Dynamic Voltage Restorer to allow LVRT for a DFIG Wind Turbine Christian Wessels, Fabian Gebhardt and Friedrich W. Fuchs Institute of Power Electronics and Electrical Drives Christian-Albrechts University of Kiel Kaiserstrasse 2, 24143 Kiel, Germany Email: [email protected], [email protected], [email protected] Abstract—The application of a Dynamic Voltage Restorer connected to a wind turbine driven doubly fed induction gen- erator (DFIG) is investigated. The setup allows the wind turbine system an uninterruptible fault ride through of voltage dips. The Dynamic Voltage Restorer can compensate the faulty line voltage while the DFIG wind turbine can continue its nominal operation as demanded in actual grid codes. Simulation results for a 2 MW wind turbine and measurement results on a 22 kW laboratory setup show the effectiveness of the Dynamic Voltage Restorer in comparison to the low voltage ride through of the DFIG using a crowbar which does not allow continuous reactive power production. I. I NTRODUCTION The increased amount of power from decentralised, re- newable energy systems, as especially wind energy systems, requires ambitious grid code requirements to maintain a stable and safe operation of the energy network. The grid codes cover rules considering the fault ride through behaviour as well as the steady state active power and reactive power production. The actual grid codes stipulate that wind farms should contribute to power system control like frequency and voltage control to behave similar to conventional power stations. A detailed review of grid code technical requirements regarding the connection of wind farms to the electrical power system is given in [1]. For operation during grid voltage faults it becomes clear that grid codes prescribe that wind turbines must stay connected to the grid and should support the grid by generating reactive power to support and restore quickly the grid voltage after the fault. Among the wind turbine concepts turbines using the doubly fed induction generator (DFIG) as described in [2] and [3] are dominant due to its variable speed operation, its separately controllable active and reactive power and its partially rated power converter. But, the reaction of DFIGs to grid voltage disturbances is sensitive, as described in [4] and [5] for symmetrical and unsymmetrical voltage dips, and requires additional protection for the rotor side power electronic con- verter. Conventionally a resistive network called crowbar is connected in case of rotor overcurrents or DC link overvoltages to the rotor circuit and the rotor side converter is disabled as described in [6], [7] and [8]. But the machine draws a high short circuit current when the crowbar is activated as described in [9] resulting in a large amount of reactive power drawn from the power network, which is not acceptable when considering actual grid code requirements. Thus other protection methods have to be investigated to ride through grid faults safely and fulfill the grid codes. There are several approaches limiting the rotor currents during transient grid voltage dip by changing the rotor side converters control in [10], [11] or in other publications dealing with an improved control structure during asymmetrical grid voltage conditions [12] and [13]. In all the proposed methods the control algorithms have to be changed which might be complicated or not possible in existing wind turbines. If an external power electronic device is used to protect the wind turbine system from the faulty grid, the wind turbine system can remain unchanged and continue nominal operation and standard control. Such a system is called a Dynamic Voltage Restorer (DVR), which is a voltage source converter connected by a coupling transformer in series to the grid to correct deteriorated line voltages to reduce possible problems on a sensitive load. In [14] different DVR topologies are compared with respect to rating in power and voltage. Control structures based on resonant controllers to compensate unsymmetrical voltages are presented in [15] and [16]. In this paper the application of a DVR connected to a wind turbine driven DFIG to allow uninterruptible fault ride through of voltage dips fulfilling the grid code requirements is investi- gated. The DVR can compensate the faulty line voltage while the DFIG wind turbine can continue its nominal operation as demanded in actual grid codes. A DVR to protect a DFIG wind turbine has been presented in [17], but only symmetrical voltage dips have been investigated, and in [18], but the reactive power is not considered and measurement results do not cover transient grid faults. Here, also unsymmetrical faults are investigated and measurement results under transient grid voltage dips on a 22 kW laboratory setup are presented. The paper is structured as follows. In section II the wind turbine system and the overall control structure, using a DFIG protected from grid faults by a DVR, is described. Simulation results for a 2 MW wind turbine in section IV and measurement results on a 22 kW laboratory test bench in section V show the effectiveness of the proposed technique in comparison to the low voltage ride through of the DFIG using a crowbar. A conclusion closes the paper. 978-1-4244-6391-6/10/$26.00 ゥ2010 IEEE 803

Upload: others

Post on 10-Apr-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Dynamic Voltage Restorer to allow Low Voltage Ride Through

Dynamic Voltage Restorer to allow LVRT

for a DFIG Wind Turbine

Christian Wessels, Fabian Gebhardt and Friedrich W. Fuchs

Institute of Power Electronics and Electrical Drives

Christian-Albrechts University of Kiel

Kaiserstrasse 2, 24143 Kiel, Germany

Email: [email protected], [email protected], [email protected]

Abstract—The application of a Dynamic Voltage Restorerconnected to a wind turbine driven doubly fed induction gen-erator (DFIG) is investigated. The setup allows the wind turbinesystem an uninterruptible fault ride through of voltage dips.The Dynamic Voltage Restorer can compensate the faulty linevoltage while the DFIG wind turbine can continue its nominaloperation as demanded in actual grid codes. Simulation resultsfor a 2 MW wind turbine and measurement results on a 22 kWlaboratory setup show the effectiveness of the Dynamic VoltageRestorer in comparison to the low voltage ride through of theDFIG using a crowbar which does not allow continuous reactivepower production.

I. INTRODUCTION

The increased amount of power from decentralised, re-

newable energy systems, as especially wind energy systems,

requires ambitious grid code requirements to maintain a stable

and safe operation of the energy network. The grid codes

cover rules considering the fault ride through behaviour as

well as the steady state active power and reactive power

production. The actual grid codes stipulate that wind farms

should contribute to power system control like frequency

and voltage control to behave similar to conventional power

stations. A detailed review of grid code technical requirements

regarding the connection of wind farms to the electrical power

system is given in [1]. For operation during grid voltage faults

it becomes clear that grid codes prescribe that wind turbines

must stay connected to the grid and should support the grid

by generating reactive power to support and restore quickly

the grid voltage after the fault.

Among the wind turbine concepts turbines using the doubly

fed induction generator (DFIG) as described in [2] and [3] are

dominant due to its variable speed operation, its separately

controllable active and reactive power and its partially rated

power converter. But, the reaction of DFIGs to grid voltage

disturbances is sensitive, as described in [4] and [5] for

symmetrical and unsymmetrical voltage dips, and requires

additional protection for the rotor side power electronic con-

verter.

Conventionally a resistive network called crowbar is connected

in case of rotor overcurrents or DC link overvoltages to

the rotor circuit and the rotor side converter is disabled as

described in [6], [7] and [8]. But the machine draws a high

short circuit current when the crowbar is activated as described

in [9] resulting in a large amount of reactive power drawn from

the power network, which is not acceptable when considering

actual grid code requirements. Thus other protection methods

have to be investigated to ride through grid faults safely and

fulfill the grid codes.

There are several approaches limiting the rotor currents during

transient grid voltage dip by changing the rotor side converters

control in [10], [11] or in other publications dealing with an

improved control structure during asymmetrical grid voltage

conditions [12] and [13].

In all the proposed methods the control algorithms have to

be changed which might be complicated or not possible in

existing wind turbines. If an external power electronic device

is used to protect the wind turbine system from the faulty grid,

the wind turbine system can remain unchanged and continue

nominal operation and standard control. Such a system is

called a Dynamic Voltage Restorer (DVR), which is a voltage

source converter connected by a coupling transformer in series

to the grid to correct deteriorated line voltages to reduce

possible problems on a sensitive load. In [14] different DVR

topologies are compared with respect to rating in power and

voltage. Control structures based on resonant controllers to

compensate unsymmetrical voltages are presented in [15] and

[16].

In this paper the application of a DVR connected to a wind

turbine driven DFIG to allow uninterruptible fault ride through

of voltage dips fulfilling the grid code requirements is investi-

gated. The DVR can compensate the faulty line voltage while

the DFIG wind turbine can continue its nominal operation as

demanded in actual grid codes. A DVR to protect a DFIG

wind turbine has been presented in [17], but only symmetrical

voltage dips have been investigated, and in [18], but the

reactive power is not considered and measurement results do

not cover transient grid faults. Here, also unsymmetrical faults

are investigated and measurement results under transient grid

voltage dips on a 22 kW laboratory setup are presented.

The paper is structured as follows. In section II the wind

turbine system and the overall control structure, using a

DFIG protected from grid faults by a DVR, is described.

Simulation results for a 2 MW wind turbine in section IV

and measurement results on a 22 kW laboratory test bench in

section V show the effectiveness of the proposed technique in

comparison to the low voltage ride through of the DFIG using

a crowbar. A conclusion closes the paper.

978-1-4244-6391-6/10/$26.00 ©2010 IEEE 803

Page 2: Dynamic Voltage Restorer to allow Low Voltage Ride Through

Fig. 1. Schematic diagram of DFIG wind turbine system with dynamic voltage restorer

II. DFIG ELECTRICAL SYSTEM AND CONTROL

The investigated wind turbine system shown in Fig. 1

consists of the basic components like the turbine, a gear (in

most systems), a DFIG generator and a back-to-back voltage

source converter with a DC link. A DC-chopper to limit

the DC voltage across the DC capacitor and a crowbar are

included. The back-to-back converter consists of a rotor side

converter (RSC) and a line side converter (LSC) connected

to the grid by a line filter to reduce the harmonics caused

by the converter. A Dynamic Voltage Restorer is included to

protect the wind turbine from voltage disturbances. Due to the

short period of time of voltage disturbances the dynamics of

the mechanical part of the turbine will be neglected and the

mechanical torque brought in by the wind is assumed to be

constant.

A. RSC control

The RSC provides decoupled control of stator active and

reactive power. A cascade vector control structure with inner

current control loops is applied. The overall control structure

is shown in Fig. 2. The mathematical model of the DFIG has

been well documented in literature [4] and will only briefly

be discussed here. From the per-phase equivalent circuit of the

DFIG in an arbitrary reference frame rotating at synchronous

angular speed ωs the following stator and rotor voltage and

flux equations can be derived.

Vs = RsIs + Ls

dIs

dt+ Lh

dIr

dt+ jωsψs (1)

Vr = RrIr + Lr

dIr

dt+ Lh

dIs

dt+ jωslipψr (2)

ψs = LsIs + LhIr (3)

ψr = LrIr + LhIs (4)

where ψ,U and I represent the flux, voltage and current vec-

tors respectively. Subscripts s and r denote the stator and rotor

quantities respectively. Ls = Lsσ + Lh and Lr = Lrσ + Lh

represent the stator and rotor inductance, Lh is the mutual

inductance, Rs and Rr are the stator and rotor resistances and

ωslip is the slip angular frequency ωslip = ωs − ωmech.

The rotor currents are controlled by the rotor side voltage

source converter. Substituting Is = ψs/Ls − (Lh/Ls)Ir

from (3) in (2) and assuming the stator flux to be constant

(dψs/dt = 0) yields the rotor voltage equation

Vr = RrIr + σLr

dIr

dt+ jωslipψr (5)

that is used to design the inner current loop controllers,

where jωslipψr is used as decoupling term. When adopting

stator voltage oriented control (SVO) a decomposition in d,q

components is performed (Vsq = 0). Neglecting the stator

resistive voltage drop the stator output active and reactive

powers are expressed as

Ps ≈

3

2

Lh

Ls

VsdIrd (6)

Qs ≈ −

3

2

Vsd

Ls

(Vsd

ωs

+ LhIrq) (7)

thus the stator active and reactive power can be controlled

independently, controlling the d and q components of the rotor

current. Based on equation (6) and (7) the outer power control

loops are designed.

B. LSC control

The line side converter controls the DC voltage VDC and

provides reactive power support. A voltage oriented cascade

vector control structure with inner current control loops is also

applied (see Fig. 2 right). The line current Il can be controlled

by adjusting the voltage drop across the line inductance Ll

giving the following dynamics

Vs = RlIl + Ll

dIl

dt(8)

used to design the current controller, while the DC voltage

dynamics can be expressed by

CDC

dVDC

dt= IDC − Iload (9)

used to design the outer DC voltage control loop, where CDC

is the DC capacitance and IDC and Iload are the DC currents

on LSC and RSC side, respectively.

C. Crowbar protection

To protect the rotor side converter from tripping due to

overcurrents in the rotor circuit or overvoltage in the DC link

during grid voltage dips a crowbar is installed in conventional

DFIG wind turbines, which is a resistive network that is

connected to the rotor windings of the DFIG. The crowbar

804

Page 3: Dynamic Voltage Restorer to allow Low Voltage Ride Through

PWM

PWM

dq

d,q

a,b,c

a,b,c

Il,dq

VDC

V

VDC

V , Q

controlDC

DC

*PI currentcontrol

PI currentcontrol

PLLVs,abc

Vs,dq

Vr,abcVr,dq

wmech

wmech

wmech

Is,abc

Ir,abc

Il,abc

DFIG

RSC

DVR

CB

LSC

PWM

dq

dq

dq

abc

abc

abcIR,dq

Ir,dq*

gr

Qs

Qs Q ,S wmech

control

Grid

Q ,s

calculation

gr

RSC controller

LSC controller

DVR controller

gr

gl

gl

P+Res voltagecontroller

Voltage referencegenerator

*

*

* *

Q*

Fig. 2. Schematic diagram of DFIG wind turbine and Dynamic Voltage Restorer control structure

limits the voltages and provides a safe route for the currents

by bypassing the rotor by a set of resistors. When the crowbar

is activated the rotor side converters pulses are disabled and

the machine behaves like a squirrel cage induction machine

directly coupled to the grid. The magnetization of the machine

that was provided by the RSC in nominal condition is lost and

the machine absorbs a large amount of reactive power from

the stator and thus from the network [9], which can further

reduce the voltage level and is not allowed in actual grid codes.

Triggering of the crowbar circuit also means high stress to the

mechanical components of the system as the shaft and the

gear. Detailed analyses on the DFIG behavior during voltage

dip and crowbar protection can be found in [6] and [9]. Thus,

from network and from machine mechanical point of view a

crowbar triggering should be avoided.

Anyway, to compare the presented technique here with a con-

ventional DFIG wind turbine system protected by a crowbar

circuit, simulation results including crowbar protection are

examined. Therefore the crowbar resistance is designed. The

value of the crowbar resistance should be chosen carefully.

There are two requirements that give an upper and a lower

limit to the crowbar resistance. It should be high enough

to limit the short circuit rotor current and it should be low

enough to avoid too high voltage in the rotor circuit. If the

voltage across the crowbar terminals rises above the DC-

link voltage of the RSC high currents will flow through

the antiparallel diodes of the converter. Appropriate crowbar

resistances are designed in [8] and [9]. A crowbar resistance

of Rcrow = 50Rr is used in the simulations done here. In

simulation and in the laboratory setup a passive crowbar circuit

is used that is triggered by a rotor overcurrent. The crowbar

can be disabled manually by the user when safe circumstances

are reestablished.

III. DVR ELECTRICAL SYSTEM AND CONTROL

A Dynamic Voltage Restorer is a voltage source converter.

Usually it is coupled via line filter (usually LC type) and a cou-

pling transformer in series to the grid to correct deteriorated

line voltages to reduce possible problems on a sensitive load

or generator. In [14] different DVR topologies are compared

with respect to rating in power and voltage. For control a

closed loop control in the rotating dq reference frame is

introduced but identified as unsuitable for the compensation

of unsymmetrical grid faults. Because the majority of faults

on a power system are unbalanced in nature which results in

unbalanced voltages, appropriate generation of unsymmetrical

compensation voltage components by the DVR is an important

feature. Thus, in [15] stationary-frame controllers for DVR

implementation are designed to achieve good positive- and

negative-sequence voltage regulation. The cascade control

structure includes inner proportional current controllers and

as outer voltage controllers a proportional + resonant (P+Res)

controller is compared to a H∞ controller. In [16] multiloop

controllers using a similar control structure with outer P+Res

voltage controllers and an inner PID curent controllers with

filter capacitor voltage feedback are presented. Both control

structures have good steady-state sinusoidal error tracking

of the positive and negative sequence voltage components.

Anyway, [18] describes that DVR current control is inadequate

if DFIG is current controlled too. Therefore, P+Res voltage

controllers controlling directly the voltage across the filter

capacitors without inner current controllers are used here.

IV. SIMULATION RESULTS

To show the effectiveness of the proposed technique sim-

ulations have been performed using MATLAB/Simulink and

PLECS for a 2 MW DFIG wind turbine system and a DVR

as shown in Fig. 1. The simulation parameters are given in

the appendix. The control structure as shown in Fig. 2 is im-

plemented in Simulink while all power electronic components

are modelled in PLECS.

The system performance of the DFIG is shown in Fig. 3

protected by the conventional crowbar and in Fig. 4 protected

by the DVR during a two phase 37 % voltage dip of 100 ms

duration (see Fig. 3,4 a)). The DFIG reacts with high stator

currents Is and thus high rotor currents are induced in the rotor

circuit. When the rotor currents exceed the maximum level

the crowbar is triggered to protect the RSC from overcurrents

IRSC (Fig. 3 e),f)). Due to the unsymmetrical nature of voltage

fault the voltage oriented control of the RSC controller is

805

Page 4: Dynamic Voltage Restorer to allow Low Voltage Ride Through

Fig. 3. Simulation of DFIG performance with Crowbar protection during 10% single phase voltage dip a) line voltage b) stator voltage c) stator currentd) rotor side converter current e) crowbar current f) active and reactive statorpower g) mechanical speed h) DVR voltage i) active and reactive DVR power

not able to stabilize the rotor currents and the crowbar has

to stay activated during the voltage dip. When the voltage

level has been reestablished and transients have decayed, the

crowbar can be deactivated, which is not shown here. When

the RSC is in operation the machine magnetization is provided

by the rotor but when the crowbar is triggered the RSC is

disabled and the machine excitation is shifted to the stator.

Thus, reactive power control cannot be provided during the

Fig. 4. Simulation of DFIG performance with DVR protection during 10% single phase voltage dip a) line voltage b) stator voltage c) stator currentd) rotor side converter current e) crowbar current f) active and reactive statorpower g) mechanical speed h) DVR voltage i) active and reactive DVR power

voltage dip (see Fig. 3 h)) without other additional measures

which is not acceptable when considering the grid codes. The

machine can not generate enough torque so that the rotor

accelerates, which can lead to disconnection of the turbine

due to overspeed. The DVR is not activated in the simulations

shown in Fig. 3.

When the wind turbine system is protected by the DVR as

shown in Fig. 4 the voltage dip can almost be compensated

806

Page 5: Dynamic Voltage Restorer to allow Low Voltage Ride Through

Fig. 5. Measurement results for DFIG with crowbar protection; a) statorvoltages, b) stator currents and c) rotor currents

(Fig. 4 c)). The DFIG response is much less critical, which

means lower stator overcurrents and rotor overcurrents are

produced so that the crowbar does not have to be triggered

(Fig. 4 d),e),f)). Note, that although the stator voltage dip

is fairly well compensated a slight distortion in the stator

currents (DC components) and thus disturbed rotor currents

can be observed. In Fig. 4 i) the DVR power to compensate

the voltage dip is shown. It becomes clear that the active power

that can not be fed into the faulty grid during grid fault must

be consumed by the DVR.

V. MEASUREMENT RESULTS

Measurement results are taken at a 22 kW DFIG wind

turbine test bench and a 30 kVA Dynamic Voltage Restorer

connected in series to the grid. The DVR converter is based on

three single-phase full-bridge voltage-source converters using

a common dc link (see Fig. 1). These converters are series

coupled into the supply using three single-phase transformers.

A LC line filter is located at the converter side to filter out the

switching harmonics generated by the converter. The dc link is

charged with a passive six-pulse diode bridge and protected by

a DC chopper. In the laboratory setup the DVR is connected

only to the stator of the machine; the LSC is connected to a

separate faultless grid. Both the RSC and the LSC are 2-level

PWM converters consisting of IGBT modules connected to a

DC capacitor. The schematic diagram of the laboratory setup

is similar to the one shown in Fig. 1. The DFIG is driven by

an industrial 18,5 kW induction machine drive to emulate the

wind. The two phase 37 % grid voltage dip (from 330 V to 125

V) of 100 ms duration is generated by a transformer based

voltage sag generator as described in [19]. In all laboratory

tests the grid voltage level has been lowered to 330 V (line to

Fig. 6. Measurement results for DFIG with DVR protection; a) line voltage,b) DVR voltage, c) stator voltage, d) stator currents and e) rotor currents

line) by a separate transformer to avoid saturation problems

in the series connected transformers of the DVR. The results

have been recorded with a Dewetron data acquisition device.

For both tests the DFIG is operated supersynchronous with a

slip of s = 0,2 (mechanical speed of 1800 r/min) feeding an

active stator power of Ps = 10 kW to the grid.

Without DVR the RSC of the DFIG must be protected by

the crowbar from overcurrents as shown in Fig. 5 c) where

the crowbar is trigerred when the rotor currents exceed the

critical limit of Ir = 80 A. The stator currents contain DC

components and the rotor currents have ωmech = 60 Hz

components superimposed. The rotor currents decay with the

stator time constant of τs ≈ Lh/Rs = 330 ms. Note that this

duration is much shorter than in the simulation results, where

the stator time constant of the 2 MW machine is τs ≈ Lh/Rs

= 1,85 s. When the voltage dip is cleared after 100 ms

high stator currents are generated and the machine continues

with inductive reactive power consumption (stator currents are

807

Page 6: Dynamic Voltage Restorer to allow Low Voltage Ride Through

lagging stator voltages) that leads to a slight decrease of stator

voltage amplitude.

The same two phase voltage dip is investigated and shown in

Fig. 6 but here the DFIG is protected by the series connected

DVR. Before the voltage dip at nominal operation the DVR

does not compensate the line voltage. The DVR voltages

are only slightly distorted by the grid voltage harmonics of

the laboratory grid. When the voltage dip occurs the DVR

compensates the missing voltage in the two phases (Fig.6 b))

so that the stator voltage (Fig.6 c)) is only slightly affected by

the line voltage dip. No mentionary overcurrents are generated

in the stator currents or rotor currents and the DFIG can

directly continue its nominal operation feeding active power.

Note, that during grid voltage compensation the active power

generated by the DFIG must be absorbed by the DVR and is

choppered in the DC link.

As the result one can conclude that the DVR can fully

protect the DFIG system from grid voltage dips to allow

uninterruptible low voltage ride through.

VI. CONCLUSION

The application of a Dynamic Voltage Restorer connected

to a wind turbine driven doubly fed induction generator to

allow uninterruptible fault ride through of voltage dips is

investigated. The Dynamic Voltage Restorer can compensate

the faulty line voltage while the DFIG wind turbine can

continue its nominal operation as demanded in actual grid

codes. Simulation results for a 2 MW wind turbine show

the effectiveness of the proposed technique in comparison to

the low voltage ride through of the DFIG using a crowbar

where continuous reactive power production is problematic.

The proposed technique is verified by measurement results on

a 22 kW DFIG setup protected by a Dynamic Voltage Restorer.

APPENDIX

TABLE ISIMULATION AND EXPERIMENTAL PARAMETERS

Simulation Parameters

Symbol Quantity Value

Uline low voltage level (phase-to-phase, rms) 690 V

ω Line angular frequency 2 π 50 Hz

PDF IG Wind turbine rated power 2 MW

i stator to rotor transmission ratio 1

n Rated speed 1800 r/min

Lh mutual inductance 3,7 mH

Rs, Rr, stator and rotor resistance 2 mΩ

Rcrowbar crowbar resistance 0,1 Ω

Experimental Parameters

Symbol Quantity Value

Uline grid voltage (phase-to-phase, rms) 330 V

ωs Line angular frequency 2 π 50 Hz

PDF IG DFIG rated power 22 kW

Ptest DFIG experimental test power 10 kW

nmech Operation speed 1800 r/min

i stator to rotor transmission ratio 1,5

Lh mutual inductance 37,13 mH

Rs stator resistance 112 mΩ

Rcrowbar crowbar resistance 2,7 Ω

fs switching frequency for LSC and RSC 5 kHz

VDC DVR DC voltage 560 V

n series transformer ratio (DVR to line)√

3

CDC DVR DC link capacitance 7,5 mF

REFERENCES

[1] M. Tsili and S. Papathanassiou, “A review of grid code technicalrequirements for wind farms,” Renewable Power Generation, IET, vol. 3,no. 3, pp. 308–332, Sept. 2009.

[2] R. Pena, J. Clare, and G. Asher, “Doubly fed induction generator usingback-to-back pwm converters and its application to variable-speed wind-energy generation,” Electric Power Applications, IEE Proceedings -, vol.143, no. 3, pp. 231–241, May 1996.

[3] S. Muller, M. Deicke, and R. De Doncker, “Doubly fed inductiongenerator systems for wind turbines,” Industry Applications Magazine,

IEEE, vol. 8, no. 3, pp. 26–33, May/Jun 2002.[4] J. Lopez, P. Sanchis, X. Roboam, and L. Marroyo, “Dynamic behavior

of the doubly fed induction generator during three-phase voltage dips,”Energy Conversion, IEEE Transactions on, vol. 22, no. 3, pp. 709–717,Sept. 2007.

[5] J. Lopez, E. Gubia, P. Sanchis, X. Roboam, and L. Marroyo, “Windturbines based on doubly fed induction generator under asymmetricalvoltage dips,” Energy Conversion, IEEE Transactions on, vol. 23, no. 1,pp. 321–330, March 2008.

[6] S. Seman, J. Niiranen, and A. Arkkio, “Ride-through analysis of dou-bly fed induction wind-power generator under unsymmetrical networkdisturbance,” Power Systems, IEEE Transactions on, vol. 21, no. 4, pp.1782–1789, Nov. 2006.

[7] L. Peng, B. Francois, and Y. Li, “Improved crowbar control strategy ofdfig based wind turbines for grid fault ride-through,” Applied Power

Electronics Conference and Exposition, 2009. APEC 2009. Twenty-

Fourth Annual IEEE, pp. 1932–1938, Feb. 2009.[8] W. Zhang, P. Zhou, and Y. He, “Analysis of the by-pass resistance of an

active crowbar for doubly-fed induction generator based wind turbinesunder grid faults,” Electrical Machines and Systems, 2008. ICEMS 2008.

International Conference on, pp. 2316–2321, Oct. 2008.[9] J. Morren and S. de Haan, “Short-circuit current of wind turbines with

doubly fed induction generator,” Energy Conversion, IEEE Transactions

on, vol. 22, no. 1, pp. 174–180, March 2007.[10] K. Lima, A. Luna, P. Rodriguez, E. Watanabe, R. Teodorescu, and

F. Blaabjerg, “Doubly-fed induction generator control under voltagesags,” Energy 2030 Conference, 2008. ENERGY 2008. IEEE, pp. 1–6,Nov. 2008.

[11] J. Liang, W. Qiao, and R. Harley, “Direct transient control of windturbine driven dfig for low voltage ride-through,” in Power Electronics

and Machines in Wind Applications, 2009. PEMWA 2009. IEEE, June2009, pp. 1–7.

[12] O. Gomis-Bellmunt, A. Junyent-Ferre, A. Sumper, and J. Bergas-Jan, “Ride-through control of a doubly fed induction generator underunbalanced voltage sags,” Energy conversion, IEEE Transactions on,vol. 23, no. 4, pp. 1036–1045, Dec. 2008.

[13] L. Xu, “Coordinated control of dfig’s rotor and grid side convertersduring network unbalance,” Power Electronics, IEEE Transactions on,vol. 23, no. 3, pp. 1041–1049, May 2008.

[14] J. Nielsen and F. Blaabjerg, “A detailed comparison of system topologiesfor dynamic voltage restorers,” Industry Applications, IEEE Transactions

on, vol. 41, no. 5, pp. 1272–1280, Sept.-Oct. 2005.[15] Y. W. Li, F. Blaabjerg, D. Vilathgamuwa, and P. C. Loh, “Design and

comparison of high performance stationary-frame controllers for dvrimplementation,” Power Electronics, IEEE Transactions on, vol. 22,no. 2, pp. 602–612, March 2007.

[16] F. Marafao, D. Colon, J. Jardini, W. Komatsu, L. Matakas, M. Galassi,S. Ahn, E. Bormio, J. Camargo, T. Monteiro, and M. Oliveira, “Multi-loop controller and reference generator for a dynamic voltage restorerimplementation,” in Harmonics and Quality of Power, 2008. ICHQP

2008. 13th International Conference on, 28 2008-Oct. 1 2008, pp. 1–6.[17] C. Wessels and F. Fuchs, “High voltage ride through with facts for dfig

based wind turbines,” in Power Electronics and Applications, 2009. EPE

’09. 13th European Conference on, Sept. 2009, pp. 1–10.[18] A. O. Ibrahim, T. H. Nguyen, D.-C. Lee, and S.-C. Kim, “Ride-through

strategy for dfig wind turbine systems using dynamic voltage restorers,”in Energy Conversion Congress and Exposition, 2009. ECCE. IEEE,Sept. 2009, pp. 1611–1618.

[19] C. Wessels, T. Wehrend, and F. W. Fuchs, “Transformer based voltagesag generator to test renewable energy systems during grid faults in thelaboratory,” in EPE Wind Energy Chapter Symposium 2010, April 2010.