dstatcom and dvr in power system

Upload: tariq76

Post on 03-Apr-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 dstatcom and dvr in power system

    1/50

  • 7/28/2019 dstatcom and dvr in power system

    2/50

    2

    1.2LITERATURE SURVEYSeveral research papers and reports addressed the subject of improving power quality

    in distribution system by the use of custom power devices. The followings present a brief

    review of the work undertaken so far.

    N.G.Hingorani, prstesents the concept of custom power is now becoming familiar.

    The book describes the value- added power that electric utilities and other service providers

    will offer their customers in the future. The enhanced level of reliability of this power, in

    terms of problem, of which a prominent feature will be the application of power electronics

    controllers to utility distribution system and at the supply end of many industrial and

    commercial customer and industrial parks.

    Olimpo Anaya-Lara and E. Acha,et al [3] This paper presents the modeling and

    analysis of custom power controllers, Graphics-based models suitable for electromagnetic

    transient studies are presented for the following three custom power controllers: the

    distribution static compensator (D-STATCOM), the dynamic voltage restorer (DVR), and the

    solid-state transfer switch (SSTS). Comprehensive results are presented to assess the

    performance of each device as a potential custom power solution

    M.H.J.Bollen, et al. [4] presents the influence of sags that leads to an interruption of

    plant operation. The assumption that voltage sag is not correct in a power system with large

    loads. After fault- clearing, they will accelerate again, drawing a high reactive current from

    the supply, causing extended post fault of some voltage sags in an example power system is

    shown and discussed. The influence of faster protection and of reduced transformer

    impedance on the table is presented. A simple model is implemented in a method for

    including interruptions due to voltage sag in the reliability of power systems.

    H.P.Tiwari, et al [8] presents dynamic voltage restorer against voltage sag. A

    dynamic voltage restorer (DVR) is a custom power device used to correct the voltage sag by

    injecting voltage as well power into the system. The mitigation capability of these devices is

    generally influence by the maximum load; power factor and maximum voltage dip to becompensated. Voltage dip on a feeder is a main task for DVR system operation and

    appropriate desired voltage sag compensation. This paper is intended to assimilate the

    amount of DC energy storage depends on voltage dip. It is available in a convenient manner

    for DVR power circuit.

    Arindam Ghosh, et al [6] presents the performance of voltage-source converter-

    based shunt and series compensators used for load voltage control in electrical power

    distribution system has been analyzed and compared, A distribution static compensator (D-

    STATCOM) as shunt device and a dynamic voltage restorer (DVR) as a series device are

  • 7/28/2019 dstatcom and dvr in power system

    3/50

    3

    considered in the voltage control mode for the comparison. The effect of various system

    parameters on the control performance of the compensator studied using the proposed

    analysis. The experimental verification of the analytical result derived has been obtained

    using a laboratory model of the single-phase D-STATCOM and DVR.

    Arindam Ghosh, et al. [7] presents the Dynamic Voltage Restorer (DVR) with ESS

    based PI Controller method to compensate balanced voltage sag. Voltage sag is one of the

    major power quality problems which result in a failure of end use equipments. Sensitive

    industrial load and utility distribution networks all suffer from various types of outages and

    service interruptions which can cost significant financial loss per event. The aim therefore is

    to recommend measures that can improve voltage sag.

    C.S.Chang, et al [9] presents performance of voltage sag mitigation devices such as

    the Dynamic voltage restorer(DVR) has been analyzed in highly simplified electrical

    environment consisting of simple line and load models. The negative influence of dynamic

    load on the existing voltage disturbance, such as post- fault sags, further during fault phase

    angle deviations, during- fault and post-fault voltage fluctuations have often been unnoticed.

    First, the influence of load operation on the during-fault and post-fault waveforms will be

    discussed. After which ability of the DVR to dynamically respond to the various types of

    voltage sag condition at the terminals of a dynamic load and restore the sagging voltage to its

    pre-fault conditions is presented.

    1.3SCOPE OF WORKFrom the literature review, it is observed that the work on the investigation on power

    with compensating devices have the wide area. However it is observed that there is scope to

    investigate the effectiveness of compensating devices for different loads and with different

    loading conditions in distribution system. As the distribution system locates the end of power

    system and is connected to the customer directly, so the reliability of power supply is

    increasing day by day, so the reliability of the distribution system has to be increased.

    Electrical distribution network failures account for about for the average customer

    interruptions. So it is highly required to increase the reliability of the distribution system.

    The objective of proposed work is to improve the power quality or reliability in the

    distribution system with the use of custom power devices like D-STATCOM and DVR.

    Different fault conditions are applied the load to analyzed the comparative operation of D-

    STATCOM and DVR for the improvement the power quality in distribution system.

  • 7/28/2019 dstatcom and dvr in power system

    4/50

    4

    1.4ORGANIZATION OF THESISChapter-1 Provide introduction and work in this field which has been carried out till date. It

    also includes scope of work and organization of the thesis.

    Chapter-2 gives the fundamentals of power quality, power quality problem and their

    associated solutions.

    Chapter-3 presents the concept and need of custom power devices.

    Chapter-4 presents the operation, modeling and applications of Dynamic voltage Restorer

    (DVR).

    Chapter-5 presents the operation, modeling and applications of D-STATCOM.

    Chapter-6 gives the ideas of proposed controller.

    Chapter-7 presents DVR test system and simulation results.

    Chapter-8 presents D-STATCOM test system and simulation results.

    Chapter-9 present the conclusion of the work presented in this thesis. It also presents the

    future scope of this work.

    Chapter-10 References.

  • 7/28/2019 dstatcom and dvr in power system

    5/50

  • 7/28/2019 dstatcom and dvr in power system

    6/50

    6

    Voltage sags; it may be define as A decrease to between 0.1 and 0.9 pu in rms voltage or

    Current at the power frequency for durations of 0.5 cycles to 1 minute. Voltage sags are

    mostly cause be system faults and may be occurred from 3 cycles to 30 cycles depending on

    the fault clearing time. Starting of large induction motor, transformer energies, load switching

    etc can cause the voltage sag.

    Voltage swells; it maybe define as, An increase to between 1.1 pu and 1.8 pu in rms

    voltage or current at the power frequency durations from 0.5 to 1 minute . Similarly as sag

    swell is also associate with system faults. A single line to ground fault can result in a voltage

    swell in the healthy phases. Swell can also result from energizing a large capacitor banks.

    2.3.2 Voltage fluctuation and flicker

    Voltage fluctuations are systematic variation of the voltage or a series of random

    changes in the voltage magnitude which lies in the range of 0.9 to 1.1 p.u. High power loads

    that draw fluctuating current, such as large motor drives and arc furnaces, cause low

    frequency cyclic voltage variation that result in flickering of light sources like incandescent

    and fluorescent lamps which can cause significant irritation in human beings. The voltage

    flicker can also affect stable operation of electrical and electronics devices.

    2.3.3 Frequency variations

    Power frequency variations are defined as the variation of the system frequency from

    its value of 50 Hz. The frequency variations start from the change in the load and the

    response of the generators to meet the load.

    2.4 SOLUTION OF POWER QUALITY PROBLEMS

    The power quality problems can be solving by considering two approaches.

    According to first approach the solution to the power quality problems can be done from the

    utility side. This approach is called as load conditioning, in which the equipment is

    considered less sensitive to power disturbances, allowing the operation even under significant

    variation distortion.

    In second approach, install line conditioning system that suppresses the power system

    disturbances. In this approach the compensating devices is connect to low and medium

    voltage distribution system in shunt or in series. Shunt power filters operate as a controllable

    current source and series active power filters operates as controllable voltage source. Both

    schemes are implemented with voltage source PWM inverters, with a dc source having a

    reactive element such as a capacitor. Apart from this there are many approaches to nullified

    the problems, but in this thesis concentration on shunt and series controller only.

  • 7/28/2019 dstatcom and dvr in power system

    7/50

    7

    3.1 INTRODUCTION

    STATCOM, SSSC, IPFC and UPFC etc are the FACTS devices and these are design

    for the transmission system. But today, more attention has to be given on the distribution

    system for the improvement of power quality. Hence, these devices are modified and known

    as custom power devices. The custom power is the value- added powers that given to the

    customers. The value added power consists of the application of high power electronic

    controllers to distribution system, at the supply end of industrial, commercial consumers.

    The custom power devices which are used in distribution system to maintain the

    power quality are distribution static synchronous compensator (D-STATCOM), dynamic

    voltage Restorer (DVR), active filter (AF), unified power quality conditioner (UPQC) etc. All

    are base on voltage source converter (VSC). The DVR is similar to SSSC where as UPQC is

    similar to UPFC. In spite of the similarities, the control techniques are quite different for

    improving power quality. A DVR can work as a harmonic isolator to prevent the harmonics

    in the source voltage reaching the load in addition to balancing the voltage and providing

    voltage regulation. A D-STATCOM is utilized to eliminate the harmonics from the source

    current and also balance them in addition to providing reactive power compensation to

    improve power factor or regulate the load bus voltage. To solve the power quality problem,

    custom power devices used here are D-STATCOM and DVR. D-STACOM DVR are the

    most efficient and effective modern customs power device used in power distribution

    networks.

    3.2 BENEFIT OF CUSTOM POWER DEVICES

    1. They contribute to best possible system operation by improving voltage profile and

    reducing power losses.

    2. Improve the power flow in critical lines.

    3. The transient stability limit is improved thereby improving dynamic security of the system

    and reducing the incidence of blackouts caused by cascading outages.

    4. The problem of voltage fluctuations and in, dynamic over voltages can be overcome by

    these controllers.

    5. The problem of voltage sag and voltage swell in case of industrial loads like motor,

    switching, transformer energies etc. can be reduced by these devices.

  • 7/28/2019 dstatcom and dvr in power system

    8/50

    8

    4.1 INTRODUCTION

    The DVR is a solid state dc to ac switching power converter that injects a set of three

    single phase ac output voltages in series with the distribution feeder and in synchronism with

    the voltages of the distribution system. By injecting voltages of controllable amplitude, phase

    angle and frequency (harmonic) into the distribution feeder in instantaneous real time via a

    series injection transformer, the DVR can restore the quality of voltage at its load side

    terminals when the quality of the source side terminal voltage is significantly out of

    specification for sensitive load equipment.

    The reactive power exchanged between the DVR and distribution system is internally

    generated by the DVR without any ac passive reactive components, i.e. reactors and

    capacitors. For large variations in the source voltage, the DVR supplies partial power to the

    load from a rechargeable energy source attached to the DVR dc terminal. The DVR, with its

    three single phase independent control and inverter design is able to restore line voltage to

    critical loads during sags caused by unsymmetrical as well as symmetrical three phase faults

    on adjacent feeders or disturbances that may originate many miles away on the higher voltage

    interconnected transmission system. Connection to the distribution network is via three

    single-phase series transformers there by allowing the DVR to be applied to all classes of

    distribution voltages. At the point of connection the DVR will, within the limits of its

    inverter, provide a highly regulated clean output voltage.

  • 7/28/2019 dstatcom and dvr in power system

    9/50

    9

    4.2 WORKING PRINCIPLE OF DVR

    The DVR is a solid state dc to ac switching power converter that injects a set of three

    single phase ac output voltages in series with the distribution feeder and in synchronism with

    the voltages of the distribution system. A DC to AC inverter regulates this voltage by

    sinusoidal PWM technique. By injecting voltages of controllable amplitude, phase angle and

    frequency (harmonic) into the distribution feeder in instantaneous real time via a series

    injection transformer, the DVR can restore the quality of voltage at its load side terminals

    when the quality of the source side terminal voltage is significantly out of specification for

    sensitive load equipment.

    The reactive power exchanged between the DVR and distribution system is internally

    generated by the DVR without any ac passive reactive components, i.e. reactors and

    capacitors. For large variations in the source voltage, the DVR supplies partial power to the

    load from a rechargeable energy source attached to the DVR dc terminal. The DVR, with itsthree single phase independent control and inverter design is able to restore line voltage to

    critical loads during sags caused by unsymmetrical as well as symmetrical three phase faults

    on adjacent feeders or disturbances that may originate many miles away on the higher voltage

    interconnected transmission system. Connection to the distribution network is via three

    single-phase series transformers there by allowing the DVR to be applied to all classes of

    distribution voltages. At the point of connection the DVR will, within the limits of its

    inverter, provide a highly regulated clean output voltage.

  • 7/28/2019 dstatcom and dvr in power system

    10/50

    10

    4.3 BASIC CONFIGURATION OF DVR

    The general configuration of the DVR consists of,

    1. An Injection/ Booster transformer

    2. A Harmonic filter

    3. Storage Devices

    4. A Voltage Source Converter (VSC)

    5. DC charging circuit

    6. A Control and Protection system

    4.3.1 Voltage Injection/ Booster transformer

    The primary side of the injection transformer is connected in series to the distribution

    line, while the secondary side is connected to the DVR power circuit. 3 single phase

    transformers can be used for 3 phase DVR. Basically the injection transformer is a step up

    transformer which increases the voltage supplied by filtered VSI output to a desired level and

    it also isolates the DVR circuit from the distribution network. Winding ratios are very

    important and it is predetermined according to the required voltage at the secondary side.

    High winding ratios would mean high magnitude currents on the primary side which may

    affect the components of inverter circuit. When deciding the performance of DVR, the rating

    of the transformer is an important factor. The winding configuration of the injection

    transformer is very important and it mainly depends on the upstream distribution transformer.

    In case of a -Y connection with the grounded neutral there will not be any zero sequence

    current flowing into the secondary during an unbalance fault or an earth fault in the high

    voltage side.

    4.3.2 DC charging unit

    The dc charging circuit is used after sag compensation event, the energy source is

    charged again through dc charging unit. It is also used to maintain dc link at the nominal dc

    link voltage.

    4.3.3 Voltage Source Converter (VSC)

    A voltage source converter is a power electronic system consists of a storage device

    and switching devices, which can generate a sinusoidal voltage at any required frequency,

    magnitude and phase angle. It could be a three-phase three-wire voltage source converter. In

    this thesis two level converters are used for both DVR and D-STATCOM. The VSC is used

    to momentarily replace the supply voltage or to generate the part of the supply voltage which

    is absent (missing voltage). There are four main types of switching devices: Metal Oxide

    Semiconductor Field Effect Transistor (MOSFET), Gate Turn-Off thyristor (GTO), Insulated

  • 7/28/2019 dstatcom and dvr in power system

    11/50

    11

    Gate Bipolar Transistor (IGBT), and Integrated Gate Commutated thyristor (IGCT). Here,

    IGBT based two level six pulse voltage source converter is used.

    4.3.4 Simulink result of proposed two levels VSC.

    The following fig.4.3 represents the out of proposed voltage source converter. Here, the

    input given to the inverter is 6.2 KV DC and the alternating output of nearly 6.2 KV is getting

    at output side.

    Figure 4.3 output of proposed two level voltage source converters.

    4.3.5 Pulse Width Modulation Generator (PWM)

    As we well known the operation of PWM that by comparing the carrier signal and

    reference signal, required pulse are generated by this discrete PWM generator. The

    modulated signals are compared against a triangular signal in order to generate the switching

    signals which are shown in fig.4.4. The main parameters of sinusoidal PWM generator are

    amplitude modulation index and frequency modulation index. The amplitude modulation

    index is kept 1p.u and frequency modulation index depend upon the ratio of carrier frequency

    and fundamental frequency. The modulating signal is applied to the PWM in phase A, the

    angle for phase B and C are shifted by -120 and +120 respectively.

    Figure 4.4 Pulse generated by Discrete PWM Generator.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-8000

    -6000

    -4000

    -2000

    0

    2000

    4000

    6000

    8000

    Time

    V

    oltage

    (K

    V

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1

    Time

    Voltage(p.u

    )

  • 7/28/2019 dstatcom and dvr in power system

    12/50

    12

    4.3.4 Harmonic filter

    As DVR consist of power electronic devices, the possibility of generation self

    harmonics is there so harmonic filter is also become a part of DVR. In order to achieve this it

    is necessary to eliminate the higher order harmonic components during DC to AC conversion

    in Voltage Source Inverter which will also distort the compensated output voltage. Thesefilters which play a vital role can be placed either on high voltage side i.e. load side or on low

    voltage side i.e. inverter side of the injection transformers. We can avoid higher order

    harmonics from passing through the voltage transformer by placing the filters in the inverter

    side. Thus it also reduces the stress on the injection transformer. One of the problems which

    arise when placing the filter in the inverter side is that there might be a phase shift and

    voltage drop in the inverted output. So this could be resolved by placing the filter in the load

    side. But this would allow higher order harmonic currents to penetrate to the secondary side

    of the transformer, so transformer with higher rating is essential.

    4.4 OPERATING MODE OF DVR

    4.4.1During the normal operation

    During the normal operation as there is no sag, DVR will not supply any voltage to

    the load. It will be in a standby mode or it operates in the self charging mode if the energy

    storage device is fully charged. The energy storage device can be charged either from the

    power supply itself or from a different source.

    4.4.2During a voltage sag/swell on the line

    The difference between the pre sag voltage and the sag voltage is injected by the DVR

    by supplying the real power from the energy storage element and the reactive power. The

    DVR injects the difference between the pre-sag and the sag voltage, by supplying the real

    power requirement from the energy storage device together with the reactive power. Due to

    the ratings of DC energy storage and the voltage injection transformer ratio the maximum

    capability of DVR is limited. The magnitude of the injected voltage can be controlled

    individually in the case of three single-phase DVRs. With the network voltages the injected

    voltages are made synchronized (i.e. same frequency and the phase angle).

  • 7/28/2019 dstatcom and dvr in power system

    13/50

    13

    4.4.3 During a short circuit or fault in the downstream of the distribution line

    In this case we have seen before that a bypass switch (crossbar switch) will be

    activated and it will bypass the inverter circuit in order to protect the electronic components

    of the inverter.

    4.5 COMPENSATION TECHNIQUES

    4.5.1 Pre-sag Compensation

    Pre-sag compensation is a method which is generally used for non linear loads such as

    thyristor controlled drives. In non linear loads the voltage magnitude as well as he phase

    angle needs to be compensated. Figure 4.5 below describes the pre-sag compensation

    technique. A higher rated energy storage device and voltage injection transformers are

    needed for this technique.

    4.5.2 In-phase Compensation

    This technique of compensation is generally used for active loads. Only compensation

    for voltage magnitude is required whereas no phase compensation is required. In this

    particular method the compensated voltage is in phase with the sag voltage. It is clear from

    the Figure 4.6, that there is a phase shift between the voltages before the sag and after the sag.

    In above both the techniques required both real and reactive power for the compensation and

    the DVR is supported by an Energy storage device.

  • 7/28/2019 dstatcom and dvr in power system

    14/50

    14

    4.6 EQATIONS RELATED TO DVR

    The injected voltage and load impedance Zth depends on the fault level of the load bus.

    When the system voltage (Vth) drops, the DVR injects a series voltage VDVR through the

    injection transformer so that the desired load voltage magnitude VL can be maintained. The

    series injected voltage of the DVR can be written as,

    VDVR=VL+ ZthIL-Vth (1)Here, IL is load current and is given by

    IL =( +)

    When VL is considered as a reference, equation -1 can be written as

    VDVR = VL 0+ ZthIL (- ) -Vth

    Here , and are the angle of VDVR, Zth andVth respectively, is the load power factor angle,

    = tan-1 (QL/PL)

    the complex power injection of the DVR can be written as,

    SDVR=VDVRIL*

  • 7/28/2019 dstatcom and dvr in power system

    15/50

    15

    5.1 INTRODUCTION

    This chapter presents the operating principles of DSTATCOM. The DSTATCOM is

    basically one of the custom power devices. It is nothing but a STATCOM but used at the

    Distribution level. The key component of the DSTATCOM is a power VSC that is based on

    high power electronics technologies.

    The Distribution STATCOM is a versatile device for providing reactive compensation

    in ac networks. The control of reactive power is achieved via the regulation of a controlled

    voltage source behind the leakage impedance of a transformer, in much the same way as a

    conventional synchronous compensator. However, unlike the conventional synchronous

    compensator, which is essentially a synchronous generator where the field current is used to

    adjust the regulated voltage, the DSTATCOM uses an electronic voltage sourced converter

    (VSC), to achieve the same regulation task. The fast control of the VSC permits the

    STATCOM to have a rapid rate of response.

    The DSTATCOM is the solid-state based power converter version of the SVC.

    Operating as a shunt connected SVC, its capacitive or inductive output currents can be

    controlled independently from PWM technique. Because of the fast-switching characteristic

    of power converters, the DSTATCOM provides much faster response. DSTATCOM is a

    shunt connected, reactive compensation equipment, which is capable of generating and or

    absorbing reactive power whose output can be varied so as to maintain control of specific

    parameters of the electric power system. DSTATCOM employ solid state power switching

    devices, hence, it provides rapid controllability of the three phase voltages, both in magnitude

    and phase angle.

  • 7/28/2019 dstatcom and dvr in power system

    16/50

    16

    5.2 PRINCIPLE OF DSTATCOM

    Basically, the DSTATCOM system is comprised of three main parts: a VSC, a set of

    coupling reactors and a controller. The basic principle of a DSTATCOM connected in a

    power system is the generation of a controllable ac voltage source by a voltage source

    converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source,

    in general, appears behind a transformer leakage reactance. The active and reactive power

    transfer between the power system and the DSTATCOM is caused by the voltage difference

    across this reactance. The DSTATCOM is connected in shunt with the power networks at

    customer side, where the voltage-quality problem is a concern. All required voltages and

    currents are measured and are fed into the controller to be compared with the commands. The

    controller then performs feedback control and outputs a set of switching signals to drive the

    main semiconductor switches (IGBTs, which are used at the distribution level) of the power

    converter accordingly. The basic diagram of the DSTATCOM is illustrated in Fig5.2

    The ac voltage control is achieved by firing angle control. Ideally the output voltage of the

    VSC is in phase with the bus voltage. In steady state, the dc side capacitance is maintained at

    a fixed voltage and there is no real power exchange, except for losses.

  • 7/28/2019 dstatcom and dvr in power system

    17/50

    17

    5.3 PRINCIPLE OF VOLTAGE REGULATION

    5.3.1 Voltage regulation without D-Statcom

    Consider a simple phasor as shown in fig. 5.4. It consists of a source voltage Vs, VL is

    the load voltage and load current IL. Without a voltage compensator the load voltage drop

    caused by the load current IL. The change in load voltage is V.

    V=Vs-VL=Zs*IL

    IL=()

    V=(Rs+jXs)*(()

    )

    V= Vr+ Vx

    So, the voltage change has a component Vr in phase with Vth and component Vx having

    lagging phase difference.

  • 7/28/2019 dstatcom and dvr in power system

    18/50

    18

    5.3.2 Voltage regulation with DSTATCOMNow consider a compensator connected to the system. It is as shown in Fig 5.3.2 shows

    vector diagram with voltage compensation. By adding a compensator in parallel with the load,

    it is possible to supply voltage equal to Load voltage by controlling the current of the

    compensator.

    Is =Ish + IL

    Vth

    IL

    Vs

    IsRth

    jIsXth

    Figure 5.5phasor diagram for compensated

    IsIsh

  • 7/28/2019 dstatcom and dvr in power system

    19/50

    19

    6.1 INTRODUCTIONA controller is required to control or to operate both D-Statcom and DVR during the

    fault condition only. Load voltage is sensed and passed through a sequence analyzer. The

    magnitude of the actual voltage is compared with reference voltage i.e Vref. Pulse width

    modulated(PWM) control system is applied for inverter switching so as to generate a three

    phase 50Hz sinusoidal voltage at the load terminals. Switching frequency in the range of few

    KHz. The IGBT Inverter is controlled with PI controller in order to maintain 1p.u voltage at

    the load side. An advantage of proportional pulse integral controller is an actuating signal

    which is the difference between the reference voltage and feedback load voltage. Output of

    the controller is in the form of an angle , which introduces additional phase-lag/lead in the

    three-phase voltage. The output of error detector is the missing voltage. The controller output

    when compared at PWM signal generator hence, the result in the desired firing sequence.

    6.2 PHASE MODULATION

    The sinusoidal signal Vcontrol phase modulated by means of the angle are,VA=Sin (t + ) VB=sin (t + -2/3) VC =sin (t ++2/3)

    Figure 6.2 phase modulation of the control angle .

    This modulated signal is compaired with triangular signal and generates the switching signals

    for the converter valves. The main parameters of the sinusoidal PWM scheme are the

    amplitude modulation index of signal, and the frequency modulation index of the triangular

    signal. The modulating angle is applied to the PWM generator in phase A. the angles for

    Phase B and phase C are shifted by 120 and 240 lagging respectively. The speed of

    response is clearly shown in the simulation result shown.

  • 7/28/2019 dstatcom and dvr in power system

    20/50

    20

    7.1 PARAMETERS OF DVR TEST SYSTEM

    The test system consists of 13KV, 50Hz generation system (considered to be source).

    This source, feeding two transmission lines through a three winding transformer connected in

    Y// 13/115/115 KV. Such transmission lines feed two distribution network through two

    transformer connected in /Y, 115/11KV.

    Table-7.1 system parameters

    Sr. No. System Quantities Standards

    1 Source 13KV, 50Hz 100MVA

    2 Three winding transformer 100MVA,Y// 13/115/115 KV

    3 Impedance of transmission line1 R1=0.05/Km, L1=0.4806 H/Km

    4 Impedance of transmission line2 R2=1m/Km, L2=5mH/KM

    5 Two winding transformer 100MVA,50Hz, /Y 115/11 KV

    6 Injection transformer 100MVA, 50Hz,/Y 11/11KV

    7 Load on bus1 P=6.05MW(resisitive load)

    8 Load on bus2 P=3.4922KW Q=2MVAR(highly inductive)

    9 Inverter parameters IGBT based, 3 arms, 6 pulse, carrier

    Frequency=1080Hz

    10 PI controller Kp=0.5, Ki=50, Sample time=50s

    7.2 SINGLE LINE DIAGRAM OF THE DVR TEST SYSTEM

  • 7/28/2019 dstatcom and dvr in power system

    21/50

    21

    In the above test system we have a generating unit of 13KV, 50Hz which is considered as

    source of 100MVA. The test system is constructed with concerning the DVR actuation. The

    output from the source is fed to the primary of tertiary winding transformer. Now, further two

    parallel feeders of 11KV each are drawn with the help of two winding transformer. In one of

    the feeder (L2) DVR is connected in series and on other line fault is applied to creat sag or

    swell.

    7.3 SIMULINK MODEL OF TEST SYSTEM AND RESULTS

    7.3.1 Simulation of test system without fault and without DVR

    This simulink model presents the test system without any fault and without

    connecting custom device like DVR.

    Figure 7.2 Simulink model of test system without fault and without DVR

  • 7/28/2019 dstatcom and dvr in power system

    22/50

    22

    7.3.2 Simulation Results without fault and without DVR

    The following result shows the system when considering no fault and no connection

    ofDVR. RMS value of Voltage in p.u, instantaneous voltages, line to line voltage and phase

    voltage of the simulation result shown in the following figure.7.3, 7.4, 7.5 and 7.6

    respectively. The line to line voltage is 11KV and phase voltage is 6.3508V is measured.

    Figure 7.3 Voltage Vrms( p.u) at load side.

    Figure 7.4 Instantaneous value in p.u at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    Time

    V

    olta

    g

    e(P

    .U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    -1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    olta

    g

    e

    (P

    .U

    )

  • 7/28/2019 dstatcom and dvr in power system

    23/50

    23

    Figure 7.5 line to line voltage (KV) at load side

    Figure 7.6 Phase Voltage (KV) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 10

    4

    Time

    V

    o

    lta

    g

    e

    (K

    V

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    o

    lta

    g

    e

    (K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    24/50

    24

    7.3.3 Simulink model of test system with fault but without DVR

    In this simulink model we have system which fed the two buses or feeders through

    two winding transformer as shown. On the upper bus we are applying the 3phase Line to

    ground fault(3LG) , here we are not considering the presence of DVR and have to observe the

    effect on voltages on the lower bus(second bus or second feeder).

    Figure 7.7 Simulink model withfault without DVR

    7.3.4 Simulation Result of test system with fault and without DVR

    From the following results it is observed that during the fault time i.e 0.4-0.6 sec, thevoltage sag to some finite value. Since the fault is on upper bus, hence sag may be 70-80% .

    The sag on the lower bus at the load side is nearly 10-15% , and measured the line to line

    voltage value and phase voltage value during fault time is 10.1KV and 6.01KV respectively.

    Such observation can be found from the following figures.

    Figure 7.8 Voltage Vrms( p.u) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    Time(sec)

    V

    oltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    25/50

    25

    Figure 7.9 Instantaneous value in p.u at load side.

    Figure 7.10 line to line voltage (KV) at load side

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    -1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time (sec)

    V

    o

    lta

    g

    e

    (P

    .U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 10

    4

    Time(sec)

    V

    o

    lta

    g

    e

    (K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    26/50

    26

    Figure 7.11 Phase Voltage (KV) at load side.

    7.3.5 Simulink model of test system with fault and with DVR

    In this simulink model we have system which fed the two buses or feeders through

    two winding transformer as shown. On the upper bus we are applying the three phase Line to

    ground fault (3LG). And on the lower bus we have connected the DVR because in this bus

    sag is low and custom device can compensate easily. The system is shown in following fig.

    Figure 7.12 simulation test system with DVR

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    o

    lta

    g

    e

    (K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    27/50

    27

    7.3.6 Simulation Results with fault and with DVR

    From the following results it is clear that the DVR compensate the voltage sag during

    the fault time 0.4-0.6 sec. the compensated results of sag with respective rms value of

    voltage, instantaneous value, line to line voltage and phase voltages are shown in fig, 7.13,

    7.14, 7.15 and 7.16 respectively. The fig.7.17 shows the amount of voltage injected by the

    DVR which is nearly 0.5KV. The battery voltage is found to be 6.2KV.

    Figure 7.13 Voltage Vrms( p.u) at load side.

    Figure 7.14 instantaneous values in p.u at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    Time

    V

    oltage(P.U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    Time

    V

    o

    lta

    g

    e

    (P

    .U

    )

  • 7/28/2019 dstatcom and dvr in power system

    28/50

    28

    Figure 7.15 line to line voltage (KV) at load side

    Figure 7.16 Phase Voltage (KV) at load side.

    Figure 7.17 Injected voltage by DVR

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 10

    4

    Time

    V

    oltage(P.

    U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    oltage(P.U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    oltage(K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    29/50

    29

    7.3.7 Simulation of test system for voltage swells without DVR

    The following simulink model represent the creation of swell for the time 0.4-0.6 sec.

    to create the swell capacitor switching is proposed on lower bus.

    Figure 7.18 simulink model of test system for voltage swell.

    7.3.8 Simulation Results for voltage swell without DVRDuring the capacitor switching the voltage is swell to 10-15% of its normal value at

    the interval of 0.4-0.6, which are shown in the following fig. 7.19, 7.20, 7.21 and 7.22

    represent rms value of voltage in p.u, three phase instantaneous value in p.u, line to line

    voltage and phase voltage in KV respectively. The line to line voltage and phase voltage

    during the 0.4-0.6 are 0.77KV and 0.445KV respectively.

    Figure 7.19 Voltage Vrms( p.u) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    Time

    Voltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    30/50

    30

    Figure 7.20 Instantaneous value in p.u at load side.

    Figure 7.21 line to line voltage (KV) at load side.

    Figure 7.22 Phase Voltage (KV) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    -1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    Volt

    age(P.

    U)

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    oltage(K

    V

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 10

    4

    Time

    V

    oltage(K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    31/50

    31

    7.3.9 Simulation of test system for voltage swells with DVR

    In the following simulink model we are considering the working of DVR to eliminate

    the swell during the capacitor switching.

    Figure 7.23 simulation test system for voltage swell with DVR.

    7.3.10 Simulation Results for voltage swell with DVR

    From the following results it is clear that the DVR compensate the voltage swell

    during the switching time 0.4-0.6 sec. the compensated results of swell with respective rms

    value of voltage, instantaneous value, line to line voltage and phase voltages are shown in fig,

    7.24, 7.25, 7.26 and 7.27 respectively.

    Figure 7.24 Voltage Vrms( p.u) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    Time

    V

    oltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    32/50

    32

    Figure 7.25 instantaneous values in p.u at load side.

    Figure 7.26 line to line voltage (KV) at load side.

    Figure 7.27 Phase Voltage (KV) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    -1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    Volta

    ge(P.

    U)

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 10

    4

    Time

    V

    oltage(K

    V

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    oltage(

    K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    33/50

    33

    8.1 PARAMETERS OF D-STATCOM TEST SYSTEM

    The test system consists of 230KV, 50Hz transmission line (considered to be source).

    This source, feeding two distribution network through a three winding transformer connected

    in Y// 230/11/11 KV.

    Table-8.1 system parameters

    Sr. No. System Quantities Standards

    1 Source 230KV, 50Hz 100MVA

    2 Three winding transformer 100MVA,Y/Y/Y 230/11/11 KV

    3 Load on bus1 P=1.776MW, Q= 65.26MVAR(highly inductive)

    4 Load on bus2 P=385.124KW Q=2MVAR(highly inductive)

    5 Injection transformer 100MVA, 50Hz,/Y 11/11KV

    6 Inverter parameters IGBT based, 3 arms, 6 pulse, carrier

    Frequency=1080Hz

    8.2 SINGLE LINE DIAGRAM OF THE DVR TEST SYSTEM

    In the above test system we have a transmission line of 230KV, 50Hz which is considered as

    source of 100MVA. The test system is constructed with concerning the D-Statcom actuation.

    The source is fed to the primary of tertiary winding transformer. Now, further two parallel

    feeders of 11KV each are drawn from secondary winding the transformer. In one of the

    feeder D-STATCOM is connected in shunt and on other line two parallels loads are

    connected. The fault is applied at load side to create sag or swell.

  • 7/28/2019 dstatcom and dvr in power system

    34/50

    34

    8.3 SIMULINK MODEL OF TEST SYSTEM AND RESULTS

    8.3.1 Simulation of test system without fault and without D-STATCOM

    This simulink model presents the test system without any fault and no connecting

    custom device like DVR.

    Figure 8.2 simulink mode without fault and without D-STATCOM.

    8.3.2 Simulation Results without fault and without D-STATCOM

    The following results shows the system when considering no fault and no connection

    of D-STATCOM rms value of Voltage in p.u, instantaneous voltages, line to line voltage and

    phase voltage of the simulation result shown in the following figure.8.3, 8.4, 8.5 and 8.6

    respectively. The line to line voltage and phase voltage are nearly11KV and 6.3508V is

    measured.

    Figure 8.3 Voltage Vrms( p.u) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.70.8

    0.9

    1

    Time

    V

    oltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    35/50

    35

    Figure 8.4 instantaneous values in p.u at load side.

    Figure 8.5 line to line voltage (KV) at load side.

    Figure 8.6 Phase Voltage (KV) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    oltage(P.

    U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 10

    4

    Time

    V

    oltage(P.U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    oltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    36/50

    36

    8.3.3 Simulation of test system with fault but without D-STATCOM

    In this simulink model we have system in which source is connect to primary side of

    tertiary transformer as shown. The load is connected to the secondary sides of 11KV.the sag

    is create here by providing the switching for the interval of 0.4-0.6 sec.

    Figure 8.7 simulation test system without D-STATCOM

    8.3.4 Simulation Results with fault but without D-STATCOM

    From the following results it is observed that during the fault time i.e 0.4-0.6 sec, the

    voltage sag to some finite value.The sag during the fault at the load side is nearly 10-15% ,

    and measured the line to line voltage value and phase voltage value during fault time is

    10.25KV and 6.01KV respectively. Such observation can be found on the following figures.

    Figure 8.8 Voltage Vrms( p.u) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    oltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    37/50

    37

    Figure 8.9 instantaneous values in p.u at load side.

    Figure 8.10 line to line voltage (KV) at load side.

    Figure 8.11 Phase Voltage (KV) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    oltage(P

    .U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 104

    Time

    V

    oltage(P.U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    Voltage(KV)

  • 7/28/2019 dstatcom and dvr in power system

    38/50

    38

    8.3.5 Simulation of test system with D-STATCOM

    In this simulink model we have system which fed the load through secondary winding

    of tertiary transformer as shown. Out of two parallel loads, sag is created by providing the

    switching on one of load. The D-STATCOM is connected to one of the secondary winding of

    tertiary transformer .The system is shown in following fig.8.12

    Figure 8.12 simulation test system with D-STATCOM

    8.3.6 Simulation Results with fault and with D-STATCOM

    From the following results it is clear that the D-STATCOM compensate the voltage

    sag during the fault time 0.4-0.6 sec. the compensated results of sag with respective rms value

    of voltage, instantaneous value, line to line voltage and phase voltages are shown in fig, 8.13,

    814, 8.15 and 8.16 respectively. The battery voltage is found to be 28KV.

    Figure 8.13 Voltage Vrms( p.u) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    Time

    Voltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    39/50

    39

    Figure 8.14 instantaneous values in p.u at load side with fault but without D-STATCOM

    Figure 8.15 line to line voltage (KV) at load side. with fault but without D-STATCOM

    Figure 8.16 Phase Voltage (KV) at load side. with fault but without D-STATCOM

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    -1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    oltage(P

    .U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2 x 10

    4

    Time

    V

    oltage(K

    V

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    oltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    40/50

    40

    8.3.7 Simulation of test system for voltage swells without D-STATCOM

    The following simulink model represent the creation of swell for the time 0.4-0.6 sec.

    to create the swell switch is closed for the interval of 0.4-0.6 sec. As shown in following fig.

    Figure 8.17 Simulation of test system for voltage swells without D-STATCOM.

    8.3.7 Simulation Results for voltage swell without D-STATCOM

    The voltage swell is created by closing the switch during 0.4-0.6 sec. The swell of 10-15% of

    its normal value is found at the interval of 0.4-0.6 sec, which is shown in the following fig.

    8.18, 8.19, 8.20 and 8.21 representing rms value of voltage in pu, three phase instantaneous

    value in p.u, line to line voltage and phase voltage in KV respectively. The line to line

    voltage and phase voltage during the 0.4-0.6 are 0.93KV and 0.588KV respectively.

    Figure 8.18 Voltage Vrms( p.u) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    oltage(P.U

    )

  • 7/28/2019 dstatcom and dvr in power system

    41/50

    41

    Figure 8.19 instantaneous values in p.u at load side.

    Figure 8.20 line to line voltage (KV) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    -1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    o

    lta

    g

    e

    (P

    .U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-2

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    2x 10

    4

    Time

    V

    o

    lta

    g

    e

    (K

    V)

  • 7/28/2019 dstatcom and dvr in power system

    42/50

    42

    Figure 8.21 Phase Voltage (KV) at load side.

    8.3.8 Simulation of test system for voltage swells with D-STATCOM

    In the following simulink model we are considering the working of D-STATCOM to

    eliminate the swell during the switching of load.

    Figure 8.22 simulation test system for voltage swell with D-STATCOM

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    o

    lta

    g

    e

    (K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    43/50

    43

    8.3.9 Simulation of test system for voltage swells with D-STATCOM

    From the following results it is clear that the DVR compensate the voltage swell

    during the switching time 0.4-0.6 sec. the compensated results of swell with respective rms

    value of voltage, instantaneous value, line to line voltage and phase voltages are shown in fig,

    8.23, 8.24, 8.25 and 8.26 respectively.

    Figure 8.23 Voltage Vrms( p.u) at load side.

    Figure 8.24 instantaneous values in p.u at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    oltage(P.U

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    Time

    V

    o

    lta

    g

    e

    (P

    .U

    )

  • 7/28/2019 dstatcom and dvr in power system

    44/50

    44

    Figure 8.25 line to line voltage (KV) at load side.

    Figure 8.26 Phase Voltage (KV) at load side.

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1.5

    -1

    -0.5

    0

    0.5

    1

    1.5x 10

    4

    Time

    V

    o

    lta

    g

    e

    (K

    V

    )

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-1

    -0.5

    0

    0.5

    1x 10

    4

    Time

    V

    o

    lta

    g

    e

    (K

    V

    )

  • 7/28/2019 dstatcom and dvr in power system

    45/50

    45

    9.1 CONCLUSION

    The thesis has presented the study and simulation model of custom power equipment,

    namely D-STATCOM and DVR, and applied them for power quality problem such as voltage

    sag and voltage swell. The highly develop graphic facilities available in MATLAB is used to

    conduct all the aspect of model implementation and to carry out extensive simulation studies.

    A controller which is based on closed loop technique is used which generate error signals and

    this signals are used to trigger the switches of inverter using pulse width modulation (PWM)

    scheme in the D-STATCOM and DVR, this PWM control scheme only requires voltage

    measurements. The simulations are carried out for both sag and swell on 11KV feeder using

    both D-Statcom and DVR as custom power devices and it has been found that DVR provide

    excellent voltage regulation capabilities. It is also observed that the DVR capacity for power

    compensation and voltage regulation depends mainly on two factors that is, the rating of the

    dc storage device and the coupling transformer.

    9.2 FUTURE SCOPE

    The following point can be consider for future extension of work

    The control circuit can be change. The other controller like fuzzy, PQ techniqueand adaptive PI fuzzy controller may employ in the compensation scheme.

    Result can be improve by considering the operation with multi-level inverter Both custom devices can be established for active loads like wind turbine and

    solar source.

  • 7/28/2019 dstatcom and dvr in power system

    46/50

    46

    REFERENCES

    [1] N.G.Hingorani,Flexible AC Transmission, IEEE Spectrum, vol. 30, pp.40-44,1993.

    [2] N.G.Hingorani, Introducing Custom Power, IEEE Spectrum, vol. 32 pp.41-48,1995.

    [3] Anaya-Lara O, Acha E., Modeling and analysis of custom power system by

    PSCAD/EMTDC, IEEE Transactions on Power Delivery, Vol.17, and Issue: 1, Jan.2002. Pp.266-272.

    [4] M.J.H.Bollen, Voltage sags in three-phase system Power Engineering Review,

    IEEE, Vol.21 Issue:9, Sept.2001.pp.8-11.

    [5] Haque. M.H, Compensation of distribution system voltage sag by DVR and D-

    STATCOM. Power Tech. proceeding. 2001IEEE Porto, vol.11, Issue: Sept. 2001

    pp.10-13

    [6] Arindam Ghosh, Performance Comparision of VSC-Based Shunt and Series

    Compensators Used for Load Voltage Control in Distribution System.IEEE

    Transaction on power delivery, vol.26, No.1, Jan, 2011. pp.268-278.

    [7] Arindam Ghosh, Copensation of Distribution System Voltage Using DVR. IEEE

    Transaction on power delivery, vol.17, No.4, Oct. 2002. pp.1030-1036.

    [8] H.P Tiwari and Sunil Kumar Gupta Dynamic Voltage Restorer against Voltage Sag

    International of Innovation, Management and Technology vol.03, pp. 232-237,2010.

    [9] C.S Chang, Y.S Ho, The Influence of Motor Load on the Voltage Restoration

    Capability of Dynamic Voltage Restorer. Power System Technology, Proceedings,

    Power Con, International Conference, vol.2,pp. 637-642,2000.

    [10] M.H. Rashid, Power Electronics 2nd edition, Elsevier, Inc, Publication, Californial,

    U.S.A 2007.

    [11] Rakosh Das Begamudre, Extra High Voltage AC Transmission Engineering, 2nd

    Edition, New Age International Limited, New Delhi 1990.

    [12] Majid Moradlou and Hamid R. Karshenas, Design Strategy for Optimum RatingSelection of Interline DVRIEEE, VOL. 26, NO. 1, Jan, 2011.

  • 7/28/2019 dstatcom and dvr in power system

    47/50

    47

    LIST OF PUBLICATIONS

    Sr.

    No.

    Authors Title of Paper Name of

    International

    Journals /

    International

    Conference

    Place and date of

    Publication with

    Citation Index

    1

    Akil

    Ahemad,

    Prof. N.T.

    Sahu

    Simulation of DVR

    in power system.

    National Conference

    On Advances In

    Engineering And

    Technology.

    Anjuman College of

    Engineering &

    Technology. Sadar,

    Nagpur-440001

    March 13, 2012

    2

    Akil

    Ahemad,

    Prof. N.T.

    Sahu

    Performance of

    DVR in Power

    system.

    International

    conference on

    Interdisciplinary

    Research and

    Development in

    Management,

    Engineering,Technology and

    Social Sciences

    (ICMETSS) 2012.

    Choice Institute of

    Management Studies

    & Research, Pune.

    28th and 29th April,

    2012.

  • 7/28/2019 dstatcom and dvr in power system

    48/50

    48

  • 7/28/2019 dstatcom and dvr in power system

    49/50

    49

  • 7/28/2019 dstatcom and dvr in power system

    50/50

    .