DT3000 to EDR-3000 Retrofit
Guide
Replacement Catalog Number
• EDR-3000-2C0BA1
– 4DI, 4RO, ZI
– Projection Mount
– RS-485, Modbus RTU, DNP3.0
• See Tech Data for other
communications options
• ER-IQRETROKIT
– Mounting filler plate
Rear Connections
DT3000
DT3000 Typical Schematic
EDR-3000 Typical Schematic
Current Demand alarm
on RO2
DT to EDR Zero Sequence Ground
DT3000 EDR-3000
DT to EDR Residual Ground
DT3000 EDR-3000
DT3000 Phase/Ground Settings
• Time Overcurrent
– Curve shape
– Pickup (x In)
– Time multiplier
• Short Delay
– Pickup (x In)
– Time
• Instantaneous
– Pickup (x In)
DT3000 System Settings
• Discriminator (11X Inst)
• High Load Time (85% of TOC pickup)
• Frequency
• Phase CT ratio
• Ground CT ratio
Settings Sheet
Start with setting file – “EDR-3000 From DT3000 Retrofit Template.ErPara”
DT3000 Parameter Value
EDR-3000
Parameter Value Menu Location Note
Phase
Time Overcurrent 51P[1] Function - Active Protection Para/Set 1 Should always be Active
Curve shape Curve Shape Select from List Protection Para/Set 1/51P[1]
Pickup (x In) Pickup 0.02 - 4.00 X In Protection Para/Set 1/51P[1]
Time multiplier t-multiplier Depends on curve Protection Para/Set 1/51P[1] For thermal curves (Flat, IT, I2T, I4T) multiply DT time multiplier by 5 to get equivalent EDR multiplier
Short Delay 50P[2] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired
Pickup (x In) Pickup 0.02 - 40.00 In Protection Para/Set 1/50P[2]
Time t 0.00 - 300.00s Protection Para/Set 1/50P[2]
Instantaneous 50P[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired
Pickup (x In) Pickup 0.02 - 40.00 In Protection Para/Set 1/50P[1]
Ground
Time Overcurrent 51X[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired
Curve shape Curve Shape Select from List Protection Para/Set 1/51X[1]
Pickup (x In) Pickup 0.02 - 4.00 X In Protection Para/Set 1/51X[1]
Time multiplier t-multiplier Depends on curve Protection Para/Set 1/51X[1] For thermal curves (Flat, IT, I2T, I4T) multiply DT time multiplier by 5 to get equivalent EDR multiplier
Short Delay 50X[2] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired
Pickup (x In) Pickup 0.02 - 20.00 In Protection Para/Set 1/50X[2]
Time t 0.00 - 300.00s Protection Para/Set 1/50X[2]
Instantaneous 50X[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired
Pickup (x In) Pickup 0.02 - 20.00 In Protection Para/Set 1/50X[1] DT allows setting of discriminator only if pickup is set to none
System
Discriminator (11X Inst) 50P[1] Function - Active Protection Para/Set 1 Set Function Active if this protection is desired
Pickup 11 In Protection Para/Set 1/50P[1] Adaptive Setting Based on SOTF in Global 50P[1]
High Load Time Current Demand Alarm SysA/Demand/Current Demand Set Demand level and time delay (DT is 85% of TOC pickup)
Frequency f 50/60 Hz System Para/General Settings Default - 60Hz
Phase CT ratio CT pri 1 - 50000 A System Para/General Settings 5A secondary
Ground CT ratio XCT pri 1 - 50000 A System Para/General Settings 5A secondary
Zone Interlocking - Phase NA - Wiring Zone Out/Zone Trip Phase or Both Protection Para/Set 1/ZI Enable ZI function under General Settings
Zone Interlocking - Ground NA - Wiring Zone Out/Zone Trip Ground or Both Protection Para/Set 1/ZI Enable ZI function under General Settings
Phase Time Overcurrent
Pickup (x In)
Curve shape
Time multiplier
Phase Time Overcurrent
DT3000 Parameter
Note: For thermal curves (Flat, IT, I2T, I4T) divide DT
time multiplier by 5 to get equivalent EDR multiplier
Phase Short Delay
Pickup (x In)
Time
Short Delay
DT3000 Parameter
Pickup =NONE= Inactive
Set Function Active if this
protection is desired
Phase Instantaneous
Pickup (x In)
Time = 0
Instantaneous
DT3000 Parameter
Pickup =NONE= Inactive
Set Function Active if this
protection is desired
Discriminator
Pickup = 11 (x In)
Time = 0
Discriminator
DT3000 ParameterDiscriminator =Doff= Inactive
Also known as a making current release, the discriminator in the DT-3000 is active for 10 cycles
after the breaker closes. The EDR-3000 has a similar function called Switch on to Fault (SOTF)
with a selectable time.
Maximum setting to prevent
tripping after delay
Adaptive setting only active
during SOTF time
Set SOTF function to
“Active” to enable Inst
Pickup during this time after
breaker close.
Set Function Active if this
protection is desired
Ground Time Overcurrent
Pickup (x In)
Curve shape
Time multiplier
Ground Time Overcurrent
Pickup =NONE= Inactive
DT3000 Parameter
Set Function Active if this
protection is desired
Note: For thermal curves (Flat, IT, I2T, I4T) divide DT
time multiplier by 5 to get equivalent EDR multiplier
Ground Short Delay
Pickup (x In)
Time
Short Delay
DT3000 Parameter
Pickup =NONE= Inactive
Set Function Active if this
protection is desired
Ground Instantaneous
Pickup (x In)
Time = 0
Instantaneous
DT3000 Parameter
Pickup =NONE= Inactive
Set Function Active if this
protection is desired
EDR-3000 System Settings EDR-3000 System Para/General Settings Menu
Frequency
Phase CT ratio
Ground CT ratio
Program with Breaker Open/Closed (Dip Switch S2)
DT3000 Parameter
High Load Alarm
High Load Time
High Load (set at .85*51P[1] pickup)
DT3000 Parameter
(output contact RO2 Terminals – X2-5, X2-6)