2 PSsystec SMARTbox IO Agent User Guide

SMARTbox Mini ____________Smartbox, based on the Telit Chipset HE910 is a ready to use solution for connecting Modbus devices to Cloud der Dinge. It provides a Master Slave Communication on RS485 for connecting up to 10 devices. Easy configure the SetUp of building automation fielddevices like pumps, e-meters, Airhandling units in the Cumulocity Fieldbus cloud. Using the MQTT protocol the terminal comes up with a low traffic solution for decentralized applications.

SMARTBox

SmallHousing70mmx50mm

OutOfBoxModbusSolution

MountingbyMagnetorSwitchboardclips

Montage

ModbusRTURS485-ModbusMaster-Frames:Parity/Even/ODD-Stoppbits:1/2-Baudrate:4800,9600,19200..115200-FunctionCodes;F1/F2/F3/F4/F5/F6-Upto20DevicesonModbusLine

DevelopedforCloudFieldbus-FlexibleDevicedatabase-Alarming-Events-Measurments-Value/Operations-SetUpModbusMasterCommunication-Remoterestart

-GE910(2G)-HE910(3G)

TelitChipSet2OptionsBetriebsspannung12-24V

SMARTBoxMiniTestedonmodbusbuildingautomationdevices

GeneralFeatures-OfflineBufferforAlarmsandmeasurementsup24hours-m2MLocateoncellularnetwork-FullSmartrestSupport(lowdatatraffic)-Sendingcycledefinedbysmsduringruntime

DixellColdRoomControl

DaikinAirConditioning

CarelChiller/Heatpumpsystem

CarelCompressorracksShowcases

Carel-EMeter

Carel-AirHandlingUnit

Page 3: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

3 PSsystec SMARTbox IO Agent User Guide

SMARTbox Mini - Overview ____________

- 2G - global - 3G - EMEA, APAC, NA, Global - LTE - EMEA, APAC, Americas - GNSS

Fieldbus - Modbus RTU (RS232/RS485)

Sensors - Digital Input (DIN)

- AIN (NTC,0..20mA) MQTT Agent for T-Systems- Cloud der Dinge

- For further information: please refer to the datasheet provided by PSsystec

https://www.pssystec.de/downloads/ - For installing the agent and SW releases, pls refer to:

http://www.pssystec.de/smartbox/smartbox-agent/ - For getting the device pls contact Telekom Hardware support or Pssystec

[email protected] - The full product overview pls download it https://www.pssystec.de/downloads/

Wire your Smartbox ____________ - Connect your sensors and Modbus Devices to the terminal block - You can use external 24VDC (200mA) or the with the delivered PowerSupply

Powersupply24VDC

IOSensorsDIDI/ONTCAI/O0..20mAAI/P+

ModbusRTUMaster

ProgrammingDebug

GSM–flashing:RegisterdinNetworkRUN–flashing:ServerExchange

GPS(opt.)

GSMAntenna

SIMCard2FF

TLS Support ____________ Agent Version 1.x support TLS 1.0 Agent Version 2.4.x support TLS 1.2 Connect the SMARTbox to your Cloud der Dinge Account ____________ Power on the Terminal and wait until the RUN LED is flashing 2xflash-pause-2xflash-

Page 4: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

4 PSsystec SMARTbox IO Agent User Guide

In the CoT Devicemanagement, go to the menu Device Registration. Enter the Terminal's IMEI as an ID. The IMEI is printed on the devices itself:

After accepting the device (this process may take 30 seconds) you should be able to see it in the All Devices list after a short delay

Configuration ____________ The SMARTbox supports the configuration tab to set specific properties, independent of Fieldbus connectivity features. You can get an actual snapshot or set a property in the Configuration window.

Following Configurations are supported: Valid for Product Agent c8y.ConfigDin=0 Enable the extra digital input

Note: Mini,DP, CubeIO >2.3.x

Page 5: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

5 PSsystec SMARTbox IO Agent User Guide

- Jumper must be set on the Smartbox (during production)

- It creates an event c8y.ConfigAin=0 Enable the extra analogue Input

Note: - Jumper must be set on the

Smartbox for NTC and different Jumpersetting for 0..20mA (during production)

- It creates and measurement The settings are as follows: 0 – disabled 1 – NTC 2 – 0…20mA

Mini,DP, CubeIO >2.3.x

c8y.DinLogic=0 Define the Logic of DIN Input 0 = NO 1 = NC

Mini,DP, CubeIO >2.3.x

c8y.cycle=900 Define the send measurement cycle of the extra analogue Input

Mini,DP, CubeIO >2.3.x

c8y.ditext=<Name> Define the Text of the event by DIN Mini,DP, CubeIO >2.3.x c8y.ditype=<Name> Define the type of the event by DIN Mini,DP, CubeIO >2.3.x c8y.adcseries=<Name> Define the Series of Measurement by AIN Mini,DP, CubeIO >2.3.x c8y.adctype=<Name> Define the Type of Measurement by AIN Mini,DP, CubeIO >2.3.x c8y.LocationCycle=0 Define the Location update in min

If it is set to 0, then Location is derived only at startUp.

all >2.3.x

c8y.min=0 Define the Min of AIN Value conversion (if AIN is set to 0…20mA by jumper)

Mini,DP, CubeIO >2.3.x

c8y.max=0 Define the Max of AIN Value conversion (if AIN is set to 0…20mA by jumper)

Mini,DP, CubeIO >2.3.x

c8y.GPS=0 If GPS Hardware option is available you can enable the GPS function by setting 1 and disable by settings 0. Note:

- The locationcycle is also valid for GPS enabled.

- If GPS=0, the cellular location determination is active

All with GPS Option

>1.3.4

DeleteTenant >1.3.4 Note: All other configuration settings which you will get with the Snapshot are only for Information and refers to internal settings. Note: To set a configuration proceed as follows, put all statements in a new line e.g. c8y.DinLogic=1 c8y.min=1 press save Use the Built-In IOs ____________1. Note that the SMARTbox Mini supports:

- 1 x Digital Input (DIN) - 1 x AIN (NTC,0..20mA)

Note the activation of NTC or 0..20mA must be defined during production

Page 6: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

6 PSsystec SMARTbox IO Agent User Guide

Connect a Modbus Device to the SMARTbox ____________ The Smartbox supports Modbus RTU – all Connections parameters are configurable in the Cloud.

Type Modbus RTU (Master) Cloud Baudrate 4800, 9600, 19200, 38400, 115200 (Change during Runtime possible) Modbus Tab Parity Even, ODD, NONE (Change during Runtime possible) Modbus Tab Stopbits 2,1 (Change during Runtime possible) Modbus Tab Functioncodes Funct.1 (Read Single Coils)

Funct.2 (Read Input Status) Funct.3 (Read Holding Registers) Funct.4 (Read Input Registers) Funct.5 (Write Coil) Funct.6 (Write Holding Register)

Device database (model)

Datapoints 1.. 10 Slaves with each 100 datapoints fix Polling Rate on Bus

500ms fix

We assume that you already defined your Modbus device(s) which you want to connect in the device database. In this exemplary SetUp you need 4 Models in the device database, which can and should be defined offline in the Cloud (see also chapter Help Device database)

Device1: Chiller on Address1 Device2: Energy Meter on Address2 Device3: Frontcooler for Serverline1 on Address5 Device4: Frontcooler for Serverline2 on Address6

Page 7: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

7 PSsystec SMARTbox IO Agent User Guide

To connect 1 Modbus Device to the RTU network:

a. Physically wire the Modbus/RTU device through RS485 to the terminal. b. Give the device a unique Modbus address according to the instructions provided

with the Modbus device (e.g. by setting a jumper on the device). c. Check the serial communication settings of the device according to the instructions

provided with the device (i.e. baud rates and communication protocol). These have to match with all devices on the bus.

d. Navigate to the terminal in Cumulocity and click on the "Modbus" tab. e. Change the communication settings shown in the section "Serial Communication"

to match the settings on the bus, if needed. f. Change the transmit rate and the polling rate according to your requirements. The

polling rate is the frequency at which the Modbus devices are polled for changes. The transmit rate is the frequency where measurements are sent to CoT.

g. Click "Save changes" if you made changes. h. To start communication between the terminal and the Modbus device, click "Add

new device". i. Enter a name for the device and select the type of the device from the drop-down

box. To add new device types, see www.youtube.com/watch?v=99dj4PDMwQQ below. Set the Modbus address of the connected device.

j. Click "Add". CoT will now send a notification to the SMARTbox that a new device is ready to be managed. This may take a few seconds.

Page 8: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

8 PSsystec SMARTbox IO Agent User Guide

Use the built-in Location and Tracking functionality (>2.3.x) ____________ The terminal features cell location and is available in Location tab on terminal level. Devices are shown as "pins" that you can click to see the name of the device. Clicking the name of the device takes you to the detailed view of the device. You have 3 Options:

1. Using the built in Cell Location. The terminal identifies 3 cells in the near environment and derives the location (default)

2. Using the hardware Option with a built in- GPS (this is an extra option). Set c8y.GPS=1 then GPS is enabled. Setting c8y.GPS=0 Cell location is enabled (default)

3. Activate a regular identification of the location. In Configuration tab you can set: c8y.LocationCycle=60; define in min, how often the location should be checked. 0 means the cycled checking is disabled. If a value >0 ist set, also the tracking is enabled

Page 9: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

9 PSsystec SMARTbox IO Agent User Guide

Devices can record the history of their movements in CoT. Using the tracking tab, you can select a time period and visualize the movements of the device during this time period. Movements are shown as red lines on the map.

Next to the map, the individual recordings with their time are listed ("location update events"). When you click a recording, a "pin" on the map will show the location at the time of the recording.

Activate a regular identification of the location. In Configuration tab you can set. If the value of c8y.LocationCycle is greater 0 then tracking is enabled.

Depending on the type of device and the integration into CoT, you can also configure device-side geo-fencing and motion detection.

Additionally, when the feature is activated, Cell ID information can be used to determine the position of the device. Currently, the services from Combain and Google are supported. The user can see the tracks based on both data, or filter out GPS based data or Cell ID based data. Manage the Agent ____________ The installed software on the SMARTbox can be remotely managed using the standard software and management feature from Cumulocity, as described in the Device management user's guide. You can also install the agent manually, follow the instructions here: http://www.pssystec.de/smartbox/smartbox-agent/ Remotely Manage APN, Tenant, Reboot (OnRequest) ____________ DELETE deletes the registration in CC and you can

register on a new tenant RESET Restarts the device

Page 10: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

10 PSsystec SMARTbox IO Agent User Guide

GPRS=<APN>,<User>,<Password> Change APN, if no User or Password is required,

the fields free Operate the Device by SMS (OnRequest)____________ Since Agent Version 2.3.x. This service allowing the user to run on the module itself AT Commands sent from a mobile via SMS messages. You will get the answer from the SMARTbox directly on your mobile phone. This allows you, to make troubleshooting in any case of error. Example: Type AT+COPS? Result on your mobile Phone: +COPS: 0,0,"Vodafone.de",2 OK All AT command supported are listed here: http://www.pssystec.de/downloads/ à supported AT commands and includes a huge amount of different AT commands. Operate AT commands via device shell (>V2.3.x)____________ The device shell enables you to read and write configuration parameters to interactively work with remote devices. You can send AT commands in the respective language of the device and view the results of the commands. You can sent any At Command. Check here in Chapter “supported AT commands”: https://www.pssystec.de/downloads/. Frequently used commands are available by clicking the "Get predefined" button

Local Debug and operate the device____________

1. Install the Telit USB driver on your PC: https://www.pssystec.de/downloads/. The PC will recognize 6 new USB Ports

For debug service: 1. Open an Terminal program

Page 11: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

11 PSsystec SMARTbox IO Agent User Guide

2. Connect your PC on Telit High Speed Modem USB Port with USB port on the Smartbox

3. you will get details of the running machine. For setting generic AT commands:

1. Open an Terminal program 2. Connect your PC on USB4 Port with USB port on the Smartbox 3. you can set now at commands

Note: Using Agent Versions <2.3.x you have to connect to USB3 Help for Setting up the Device database____________ All devices which are connected to the SMARTbox are needed to define in Device Database. The definition includes all supported datapoints of this connected device. Even more, you can not only define the “physical datapoint” like register address, you can also define if this datapoint comes in the cloud as a measurement, event, alarm or write value. In addition some control field per datapoint are available which includes metadata like the Unit or Display Category.

Page 12: DT UserGuide SMARTbox Mini 23-05-2018 - PSsystec GmbH...Dixell Cold Room Control Daikin AirConditioning Carel Chiller/ Heatpumpsystem Carel Compressorracks Showcases Carel-EMeter

12 PSsystec SMARTbox IO Agent User Guide