 PH WALL (16)(5) 600
800 A.M.P ALIMCT227 1 PH WALL (3)(4) 250
800 A.M.P ALIMCT227L 1 PH WALL/PAD (23) 250
800 A.M.P ALIMCT327 3 PH WALL (3)(4) 250
800 A.M.P ALIMCT327L 3 PH WALL/PAD (23) 250
800 A.M.P ALIMCT367L 3 PH WALL/PAD (16)(23) 600
800 A.M.P ALIPCT8-3L 1 PH PAD (2)(8) 600
800 A.M.P ALIPCT8-4L 3 PH PAD (2)(8) 600
800 A.M.P ALISCT8-3L 1 PH WALL/PAD (23) MULTI 250
800 A.M.P ALISCT8-4L 3 PH WALL/PAD (23) MULTI 250
800 EMI ALICT180 1 PH WALL 250
800 EMI ALICT180P 1 PH PAD (11)(12) 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 50
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
800 EMI ALICT380 3 PH WALL 600
800 EMI ALICT380P 3 PH PAD (2)(11)(12) 600
800 EMI ALIMSCT8 3 PH WALL 600
800 EMI ALIPM380 3 PH PAD (11) 600
800 Erickson Electric CT81-ALI 1 PH WALL/PAD (6) 250
800 Erickson Electric CT84-ALI 3 PH WALL/PAD (6) 250
800 Erickson Electric CT84-PT-ALI 3 PH WALL/PAD (1)(6) 600
800 Erickson Electric PMCTMS-427NMFALI 3 PH PAD (8) 250
800 Erickson Electric PMCTMS-467NMFPTALI 3 PH PAD (8) 600
800 Galva Closure ALI-813 1 PH WALL 250
800 Galva Closure ALI-813PM 1 PH PAD (8)(11) 250
800 Galva Closure ALI-813UGBX 1 PH WALL (11) 250
800 Galva Closure ALI-834 3 PH WALL 250
800 Galva Closure ALI-834PM 3 PH PAD (8)(11) 250
800 Galva Closure ALI-834UGBX 3 PH WALL (11) 250
800 Galva Closure ALI-864 3 PH WALL (2) 600
800 Galva Closure ALI-864PM 3 PH PAD (2)(8)(11) 600
800 Galva Closure ALI-864UGBX 3 PH WALL (2)(11) 600
800 Galva Closure ALI-CTMGL12A-813 1 PH WALL (21) 800 250
800 Galva Closure ALI-CTMGL12A-834 3 PH WALL (21) 800 250
800 Galva Closure ALI-CTMGL12L-813PM 1 PH PAD 250
800 Galva Closure ALI-CTMGL12L-813UGBX 1 PH WALL (21) 800 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 51
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
800 Galva Closure ALI-CTMGL12L-834PM 3 PH PAD (21) 800 250
800 Galva Closure ALI-CTMGL12L-834UGBX 3 PH WALL (21) 800 250
800 Galva Closure ALI-CTMGL12L-864PM 3 PH PAD (21) 800 600
800 Galva Closure ALI-CTMGL12L-864UGBX 3 PH WALL (21) 800 600
800 Galva Closure ALI-CTMGL14A-864 3 PH WALL (21) 800 600
800 Galva Closure ALI-CTMGL14L-864PM 3 PH PAD 600
800 Galva Closure ALI-CTMJL14L-864PM 3 PH PAD 600
E206 METERING TRANSFORMER CABINETS - 800 AMPS
1200 Galva Closure ALI-PGL12L-1234PM 3 PH PAD (21) 800 250
1200 A.M.P ALICT12-4L 3 PH WALL (2)(11) 600
1200 A.M.P ALIECT12-4L 3 PH WALL/PAD (16) 600
1200 A.M.P ALIMCT368L 3 PH WALL/PAD (16)(23) 600
1200 A.M.P ALIPCT12-4L 3 PH PAD (2)(8)(11) 600
1200 A.M.P ALISCT12-4L 3 PH WALL/PAD (23) 600
1200 EMI ALICT312 3 PH WALL 250
1200 EMI ALICT312P 3 PH WALL/PAD (3)(11)(12) 600
1200 EMI ALIPM312 3 PH PAD (5)(11) 600
1200 Erickson Electric CT124-ALI 3 PH WALL (3) 250
1200 Erickson Electric CT124-PT-ALI 3 PH WALL (1)(3) 600
1200 Erickson Electric PMCT124MF-ALI 3 PH PAD (8) 250
1200 Erickson Electric PMCT124MF-PT-ALI 3 PH PAD (8) 600
1200 Erickson Electric PMCTMS-428NMFALI 3 PH PAD (8) 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 52
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
1200 Erickson Electric PMCTMS-468NG6MFPTALI 3 PH PAD (8) 600
1200 Galva Closure ALI-1234 3 PH WALL 250
1200 Galva Closure ALI-1234PM 3 PH PAD (8)(11) 250
1200 Galva Closure ALI-1234UGBX 3 PH WALL 250
1200 Galva Closure ALI-1264 3 PH WALL (2) 600
1200 Galva Closure ALI-1264PM 3 PH PAD (2)(8)(11) 600
1200 Galva Closure ALI-1264UGBX 3 PH WALL (2) 600
1200 Galva Closure ALI-CTPGL12A-1234 3 PH WALL (22) 1200 250
1200 Galva Closure ALI-CTPGL12L-1234PM 3 PH PAD 600
1200 Galva Closure ALI-CTPGL12L-1234UGBX 3 PH WALL (22) 1200 250
1200 Galva Closure ALI-CTPGL12L-1264UGBX 3 PH WALL (22) 1200 600
1200 Galva Closure ALI-CTPGL14A-1264 3 PH WALL (22) 1200 600
1200 Galva Closure ALI-CTPGL14L-1264PM 3 PH PAD 600
1200 Galva Closure ALI-CTPJL14L-1264PM 3 PH PAD 600
E207 TRANSFORMER METERING CABINETS - 1600 AMP
1600 A.M.P ALICT16-4L 3 PH WALL (2)(11) 600
1600 A.M.P ALIECT16-4L 3 PH WALL/PAD (16) 600
1600 A.M.P ALIPCT16-4L 3 PH PAD (2)(8)(11) 600
1600 EMI ALICT316 3 PH WALL 250
1600 EMI ALIPM316 3 PH PAD (10)(11) 600
1600 Erickson Electric CT164-ALI 3 PH WALL (3) 250
1600 Erickson Electric CT164-PT-ALI 3 PH WALL (1)(3) 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 53
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
1600 Erickson Electric PMCT164MF-ALI 3 PH PAD (8) 250
1600 Erickson Electric PMCT164MF-PT-ALI 3 PH PAD (8) 600
1600 Erickson Electric PMCTMS-429NMFALI 3 PH PAD (8) 250
1600 Erickson Electric PMCTMS-469G6MFPTALI 3 PH PAD (8) 600
1600 Galva Closure ALI-1634 3 PH WALL 250
1600 Galva Closure ALI-1634PM 3 PH PAD (8)(11) 250
1600 Galva Closure ALI-1634UGBX 3 PH WALL (11) 250
1600 Galva Closure ALI-1664 3 PH WALL (2) 600
1600 Galva Closure ALI-1664PM 3 PH PAD (2)(8)(11) 600
1600 Galva Closure ALI-1664UGBX 3 PH WALL (2)(11) 600
E208 TRANSFORMER METERING CABINETS - 2000 AMP
2000 A.M.P ALICT20-4L 3 PH WALL (2)(11) 600
2000 A.M.P ALIECT20-4L 3 PH WALL/PAD (16) 600
2000 A.M.P ALIPCT20-4L 3 PH PAD (2)(8)(11) 600
2000 EMI ALICT320 3 PH WALL 250
2000 EMI ALIPM320 3 PH PAD (10)(11) 600
2000 Erickson Electric CT204-ALI 3 PH WALL (3) 250
2000 Erickson Electric CT204PTALI 3 PH WALL (1)(3) 600
2000 Erickson Electric PMCT204MF-ALI 3 PH PAD (8) 250
2000 Erickson Electric PMCT204MFPTALI 3 PH PAD (8) 600
2000 Erickson Electric PMCTMS-4210NMFALI 3 PH PAD (8) 250
2000 Erickson Electric PMCTMS-4610NG6MFPTALI
3 PH PAD (8) 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 54
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
2000 Galva Closure ALI-2034 3 PH WALL 250
2000 Galva Closure ALI-2034PM 3 PH PAD (11) 250
2000 Galva Closure ALI-2034UGBX 3 PH PAD (11) 250
2000 Galva Closure ALI-2064 3 PH WALL (2) 600
2000 Galva Closure ALI-2064PM 3 PH PAD (2)(11) 600
2000 Galva Closure ALI-2064UGBX 3 PH WALL (2)(11) 600
E209 TRANSFORMER METERING CABINETS - 2500 AMP
2500 A.M.P ALICT25-4L 3 PH WALL (2)(11) 600
2500 A.M.P ALIPCT25-4L 3 PH PAD (2)(8)(11) 600
2500 EMI ALIPM325 3 PH PAD (10)(11) 600
2500 Erickson Electric CT254ALI 3 PH WALL (3) 250
2500 Erickson Electric CT254PTALI 3 PH WALL (1)(3) 600
2500 Erickson Electric PMCT254MFALI 3 PH PAD (8) 250
2500 Erickson Electric PMCT254MFPTALI 3 PH PAD (8) 600
2500 Erickson Electric PMCTMS-4211NMFALI 3 PH PAD (8) 250
2500 Erickson Electric PMCTMS-4611NG6MFPTALI
3 PH PAD (8) 600
2500 Galva Closure ALI-2534 3 PH WALL 250
2500 Galva Closure ALI-2534PM 3 PH PAD (8)(11) 250
2500 Galva Closure ALI-2534UGBX 3 PH WALL (11) 250
2500 Galva Closure ALI-2564 3 PH WALL (2) 600
2500 Galva Closure ALI-2564PM 3 PH PAD (2)(8)(11) 600
2500 Galva Closure ALI-2564UGBX 3 PH WALL (2)(11) 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 55
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
E210 TRANSFORMER METERING CABINETS - 3000 AMP
3000 A.M.P ALICT30-4L 3 PH WALL (2)(11) 600
3000 A.M.P ALIPCT30-4L 3 PH PAD (2)(8)(11) 600
3000 EMI ALIPM330 3 PH PAD (10)(11) 600
3000 Erickson Electric CT304-ALI 3 PH WALL (3) 250
3000 Erickson Electric CT304PTAL 3 PH WALL (1)(3) 600
3000 Erickson Electric PMCT304MFALI 3 PH PAD (8) 250
3000 Erickson Electric PMCT304MFPTALI 3 PH PAD (8) 600
3000 Erickson Electric PMCTMS-4212NMFALI 3 PH PAD (8) 250
3000 Erickson Electric PMCTMS-4612NG6MFPTALI
3 PH PAD (8) 600
3000 Galva Closure ALI-3034 3 PH WALL 250
3000 Galva Closure ALI-3034PM 3 PH PAD (11) 250
3000 Galva Closure ALI-3034UGBX 3 PH WALL (11) 250
3000 Galva Closure ALI-3064 3 PH WALL (2) 600
3000 Galva Closure ALI-3064PM 3 PH PAD (2)(11) 600
3000 Galva Closure ALI-3064UGBX 3 PH WALL (2)(11) 600
E211 TERMINATION BOXES 400 AMPS MAX.
400 A.M.P ALIPTB4-3L 1 PH PAD (8) 600
400 A.M.P ALIPTB4-4L 3 PH PAD (8) 600
400 A.M.P ALITB4-3L 1 PH WALL (5) 600
400 A.M.P ALITB4-4L 3 PH WALL (5) 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 56
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
400 EMI ALITB140 1 PH WALL 600
400 EMI ALITB340 3 PH WALL 600
400 Erickson Electric ALITB-365N 1 PH WALL 250
400 Erickson Electric ALITB-465N 3 PH WALL 600
400 Galva Closure TBALI-413-1 1 PH WALL 600
400 Galva Closure TBALI-434-1 3 PH WALL 600
400 Galva Closure TBBXALI413-1 1 PH WALL (11) 600
400 Galva Closure TBBXALI434-1 3 PH WALL (11) 600
400 Galva Closure TBPMALI-413-1 1 PH PAD 600
400 Galva Closure TBPMALI-434-1 3 PH PAD 600
E212 TERMINATION BOXES 600 AMPS MAX.
600 A.M.P ALIPTB6-3L 1 PH PAD (8) 600
600 A.M.P ALIPTB6-4L 3 PH PAD (8) 600
600 A.M.P ALITB6-3L 1 PH WALL (5) 600
600 A.M.P ALITB6-4L 3 PH WALL (5) 600
600 EMI ALITB160 1 PH WALL 600
600 EMI ALITB360 3 PH WALL 600
600 Erickson Electric ALITB-366N 1 PH WALL 250
600 Erickson Electric ALITB-466N 3 PH WALL 600
600 Galva Closure TBALI613-2 1 PH WALL 600
600 Galva Closure TBALI634-2 3 PH WALL 600
600 Galva Closure TBBXALI613-2 1 PH WALL (11) 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 57
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
600 Galva Closure TBBXALI634-2 3 PH WALL (11) 600
600 Galva Closure TBPMALI-613-2 1 PH PAD 600
600 Galva Closure TBPMALI-634-2 3 PH PAD 600
E213 TERMINATION BOXES 800 AMPS MAX
800 A.M.P ALIPTB8-3L 1 PH PAD (8) 600
800 A.M.P ALIPTB8-4L 3 PH PAD (8) 600
800 A.M.P ALITB8-3L 1 PH WALL (5) 600
800 A.M.P ALITB8-4L 3 PH WALL (5) 600
800 A.M.P ALITC8-3L 1 PH WALL 600
800 A.M.P ALITC8-4L 3 PH WALL 600
800 EMI ALITB180 1 PH WALL 600
800 EMI ALITB380 3 PH WALL 600
800 Erickson Electric ALITB365N 1 PH WALL 250
800 Erickson Electric ALITB467N 3 PH WALL 600
800 Galva Closure TBALI813-3 1 PH WALL 600
800 Galva Closure TBALI834-3 3 PH WALL 600
800 Galva Closure TBBXALI813-3 1 PH PAD (11) 600
800 Galva Closure TBBXALI834-3 3 PH PAD (11) 600
800 Galva Closure TBPMALI-813-1 1 PH PAD 600
800 Galva Closure TBPMALI-834-1 3 PH PAD 600
E214 TERMINATION BOXES 1200 AMPS MAX
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 58
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
1200 A.M.P ALIPTB12-4L 3 PH PAD (8)(11) 600
1200 A.M.P ALITB12-4L 3 PH WALL (11) 600
1200 A.M.P ALITC12-4L 3 PH WALL 600
1200 EMI ALITB312 3 PH WALL 600
1200 Erickson Electric ALIPMTB-468N 3 PH PAD 600
1200 Erickson Electric ALITB468N 3 PH WALL 600
1200 Erickson Electric ALITB468NSG 3 PH WALL 600
1200 Galva Closure TBALI1234-5 3 PH WALL 600
1200 Galva Closure TBBXALI-1234-5 3 PH WALL 600
1200 Galva Closure TBPMALI-1234-5 3 PH PAD 600
E215 TERMINATION BOXES 1600 AMPS MAX.
1600 A.M.P ALIPTB16-4L 3 PH PAD (8)(11) 600
1600 A.M.P ALITB16-4L 3 PH WALL (11) 600
1600 A.M.P ALITC16-4L 3 PH WALL 600
1600 EMI ALITB316 3 PH PAD 600
1600 Erickson Electric ALIPMTB469N 3 PH PAD 600
1600 Erickson Electric ALITB469N 3 PH WALL 600
1600 Erickson Electric ALITB469NSG 3 PH WALL 600
1600 Galva Closure TBALI-1634-4 3 PH WALL 600
1600 Galva Closure TBBXALI-1634-4 3 PH WALL (11) 600
1600 Galva Closure TBPMALI-1634-4 3 PH PAD 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 59
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
E216 TERMINATION BOXES 2000 AMPS MAX
2000 A.M.P ALIPTB20-4L 3 PH PAD (8)(11) 600
2000 A.M.P ALITB-20-4L 3 PH WALL (11) 600
2000 A.M.P ALITC20-4L 3 PH WALL 600
2000 EMI ALITB320 3 PH PAD 600
2000 Erickson Electric ALIPMTB4610N 3 PH PAD 600
2000 Erickson Electric ALITB4610N 3 PH WALL 600
2000 Erickson Electric ALITB4610NSG 3 PH WALL 600
2000 Galva Closure TBALI-2034-5 3 PH WALL 600
2000 Galva Closure TBBXALI-2034-5 3 PH WALL (11) 600
2000 Galva Closure TBPMALI-2034-5 3 PH PAD 600
E217 TERMINATION BOXES 2500 AMPS MAX.
2500 A.M.P ALIPTB25-4L 3 PH PAD (8)(11) 600
2500 A.M.P ALITB25-4L 3 PH WALL (11) 600
2500 EMI ALITB325 3 PH PAD 600
2500 Erickson Electric ALIPMTB4611N 3 PH PAD 600
2500 Erickson Electric ALITB4611N 3 PH WALL 600
2500 Erickson Electric ALITB4611NSG 3 PH WALL 600
2500 Galva Closure TBALI-2534-7 3 PH WALL 600
2500 Galva Closure TBBXALI-2534-7 3 PH PAD (11) 600
2500 Galva Closure TBPMALI-2534-7 3 PH PAD 600
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 60
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
E218 TERMINATION BOX 3000 AMP MAX
3000 A.M.P ALIPTB30-4L 3 PH (8)(11) 600
3000 A.M.P ALITB30-4L 3 PH (11) 600
3000 EMI ALITB330 3 PH PAD 600
3000 Erickson Electric ALIPMTB4612N 3 PH PAD 600
3000 Erickson Electric ALITB4612N 3 PH WALL 600
3000 Erickson Electric ALITB4612NSG 3 PH 600
3000 Galva Closure TBALI-3034-8 3 PH WALL 600
3000 Galva Closure TBBXALI-3034-8 3 PH WALL 600
3000 Galva Closure TBPMALI-3034-8 3 PH PAD 600
E219 HORIZONTAL BUSSED CABINETS - 400AMPS, TERM.,BREAKER AND DISCO- METERING 250V MAX
400 Eaton-CH ALI-TRB-325N-CH 1 PH WALL
400 Eaton-CH ALI-TRB-425N-CH 3 PH WALL
400 Eaton-CH ALI-XMCBE-400R 3 PH WALL (14)
400 Siemens/Murray WEB1400BU 1 PH WALL
400 Siemens/Murray WEB3400BU 3 PH WALL
400 Siemens/Murray WES1400BU 1 PH WALL
400 Siemens/Murray WES3400BU 3 PH WALL
400 Eaton-CH ALI-CTA-P-4244N-CM8-CH 3 PH WALL (7)(13)(15)
400 Eaton-CH ALI-CTA-P-425N-CM8-CH 3 PH WALL (7)(13)(15)
400 Eaton-CH ALI-CTA-T-425N-CM8-CH 3 PH WALL (7)(13)(15)
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 61
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
400 Erickson Electric ALI-CTA-DK-425N-CM8 3 PH (7)(15)
400 Erickson Electric ALI-CTA-P-425-CM8 3 PH WALL (7)(15)
400 Erickson Electric ALI-CTA-T-425N-CM8 3 PH WALL
400 Erickson Electric ALI-TRB-425N 3 PH WALL (13)(15)
E220 HORIZONTAL BUSSED CABINETS-600 AMP TERM BREAKER DISCO METERING-250V
600 Eaton-CH ALI-TRB-326N-CH 1 PH WALL (13)
600 Eaton-CH ALI-TRB-426N-CH 3 PH WALL (13)
600 Eaton-CH ALI-CTA-T-426N-CM8-CH 3 PH WALL (13)
600 Erickson Electric ALI-CTA-LD-426N-CM8 3 PH WALL (7)(15)(13)
600 Erickson Electric ALI-CTA-T-426N-CM8 3 PH WALL (7)(15)(13)
600 Erickson Electric ALI-TRB-426N 3 PH WALL (15)(13)
600 Siemens/Murray WEB1600BU-1PHASE 1 PH WALL
600 Siemens/Murray WEB3600BU-3PHASE 3 PH WALL
600 Siemens/Murray WES1600BU-1PHASE 1 PH WALL
600 Siemens/Murray WES3600BU-3PHASE 3 PH WALL
E221 HORIZONTAL BUSSED CABINETS-800 AMP TERM BREAKER DISCO METERING-250V MAX
800 Eaton ALI-TRB327N-CH 1 PH WALL
800 Eaton ALI-TRB427N-CH 3 PH WALL
800 Eaton-CH ALI-CTA-T-427N-CM8-CH 3 PH WALL
800 Erickson Electric ALI-CTA-MD-427N-CM8 3 PH WALL (7)(15)
800 Erickson Electric ALI-CTA-T-427N-CM8 3 PH WALL (7)(15)
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 62
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
800 Erickson Electric ALI-TRB327N-LE 1 PH WALL
800 Erickson Electric ALI-TRB427N-LE 3 PH WALL
800 Siemens/Murray WEB1800BU-1PHASE 1 PH WALL
800 Siemens/Murray WEB3800BU-3PHASE 3 PH WALL
800 Siemens/Murray WES1800BU-1PHASE 1 PH WALL
800 Siemens/Murray WES3800BU-3PHASE 3 PH WALL
E222 HORIZONTAL BUSSED CABINETS-1200 AMP TERM BREAKER DISCO METERING-250V
1200 Eaton-CH ALI-TRB-428N-CH 3 PH WALL (13)
1200 Erickson Electric ALI-CTA-124-2-CM8 3 PH WALL (7)(15)(13)
1200 Erickson Electric ALI-TRB-428N 3 PH WALL (13)
1200 Siemens/Murray WEB11200BU-1PHASE 1 PH WALL
1200 Siemens/Murray WEB31200BU-3PHASE 3 PH WALL
1200 Siemens/Murray WES11200BU-1PHASE 1 PH WALL
1200 Siemens/Murray WES31200BU-3PHASE 3 PH WALL
E223 HORIZONTAL BUSSED CABINET- 1600 AMPS TERM. BREAKER & DISCO 250V MAX
1600 Eaton-CH ALI-TRB-429N-CH 3 PH WALL (13)
1600 Erickson Electric ALI-TRB-429N 3 PH (13)
E224 HORIZONTAL BUSSED CABINET- 2000 AMPS TERM. BREAKER & DISCO 250V MAX
2000 Eaton-CH ALI-TRB-4210N-CH 3 PH WALL (13)
2000 Erickson Electric ALI-TRB-4210N 3 PH (13)
E225 Horiz Bussed Term Box & Metering Trans Cabinets 600V Max
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 63
Amps Manufacturer Catalog Number PH Mounting Foot Notes Main Size Voltage Range Top In /
Btm OutBtm In/ Top Out
Btm In/ Btm Out
Pad- Mount
Wall-mount Configuration
1200 Erickson Electric ALI-CTA124-2-PT-6CM8 3 PH (7)(13)
400 Erickson Electric ALI-CTA-KD-465N-PT-6CM8 3 PH (7)(13)
600 Erickson Electric ALI-CTA-LD-466N-PT-6CM8 3 PH (7)(13)
800 Erickson Electric ALI-CTA-MD-467N-PT-6CM8 3 PH (7)(13)
400 Erickson Electric ALI-CTA-P-465-PT-6CM8 3 PH (7)(13)
400 Erickson Electric ALI-CTA-T-465N-PT-6CM8 3 PH (7)(13)
600 Erickson Electric ALI-CTA-T-466N-PT-6CM8 3 PH (13)
800 Erickson Electric ALI-CTA-T-467N-PT-6CM8 3 PH (7)(13)
2000 Erickson Electric ALI-TRB-42610N 3 PH
400 Erickson Electric ALI-TRB-465N 3 PH (13)
600 Erickson Electric ALI-TRB-466N 3 PH (13)
800 Erickson Electric ALI-TRB-467N 3 PH (13)
1200 Erickson Electric ALI-TRB-468N 3 PH (13)
1600 Erickson Electric ALI-TRB-469N 3 PH
E226 SWITCHBOARD STRUCTURES - 400 TO 3000 AMPS (250 VOLT MAX.)
0 A.M.P ALIFMURCTCB 3 PH PAD 250
0 A.M.P ALIFMURCTCT 3 PH PAD 250
0 A.M.P ALIFMURCTCTS 3 PH PAD (24) 250
0 A.M.P ALIFMURCTS 3 PH PAD (24) 250
0 A.M.P ALIFMURMCT 3 PH PAD 250
0 A.M.P ALIFMURMS 3 PH PAD 250
0 A.M.P ALIFMURTC 3 PH PAD 250
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 64
Amps Manufacturer Catalog Number PH Mounting Foot Notes Voltage Range
250A.M.P. ALIRMR90 3 PH PAD
Chapter 2 EQUIPMENT- CABINETS
IOWA / WISCONSIN ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Footnotes on Pg. 42 Page 65
ALLIANT ENERGY
ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Page 66
E227. DEADFRONT PRIMARY METERING ENCLOSURES – 15 KV Durham – Cabinet – No. PME-3P-15KV- 200A-XY-ALI PME- 3P-15KV-600A-XY-ALI IPME-3P-15KV-600A-XY-ALI a. JVM-5 PT’s (indoor w/fuse) & JKM-5a CT (Indoor) (Line bushing-(1)/Load bushing-(1))
ABB/Malton – Cabinet – No. MEF72652DFM-15 – 600 Amp. a. JVM-5PT’s (Indoor w/fuse) & JKW-5A CT’s (Indoor) (Line bushing – 1-600, 1-200)/Load bushing- (1))
Elliot – Cabinet – No. EPM-PMS – 15-3XYP-E2-ALI – 200 Amp EPM-PMS – 15-3XYP-E6-ALI - 600 Amp a. VW-5PT’s (Outdoor w/o fuse) and jkw-5A CT’s (Outdoor) (line bushing –(1 or 2)/Load bushing-(1 or 2) Shallbetter – Cabinet – No. SPMD-31511-66-GA
E228. DEADFRONT PRIMARY METERING ENCLOSURES – 25 KV
Durham – Cabinet – No. PME-3P-25KV-200A-XY-ALI PME-3P-25KV-600A-XY-ALI a. JVW-6PT”s (outdoor) and JKW-6A CT’s (Outdoor) (#Line bushing-(X)/#Load bushing-(Y)) Elliot – Cabinet – No. EPM – PMS – 25 – 3XYP-E2 – ALI EPM – PMS – 25 – 3XYP-E6 – ALI (Alliant Energy provides separate PT fuses) Shallbetter – Cabinet – No. SPMD-32511-66-GA
NOTE: WE WILL ONLY LIST POLE TOP(SITE ISOLATING DEVICES) AND GRADE
LEVEL TRANSFER SWITCHES WITH METER SOCKETS. ALL OTHER TRANSFER SWITCHES, 600 VOLTS OR LESS, WILL BE ALLOWED, PROVIDED THEY MEET THE REQUIREMENTS LISTED IN CHAPTER 12, U.L., AND MEET NEC REQUIREMENTS
E229. FARMSTEAD POLE TOP TRANSFER SWITCHES – 250 VOLTS MAX.
NEC 547.2 Site-Isolating Device MANUF. SIZE(AMPS) ITEM# REMARKS Ronk Electric Industries 400 9406 Single phase – 2 pole 400 9806 Three phase – 3 pole 800 R8208 Single phase – 2 pole 800 R8808 Three phase – 3 pole E230. FARMSTEAD POLE TOP TRANSFER SWITCHES – 600 VOLT MAX.
NEC 547.2 Site-Isolating Device MANUF. SIZE (AMPS) ITEM # REMARKS Ronk Electric Industries 400 9808 Three phase – 3 pole 800 R8808 Three phase – 3 pole E231. RESIDENTIAL GRADE LEVEL TRANSFER SWITCHES WITH METER SOCKET – 250 VOLT
ALLIANT ENERGY
ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Page 67
MANUFACTURER SIZE(AMPS) ITEM# REMARKS Ronk Electric Industries 200 7215-MSH(*) – (**) Single phase – 2 pole Note: (*) = H / Horn Bypass or L / Lever Bypass. (**) = OH / Over Head, UG / Underground or SS / Side by Side (Overhead or Underground). Unit has 10,000 AIC rating only. E232. GRADE LEVEL OPERATED PRIMARY VOLTAGE POLE TOP LOAD BREAK
SWITCH MANUFACTURER SIZE (VOLTS) ITEM# REMARKS S&C 15KV 137032R1-S101 Single phase – 1 pole (ED-92AR-T200) (Horizontal) 15KV 137032R1-S101 Single phase – 1 pole (ED-7867) (Vertical) 25KV 147413/ED-701 Three phase – 3 pole Gang Operated
E233. 3 PHASE PADMOUNT TRANSFORMERS BOX PADS
E234. UNDERGROUND SERVICE WIREWAYS (Approved for maintenance use and where standard conduits are impractical only).
MANUFACTURER ITEM #.
A.M.P. WWPBXX & WWLPXX Galva Closure Model CC & CCL
ALLIANT ENERGY
ELECTRIC SERVICE EQUIPMENT Issued Jan. 2016
Page 68
E235. EQUIPMENT MANUFACTURES PHONE NUMBERS
MANUFACTURER TECHNICAL SUPPORT PRODUCT INFORMATION A.M.P. 1-800-328-8658 1-800-328-8658
CONCAST 1-507-732-4094 1-507-732-4094
DURHAM/UPPER MIDWEST 1-417-532-7121 1-417-532-7121
EATON/CUTLER HAMMER 1-800-356-1243 1-800-356-1243
ELECTRIC GLASS INC 1-731-427-0433 1-731-427-0433
EMI 1-800-536-3678 1-800-536-3678
ERICKSON ELECTRIC 1-800-952-7225 1-800-952-7225
GALVA CLOSURE 1-608-873-3044 1-608-873-3044
GE 1-800-431-7867 1-800-431-7867
LANDIS & GYR 1-800-777-2774 1-800-428-7853
MIDWEST ELECTRIC PRODUCTS 1-507-345-2543 1-507-345-2543
MILBANK 1-816-410-7217 1-877-483-5314
SIEMENS/TALON 1-800-333-7732 1-800-333-7732
NORDIC 1-218-745-5095 1-218-745-5095
RONK 1-800-221-7665 1-800-221-7665
SQUARE D 1-888-778-2733 1-888-778-2733