Basic Electric - Shunt Formulas
• Calculate Current– Given - Shunt ( .01 ohms & voltage across the shunt = 50 Mv)
– Convert units of voltage, 50mv = .05v
– Calculate current using Ohm’s law• I = .05 v/.01 ohms = 5 amps
– Given - Shunt ( 15 amps, 50mV)• Measured voltage drop = 28mV
– Determine shunt rating• Rating = 15 amps/50mV = .3 amps / mV
– Calculate current• Current = .3 amps / mV x 28 mV = 8.4 amps
![Page 4: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/4.jpg)
![Page 5: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/5.jpg)
![Page 6: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/6.jpg)
Slide Resister Application
![Page 7: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/7.jpg)
Resister Wire Application
The amount of Resistance is made by the Length of the Wire.
![Page 8: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/8.jpg)
Disconnect Bond Wire for Amp Drain Reading
![Page 9: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/9.jpg)
Amp Drain Reading
Make Connection in series with the Circuit
1.36 Amp Current Drain
![Page 10: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/10.jpg)
![Page 11: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/11.jpg)
Slide Resister
Lighting Arrestor
![Page 12: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/12.jpg)
Connection Made on Resister from Foreign Structure and Columbia.
![Page 13: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/13.jpg)
Disconnection to get Amp Drain must be made in series with the circuit.
![Page 14: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/14.jpg)
Direct Bond Connection, No Resistance
![Page 15: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/15.jpg)
Shunt Resister
![Page 16: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/16.jpg)
Measuring Amp Drain by Measuring Voltage Drop Across the Shunt. Ratio is normally found on Shunt. .001V = 1A
![Page 17: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/17.jpg)
7 milivolts = 7 Amps
Polarity does not matter.
Make connection across Shunt.
![Page 18: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/18.jpg)
Ratio for Shunt
Shunts do not have to be disconnected in BI-monthly and Annual inspection.
![Page 19: Rectifier and Bond Reading Tim Jenkins. Basic Electric - Shunts](https://reader030.vdocuments.us/reader030/viewer/2022033104/56649dc55503460f94ab8944/html5/thumbnails/19.jpg)
Connect meter in serious for amp reading
on the structure or anode wire.
Alternative method – use shunt for amp readings.