Page 1: split Repair Gasket for Victaulic couplings • Read and understand all instructions in this sheet and the I-100 Field Installation Handbook before attempting to use split repair gaskets

WARNING

• Read and understand all instructions in this sheet and the I-100 Field Installation Handbook before attempting to use split repair gaskets.

• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic piping products.

• Wear safety glasses, hardhat, and foot protection during installation.

Failure to follow these instructions could result in serious personal injury, improper product installation, and/or property damage.

WARNING

IMPORTANT INFORMATION• ThefollowinginstructionsareaguideforproperinstallationofVictauliccouplingswithsplitrepairgaskets.Standardmoldedgasketsare

recommendedforpositivesealingandmustbeusedwheneverpossible.SplitrepairgasketsshouldbeusedONLYwhencircumstancesmakeitimpossibletoreplacethestandardmoldedgasket.Full PeRFORMANce cAPAbIlITIes MAy NO lONGeR APPly TO cOuPlINGs INsTAlleD WITH sPlIT RePAIR GAskeTs, sINce sPlIT RePAIR GAskeTs ARe INTeNDeD ONly FOR TeMPORARy use.SplitrepairgasketsmustbespecialorderedandsuppliedonlybyVictaulic.

• Makesurethegasketgradesuppliedissuitablefortheintendedservice.Maximumgasketlifeisdependentuponpropergasketgradeselectionandinstallation.Victaulicpublication05.01,“GasketSelectionGuide,”mustbereferencedtodeterminegasketgraderecommendationsforeachapplication.

• Theoutsidesurfaceofthepipe,betweenthegrooveandthepipeend,mustbesmoothandfreefromindentations,projections(includingweldseams),androllmarkstoensurealeak-tightseal.Alloil,grease,loosepaint,dirt,andcuttingparticlesmustberemoved.

• VerifythatthepipeandgroovedimensionsarewithincurrentVictaulicspecifications.Measurementstakenacrossgroovedpipeendsmustnotexceedthemaximumallowableflarediameter.

• Lubricationofthegasketisrequiredtopreventthegasketfrompinchingortearingduringinstallation.Refertotheinstructionsonthefollowingpageforlubricantrequirements.

• Splitrepairgasketsthatare18-inch/457-mmandsmallerinsizeareaspecialanglecutanddonotrequirebonding.Refertotheinstructionsonthefollowingpage.

• Splitrepairgasketsthatare20-inch/508-mmandlargerinsizearesquarecutandmustbebondedwithalightcoatingofadhesive(notprovided).Refertothetablebelowandtheinstructionsonthefollowingpageforadhesiverequirements.NOTe: Only Grades “e”, “T”, “s”, and “l” can be bonded.

ADHesIVe ReQuIReMeNTs FOR bONDING 20-INcH/508-MM AND lARGeR sPlIT RePAIR GAskeTs

Gasket Grade color code/Description Primer Adhesive

E – EPDM Green Stripe/Standard Gasket for IPS Couplings Not Needed 3M™ Scotch-Weld™ Instant Adhesive CA40H or CA40

T – Nitrile Orange Stripe/Standard Gasket for IPS Couplings Not Needed 3M™ Scotch-Weld™ Instant Adhesive CA40H or CA40

S – Nitrile Orange Stripe/Gasket for AWWA Couplings Not Needed 3M™ Scotch-Weld™ Instant Adhesive CA40H or CA40

L – Silicone Red Gasket/Special Gasket for IPS Couplings Hernon® EF® Adhesion Promoter 42 Hernon® Quantum® 124

3M and Scotch-Weld are Trademarks of 3M Hernon, EF, and Quantum are Registered Trademarks of Hernon Manufacturing, Inc.

cAuTION

• Always use a compatible lubricant to prevent the gasket from pinching or tearing during installation.

• DO NOT use petroleum-based lubricants on Grade “e” and Grade “l” gaskets.

Failure to follow these instructions could result in joint leakage and property damage.

cAuTION

I-sRG_1

split Repair Gasket for Victaulic couplings

I-sRGsPlIT RePAIR GAskeT INsTRucTIONs

www.victaulic.comVicTAuLiciSAReGiSTeRedTRAdeMARkOfVicTAuLiccOMpANY.©2010VicTAuLiccOMpANY.ALLRiGhTSReSeRVed.pRiNTediNTheuSA.

ReV_b

Page 2: split Repair Gasket for Victaulic couplings • Read and understand all instructions in this sheet and the I-100 Field Installation Handbook before attempting to use split repair gaskets

1.Wrapthesplitrepairgasketaroundthepipeendwiththesealinglipsfacingoutward,asshownabove.Makesurethegasketisnottwisted.

2.checkthesplicedsurfacestomakesuretheyaredryandfreeofanydebris.Brusheachendwithrubbingalcoholandallowtodrycompletely.

3. Refertothe“AdhesiveRequirements”tableonthepreviouspage.Applyprimer(ifapplicable)and/oradhesivetothesplicedend(s)ofthesplitrepairgasketinaccordancewiththeadhesivemanufacturer’sinstructions;theseinstructionsmustbereferencedforcompleteapplicationandcuringinformation.

4.immediatelybringthesplicedendstogetheraftertheadhesiveisapplied.Makesurethematinglipsarealigned.NOTe:Realignmentmaynotbepossibleaftercontactismadebetweenthetwosplicedends.

INsTRucTIONs FOR bONDING 20-INcH/508-MM AND lARGeR sPlIT RePAIR GAskeTs

5.Allowthebondedareatodrycompletely,thenlightlybuffthebondedareausingafinegradesandpaper(100gritminimum).Becarefulnottogougethegasketsurface.

6.ApplyathincoatofVictaulicLubricanttothesealinglipsofthegasket,thenrollthegasketintopositionandcenteritbetweenthegrooveineachpipeend.Makesurenoportionofthegasketextendsintothegrooves.ApplyathincoatofVictaulicLubricanttotheexteriorofthegasket,asshownabove.

Spliced Ends HereGasket

Pipe

Coupling Housing

45˚

Exaggerated for Clarity

6a.positionthebondedareaofthegasketata45°anglewiththehorizontal.Thebondedareashouldbepositionedawayfromthecouplingboltpads.

7.installthecouplinghousings,pertheinstructionsintheVictaulici-100fieldinstallationhandbook.NOTe:for20-inch/508-mmsizecouplingsthatarecastinmultiplesegments,assemblethesegmentslooselyintotwoequalhalves.Allowclearancebetweenthesegmentstoeaseassemblyontothepipe.Makesurethegasketremainscenteredbetweenthegrooveineachpipeendduringcouplingassembly.

1.ApplyathincoatofVictaulicLubricanttothegasketsealinglipsandexterior.

Spliced Ends HereGasket

Pipe

Coupling Housing

45˚

Exaggerated for Clarity

2.Wrapthesplitrepairgasketaroundthepipeends,makingsurethegasketisnottwistedandthattheangledendsarematedproperly.centerthegasketbetweenthegrooveineachpipeend.Makesurenoportionofthegasketextendsintothegrooves.positionthesplicedendsofthegasketata45°anglewiththehorizontal.Thesplicedendsshouldbepositionedawayfromthecouplingboltpads.

3.placethelowercouplinghousinginpositionoverthegasket/pipeends.NOTe:for14–18-inch/355.6–457-mmsizecouplingsthatarecastinmultiplesegments,assemblethesegmentslooselyintotwoequalhalves.Allowclearancebetweenthesegmentstoeaseassemblyontothepipe.Makesurethegasketremainscenteredbetweenthegrooveineachpipeendduringcouplingassembly.

4.placetheuppercouplinghousing(orsegmentassembly)inpositionoverthegasket/pipeends.finishtheinstallationbyreferringtotheinstructionsintheVictaulici-100fieldinstallationhandbook.

INsTRucTIONs FOR INsTAllING 18-INcH/457-MM AND sMAlleR sPlIT RePAIR GAskeTs

I-sRG

split Repair Gasket for Victaulic couplings

I-sRGsPlIT RePAIR GAskeT INsTRucTIONs

forcompletecontactinformation,visitwww.victaulic.comI-sRG 2083 ReV b uPDATeD 09/2010 Z0000000bGVicTAuLiciSAReGiSTeRedTRAdeMARkOfVicTAuLiccOMpANY.©2010VicTAuLiccOMpANY.ALLRiGhTSReSeRVed.pRiNTediNTheuSA.