Plug on Type MCBs & Distribution BoardsIntelligent Choice forPrestigious Buildings
Table of ContentsQO Series Miniature Circuit Breakers
Specifications
QOvsRCBO Residual Current Circuit Breakers
with Integral Overcurrent Protection
QOE QWIK-GARD Residual Current Circuit
Breakers with Integral Overcurrent Protection
QOvs Miniature Circuit Breakers
LoadCentre Distribution Boards
Specifications
Rated Current 100A
Rated Current 200A
CLASSIC Metal Consumer Units
Specifications
Rated Current 100A
Certificates
1
2
3
4
6
8
9
10
11
11
12
2
QO Series Miniature Circuit Breakers
Specifications
Comply with BS EN 60898.Comply with BS EN 60947-3 : 1992.Add i t i ona l sa fe ty requ i rements fo r Disconnectors and Switch Disconnectors as referred to in BS 7671.Trip-free handle ensures tripping even when the circuit breaker handle is held or locked in the ON position.To restore service, simply switch the indicative buttom from OFF to ON position once the fault has been cleared, which completely eliminates the cost and inconvenience of replacing fuse links or fuse wire.
All circuit breakers fit all LoadCentre Distribution Boards and Consumer Units in the range.Plug-on circuit breakers are tamperproof and provide positive connection to the busbar in one quick operation.Easy for installation and maintenance, with labour cost saved up to 50%.Current ratings from 6A to 63A, single, double and triple pole.Instantaneous trip type B, C and D.Rated voltage up to 240V AC single phase or 415V AC three phase 50/60Hz.
Full Range of QO Series Miniature Circuit Breaker Breakers
3
QO Series RCBO
QOvsRCBO Residual Current Circuit Breakerswith Integral Overcurrent Protection
Used in Schneider Electric consumer units, LoadCentre Distribution Boards.Compliance with International Standards: IEC 61009-2-2 and BSEN 61009-1, CE marked.Rated voltage: 240V AC, +10%, -15%.Frequency: 50...60 Hz.Class: AC.Ratings: 10-45 A to 40ºC.Breaking capacity as per IEC 61009: 6 kA.Tripping characteristics: Type C (5-10 In).Tripping time is in compliance with IEE wiring regulations BS7671.Sensitivities: 10 or 30 mA (for protection against direct and indirect contact).ON/OFF Indication:
Trip-free handle through an over-center toggle mechanism that ensure tripping even when the handle is held or locked at the ON position.Overload, short circuit, and earth fault currects are indicated by location of the handle in the OFF position.
Push-to-test Function:A Yellow push-test button “T” is positioned on the front of the device for testing that product is operationalThe smallest operating voltage for the test button: 200V AC (0.85 Un)
Connection:Phase in: plug-on tyepPhase & Neutral out: 1 to 16mm2 flexible or rigid cable (tightening torque 2 N.m)
Catalogue Number
Single Pole
QO110vs6RCBO10QO160vs6RCBO10QO120vs6RCBO10QO132vs6RCBO10QO140vs6RCBO10QO145vs6RCBO10
QO110vs6RCBO30QO160vs6RCBO30QO120vs6RCBO30QO132vs6RCBO30QO140vs6RCBO30QO145vs6RCBO30
101010101010
303030303030
101620324045
101620324045
Sensitivity
mA
Rated Current
A
-
-
-
-
--
QO132vs6RCBO30
4
QO Series RCBO
QOE QWIK-GARD Residual Current Circuit Breakerswith Integral Overcurrent Protection
Rated voltage of 220V to 240V AC, 50/60Hz, operating voltage: 50V 250V AC, 50/60Hz.Used in Schneider Electric Consumer Units, LoadCentre Distribution Boards and can be retrofitted to existing installations.Compliance with International Standards : Certfiied to IEC 60898 and IEC 61009, 10kA at 240V AC, 50/60Hz, CE market.ON/OFF Indication: ON/OFF marketings are on the face of the circuit breaker along with the international I/O markings.Handle Operation: Trip-free handle through an over-centre toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the OFF position. Indication of a tripped circuit breaker on residual current ground fault is by location of the handle in an intermediate position.Push-to-test Function: A push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanism tripping interface.Thermal Trip Element: Thermal trip elements are factory calibrated at 30ºC ambient temperature.Instantaneous trip level:- Type B: (3-5In) Overcurrent protection for sensitive equipment- Type C: (5-10In) Overcurrent protection for all application typesClass: ACResidual Current Protection: Residual ground-fault trip currents are factory set at 10mA, 30mA or 100mA.Trip Mechanism:
Loss of neutral Protection: Device will trip on loss of neutral and is sensitive to both AC and pulsat-ing DC fault current. Device will trip on voltage between neutral and earth greater than 50V AC.Protection against reversed polarity (Phase and Neutral)Protection against nuisance tripping (compliance with IEC 61543 for EMC)
Mounting: Plug-on connection.
-
--
QOE120C03
5
QO Series RCBO
QOE QWIK-GARD Residual Current Circuit Breakerswith Integral Overcurrent Protection
QOE132C03
Catalogue Number
Single Pole
Maximum Earth FaultLoop Impedance Zs
OHMs at 50V AC (RCCB)
Short Circuit Capacity (Icn) : 10000A
5 Seconds 0.4 Seconds
QOE106B01QOE110B01QOE116B01QOE120B01QOE132B01
QOE106B03QOE110B03QOE116B03QOE120B03QOE132B03
Type B Instantaneous Trip (3In to 5In)1 - 161 - 161 - 161 - 161 - 16
1 - 161 - 161 - 161 - 161 - 16
575575575575575
575575575575575
50005000500050005000
16671667166716671667
50005000500050005000
16671667166716671667
500500500500500
500500500500500
610162032
610162032
1010101010
3030303030
QOE106C01QOE110C01QOE116C01QOE120C01QOE132C01
QOE106C03QOE110C03QOE116C03QOE120C03QOE132C03
QOE106C10QOE110C10QOE116C10QOE120C10QOE132C10
Type C Instantaneous Trip (5In to 10In)1 - 161 - 161 - 161 - 161 - 16
1 - 161 - 161 - 161 - 161 - 16
1 - 161 - 161 - 161 - 161 - 16
575575575575575
575575575575575
575575575575575
50005000500050005000
16671667166716671667
500500500500500
50005000500050005000
16671667166716671667
500500500500500
500500500500500
500500500500500
500500500500500
610162032
610162032
610162032
1010101010
3030303030
100100100100100
RatedCurrent
A
TerminalCapacityLoad L&N
mm2
Pigtail Wire ConnectionColor & Length
EarthYellow & Green
mm
NeutralBluemm
ResidualTrippingCurrent
mA
6
QO Series Miniature Circuit Breakers
QOvs Miniature Circuit Breaker
QO132VSC6 QO132VSC10
QO110VSC10QO116VSC10QO120VSC10 QO125VSC10QO132VSC10QO140VSC10QO150VSC10QO163VSC10
Type C Instantaneous Trip (5In to 10In)1016202532405063
1 - 251 - 251 - 251 - 25
2.5 - 352.5 - 352.5 - 352.5 - 35
Short Circuit Capacity (Icn) : 10000ARated Current
A
Teminal Capacity
mm2
QO210VSC10QO216VSC10QO220VSC10 QO225VSC10QO232VSC10QO240VSC10QO250VSC10QO263VSC10
QO310VSC10QO316VSC10QO320VSC10 QO325VSC10QO332VSC10QO340VSC10QO350VSC10QO363VSC10
Catalogue Number
Single Pole Double Pole Triple Pole
QO110VSC6QO116VSC6QO120VSC6 QO125VSC6QO132VSC6QO140VSC6QO150VSC6QO163VSC6
Type C Instantaneous Trip (5In to 10In)1016202532405063
1 - 251 - 251 - 251 - 25
2.5 - 352.5 - 352.5 - 352.5 - 35
Short Circuit Capacity (Icn) : 6000ARated Current
A
Teminal Capacity
mm2
QO210VSC6QO216VSC6QO220VSC6 QO225VSC6QO232VSC6QO240VSC6QO250VSC6QO263VSC6
QO310VSC6QO316VSC6QO320VSC6 QO325VSC6QO332VSC6QO340VSC6QO350VSC6QO363VSC6
Black in color.Instantaneous trip level type C.Indication of tripped circuit breaker on overload or short circuit is by location of the handle in the OFF position & trip status window.
BS EN 60898, IEC 898 - Miniature Circuit BreakerBS EN 60947-3 : 1992Additional safety requirements for Disconnectors and Switch Disconnectors as referred to in BS 7671.
In compliance with specifications:
Catalogue Number
Single Pole Double Pole Triple Pole
QO232VSC10
QO332VSC10
7
QO Series Miniature Circuit Breakers
QOvs Miniature Circuit Breaker
Technical data
Main characteristics QOvs 6 kA QOvs 10 kA
Insulation voltage (Ui) 500 V ACOperating voltage (Ue) 240/415 V ACRated impulse withstand voltage (Uimp) 4 kV according to
IEC 60898-1Reference temperature 40°COperating frequency 50/60 HzPollution degree 3Magnetic tripping Curve C 5 to 10 In b b
According to IEC/EN 60898-1
Limitation class 3Rated breaking capacity
(Icn)
6000 A 10000 A
Service breaking capacity (Ics) 100 % Icn 75 % Icn
Additional characteristics
Degree of protection
(IEC 60529)
Device only IP20Device in modular enclosure
IP40Insulation classe II
Endurance (O-C) Electrical 4000 cyclesMechanical 20,000 cycles
Operating temperature -5°C to +60°CStorage temperature -40°C to +85°CTropicalization (IEC 60068-1) Treatment 2 (relative humidity
95 % to 55°C)
Dimensions (mm)
DB
4045
41
Weight (g)
Circuit-breaker
Type QOvs
1P 1042P 2083P 312
Circuit-breaker Type Number of poles A B C C' D E
QOvs 1P 78.3 18.7 58.8 51.4 81 86.3
2P 78.3 37.4 58.8 51.4 81 86.3
3P 78.3 56.1 58.8 51.4 81 86.3
1P, 240 V AC2P, 240/415 V AC3P, 240/415 V AC
8
Full Range of Miniature Circuit Breaker Boards
LoadCentre Distribution Boards with Finger Safe Protection
Specifications
Finger safe design for plug on - main busbar to maximize safety (live part have been totally insulated).Built-in with 4 pole main switch for complete isolation (TPN Type).Quick and easy to install.Accepts 1, 2 & 3 pole Plug-on circuit breakers and RCBOs.Range of incoming devices, including 4 pole.Brass neutral and earth terminal bars for every single pole outgoing way.Plenty of cable space, with knock-outs provid-ed at top and bottom.
Used in offices, banks, IT buildings, hotels and commercial premises.Bluish white color epoxy powder paint. Zinc coated corrosion resistant steel enclosure.Rated voltage up to 415V AC three phase.Main switch comply with BS EN 60439-3. Enclosure protection to BS EN 60529 IP41 (on request for higher IP rating).Comply with BSEN 60439 & IEC 60439.
Finger Safe
9
LoadCentre Distribution Boards
Rated Current 100A
CatalogueNumber
No. of Ways Dimensions
Heightmm
Widthmm
Depthmm
SQDLC104-100SQDLC106-100SQDLC108-100SQDLC110-100SQDLC112-100SQDLC114-100SQDLC116-100SQDLC118-100SQDLC120-100
LoadCentre TPN Type (Installed with 100A TPN Main Switch)
SQDLC204-100SQDLC206-100SQDLC208-100SQDLC210-100SQDLC212-100SQDLC214-100SQDLC216-100SQDLC218-100SQDLC220-100
468101214161820
Main isolator
SQDLC112-100
SAFE
453510567624681738795852909
380380380380380380380380380
121121121121121121121121121
453510567624681738795852909
380380380380380380380380380
121121121121121121121121121
For installation of Circuit Breaker orResidual CurrentCircuit Breakerwith IntegralOvercurrent Protection
LoadCentre Lug Type (For direct connection w/o Main Switch)
468101214161820
10
LoadCentre Distribution Boards
Rated Current 200A
CatalogueNumber
No. of Ways Dimensions
Heightmm
Widthmm
Depthmm
SQDLC104-200SQDLC106-200SQDLC108-200SQDLC110-200SQDLC112-200SQDLC114-200SQDLC116-200SQDLC118-200SQDLC120-200
LoadCentre TPN Type (Installed with 200A TPN Main Switch)468101214161820
SQDLC204-200SQDLC206-200SQDLC208-200SQDLC210-200SQDLC212-200SQDLC214-200SQDLC216-200SQDLC218-200SQDLC220-200
LoadCentre Lug Type (For direct connection w/o Main Switch)468101214161820
For installation of Circuit Breaker orResidual CurrentCircuit Breakerwith IntegralOvercurrent Protection
SAFE
SQDLC112-200
5676246817387958529099661023
380380380380380380380380380
121121121121121121121121121
5676246817387958529099661023
380380380380380380380380380
121121121121121121121121121
Main isolator
11
CLASSIC Metal Consumer Units with Finger Safe Protection
Specifications
Catalogue Number No. of Ways Dimensions
Heightmm
Widthmm
Depthmm
SDCS14SDCS16SDCS110SDCS114SDCS118
100A Rated With Space for Incoming Device46101418
206206206206206
200238315391517
9898989898
Weight
kg
1.91.92.53.14
Catalogue Number Description Dimensions
Heightmm
Widthmm
Depthmm
QO2100MBXPlug-on Incoming Device
100A double pole main switch 80 40 85
Weight
kg
0.28
Terminal Capacity
mm2
35
Finger safe design for plug on main busbar to maximize safety.Used in apartments. IT buildings, banks, hotels and commercial premises.White color, epoxy power paint.Zinc coated corrosion resistant steel enclosure.Rated voltage up to 240V AC single phase.Comply with BS EN 60439 & IEC 60439.Plug-on main switch complies with BS EN 60947-3 : 1992.Plug-on circuit breakers provide positive connection to the busbar in one quick operation, saving up to 50% on wiring and connection time.
SAFE
Rated Current 100A
SDCS14
Main Isolator
Circuit Breaker or RCBO
Finger Safe Main Busbar
12
Certificates
Miniature Circuit Breaker
Certificates
Consumer unit / LoadCentre
13
Schneider Electric (HK) Ltd. 13th Floor, East Wing, Warwick House, Taikoo Place,979 King’s Road, Quarry Bay, Hong KongTel: (852)2565 0621 Fax: (852)2811 1029Customer Care Centre: (852)2579 9699www.schneider-electric.com/hk
Macau Branch Office:Alameda Dr Carlos D’Assumpcao 180,Tong Nam Ah Central Comercio 13G, 13H & 13I, MacauTel : (853)2871 7488Fax: (853)2871 7499
SEHK/SQD/008 05/2012
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
Certificates
Distribution Board