ECLYPSE™ nLight Solution nLight protocol Solution for ECLYPSE Connected System Controllers Figure 1: ECLYPSE nLight Solution shown with the power supply module, server module, and nLight communication module Overview The ECLYPSE nLight Solution extends the power of nLight to deliver the next level of lighting control. This BTL listed B-BC device leverages native BACnet™/IP and WiFi to let you seamlessly integrate your lighting control system with your building management systems. With the ECLYPSE ECY-S1000E-48-NL server model combined with the ECY-nLight Communication module, the ECLYPSE nLight Solution enables usage of applications such as nLight Explorer and Space Utilization. A user can also generate actionable, visual data with the embedded ENVYSION user interface. Applications £ IP & building management interface for Unified Solution networks £ Unified retail store building solution £ Unified office building solution £ Unified K12 Schools Features & Benefits Connectivity The different types of connections supported by the Connected System Controller are as follows: IP wired connection Internal switch with two Ethernet ports allows the controllers to be wired in a star or daisy- chain topology. With a daisy-chain topology: £ Fewer wire runs to a centralized switch are required, thereby achieving installation and cost reduction. £ A laptop can be connected to the second Ethernet port for direct programming, configuration, and commissioning using EC- gfxProgram or ENVYSION. IP wireless (Wi-Fi) connection The following types of Wi-Fi connections are possible when using the ECLYPSE Wi-Fi Adapter: £ Wi-Fi Client - Connection to the building’s existing Wi-Fi network or to another controller’s Wi-Fi Hotspot or Access Point. £ Wi-Fi Access Point - extending the building’s wired IP network to your Wi-Fi Client devices. Datasheet

Upload: others

Post on 25-May-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE™ nLight SolutionnLight protocol Solution for ECLYPSE Connected System Controllers

Figure 1: ECLYPSE nLight Solution shown with the power supply module, server module, and nLightcommunication module

OverviewThe ECLYPSE nLight Solution extends thepower of nLight to deliver the next level oflighting control. This BTL listed B-BC deviceleverages native BACnet™/IP and WiFi to letyou seamlessly integrate your lighting controlsystem with your building managementsystems.With the ECLYPSE ECY-S1000E-48-NL servermodel combined with the ECY-nLightCommunication module, the ECLYPSE nLightSolution enables usage of applications such asnLight Explorer and Space Utilization. A usercan also generate actionable, visual data withthe embedded ENVYSION user interface.

Applications£ IP & building management interface for

Unified Solution networks£ Unified retail store building solution£ Unified office building solution£ Unified K12 Schools

Features & BenefitsConnectivityThe different types of connections supported bythe Connected System Controller are as follows:

IP wired connectionInternal switch with two Ethernet ports allowsthe controllers to be wired in a star or daisy-chain topology. With a daisy-chain topology:£ Fewer wire runs to a centralized switch are

required, thereby achieving installation andcost reduction.

£ A laptop can be connected to the secondEthernet port for direct programming,configuration, and commissioning using EC-gfxProgram or ENVYSION.

IP wireless (Wi-Fi) connectionThe following types of Wi-Fi connections arepossible when using the ECLYPSE Wi-FiAdapter:£ Wi-Fi Client - Connection to the building’s

existing Wi-Fi network or to anothercontroller’s Wi-Fi Hotspot or Access Point.

£ Wi-Fi Access Point - extending the building’swired IP network to your Wi-Fi Clientdevices.

D a t a s h e e t

Page 2: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

2 / 20 ECLYPSE nLight Solution

£ Wi-Fi Hotspot - your own wireless areanetwork, for wireless communicationbetween the controllers, or with a mobiledevice or laptop for configuration,commissioning and servicing.

Both IP wired and wireless (Wi-Fi) connectionThe availability of both Ethernet ports and USBports for the Wi-Fi Adapter, allows forsimultaneous wired IP and Wi-Fi communicationon the same controller, which means you canchoose and combine these connection methods.For example, Wi-Fi can be used between twocontrollers to jump a large atrium.

Connect from anywhereControl technicians, facility managers,occupants, and others can easily connect to thesystem, on-site or off-site, using the differentavailable tools:£ ENVYSION to create and view the graphical

interface£ EC-gfxProgram to create custom control

sequences£ myDC Control to view, edit, and configure

system operating parameters£ SensorView to create custom lighting

configuration, sequences, and profiles

IP Communication£ Increased speed and improved handling of

numerous trend logs that enableapplications, such as advanced analyticsthat require a large amount of data.

£ Experience faster response and save timewhen programming, configuring, creatingand viewing graphics, and upgrading yoursystem.

£ Control technicians can connect theECLYPSE Wi-Fi Adapter to the ConnectedSystem Controller thereby creating a Wi-FiHotspot network. The control technician canthen connect wirelessly to the system usinga mobile device or laptop, for faster, easiersystem configuration, programming,commissioning, and servicing.

£ Hostname management allows the controllerto be addressed by a nickname to facilitatenetwork management.

Open to Web ServicesWith the RESTful API, the Connected SystemController’s data can be accessed from differentapplications, such as energy dashboards,analytics tools, and mobile applications. TheRESTful API documentation explains theimplementation protocol for this interface.

HTML5 Visual InterfaceThe ECLYPSE Connected System Controllercomes embedded with both ENVYSION Studioand Viewer, and xpressENVYSION.

ENVYSION – Web-based graphic design and vi-sualization interfaceENVYSION is a web-based graphic design andvisualization interface used to create and deliverinteractive graphical user interfaces and anoptimal user experience for building owners andfacility managers to better manage facility data.

ProgrammabilitySupports Distech Controls’ EC-gfxProgram,which makes Building Automation System(BAS) programming effortless, by allowing youto visually assemble building blocks to create acustom control sequence for any HVAC ,lighting, or building automation application.

Support for SensorView software makes lightingconfiguration effortless by using pre-madelighting profiles to create multiple tasks formultiple devices.

Page 3: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 3 / 20

Simplified Network CommissioningThe XpressNetwork Utility saves you time andexpense by giving you increased control overmultiple ECLYPSE controllers through devicediscovery and batch operations such asconfiguring, programming, and updating multipleECLYPSE controllers on the network.In addition, with the embedded step by stepCommissioning Wizard, all configurationoperations can be setup and applied in one go.Increase productivity using the xpressNetworkCompanion mobile app, making it easier toidentify and locate a controller on the network.Use the QR Code marked on ECLYPSEcontrollers to easily collect key controller dataand to facilitate its network integration withxpressNetwork Utility.

Scalable and ModularThe ECLYPSE nLight communication module isscalable and can be added to an ECY-S1000E-48-NL server model with any standardIO module from 0 to 48 input/output points andup to 10 Modbus devices to benefit from theHVAC VFD or metering devices near yourcontrol equipment.Benefit from three (3) nLight communicationports to support up to 300 nLight devices.

I/O modulesA range of I/O modules are available that haveuniversal inputs and outputs, digital inputs withfast pulse support for use with energy metersand counters, 24VAC triac outputs for use withsmaller load applications (up to 1 amp) such aselectric fans and motors/actuators and relayoutputs for larger load/high power applicationssuch as electric heat and high power actuators.

Power supplyThe Connected System Controller’s recurrentpower supply concept can be used when morepower is required to power a series of I/Omodules. A 100 to 240VAC power supplymodule eliminates the need for a line voltage to24VAC power transformer to save installationcosts and time. A 24 VAC / VDC power supplymodule is equally available.A connecting cable is used to connectsuccessive rows of modules within a controls’cabinet to provide power and communication.

BACnet/IP DeviceThe ECLYPSE nLight Solution is BTL-listed as aBACnet Building Controller (B-BC). It supportsBACnet/IP for faster communication incomparison to the traditional twisted paircommunication bus.

Multi-ProtocolMultiple communication protocols, like BACnet/IP and Modbus, make it easier to integrate intoexisting building automation systems and addfunctionality for multiple protocol integration.

FIPS 140-2 Level 1 CompliantFIPS 140-2 Level 1 compliance provides anenhanced level of security to protect data thecontroller is collecting and sharing making itsuitable for use in the most sensitiveenvironments.

Weather ForecastThe weather forecast is directly available fromthe internet to be shown on a connected ECx-Display or to be used by the controller’s code.

Allure™ Series Communicating Sensor SupportThese controllers work with a wide range ofsensors, such as the Allure SeriesCommunicating Sensors that are designed toprovide intelligent sensing and control devicesfor increased user experience and energyefficiency.£ Allure EC-Smart-Vue sensors feature a

backlit-display and graphical menus thatprovide precise environmental zone control,with any combination of the following:temperature, humidity, CO2, and motionsensor.

£ Allure EC-Smart-Comfort sensors featurecolored LED indicators to provide userfeedback, rotary knobs to adjust the setpointoffset and fan speed, and an occupancyoverride push button. This sensor can alsobe expanded with a combination of up to 4add-on push button modules for lighting andshade/ sunblind control.

£ Allure EC-Smart-Air sensors combineprecise environmental sensing in a discreetand alluring enclosure for temperature,humidity, and CO2.

Page 4: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

4 / 20 ECLYPSE nLight Solution

MobilityThe controller can be remotely accessed toprogram, configure, or maintain the installationthus reducing costs associated with on-sitevisits. Through a mobile device or PC, a rangeof tasks can be performed using the followingfree-to-use tools and interfaces:£ ENVYSION web-based graphic design and

visualization interface£ EC-gfxProgram graphical programming

interface£ myDC Control mobile application£ SensorView lighting configuration tool

Hand/Off/Auto Switches andPotentiometersThe front assembly of Hand/Off/Auto (HOA)equipped I/O models allow users to override thecontrol outputs for commissioning andmaintenance purposes.Universal outputs have potentiometers providingmanual analog signal and output control tooverride voltage or current signal.

High-Efficiency DesignThe power supply uses the latest high-efficiencyswitch-mode circuitry to make more poweravailable to operate additional modules and forcooler operation.

Hot-Swappable Tool-Less Design andUnique Latching MechanismThe I/O modules are hot-swappable forreplacement without interrupting power andcommunications to other modules.The front assembly of I/O modules separatefrom the wiring base by pushing the two latchesup to unlock a module’s front assembly and thenopening and pulling the hinged gull-wing covers.The latch design locks the front assembly to thewiring base.

The hinged gull-wing design protects and coverthe stacked dual row I/O terminal strips.

Ease of InstallationThe Connected System Controller modules areplug & play devices. They are equipped withHD-15 connectors that transmits power andcommunications to the next module for fast andeasy assembly.

I/O Status LEDsThe status LEDs on the I/O modules allows theuser to confirm the status of the inputs/outputsand facilitate commissioning andtroubleshooting.

Auto-AddressingThe auto-addressing feature eliminates theneed to manually assign an address to each I/Omodule therefore reducing installation andconfiguration time.

Digital Inputs Up to 120HzThe ECY-16DI module supports pulsed signalsup to 120Hz for equipment status monitoringand alarm point monitoring, commonly used inenergy metering applications.

Color-Coded, Rising Cage TerminalsTerminal blocks are uniquely identified andcolor-coded for clarity and to prevent wiringmistakes. The rising cage clamp terminal blockconnectors offer a more robust and secure wireconnection, designed to withstand activity andvibrations.

Robust ProtectionThe I/O modules are protected against mis-wiring and faults to prevent damage caused byincorrect wiring or other mishaps.The power supply module contains over-voltageand over-current output protection to protect theelectronics in unstable power supply conditionsand against mis-wiring.

Page 5: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 5 / 20

Alarms, Trend Log, Schedule SupportEmbedded alarms, trend log and schedulesupport allows for fully distributed data and logicproviding a more robust system. Embeddedtrend logs simplify system troubleshooting whencompared to a centralized system.

Email Notifications ServiceTechnicians & facility managers can receiveautomatic email notifications for system statusand alarms to ensure faster system servicingand response time. Email notification text canbe customized to provide pertinent informationabout the issue at hand.

Monitoring and ConfigurationCommunicates over IP Local Area Network(LAN) with SensorView™ and ECLYPSEdevices.£ Discover and configure nLight devices with

SensorView software£ Monitor and see system health of nLight

connected devices with the nLight Exploreredge application.

ENVYSION & xpressENVYSION –Web-based Graphic Design andVisualization InterfaceENVYSION is a web-based graphic design andvisualization interface used to create and deliverinteractive graphical user interfaces and anoptimal user experience for building owners andfacility managers to better manage facility data.

Page 6: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

6 / 20 ECLYPSE nLight Solution

Model SelectionThe ECLYPSE nLight Solution consists of a power supply, a control, automation and connectivityserver, I/O extension modules, and communication modules to create a controller tailored to itsapplication. The different models for each are shown in the tables below.

Power SupplyA power supply module must be added after each HD15 cable (see Accessories below).

ECY-PS24 24VAC/VDC power supply module for the ECLYPSE Connected SystemController.

ECY-PS100-240 100 to 240VAC power supply module for the ECLYPSE ConnectedSystem Controller.

Control, Automation and Connectivity ServerConnected System Controller for a Unified Building Solution

Model WithEmbeddedENVYSION

Application Max Numberof PointsSupported

BACnet MS/TP to IPRoutingSupport

Max Numberof ModbusDevices (RTUor TCP)

Max Numberof nLightDevicesSupported

ECY-S1000E-48-NL1

Small sizeequipment(large rooftopunit or a smallAHU)

48 No 10 300

1. The ECY-S1000E-48-NL models support the ECY-nLight communication module.

Page 7: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 7 / 20

I/O Modules SelectionInputs Outputs

Basi

c Po

wer

Con

sum

ptio

n2 ,WQ

uant

ity

Digital Analog

18VD

C P

ower

Sup

ply

Qua

ntity

Digital Analog

HO

A

Con

tact

Cou

nter

120H

z Pu

lse

Cou

ntin

g0

to 1

0VD

C0

to 5

VDC

0 to

20m

AR

esis

tanc

eTh

erm

isto

r

0-27

7VAC

/ 0-

30VD

CFo

rm-C

, 10A

24VA

C T

riac,

0.5

A0

or 1

2VD

CPW

MFl

oatin

g0

to 1

0VD

C1

0 to

20m

A1

ECY-8UI 8 0.94ECY-16DI 16 0.94ECY-6UO 6 UO1

UO2UO3

0.94

ECY-6UO-HOA 6 UO1UO2UO3

0.94

ECY-8DOR 8 0.94ECY-8DOR-HOA 8 0.94ECY-4UI4UO 4 4 UO1

UO2UO3

0.94

ECY-4UI4UO-HOA 4 4 UO1UO2UO3

0.94

ECY-8UI6UO 8 6 UO1UO2UO3

0.94

ECY-8UI6UO-HOA 8 6 UO1UO2UO3

0.94

ECY-8UI6DOT 8 6 0.94ECY-8UI6DOT-HOA 8 6 0.941. 0 to 10VDC is available on UO1 to UO6. 0 to 20 mA is available on UO1, UO2, and UO3; this option is individually selected through an on-board DIP switch

setting.2. External loads excluded. See the ECLYPSE Selection Tool to calculate the number of Input/Output Extension Modules that can operate with a power supply.

AccessoriesECLYPSE HD15 Cable 6ft (1.8m) cable for Connected System Controller multiple-row panel

installations. An HD15 cable must always be followed by a power supplymodule. For more information, refer to the Hardware Installation Guide.

ECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers.

Page 8: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

8 / 20 ECLYPSE nLight Solution

Product SpecificationsnLight Communication Interface Module (ECY-nLight)Supported Quantity 1 × ECY-nLight per ECY-S1000-NLVoltage 18VDCPower Consumption 2 W

CommunicationsPorts 3 × nLight RJ-45 bus portsStatus Indicators Green LED: TX

Orange LED: RX

HardwareConnection Always the first module connected to the right side of the server

MechanicalDimensions (H × W × D) 4.80 × 3.20 × 2.31” (121.75 × 81.17 × 58.56mm)

Shipping weight 0.55lbs (0.25kg)Mounting DIN rail or screw mountingEnclosure Material FR/ABSEnclosure Rating1 Plastic housing, UL94-V0 flammability rating

Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingIngress Protection Rating IP20Nema Rating 1

Page 9: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 9 / 20

Standards and RegulationsCE:£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL916 Energy management equipment

             

Power Supply (ECY-PS24)Power Supply InputVoltage Range 24VAC/DC; ±15%; Class 2Power Consumption 60VAFrequency Range 50 to 60HzOvercurrent Protection Field replaceable fuseFuse Type 4A, fast-acting, 5 × 20mm (GMA-4A)

Power Supply OutputDC Voltage 18VDC regulatedRated Current Range 0 to 1.6ARated Power 30W1

1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connectedloads, must be less than this value. A separate transformer rated at 60VA minimum and 100VA maximum must be used for each ECY-PS24 power supply for it tooperate at full capacity.

HardwarePower Distribution Direction Powered modules are connected to the rightBackplane Bus Pass-through connection for data and control signalsStatus Indicator Green LED: power status

MechanicalDimensions (H × W × D) 4.74 × 2.85 × 2.31" (120.31 × 72.38 × 58.56mm)

Page 10: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

10 / 20 ECLYPSE nLight Solution

4.74" 120.31 3.18" 80.82

18.390.72

21.130.83

2.31" 58.5672.38

Inches Millimeters

0.01" 0.40Inter-Connection Gap:

2.61" 66.190.06" 1.44

0.17" 4.24 2.85"

5.20" 132.00

Front BackProfile

Shipping weight 0.75lbs (0.34kg)Mounting DIN rail or screw mountingEnclosure Material1 FR/ABSEnclosure Rating Plastic housing, UL94-V0 flammability ratingPlenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingIngress Protection Rating IP20Nema Rating 1

Standards and RegulationsCE:£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL916 Energy management equipment

             

Power Supply (ECY-PS100-240)Power Supply InputVoltage Range 100 to 240 VAC Universal; +10%/-15%Input Current 400mA typicalFrequency Range 50 to 60HzStandby Power consumption <0.5W

Page 11: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 11 / 20

Overcurrent Protection Field replaceable fuseFuse Type 2.5A, Fast-acting, high-breaking, 250VAC, 5 × 20mm (TF2.5AH250V, IEC60127-2)

Power Supply OutputDC Voltage 18VDC regulatedRated Current Range 0 to 2ARated Power 40W1

1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connectedloads, must be less than this value.

HardwarePower Distribution Direction Powered modules are connected to the rightBackplane Bus Pass-through connection for data and control signalsStatus Indicator Green LED: power status

MechanicalDimensions (H × W × D) 4.74 × 4.08 × 2.31" (120.31 × 103.65 × 58.56mm)

3.18" 80.82

18.390.72

21.130.83

2.31" 58.56

0.06" 1.44BackProfile

103.654.08"

5.24 133.03

4.74" 120.31

0.44" 11.13

3.83" 97.33Front

0.01" 0.40Inter-Connection Gap:

Inches Millimeters

Shipping weight 0.71lbs (0.32kg)Mounting DIN rail or screw mounting

Refer to Hardware Installation Guide for more informationEnclosure Material1 FR/ABSEnclosure Rating Plastic housing, UL94-5VB flammability rating1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingAltitude <6562ft (2000m)Pollution Degree 2Ingress Protection Rating IP20(must be mounted in a protective enclosure to conform with electrical installation standards)Overvoltage Category II - 2.5 kV

Page 12: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

12 / 20 ECLYPSE nLight Solution

Electrical Protection DC output is Separated Extra-Low Voltage (SELV); SELV is implemented through reinforced insulation

Standards and RegulationsCE:£ Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household

and similar use - Part 1: General requirements£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsUL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment

For Measurement, Control, And Laboratory Use - Part 1: General Requirements - Edition 2 - Revision Date 2008/10/28

FCC This device complies with FCC rules part 15, subpart B, class B

             

Control, Automation and Connectivity Server (ECY-S1000)Power Supply InputVoltage 18VDCPower Consumption 8.9W; external loads excluded

CommunicationsEthernet Connection Speed 10/100 Mbps£ Addressing IPv4 or HostnameBACnet Profile BACnet Building Controller (B-BC))BACnet Listing BTL, WSP B-BCBACnet Interconnectivity BBMD capabilitiesWeb Server Protocol HTML5Web Server Application Interface REST APISupported Modbus RTU and TCP Connectivity:£ Modbus RTU 1 × RS-485 serial communications ports£ RS-485 Wiring 1-pair + Common/shield£ RS-485 EOL Resistor Built-in£ RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps£ RS-485 Addressing Controller’s Web Configuration Interface£ Modbus TCP Devices must be on the same subnetSupported Wireless Connectivity:£ Wireless Adapter Optional, USB Port Connection£ Wi-Fi Communication Protocol IEEE 802.11b/g/n and 802.11s£ Wi-Fi Network Types Client, Access Point, Hotspot

Supported Smart Room Control Components1:Maximum number of supported devices per controller combined 12£ Allure EC-Smart-Vue Series Up to 121

Page 13: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 13 / 20

£ Allure EC-Smart-Comfort Series Up to 6£ Allure EC-Smart-Air Series Up to 61

£ EC-Multi Sensor Up to 42

1. For more details about supported quantities, see the ECLYPSE Selection Tool.xlsm spreadsheet file available for download from SmartSource.2. A controller can support a maximum of 2 Allure sensor models equipped with a CO2 sensor. Any remaining connected sensors must be without a CO2 sensor.

HardwareProcessor Sitara ARM processorCPU Speed 1GHzMemory 4GB Non-volatile Flash (applications & storage)

512MB RAMReal Time Clock (RTC) Real Time Clock with rechargeable battery

Supports SNTP network time synchronizationRTC Battery 20 hours charge time, 20 days discharge time

Up to 500 charge / discharge cyclesCryptographic Module FIPS 140-2 Level 1 CompliantCommunications Ports:£ Ethernet 2 switched RJ-45 Ethernet ports

Supported Protocols BACnet/IP, Modbus TCP, NTP, and REST£ USB Connections 2 × USB 2.0 Ports

1 × Micro-USB 2.0 Ports£ RS-485 Serial Communications Screw terminals

Supported Protocols Modbus RTU£ Subnet RJ-45Status Indicators Green LED: Power status, Subnet TX, RS-485 TX, and Ethernet Traffic

Orange LED: Controller status, Subnet RX, RS-485 RX, and Ethernet Speed

MechanicalDimensions (H × W × D) 4.74 × 3.57 × 2.31" (120.31 × 90.67 × 58.56mm)

3.18" 80.82

18.540.73

21.080.83

3.33" 84.47

0.4" 1.092.31" 58.563.57" 90.67

Inches Millimeters

Inter-Connection Gap: 0.01" 0.40

5.13" 130.29

0.06" 1.44

4.74" 120.31

0.39" 9.98 Front BackProfile

Shipping weight 0.85lbs (0.39kg)Mounting DIN rail or screw mountingEnclosure Material FR/ABS

Page 14: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

14 / 20 ECLYPSE nLight Solution

Enclosure Rating1 Plastic housing, UL94-V0 flammability rating Plenum rating per UL1995

1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingIngress Protection Rating IP20Nema Rating 1

Standards and RegulationsCE:£ Emission EN61000-6-3: 2007+A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL916 Energy management equipment

                 

I/O ModulesPower Supply InputVoltage 18VDCPower Consumption Calculate power supply requirements with the ECLYPSE Selection Tool

HardwareStatus Indicator Green LEDs: inputs and outputs

For ECY-8UI, ECY-16DI, ECY-6UO, ECY-6UO-HOA, ECY-4UI4UO, ECY-4UI4UO-HOA, ECY-8UI6UO, ECY-8UI6UO-HOA, ECY-8UI6DOT, & ECY-8UI6DOT-HOAModels:

MechanicalDimensions (H × W × D) 4.74 × 3.20 × 2.31" (120.31 × 81.17 × 58.56mm)

Page 15: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 15 / 20

2.95" 74.99

4.74" 120.31

3.20" 81.17 2.31" 58.56

3.18" 80.82

18.540.73

21.080.83

Inches Millimeters

Inter-Connection Gap: 0.01" 0.40

Front BackProfile0.06" 1.44

4.80" 121.75

Shipping weight 0.85lbs (0.39kg)Mounting DIN rail or screw mountingHot-swappable YesEnclosure Material FR/ABSEnclosure Rating1 Plastic housing, UL94-V0 flammability rating; Plenum rating per UL19951. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

I/O Modules - Universal Inputs (UI)GeneralInput Type Universal; software configurableCurrent Input Option Selection DIP switchInput Resolution 16-bit analog to digital converterPower Supply Output 18VDC; 20mA maximum per 0 to 20 mA input

ContactType Dry contact

CounterType Dry contactMaximum Frequency 1Hz maximum,Minimum Duty Cycle 500milliseconds On / 500milliseconds Off

0 to 10VDCRange 0 to 10VDC (40kΩ input impedance)

0 to 5VDCRange 0 to 5VDC (high input impedance)

0 to 20mARange 0 to 20mA

249Ω DIP-switch configurable internal resistor

Page 16: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

16 / 20 ECLYPSE nLight Solution

Resistance/ThermistorRange 0 to 350 KΩSupported Thermistor Types Any that operate in this rangePre-configured Temperature Sensor Types:£ Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF; 25ºC)£ Platinum Pt1000 (1KΩ @ 32ºF; 0ºC)£ Nickel RTD Ni1000 (1KΩ @ 32ºF; 0ºC)

RTD Ni1000 (1KΩ @ 69.8ºF; 21ºC)

I/O Modules - Digital Inputs (DI)GeneralInput Type Dry contact or Open-CollectorLow Threshold < 2.5VHigh Threshold > 3.0V

Pulse/CounterPulse Input S0 output compatibleMaximum Frequency 120HzMinimum Duty Cycle 4.167milliseconds On / 4.167milliseconds Off

I/O Modules - Universal Outputs (UO)GeneralOutput Type Universal; software configurableOutput Resolution 10-bit digital to analog ConverterOutput Protection Built-in snubbing diode to protect against back-EMF,

for example when used with a 12VDC relayLoad Resistance Minimum 200Ω for 0 to 10VDC and 0 to 12VDC outputs

Maximum 500Ω for 0 to 20mA outputAuto-reset Fuse 60mA @ 140ºF; 60ºC

0 or 12VDC (On/Off)Range 0 or 12VDC

PWMRange Adjustable period from 2 to 65seconds

FloatingMinimum Pulse On/Off Time 500millisecondsDrive Time Period Adjustable

0 to 10VDCRange 0 to 10VDC linear

0 to 20mARange 0 to 20mA

Page 17: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 17 / 20

Current Source 20mA maximum per 0 to 20 mA outputPorts UO1, UO2, and UO3 only DIP switch

HOAHand-Off-Auto switch When equipped

Supervision allows control logic to read the current HOA switch and potentiometer settings

Threshold ConfigurablePotentiometer Voltage Range 0 to 12VDC

I/O Modules - Digital Output (DOT)GeneralOutput Type 24VAC Triac; software configurableMaximum Current 0.5A continuous

1A @ 15% duty cycle for a 10 minute periodPower Source External power supply

0 or 24VAC (On/Off)Range 0 or 24VAC

PWMRange Adjustable period from 2 to 65seconds

FloatingMinimum Pulse On/Off Time 500millisecondsDrive Time Period Adjustable

HOAHand-Off-Auto switch When equipped

Supervision allows control logic to read the current HOA switch setting

I/O Modules - Digital Output (DOR)For ECY-8DOR & ECY-8DOR-HOA Models:GeneralOutput Type Relay contactRelay Type Form CPower Source Dry contact (external power supply)Operating Voltage 0 to 277VAC or 0-30VDC ±10%, see HIG for mounting specifications

Maximum Current£ Resistive Load 10A£ Inductive Load 6A£ Motor Load 3AProtection Outputs must be protected with max 10 A external circuit breaker

Page 18: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

18 / 20 ECLYPSE nLight Solution

DigitalRange On/Off

HOAHand-Off-Auto switch When equipped

Supervision allows control logic to read the current HOA switch setting

MechanicalDimensions (H × W × D) 4.74 × 5.15 × 2.31" (120.31 × 130.07 × 58.56mm)

4.74" 120.31

2.31" 58.56

Front Profile

O6O3O1 O4 O7 O8O5O2

MAN

AUTO

OFF

Inter-Connection Gap: 0.01" 0.40

5.15" 130.07

4.94" 125.32

Back

3.18" 80.82

18.540.73

21.080.83

Inches Millimeters0.06" 1.44

4.8" 121.75

Shipping weight 0.75lbs (0.34kg)Mounting DIN rail or screw mountingHot-swappable Yes (once high voltages have been removed)Enclosure Material FR/ABSEnclosure Rating1 Plastic housing, UL94-5VB flammability rating1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

EnvironmentalOperating Temperature 32 to 122°F (0 to 50°C)Storage Temperature -22 to 158°F (-30 to 70°C)Relative Humidity 0 to 90% non-condensingAltitude <6562ft (2000m)Pollution Degree 2Ingress Protection Rating IP20

(must be mounted in a protective enclosure to conform with electrical installation standards)Overvoltage Category II - 2.5 kV

Standards and RegulationsCE:£ Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household

and similar use - Part 1: General requirements£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,

commercial and light-industrial environments£ Immunity EN61000-6-1: 2007; Generic standards for residential,

commercial and light-industrial environments

Page 19: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

ECLYPSE nLight Solution 19 / 20

UL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment For Measurement, Control, And Laboratory Use - Part 1:

General Requirements - Edition 2 - Revision Date 2008/10/28FCC This device complies with FCC rules part 15, subpart B, class B

             

Page 20: ECY-nLight DS 10 EN...BACnet Building Controller (B-BC). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol

20 / 20 ECY-nLight_DS_10_EN

Specifications subject to change without notice.ECLYPSE, Distech Controls, the Distech Controls logo, EC-Net, and Allure are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE; BTL

is a registered trademark of the BACnet Manufacturers Association. All other trademarks are property of their respective owner.©, Distech Controls Inc., 2015 - 2017. All rights reserved.