EBH

ED

S

EBH high pressure ducted units and EDS Double Skin units, thanks to their high pressure fan

decks, permit to satisfy every request of heating and cooling applications in big environments,

where ducted air distribution is requested. They are suitable for horizontal installation.

These are units for COOLING and HEATING applications; they are fed with cold and hot water

and used according to their relevant performance features. EBH and EDS units are components

of cooling and/or heating systems; consequently, they are without any safety devices on the

water circuit. These units have been designed for temperatures up to 100 °C.

When you want to connect this high pressure unit to a condensing unit in COOLING mode, it

must be ordered with a direct expansion coil (optional upon request, except for sizes 060-070).

EBH | EDS HIGH PRESSURE UNITS

EDSHIGH PRESSURE UNIT

EBHHIGH PRESSURE UNIT

DUCTED UNITS EBH | EDS

EBH features

EBHUNIT WITH AIR SUPPLY

PLENUM

• 6 SIZES for horizontal ducted installation, 2 and 4 pipe system.

• HIGH PRESSURE: they are designed for ducted installation with external static pressure up to

300 Pa.

• STRUCTURE is realized in galvanized metal sheet, insulated internally; in order to facilitate all

maintenance operations, the structure is divided in three separate and independent sections

(condensate tray, fan deck, air filter).

• HEAT EXCHANGERS can have 2, 3 or 4 rows, made by copper pipes and aluminium fin pack;

5-row coils are available for sizes 060 and 070. Up to size 050 all coils are provided with air vent

valves. For sizes 060 and 070, the air vent valve is supplied only with the valve kit (optional).

• REVERSIBLE WATER CONNECTIONS: these high-pressure units can be ordered with right

(standard) or left water connections; it is possible to reverse the water connections on site, if

necessary.

• FAN DECK is composed by a 3 speed motor and two centrifugal galvanized steel scrolls. All

motors are provided with a permanently connected capacitor and thermal protection of the

windings with automatic reset.

• CONDENSATE TRAY is realized in galvanized steel with water discharge pipes on both sides.

• AIR FILTER consists of a washable polyester acrylic fibre, pleated and protected by a metal

frame.

The filter section can be easily removed for cleaning and maintenance. Filtration class G3.

• ELECTRIC PANEL is composed by a terminal board with screw terminals contained in an ABS

plastic box (IP30). A supporting relay is supplied as standard starting from size 040.

• 4 BRACKETS are supplied along with the unit, to fix it to the ceiling.

EBH

ED

SEB

H E

DS

EDS features

EDSHIGH PRESSURE UNIT

• 9 SIZES for horizontal ducted installation, 2 pipe system.

• HIGH PRESSURE: they are designed for ducted installation with external static pressure up to

300 Pa.

• DOUBLE SKIN STRUCTURE is composed by insulated 25 mm thick panels, colour RAL9002,

and aluminium supporting frame.

• HEAT EXCHANGERS can have 2, 3 or 4 rows, made by copper pipes and aluminium fin pack;

5-row coils are available for sizes 060 and 070. Up to size 050 all coils are provided with air

vent valves.

• NOT REVERSIBLE WATER CONNECTIONS: EDS units can be ordered with right (standard) or

left water connections.

• FAN DECK is composed by a 3 speed motor and two centrifugal galvanized steel scrolls. All

motors are provided with a permanently connected capacitor and thermal protection of the

windings with automatic reset.

• CONDENSATE TRAY is realized in galvanized steel with water discharge pipe located on the

water connections’ side.

• AIR FILTER consists of a washable polyester acrylic fibre, pleated and protected by a metal

frame. The filter section can be easily removed for cleaning and maintenance. Filtration class

G3.

• ELECTRIC PANEL is composed by a terminal board with screw terminals contained in a high

protection box (IP44). A supporting relay is supplied as standard starting from size 040.

• 4 BRACKETS are supplied along with the unit, to fix it to the ceiling.

HIGH PRESSURE UNIT EDS

EBH WITH VALVE

• quiet operation

• reliability

• excellent quality/price ratio

• high coefficient of performance

• sturdiness and solid construction

• accurate choice of each single component

• environmentally friendly sandwich panels (EDS model)

• high protection electric panel (IP44), available also on EBH models

• easy installation and maintenance operations

The big advantages of the EURAPO high pressure units are:

EBH

ED

S

• VALVE KIT 3 way 4-port regulating valves with ON/OFF or modulating actuators, provided with

copper connection kit and insulation shell (supplied loose).

• CONDENSATE PUMP with 6 m maximum head.

• CONDENSATE TRAY in stainless steel.

• SPECIAL FILTER made of washable polyester acrylic fibre, filtration class F5.

• ADDITIONAL COILS for hot water with 2 or 3 rows, for units to be installed in 4-pipe systems.

• DISTRICT COOLING COILS: Heat exchangers with a reduced number of circuits, suitable for

applications where the water thermal head is about 9 °C.

• ELECTRIC HEATER it is an additional section to be mounted on the air outlet, provided with all

necessary safety thermostats. The heating capacity is different from size to size, up to 9 kW.

• AIR DELIVERY/AIR INTAKE PLENUM with several frontal spigots.

• RAL 9001 PAINTING with oven dried epoxy powders. All RAL colours are available.

• REGULATING SYSTEMS: the whole range of EURAPO regulators is available: fan speed

selectors, electro-mechanical controllers, electronic controllers with microprocessor, digital

regulators with a centralized supervision system communicating via Bus based on standard

protocols. For more information, please either refer to the specific EURAPO technical literature

or visit the official web site www.eurapo.it.

Accessories for EBH units:

Additional coils Electric heater Valve kit

Condensate pump Air delivery/air intake plenum RAL 9001 painting

• VALVE KIT 3 way 4-port regulating valves with ON/OFF or modulating actuators, provided with

copper connection kit.

• CONDENSATE PUMP with 6 m maximum head.

• SPECIAL FILTER made of washable polyester acrylic fibre, filtration class F5.

• DISTRICT COOLING COILS: Heat exchangers with a reduced number of circuits, suitable for

applications where the water thermal head is about 9 °C.

• ELECTRIC HEATER it is an additional section to be mounted on the air outlet, provided with all

necessary safety thermostats. The heating capacity is different from size to size, up to 9 kW.

• AIR DELIVERY/AIR INTAKE PLENUM with several frontal spigots.

• REGULATING SYSTEMS: the whole range of EURAPO regulators is available: fan speed

selectors, electro-mechanical controllers, electronic controllers with microprocessor, digital

regulators with a centralized supervision system communicating via Bus based on standard

protocols. For more information, please either refer to the specific EURAPO technical literature

or visit the official web site www.eurapo.it.

Accessories for EDS units:

Electric heater Air delivery/air intake plenumValve kit Special filter

Analogue plus consoleDisplay console

EBH

ED

S

STANDARD TECHNICAL DATA AT DIFFERENT Pa OF EXTERNAL STATIC PRESSURE-ASYNCHRONOUS

Technical data EBH UNIT:

STANDARD TECHNICAL DATA 50 Pa EXTERNAL STATIC PRESSURE-ASYNCHRONOUS

Technical data EDS UNIT:

Models EBH EBH EBH EBH EBH EBH020 030 040 050 060 070 (4)

MAX External static pressure [Pa] 125 175 200 250 300 300

Total cooling capacity [kW] (1)

MAX 6,95 9,49 11,77 13,72 23,83 28,99

MED 5,90 8,23 10,35 12,60 21,59 26,64

MIN 4,30 7,11 8,91 11,36 17,15 24,28

Heating capacity [kW] (2)

MAX 7,08 11,40 14,32 17,40 28,08 35,01

MED 6,20 9,62 12,19 15,53 24,95 32,16

MIN 4,55 8,20 10,39 13,85 18,90 28,84

Air volume [m3/h]

MAX 1145 1910 2680 3250 4120 5493

MED 920 1520 2130 2870 3610 4926

MIN 620 1205 1655 2470 2580 4330

Sound pressure level [dB(A)] (3)

MAX 53,0 54,0 58,0 61,0 66,0 68,0

MED 47,0 50,0 52,0 57,0 63,0 65,0

MIN 37,0 46,0 47,0 54,0 54,0 63,0

Absorbed current [A]

MAX 0,74 1,62 2,05 2,83 4,47 8,08

MED 0,52 1,21 1,61 2,47 4,03 7,24

MIN 0,33 1,12 1,30 2,25 2,85 6,82

Power input [W]

MAX 171 352 451 588 1007 1767

MED 119 305 361 512 845 1629

MIN 72 267 274 440 586 1449

N° rows (standard) 4 4 4 4 4 4

Power supply [V-ph-Hz] 230-1-50/60

Models EDS EDS EDS EDS EDS EDS EDS EDS EDS004 006 008 020 030 040 050 060 070

MAX External static pressure [Pa] 50 50 50 125 175 200 250 300 300

Total cooling capacity [kW] (1)

MAX 2,58 3,35 4,79 7,43 10,15 12,67 12,95 23,88 27,70

MED 1,91 2,38 3,86 5,44 7,89 10,24 11,98 21,21 25,44

MIN 0,96 1,65 2,65 3,13 6,98 7,99 11,17 15,91 23,56

Heating capacity [kW] (2)

MAX 2,85 3,76 5,31 8,14 12,39 15,71 16,45 25,42 32,64

MED 2,16 2,92 4,42 5,89 9,27 12,59 15,24 22,22 30,17

MIN 1,11 1,80 3,42 3,43 8,06 9,63 13,78 16,11 27,28

Air volume [m3/h]

MAX 398 595 843 1396 2347 2817 3259 4335 5492

MED 283 431 693 943 1600 2162 2849 3644 4860

MIN 143 245 505 480 1297 1606 2430 2529 4275

Sound pressure level [dB(A)] (3)

MAX 41,4 43,4 45,4 51,3 55,8 60,2 61,9 65,6 68,0

MED 37,4 40,4 43,4 45,1 49,7 55,6 59,6 61,7 65,4

MIN 31,4 34,4 39,4 35,3 45,8 50,1 56,6 53,2 63,4

Absorbed current [A]

MAX 0,26 0,35 0,44 0,79 1,65 1,95 2,64 4,79 7,33

MED 0,20 0,27 0,36 0,51 1,17 1,55 2,22 4,03 7,56

MIN 0,14 0,20 0,29 0,30 1,03 1,21 1,90 2,72 6,72

Power input [W]

MAX 59 80 101 183 358 441 563 1037 1781

MED 46 62 84 117 246 337 479 874 1613

MIN 33 44 65 69 212 255 409 573 1417

N° rows (standard) 4 4 4 4 4 4 4 4 4

Power supply [V-ph-Hz] 230-1-50/60

(1) Air temperature: 27 °C d.b., 48% rel. humidity - Water temperature: 7/12 °C

(2) Air temperature: 20 °C, 50% rel. humidity - Water inlet temperature:

45/50 °C.(3) Pressure level in open field at 1 m distance.

(4) Performances are out of scope Eurovent FCP.In order to select the EBH or EDS ducted fancoil with District Cooling coils, please use the EURAPO software for selection.

C

A

F

134

B

134

D

31,5

E

21

91,5H

200

350

G

78,2

I

Model A B C D E F G H I Connections Spigots

020÷030 990 902 408 927 366 634 963 307 404 G 1/2” F 3

040÷050 1240 902 408 1177 366 634 1213 300 404 G 1/2” F 4

060÷070 1635 1160 518 1572 476 892 1608 311 514 G 1” M 5

Dimensions [mm] EBH UNIT

Model A B C D E F G H I Connections

004 882 742 924 390 799 250 855 306 798 G 3/4” M

006÷008 1007 867 1049 390 924 250 855 306 798 G 3/4” M

020÷030 1132 992 1174 440 1049 300 855 357 798 G 3/4” M

040÷050 1382 1242 1424 440 1299 300 855 357 798 G 3/4” M

060÷070 1777 1637 1819 550 1694 410 1030 467 978 G 1” M

Dimensions [mm] EDS UNIT

OPTIONAL PLENUM

EST

W80%

70%

60%

50%

40%

30%

20%

10%

0%

W80%

70%

60%

50%

40%

30%

20%

10%

0%

EST (Energy Saving Technology) is applied to the EURAPO fan coil units and cassette units. It permits to

obtain extremely low electrical absorption and a continuous modulation of the air flow, constantly related to

the concrete need of energy in the room.

EST technology is composed by a brushless motor combined to a dedicated electronic device (inverter),

managed by specific regulators developed by EURAPO.

In comparison to the traditional units equipped with asynchronous three-speed-motors, the fan coil and

cassette units with brushless motors can obtain a considerable energy saving, by reducing the power

consumption up to 70%.

Thanks to the step-less modulation of the fan speeds it is possible to accurately regulate the air volume in a very

precise way, in strict relation to the real need of air conditioning in the room. Oscillations in the temperature

and relative humidity are reduced at lowest level: a guarantee for the highest comfort in the room.

The possibility to reach very low air volumes makes the units extremely quiet at the lowest motor revolutions.EST technology is designed in particular for offices, hospitals, nursing homes and hotels.

It is available for the EURAPO range of fan coil units, cassette units and ducted units.

6

Energy saving with EST fancoil

5 speed 4 speed 3 speed 2 speed 1

m3/h m3/h

speed 6

Asynchronous fan coil absorption (W)

EST fan coil absorption EST (W)

speed 5

speed 4

speed 3

speed 2

speed 1

STANDARD TECHNICAL DATA 50 Pa EXTERNAL STATIC PRESSURE-EST

Technical data HIGH PRESSURE UNIT EBH

STANDARD TECHNICAL DATA 50 Pa EXTERNAL STATIC PRESSURE-EST

Technical data HIGH PRESSURE UNIT EDS(1) Air temperature: 27 °C d.b.,

48% rel. humidity - Water temperature: 7/12 °C (2) Air temperature: 20 °C, 50% rel. humidity

Water inlet temperature: 45/40 °C (3) Pressure level in open field at 1 m distance.In order to select the EBH or EDS ducted fancoil with District Cooling coils, please

use the EURAPO software for selection.

Models ESTEBH ESTEBH ESTEBH ESTEBH ESTEBH

020 030 040 050 060

MAX External static pressure [Pa] 125 175 200 250 300

Total cooling capacity [kW] (1) 9 V 7,92 9,50 13,19 16,05 24,46

Heating capacity [kW] (2) 9 V 9,20 11,40 15,29 20,20 31,08

Air volume [m3/h] 9 V 1430 1981 2988 3772 4306

Sound pressure level [dB(A)] (3) 9 V 54,7 52,3 56,6 63,8 66,4

Absorbed current [A] 9 V 1,38 1,04 1,70 2,74 3,37

Power input [W] 9 V 185 232 383 617 762

N° rows (standard) 4 4 4 4 4

Power supply [V-ph-Hz] 230-1-50/60

Models ESTEDS ESTEDS ESTEDS ESTEDS ESTEDS ESTEDS ESTEDS

004 008 020 030 040 050 060

MAX External static pressure MAX [Pa] 50 50 125 175 200 250 300

Total cooling capacity [kW] (1) 9 V 3,68 5,73 8,03 9,96 9,91 13,20 25,52

Air volume [m3/h] 9 V 624 1040 1554 2191 2611 3354 4769

Sound pressure level [dB(A)] (3) 9 V 48,7 48,8 57,2 58,7 60,2 62,7 68,7

Absorbed current [A] 9 V 0,53 0,95 1,38 1,24 1,23 2,18 3,83

Power input [W] 9 V 60 114 186 279 275 488 870

N° rows (standard) 4 4 4 4 4 4 4

Power supply [V-ph-Hz] 230-1-50/60

ESTEDS unit is available for cooling operation only.

Eurapo SrlVia A. Malignani, 1233170 Pordenone - ItalyT +39 0434 572552F +39 0434 [email protected]

www.eurovent-certification.comwww.certiflash.com

District COOLING

by EURAPO6D

C030

2 - E

N18

01

As programs and technologies are always improving,

description, data and drawings must be intended as merely

indicative and can be modified without any notice.