DT3000 to EDR-3000 Retrofit Guide

Upload: others

Post on 21-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

DT3000 to EDR-3000 Retrofit

Guide

Page 2: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Replacement Catalog Number

• EDR-3000-2C0BA1

– 4DI, 4RO, ZI

– Projection Mount

– RS-485, Modbus RTU, DNP3.0

• See Tech Data for other

communications options

• ER-IQRETROKIT

– Mounting filler plate

Page 3: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Rear Connections

DT3000

Page 4: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

DT3000 Typical Schematic

Page 5: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

EDR-3000 Typical Schematic

Current Demand alarm

on RO2

Page 6: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

DT to EDR Zero Sequence Ground

DT3000 EDR-3000

Page 7: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

DT to EDR Residual Ground

DT3000 EDR-3000

Page 8: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

DT3000 Phase/Ground Settings

• Time Overcurrent

– Curve shape

– Pickup (x In)

– Time multiplier

• Short Delay

– Pickup (x In)

– Time

• Instantaneous

– Pickup (x In)

Page 9: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

DT3000 System Settings

• Discriminator (11X Inst)

• High Load Time (85% of TOC pickup)

• Frequency

• Phase CT ratio

• Ground CT ratio

Page 10: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Settings Sheet

Start with setting file – “EDR-3000 From DT3000 Retrofit Template.ErPara”

DT3000 Parameter Value

EDR-3000

Parameter Value Menu Location Note

Phase

Time Overcurrent 51P[1] Function - Active Protection Para/Set 1 Should always be Active

Curve shape Curve Shape Select from List Protection Para/Set 1/51P[1]

Pickup (x In) Pickup 0.02 - 4.00 X In Protection Para/Set 1/51P[1]

Time multiplier t-multiplier Depends on curve Protection Para/Set 1/51P[1] For thermal curves (Flat, IT, I2T, I4T) multiply DT time multiplier by 5 to get equivalent EDR multiplier

Short Delay 50P[2] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired

Pickup (x In) Pickup 0.02 - 40.00 In Protection Para/Set 1/50P[2]

Time t 0.00 - 300.00s Protection Para/Set 1/50P[2]

Instantaneous 50P[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired

Pickup (x In) Pickup 0.02 - 40.00 In Protection Para/Set 1/50P[1]

Ground

Time Overcurrent 51X[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired

Curve shape Curve Shape Select from List Protection Para/Set 1/51X[1]

Pickup (x In) Pickup 0.02 - 4.00 X In Protection Para/Set 1/51X[1]

Time multiplier t-multiplier Depends on curve Protection Para/Set 1/51X[1] For thermal curves (Flat, IT, I2T, I4T) multiply DT time multiplier by 5 to get equivalent EDR multiplier

Short Delay 50X[2] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired

Pickup (x In) Pickup 0.02 - 20.00 In Protection Para/Set 1/50X[2]

Time t 0.00 - 300.00s Protection Para/Set 1/50X[2]

Instantaneous 50X[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired

Pickup (x In) Pickup 0.02 - 20.00 In Protection Para/Set 1/50X[1] DT allows setting of discriminator only if pickup is set to none

System

Discriminator (11X Inst) 50P[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired

Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1]

High Load Time Current Demand Alarm SysA/Demand/Current Demand Set Demand level and time delay (DT is 85% of TOC pickup)

Frequency f 50/60 Hz System Para/General Settings Default - 60Hz

Phase CT ratio CT pri 1 - 50000 A System Para/General Settings 5A secondary

Ground CT ratio XCT pri 1 - 50000 A System Para/General Settings 5A secondary

Zone Interlocking - Phase NA - Wiring Zone Out/Zone Trip Phase or Both Protection Para/Set 1/ZI Enable ZI function under General Settings

Zone Interlocking - Ground NA - Wiring Zone Out/Zone Trip Ground or Both Protection Para/Set 1/ZI Enable ZI function under General Settings

Page 11: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Phase Time Overcurrent

Pickup (x In)

Curve shape

Time multiplier

Phase Time Overcurrent

DT3000 Parameter

Note: For thermal curves (Flat, IT, I2T, I4T) divide DT

time multiplier by 5 to get equivalent EDR multiplier

Page 12: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Phase Short Delay

Pickup (x In)

Time

Short Delay

DT3000 Parameter

Pickup =NONE= Inactive

Set Function Active if this

protection is desired

Page 13: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Phase Instantaneous

Pickup (x In)

Time = 0

Instantaneous

DT3000 Parameter

Pickup =NONE= Inactive

Set Function Active if this

protection is desired

Page 14: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Discriminator

Pickup = 11 (x In)

Time = 0

Discriminator

DT3000 ParameterDiscriminator =Doff= Inactive

Also known as a making current release, the discriminator in the DT-3000 is active for 10 cycles

after the breaker closes. The EDR-3000 has a similar function called Switch on to Fault (SOTF)

with a selectable time.

Maximum setting to prevent

tripping after delay

Adaptive setting only active

during SOTF time

Set SOTF function to

“Active” to enable Inst

Pickup during this time after

breaker close.

Set Function Active if this

protection is desired

Page 15: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Ground Time Overcurrent

Pickup (x In)

Curve shape

Time multiplier

Ground Time Overcurrent

Pickup =NONE= Inactive

DT3000 Parameter

Set Function Active if this

protection is desired

Note: For thermal curves (Flat, IT, I2T, I4T) divide DT

time multiplier by 5 to get equivalent EDR multiplier

Page 16: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Ground Short Delay

Pickup (x In)

Time

Short Delay

DT3000 Parameter

Pickup =NONE= Inactive

Set Function Active if this

protection is desired

Page 17: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

Ground Instantaneous

Pickup (x In)

Time = 0

Instantaneous

DT3000 Parameter

Pickup =NONE= Inactive

Set Function Active if this

protection is desired

Page 18: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

EDR-3000 System Settings EDR-3000 System Para/General Settings Menu

Frequency

Phase CT ratio

Ground CT ratio

Program with Breaker Open/Closed (Dip Switch S2)

DT3000 Parameter

Page 19: DT3000 to EDR-3000 retrofit guide...Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1] High Load Time Current Demand Alarm SysA/Demand/Current

High Load Alarm

High Load Time

High Load (set at .85*51P[1] pickup)

DT3000 Parameter

(output contact RO2 Terminals – X2-5, X2-6)